MAJOR500-500 VA Power Inverter The Major500 is a highly reliable, telecom quality, DC to AC power inverter. The Major500 features full electronic protection, high efficiency and low output noise. The built-in fan provides sufficient airflow for operation without de-rating up to 50 C ambient temperature. Extended operating temperature (-40 to +65 C), ruggedization and conformal coating are available. Product Features Available in 24/36/48/125/250 VDC Custom Input and Output Voltages available Compact size, light weight Pure sine wave output (60, 50 or 400 Hz) Full electronic protection Telecom quality Rackmount RM-3U-19" standard Options: Dry contact failure alarm Ruggedization Conformal Coating Extended Temperature Product Specifications 24, 36, 48, 125, 250 VDC ±20% are standard. Other inputs available. Input Thermal fuse, Inrush current limiting and Reverse polarity protection. Input Isolation Input-chassis: 500VDC @ <60V, 1500VDC @ >60V Input-output / Output-chassis: 2250VDC. 115VAC/60Hz @ 4.4A Standard. (230VAC/50Hz @ 2.17A and 115VAC/400Hz @ 4.4A Available) Output Voltage Continuous output with grounded neutral. Isolated floating output available. Efficiency Min 78% at full load Line Regulation Maximum 0.5% Load Regulation Maximum ±6% from 10% load to full load Output RFI Suppression Current limiting with short circuit protection. Thermal shutdown with automatic reset in case of insufficient airflow Meets requirements of EN55022: 1987 Class A conducted emissions Crest Factor Harmonics (THD) Operating Temp. Temp. Drift Connections Dimensions Weight Warranty Maximum 3.0 at 90% load Less than 5% at full load 0 C to +50 C (internal fan) 0.05% per C over operating temperature range Input: Compression-type terminal. Output: Standard AC receptacle. 5.3"H x 5"W x 15.5"L (3U Rackmount ears included) 9 pounds (4Kg) Twelve months subject to client application within accepted engineering practice. Designed to meet common approval requirements. Specifications subject to change
Power Solutions for Critical Applications Product Features: 24V, 48V, 130V Input 1 KVA / 800 Watts Output 2 KVA / 1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, High Efficiency Pure Sine Wave Output Low EMI/RFI Emissions Utility Bypass Function Intelligent Microprocessor- Based Control Output RS-232 Communication Port SNMP Communication Option User-Friendly LCD and LED Displays Smart Software for Power Management Internal Over Temperature Input Reverse Polarity Battery High/Low Voltage UL/cUL Approved (60950) Applications: Telecommunications Equipment Networking Equipment Utility Systems Control Fire Alarm Systems Building Management Systems Mission Critical Inter-Agency Communication SCADA Networks Majorsine Series Utility and Telecom Inverters Product Overview Majorsine Power Inverters feature the integrated utility bypass, and can be cascaded for redundancy. Designed for long Mean Time Between Failure, these inverters provide the dependable AC power that your networks demand. The compact 2U rackmount package makes this model the right selection for limited space applications. 19 inch and 23 inch brackets included. Majorsine Power Inverters are designed and built for full reliability at any location. These intelligent, dependable inverters provide economical AC power for all your network needs. Options SNMP Remote Communication Option: Remote monitoring is a prime consideration and requirement to manage multiple network elements from a central location. Remote access is established by simply installing the plug-n-play card, configuring your network IP address, and attaching the network interface cable. Locking - Hardwire Adapter: Reliable locking NEMA 5-15 plug to secure load circuits to the output sockets of the inverter. Heavy-duty design locks the plug in place to prevent disconnecting critical loads.
Power Solutions for Critical Applications Specifications* Order Number (VDC) Output Voltage (VAC) Capacity MAJORSINE1000-24-2U 20-30 100, 110, 115, 120 1KVA / 800W MAJORSINE1000-48-2U 40-60 100, 110, 115, 120 1KVA / 800W MAJORSINE2000-48-2U 40-60 100, 110, 115, 120 2KVA / 1600W MAJORSINE1000-125-2U 100-150 100, 110, 115, 120 1KVA / 800W MAJORSINE2000-125-2U 100-150 100, 110, 115, 120 2KVA / 1600W MAJORSINE1000i-48-2U 40-60 208, 220, 230, 240 1KVA / 800W MAJORSINE2000i-48-2U 40-60 208, 220, 230, 240 2KVA / 1600W All Units Include: Integrated AC Bypass Pure Sine Wave Output 19 /23 ; 2U rackmount UL/cUL Certification >85% Efficiency SNMP Communication Option LCD & LED Display High MTBF Hardwire Option Mechanical Drawing: *Full specification sheets available electronically at www.majorpower.com
Power Inverter Product Features: 24, 48, 130 VDC Input 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Efficiency Low EMI/RFI Emissions Utility Bypass Function Intelligent Microprocessor-Based Control Output RS-232 Communication Port SNMP Communication Option User-Friendly LCD and LED Displays Smart Software for Power Management Internal Over Temperature Input Reverse Polarity Battery High/Low Voltage UL/cUL Approved (60950) CE Approved Applications: Telecommunications Equipment Networking Equipment Utility Systems Control Fire Alarm Systems Building Management Systems Mission Critical Inter-Agency Communication SCADA Networks Majorsine Series Telecom and Utility Inverters Product Overview Majorsine Power Inverters feature the integrated utility bypass, and can be cascaded for redundancy. Designed for long Mean Time Between Failure, these inverters provide the dependable AC power that your networks demand. The compact 2U mounting package makes this model the right selection for limited space applications. Majorsine Inverters are designed and built for full reliability at any location. These intelligent, dependable inverters provide economical AC power for all your network needs. Options SNMP Remote Communication Option: Remote monitoring is a prime consideration and requirement to manage multiple network elements from a central location. Remote access is established by simply installing the plug-n-play card, configuring your network IP address, and attaching the network interface cable. Locking - Hardwire Adapter: Reliable locking NEMA 5-15 plug to secure load circuits to the output sockets of the inverter. Heavy-duty design locks the plug in place to prevent disconnecting critical loads.
Specifications 100 to 120 VAC Output Range MAJORSINE1000-24-2U MAJORSINE1000-48-2U MAJORSINE2000-48-2U DC Input Voltage 20-30 VDC 40-60 VDC 40-60 VDC Rated Current 50 Amps 25 Amps 50 Amps Fuse and DC Breaker Fuse and DC Breaker Fuse and DC Breaker Efficiency 24 VDC I/P, 120 VAC O/P 48 VDC I/P, 120 VAC O/P 48 VDC I/P, 120 VAC O/P AC Output (Load) Capacity 1KVA / 800W 1KVA / 800W 2KVA / 1600W Voltage 100, 110, 115, 120 VAC 100, 110, 115, 120 VAC 100, 110, 115, 120 VAC Voltage Regulation ±2% ±2% ±2% Frequency 50/60Hz ± 0.2Hz 50/60Hz ± 0.2Hz 50/60Hz ± 0.2Hz Wave Form Pure Sine Wave Pure Sine Wave Pure Sine Wave THD (linear load) 3% 120 V/100% 3% 120 V/100% 3% 120 V/100% THD (SPS load) 5% 120 V/100% 5% 120 V/100% 5% 120 V/100% Crest Factor 3:1 3:1 3:1 Receptacles (4) NEMA 5-20 R outlets (4) NEMA 5-15 R outlets (4) NEMA 5-20 R outlets Utility Power (Bypass) Voltage (Nominal) 120 VAC 120 VAC 120 VAC Frequency 50/60± 5 Hz 50/60± 5 Hz 50/60± 5 Hz AC Circuit Breaker AC Circuit Breaker AC Circuit Breaker Interface Communication SNMP / RS232 / Dry-contact SNMP / RS232 / Dry-contact SNMP / RS232 / Dry-Contact LED Display LCD Display Inverter On Output Voltage & Frequency Output Voltage & Frequency Output Voltage & Frequency System Model System Model System Model Internal Environmental Temp. Internal Environment Temp. Internal Environment Temp. Utility status Utility status Utility status Short circuit Short circuit Short circuit Over Temp. Over Temp. Over Temp. Short For 1 second; Switch to For 1 second; Switch to For 1 second; Switch to Bypass, then shutdown Bypass, then shutdown Bypass, then shutdown 105-125% for 3 minutes; 105-125% for 3 minutes 105-125% for 3 minutes 126-150% for 3 seconds; 126-150% for 3 seconds; 126-150% for 3 seconds >150% for 1 second; >150% for 1 second; >150% for 1 second; Switch to bypass Switch to bypass Switch to bypass Temperature 55 ± 5º(Inside the case) 55 ± 5º(Inside the case) 55 ± 5º(Inside the case) Environment Operating Temperature 0º to 50º C 0º to 50º C 0º to 50º C Storage Temperature -20º to 70º C -20º to 70º C -20º to 70º C Humidity 0º - 90ºC Relative Humidity 0º - 90ºC Relative Humidity 0º - 90ºC Relative Humidity (Non-Condensing) (Non-Condensing) (Non-Condensing) Acoustic Noise 46 dba @ 1 M 46 dba @ 1 M 46 dba @ 1 M Safety Safety UL / cul UL / cul UL / cul EMI / RFI FCC Class A FCC Class A FCC Class A Mechanical Dimensions 17.32 W x 11.81 D x 3.46 H 17.32 W x 11.81 D x 3.46 H 17.32 W x 11.81 D x 3.46 H (440x300x88mm) (440x300x88mm) (440x300x88mm) Weight 7kg / 15.4lbs 7kg / 15.4 lbs 8kg / 17.6 lbs
MAJORSINE Power Inverter Specifications 100 to 120 VAC Output Range MAJORSINE1000-125-2U MAJORSINE2000-125-2U DC Input Voltage 100-150 VDC 100-150 VDC Rated Current 10 Amps 20 Amps Fuse and DC Breaker Fuse and DC Breaker Efficiency 125 VDC I/P, 120 VAC O/P 125 VDC I/P, 120 VAC O/P AC Output (Load) Capacity 1KVA / 800W 2KVA / 1600W Voltage 100, 110, 115, 120 VAC 100, 110, 115, 120 VAC Voltage Regulation ±2% ±2% Frequency 50/60Hz ± 0.2Hz 50/60Hz ± 0.2Hz Wave Form Pure Sine Wave Pure Sine Wave THD (linear load) 5% 120 V/100% 5% 120 V/100% THD (SPS load) 3% 120 V/100% 3% 120 V/100% Crest Factor 3:1 3:1 Receptacles (4) NEMA 5-15 R outlets (4) NEMA 5-20 R outlets Utility Power (Bypass) Voltage (Nominal) 120 VAC 120 VAC Frequency 50/60± 5 Hz 50/60± 5 Hz AC Circuit Breaker AC Circuit Breaker Interface Communication SNMP / RS232 / Dry-contact SNMP / RS232 / Dry-Contact LED Display LCD Display Inverter On Output Voltage & Frequency Output Voltage & Frequency System Model System Model Internal Environment Temp. Internal Environment Temp. Utility status Utility status Short circuit Over Temp. Short circuit Over Temp. Short For 1 second; Switch to For 1 second; Switch to Bypass, then shutdown Bypass, then shutdown 105-125% for 3 minutes 105-125% for 3 minutes 126-150% for 3 seconds; 126-150% for 3 seconds >150% for 1 second; >150% for 1 second; Switch to bypass Switch to bypass Temperature 55±5º (Inside the case) 55±5º(Inside the case) Environment Operating Temperature 0º to 50º C 0º to 50º C Storage Temperature -20º to 70º C -20º to 70º C Humidity 0º - 90ºC Relative Humidity 0º - 90ºC Relative Humidity (Non-Condensing) (Non-Condensing) Acoustic Noise 46 dba @ 1 M 46 dba @ 1 M Safety Safety UL / cul UL / cul EMI / RFI FCC Class A FCC Class A Mechanical Dimensions 17.32 W x 11.81 D x 3.46 H 17.32 W x 11.81 D x 3.46 H (440x300x88mm) (440x300x88mm) Weight 7kg / 15.4 lbs 8kg / 17.6 lbs
MAJORSINE Power Inverter Specifications 208 to 240 VAC Output Range MAJORSINE1000i-48-2U MAJORSINE2000i-48-2U DC Input Voltage 40-60 VDC 40-60 VDC Rated Current 25 Amps 50 Amps Fuse and DC Breaker Fuse and DC Breaker Efficiency 48 VDC I/P, 230 VAC O/P 48 VDC I/P, 230 VAC O/P Output (Backup) Capacity 1KVA / 800W 2KVA / 1600W Voltage 208, 220, 230, 240 VAC 208, 220, 230, 240 VAC Voltage Regulation ±2% ±2% Frequency 50/60Hz ± 0.2Hz 50/60Hz ± 0.2Hz Wave Form Pure Sine Wave Pure Sine Wave THD (linear load) 3% 120 V/100% 3% 120 V/100% THD (SPS load) 5% 120 V/100% 5% 120 V/100% Crest Factor 3:1 3:1 Receptacles (4) IEC 320 outlets C13 (4) IEC 320 outlets C13 Utility Power (Bypass) Voltage Nominal 230 VAC Nominal 230 VAC Frequency 50/60± 5 Hz 50/60± 5 Hz AC Circuit Breaker AC Circuit Breaker Interface Communication SNMP / RS232 / Dry-contact SNMP / RS232 / Dry-Contact LED Display LCD Display Inverter On Output Voltage & Frequency Output Voltage & Frequency System Model System Model Internal Environment Temp. Internal Environment Temp. Utility status Utility status Short circuit Over Temp. Short circuit Over Temp. Short For 1 second; Switch to For 1 second; Switch to Bypass, then shutdown Bypass, then shutdown 105-125% for 3 minutes 105-125% for 3 minutes 126-150% for 3 seconds; 126-150% for 3 seconds >150% for 1 second; >150% for 1 second; Switch to bypass Switch to bypass Temperature 55±5º(Inside the case) 55±5º(Inside the case) Environment Operating Temperature 0º to 50º C 0º to 50º C Storage Temperature -20º to 70º C -20º to 70º C Humidity 0º - 90ºC Relative Humidity 0º - 90ºC Relative Humidity (Non-Condensing) (Non-Condensing) Acoustic Noise 46 dba @ 1 M 46 dba @ 1 M Safety Safety CE Approved CE Approved EMI / RFI FCC Class A FCC Class A Mechanical Dimensions 17.32 W x 11.81 D x 3.46 H 17.32 W x 11.81 D x 3.46 H (440x300x88mm) (440x300x88mm) Weight 7kg / 15.4 lbs 8kg / 17.6 lbs
MAJORSINE Power Inverter Mechanical Drawing