Installation Manual. APEX Series. Silicon and MOV Panel Protection. APEX Series

Similar documents
Specifications, Installation, and Operating Instructions

Installation Instructions & User Manual

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

Installation Instructions & User Manual POWERWARE TVSS ZONESENTINEL. AC Panel Transient Voltage Surge Suppressors

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Always "On" UPS Systems Inc. USER MANUAL

DAW 8/28/09. TITLE Specification I2R 120/240 RR 120V AC Split Phase Surge Protector PAGE 1 of 9 REVISIONS

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

R-LB R-LX Series Installation, Operation & Maintenance Manual

Application Techniques CENTERLINE 2100 Motor Control Centers

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)

Owner s Manual. Isolate. Restore. Inspire! Power Conditioners Audio / Video Power Isolation Units Rack Mount / Consumer Series

SEM3 - Embedded Micro Metering Module

Hubbell Surge Protective DeviceS

Secondary Surge Arrester Instruction Manual Page 1 of 5

INSTRUCTION MANUAL RA 55 RACK ADAPTER RACK ADAPTER FOR MST SERIES POWER MODULES

GE Digital Energy. Power Quality

PV Rapid Shutdown device

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

Surge Protective Devices Installation, Operation and Maintenance Manual. LoadTrack LTL

KRH CVM DWR CDD REVISIONS NOTICE: THE INFORMATION AND DESIGN CONTAINED HEREIN IS THE PROPERTY OF TRANSTECTOR SYSTEMS. WHO RESERVES ALL RIGHTS THERETO

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

BCM2 Series Branch Circuit Monitors Quick Setup Guide

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

Installation, Operation, and Service Manual SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

Installation and Operation Manual

INSTRUCTION MANUAL RA 60 SERIES RACK ADAPTER RA 60, RA 62, AND RA 63. 1) This manual is valid for the following Model and associated serial numbers:

Bulletin Installation of solar photovoltaic systems Rules , , , , and

Installation Instructions

This Datasheet for the IC660BBD101. Block 115Vac I/O Low Leakage 8 Circuits.

Site Preparation CHAPTER

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

SURGE PROTECTION USER MANUAL. Surge Protection Device PORTABLE POWER DISTRIBUTION SURGE PROTECTION DEVICE (SPD) B

PHOENIX CONTACT Features

Specifications 1 Installation Procedures 2 Wiring Diagrams 3 Installation Checklist 5 Maintenance 5 Warranty Information 6 Material Return Policy 6

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

A.C. VOLTAGE SURGE SUPPRESSOR SPECIFICATIONS (SOLID-STATE TYPE)

S66 Series Electronic Fan Speed Control

IIM Warwick Court. Williamsburg VA REV 5

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs)

PM Series Power Meter

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

BSPD Surge Protective Devices

Wise HP33 THREE PHASE HIGH PRECISION AVR SURVO-MOTOR AUTOMATIC VOLTAGE STABILIZER

TTS Series ILC-200 Integrated Load Center

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

SPECIAL SPECIFICATION 1864 Pole Mounted Cabinet

SIEMENS HEALTHCARE INTEGRATED ELECTRICAL CABINET

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual

Measure Ø-N, Ø-Ø, Ø-Gnd with voltmeter to confirm application voltage prior to installation.

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!

Power Supply and Fan Module Installation

SECTION SURGE PROTECTIVE DEVICES

SECTION TRANSIENT VOLTAGE SURGE SUPPRESSION

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

Eaton Innovative TechnologyT XT50/100 surge protective device

AIR COOLED MODULAR RECTIFIER

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

Breaker Panel Technical Practice NPDRP1114

Series Amp Pad Mount Quick Connect Input and Output Power Panels

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD)

Installation Instructions

Total Home Surge Protection for Point-of-Entry. FirstSurge TM. User Manual - Canada (English)

Replacing the Power Supply

Series 3700 Screw Terminal Assemblies Installation Instructions

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

AVR Manual. Toroidal. Isolation. Power. Conditioning. Audio / Video Power Isolation Units with Automatic Voltage Regulation

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

Installation and Operation Manual

Temperature. Power requirements. Weight. Dimensions

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

Quick Start Guide TS A

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

Model 8010 High Power Device Test Fixture Interconnection Reference Guide

Model 7705 Control Module

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

ZoneMaster Series Surge Protection Devices

Models 120LS, 200LS, 300LS, 400LS, 560LS Installation Instructions

Series Amp Quick Connect Input and Output Power Panels

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

OPERATOR S MANUAL BOP (M) (D) 100W, 200W, 400W BIPOLAR POWER SUPPLY

Model HM-535 Power Supply Installation and Service Instructions

Quick Start Guide TS 870 ATS

SAVE THESE INSTRUCTIONS

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

PowerLogic High Density Metering System 1-Meter Enclosure

5401 and 5402 Digital I/O Modules

SECTION SWITCHBOARDS

TransEnd Surge Suppression Filter Systems

Transcription:

Installation Manual APEX Series Silicon and MOV Panel Protection APEX Series

APEX Series Installation Guide 2 Table of Contents Mechanical Installation 3 Table One - Application Rating 3 Figure 1 - Mounting Details 4 Electrical Installation 5 Figure 2-120T Configuration 5 Figure 3-120S Configuration 5 Figure 4-240S Configuration 6 Figure 5-120W, 240W Configuration 6 Figure 6-240D Configuration 6 Figure 7 - Card Installation 9 WARNING: AC Power to the surge suppressor, at the surge suppressor, and in the vicinity of the surge suppressor MUST be disconnected prior to performing the following mechanical and electrical installation procedure. WARNING: Wiring conductors utilized to attach Phases L1, L2, L3, the Neutral and Safety Ground from the AC power source to the APEX Series should be color-coded to conform with appropriate electrical codes and/or accepted wiring practices. It is very important to make no assumptions that wiring colors on existing electrical installations correspond to proper phase, neutral, or ground connections. WARNING: The disconnect utilized in the current path from the electrical distribution and the APEX Series must be coordinated to operate properly in conjunction with all other disconnects contained within the same electrical distribution. WARNING: Proper electrical connections must be accomplished in accordance with applicable International, National, and/or Local electrical code requirements.

3 APEX Series Installation The APEX Series surge suppressor models are designed specifically to operate on the following configurations: Configurations 120V 1Ø 240V 3Ø Delta 120/240 Split 1Ø 220/380 3Ø Wye 120/208 3Ø Wye 230/400 3Ø Wye 240V 1Ø 240/415 3Ø Wye Suppression is accomplished in parallel between phase conductors and/or between phase and the neutral conductors, depending upon the voltage configuration. Once activated, the suppressor remains operative until excess transient energy is dissipated and instantaneous peak line voltage falls below the approximate 120% overvoltage threshold. At that time the suppressor automatically deactivates, resets to a ready state, and awaits further transient activity. Please take a moment to read and understand the installation instructions included with this product. If any questions should arise concerning the proper installation of this product, please contact us. Mechanical Installation Step 1: Select a location along the electrical distribution system as physically close to critical equipment loads as practical to install the surge suppressor. The suppressor can be installed at distribution panels, at equipment AC power inputs, or at the secondary windings of isolation transformers. The suppressor must be positioned within four (4) feet (122 cm) of the AC power source. It is recommended that the suppressor be installed within two (2) feet (61 cm) of the AC power source, if possible. CAUTION: Increasing electrical impedance values to the inputs of any transient suppressor, regardless of manufacturer, can increase the device s voltage limiting levels. Suppressors should be installed as physically close to the protected electrical distribution panel or critical load as possible using the largest size wiring/conductors as practical. Step 2: Verify that the maximum current rating of the electrical service to be protected does not exceed specified amperage rating of the suppressor model to be installed. Table One: Application Rating APEX II APEX III APEX IV 225 Amps and below 400 Amps and below 1000 Amps and below 1200-185

APEX Series Installation Guide 4 CAUTION: Transtector s Applications Engineering Department must be contacted prior to installing the APEX Series suppressor when the maximum current rating of the electrical service to be protected exceeds the specified amperage rating of the surge suppressor. Step 3: Unpack the surge suppressor from its shipping container and visually inspect for shipping related damage. Open the suppressor door and verify that all components, lights, displays, and electrical connections are secure. Step 4: Refer to the APEX Series enclosure diagram (Figure 1). Note the suggested locations on either the bottom or the left side of the suppressor enclosure to drill holes to route conduit from the AC power source to the suppressor assembly. Apertures intended to provide a path for AC wiring conductors can be bored anywhere into the suppressor enclosure as long as suppression components are not damaged or obstructed in the process. Step 5: Refer to the mounting illustration (Figure 1) for the APEX Series suppressor. Drill four (4) mounting holes anyplace on the mounting surface. Insure mounting holes are spaced 8 (20.38 cm) apart from each other horizontally and are separated 13 (33 cm) vertically. Step 6: Physically position the surge suppressor as close as possible to the AC power source and securely mount it to any surface capable of permanently supporting 20 pounds (9.1 Kg) of weight. (Mounting hardware is not included). WARNING: Serious and/or fatal electrical shock hazards exist if extreme care is not exercised during all phases of mechanical and electrical installation procedures. Figure 1 - Mounting Details

5 Electrical Installation NOTE: These instructions are intended to guide the equipment installer through a step-by-step procedure resulting with the surge suppressor being electrically connected in parallel with its AC power source. Figure 2-120T configuration - typical installation consists of two phase conductors with one neutral Figure 3-120S configuration - typical Installation consists of one phase conductor with one neutral 1200-185

APEX Series Installation Guide 6 Figure 4-240S configuration - typical Installation consists of two phase conductors with no neutral NOTE: Phase L, or Phase L2 can be substituted for neutral in international applications. Figure 5-120W, 240W configuration - international installation consists of voltages ranging from 380 to 415 between phase conductors; and ranging from 220 to 240 between phase conductors and neutral Figure 6-240D configuration - typical installation

7 WARNING: All international, national, local, and other applicable electrical codes must be followed and adhered to during all phases of the electrical installation. If any of the following electrical installation procedures conflict with applicable electrical codes, the suppressor installation must be discontinued and Transtector System s Applications Engineering department must be contacted for further instructions. Step 1: Ensure that the electrical installation is accomplished by qualified personnel that are certified and/or licensed to service and install equipment upon the appropriate electrical services. Step 2: Verify at the AC power source, at the point where the surge suppressor will be electrically attached, that the surge suppressor is designed to protect upon that specificed voltage configuration. Step 3: Verify that the maximum current rating of the electrical service to be protected does not exceed the specified amperage of the surge suppressor. Step 4: Measure AC voltages between phase(s) and neutral and/or between phases as appropriate using an AC voltmeter. Verify that the measured RMS voltages between the fore mentioned conductors complies to the nominal values appropriate for the electrical distribution. WARNING: AC Power to the surge suppressor, at the surge suppressor, and in the vicinity of the surge suppressor MUST be disconnected prior to performing the following mechanical and electrical installation procedure. Step 5: Disconnect power at the AC power source at the point where the APEX Series will be connected. Verify that AC power is disabled. NOTE: The mechanical and electrical installation illustrations are referenced in Figures 1 through 6 and are applicable with the remaining electrical installation procedural steps. WARNING: Wiring conductors utilized to attach Phases L1, L2, L3, the Neutral and Safety Ground from the AC power source to the APEX Series should be color-coded to conform with appropriate electrical codes and/or accepted wiring practices. It is very important to make no assumptions that wiring colors on existing electrical installations correspond to proper phase, neutral, or ground connections. Identify and verify each specific phase, neutral, and ground references at the AC power source prior to proceeding with these electrical installation procedures. WARNING: The disconnect utilized in the current path from the electrical distribution and the APEX Series must be coordinated to operate properly in conjunction with all other disconnects contained within the same electrical distribution. WARNING: Proper electrical connections must be accomplished in accordance with applicable International, National, and/or Local electrical code requirements. Step 6: Tap into the three (3) phase conductors via an approved disconnect, i.e. circuit breaker that is sized appropriately (typically 60 Amps) on the load side of the main circuit breaker of the AC power service requiring surge suppression. If neutral is required for the system, tap into the neutral/bus wire. These 1200-185

APEX Series Installation Guide 8 wiring conductors must be sized accordingly dependent upon the following parameters: If the APEX Series suppressor is positioned within two (2) feet (61 cm.) from the AC power source, then a minimum of #6 (4.1 mm.) sized wiring conductors are recommended. If the APEX Series suppressor is positioned within four (4) feet (122 cm.) from the AC power source, then a minimum of #4 (5.2 mm.) sized wiring conductors are recommended. CAUTION: Contact Transtector s Application Engineering Department before proceeding with the installation if the suppressor cannot be installed within four (4) feet of the AC power source requiring protection from transient overvoltages. Step 7: If a breaker cannot be supplied in the protected panelboard, install either three (3) external fuses or an external three pole thermal/magnetic circuit breaker to be used as a disconnect in series with the surge suppressor and the AC power source. Fuses should be rated at ten (10) AMPs less than the service disconnect to a maximum of 100 AMPS (Typically BUSSMAN LPN Series fuse). A 60 AMP circuit breaker can be used in conjunction with #6 AWG. (4.1 mm.) sized wire if the surge suppressor is installed within two (2) feet (61 cm.) of the AC power source. Ensure that the disconnect is installed initially in its OPEN state so that AC power cannot pass through it until it is reset. CAUTION: The disconnect addressed in the above procedural step serves a dual purpose. It provides a means for maintenance personnel to de-energize AC power supplied to the APEX Series suppressor to allow for servicing the device. It also allows the suppressor to be electrically removed from the AC power source in the event of catastrophic failure modes without disrupting AC power to critical loads. Its current rating must be rated lower than that of the main disconnect supplying power to the protected electrical loads. Step 8: Route wiring conductors through metal conduit from the disconnect installed in the previous step at the AC power source to the suppressor enclosure. Mate the conduit to the suppressor enclosure at the hole bored in Step 4 of the Mechanical Installation procedures on page 3. Ensure that the conduit is properly grounded at the AC power source. WARNING: Adequate and proper grounding practices must be heeded to insure that human safety is accomplished during electrical fault conditions. Step 9: Open the front door of the suppressor enclosure and insure that conduit and/or external grounding conductors are securely fastened to Ground lug designated with the letter G on the terminal block at the left side of the backpanel assembly where the three suppressor modules attach. Locate the labeled terminal block providing the means to attach the electrical wiring conductors from the AC power source the APEX Series suppressor. The designated labels on the terminal block correspond to specific Phase and/or Neutral conductors from the AC power wiring positions on the terminal block. WARNING: In Wye configurations verify that the neutral conductor from the AC power source is connected properly to the N designated position on the terminal block identified in Step 9. If any phase conductor should accidentally be connected to that N designated connection point severe suppressor damage will result and human safety will be compromised as AC power is applied to the APEX Series suppressor. Step 10: After electrical wiring hook-up is complete and prior to energizing electrical power, each suppressor card must be firmly inserted into it s respective backpanel slot. Refer to the installation instruction sheet

9 located inside of the enclosure door and note the phase labeling on each card. Proper slot placement will align the cards with lable on the outside of the door. Cards must be inserted into their respective slots, with the card fingers engaging the electrical stab-down contacts, and pressed completely into place. Figure 7 depicts the card finger alignment into the slots. Press adjacent cards together sideways to snap the interlock pins on the top and bottom for added stability. WARNING: the card interlock pins must be separated before removing individual cards for services. Figure 7 - card installation NOTE: Depending on the configuration of your Apex Series suppressor, this unit could have between 1 and 6 cards to install. 1200-185