ICM 400. Three Phase Voltage Monitor with Reset Switch. Low cost line voltage protection for 3-phase motor systems

Similar documents
R & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.

Tornado F-5. Motor Backspin Detect Relay And Probe For F-5 Motor Controller

User Manual THREE PHASE VOLTAGE MONITOR RELAY FASEALERT-3 MODEL F3D. The best solutions for automation and protection.

MICRO GROW GREENHOUSE SYSTEMS, INC

Install Motor Controller User Manual

Reverse Protection Relay 2. Control Power Supply Voltage None: 200/220 VAC 380: 380/400 VAC 440: 440 VAC

Installation and Operation Guide for PD5200 and PD5300 Automatic Transfer Switch

Ordering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel

Global Water globalw.com. Global Water. Instrumentation, Inc.

HUBBCOM GSC3000/GSC4000 Flush-Mount Smart Controller Quick Installation Guide

CA-A480-A Elevator Controller. Reference & Installation Manual

INSTRUCTION MANUAL RA 19-7B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

Installation, Operation and Maintenance Manual

INSTRUCTION MANUAL RA 19-6B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies

FNet Repeater Installation & Operator s Instruction Manual

INSTRUCTION MANUAL RA 19-4B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

INSTRUCTION MANUAL RA 19-5B RACK ADAPTER HOT SWAP RACK ADAPTER FOR HSF SERIES POWER SUPPLIES

MYRIAD QLC 4-CHANNEL MONITOR/CONTROLLER INSTRUCTION MANUAL

LINE VOLTAGE TESTER CT101 USER S MANUAL. Please read this manual carefully and thoroughly before using this product.

Long-time range model (0.1 min to 10 h) 24 VAC; SPDT H3RN-1 H3RN-11 12, 24 VDC DPST-NO H3RN-2 H3RN-21

MICRO GROW GREENHOUSE SYSTEMS, INC ZEVO DR., SUITE B-1, TEMECULA, CA PHONE (951) FAX

ACLD Channel Opto-isolated Digital Input Board

CM68 4 Channel NTSC/PAL Video Decoder

Operating Bulletin MODBUS-RTU. The Fastest Flow Controller Company in the World!

I/O Expansion Box Installation & Operator s Instruction Manual

USER MANUAL CCHP-6000-XX 6kJ/s Capacitor Charging Power Supply

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

TB-24P/24R/16P8R. Relay Outputs or Isolated Inputs Terminal Board Series

EASON TECHNOLOGY. IO8 & IO24 Break-Out Module

Bid Specifications and General Description

Ordering Information. I/O Relay G7T. Model Number Legend Slim-styled I/O Relay Saves Space in Panel

SOLVES-IT! 4 CHANNEL TIMER APPLICATION MODULE

Time-limit operation/ self-resetting DPDT --- H3M H3M with Y92F-40 adapter SPDT SPDT H3M-H H3M-H with Y92F-40 adapter

Wasp Embedded Controller

POWER SERIES Plus. 3 in 1 AC Voltage. Digital Switchboard Meter. User s Manual IM2493VVV-2

VIP-812A DUAL NETWORKED STATION PORT

MAXIMA + Series ROTARY LEVEL CONTROL

MAXIMA + Series ROTARY LEVEL CONTROL

Features. Measuring and Monitoring Relays K8AB Series. Cut by 50% Industry First! Two SPDT Outputs Available in New Models DIN Sized at 22.

TrendSense. Instructions for Use. TrendSense and TrendSense Communicator

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L MONITORED DEVICE

MICRO GROW GREENHOUSE SYSTEMS, INC

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

TB-100 ControLynx Terminal Block

IPS INTELLIGENT PUMP STARTER

VE8014A/VE8014AR QUAD NETWORKED STATION PORT

CM Mpixel CMOS Imaging Camera

XBDM. 1015LV, 1020LV, 1030LV, 1020HV Models USER & INSTALLATION MANUAL BYPASS DISTRIBUTION MODULE

ZC Series Zone Monitoring Controllers

Conductive Level Controller

MAXIMA+ Series Rotary Level Indicator

Section 1 Introduction

MSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR

TrendSense and TrendSense W

F E B R U A R Y 23, UT-ID Reverse Phase Relay (613BY) Line Monitors

Sonic Ruptor 400. User Manual

Solid State Relays with Failure Detection Function

INSTALLATION INSTRUCTIONS

PD10. Pulse Divider Instructions PROUDLY MADE IN THE USA

RB24 Relay Box Installation Guide For use in low voltage motorized window and skylight systems

Evolution Variable Output. With Override Pot. Hired Hand, Inc Co Rd 68 PO Box 99 Bremen, AL 35033

Operating Instructions. For. Level Control Module. Model SSR 1000

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

Tempco Instruction Manual

Manual, TAPS Traction Auxiliary Power Supply

MiT. MOVING image TECHNOLOGIES INSTRUCTIONS FOR INSTALLATION, OPERATION, AND MAINTENANCE

Innovative Circuit Technology Ltd.

INSTRUCTION MANUAL A START-UP AND SHUT DOWN LOAD SEQUENCER AND AUTOMATIC LOAD SHEDDING SYSTEM WITH INTEGRAL RELAYS FOR 8 LOADS MODEL #091-60A

KBMG MULTI-SPEED BOARD

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

IRB-MON O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY PHOTOEYE U L M O N I T O R E D DEVICE

10 Degree of Freedom IMU Sensor +-16G, dps, +-8Gauss, hPa

INSTRUCTION MANUAL IM253 R0. AquaStart COMBINATION SOFT STARTERS START-UP MANUAL

Proliphix EPA-60 Installation Guide

700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL

Wireless Expansion Module V2.0 OMN-RCV3. Reference & Installation Manual. Stand-Alone System

INSTRUCTION MANUAL RA 55 RACK ADAPTER RACK ADAPTER FOR MST SERIES POWER MODULES

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-300

G3FM. Model Number Structure. Ordering Information. Solid State Relays. Model Number Legend. List of Models

1510 MOTOR CONTROLLERS

Instruction Sheet ICLS-COOL TM. Quiet-Cool Series Closet Cooler ICLS-COOL1 ICLS-COOL2

Number of input channels

Type High-sensitivity. Medium-sensitivity models models Sensed current 30 ma (fixed) 100 ma/200 ma 200 ma/500 ma 500 ma/1,000 ma Operating time

IRB-MON UNIVERSAL SAFETY PHOTOEYE OPERATING UL MONITORED DEVICE

V-9908 MESSAGE/PAGE PANEL

COBEX RECORDERS, INC.

62533 Ethernet Adapter

Mold Control Systems, Inc.

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

G3S4-A 5 VDC 12 VDC 24 VDC 0.6 A at 75 to 264 VAC (See note 1.) G3S4-A1 5 VDC 12 VDC 24 VDC Yes G3SD-Z01P-PD 1 A at 3 to 26 VDC (See note 2.

TC1880 Series. 4/5/6/8 Channel RS-232 FIBER OPTIC MICRO MUX User's Manual

OPERATING AND SERVICE MANUAL. Universal Interface Device 47

Teslights Hybrid Lighting SCALAMAX Protocol LX10 Gateway Series. Document Number: IN R01 Copyright SCALAMAX, LLC

Photoelectric Sensor

Rimage AutoPrinter II TM User Guide

EM-15 / EM-20 Energy Management Switch

Model Number Structure. Power Controllers G3PX. Single-phase Models. Model Number Legend

Installation manual Digital Energy USB / RS232 / Relay Interface Card for use with GE Digital Energy VH Series UPS VA

MC5 Smart Relay Adapter

Transcription:

ICM 400 Three Phase Voltage Monitor with Reset Switch Low cost line voltage protection for 3-phase motor systems 3-Position Reset Switch: MAN-MAN AUTO-AUTO AUTO-MAN Installation, Operation & Application Guide For more information on our complete range of American-made products plus wiring diagrams, troubleshooting tips and more, visit us at www.icmcontrols.com

Specification Input Line Voltage: Universal, 190-630 VAC Control Voltage: 18-240 VAC Frequency: 50-60 Hz Frequency: 50-60 Hz Load Side Monitoring: Optional Output Type: Relay, SPDT Voltage Range: 240VAC @ 10A maximum Frequency: 50-60 Hz Control Operating Temperature Operating Temperature: -40ºF to +167ºF (-40ºC to +75ºC) Storage Temperature: -40ºF to +185ºF (-40ºC to +80ºC) Response Times Phase Loss: 2 seconds maximum Unbalance/High/Low: Full selected trip delay period Mechanical Mounting: Surface mount using (2) #8 screws Terminations: Screw terminals Weight: 12 ounces (341 grams) Dimensions 6 1/2 L, 4 1/4 W, 1 3/8 H (16.5 cm. L, 10.8 cm. W, 3.5 cm. H) Parameters Phase Unbalance Protection Voltage Unbalance: 2-25% adjustable Over/Under Voltage Protection Under Voltage: -12% fixed, -6% for reset Over Voltage: +12% fixed, +6% for reset Phase Loss Protection Phase Loss Condition: Equals 25% of nominal for any given phase; system will shut down should this occur Lockout Delay Timer Input: 18-240 VAC RMS Time Delay:.1 to 5 minutes adjustable Tolerance: +/-20% Bypass resistor (24 VAC only): 1 kohm @ 24 VAC Fault Interrogation Delay Time Delay: 1-15 seconds adjustable Provides a delay between fault detection and system shutdown - helps to eliminate nuisance trips or unnecessary shutdowns Caution Installation of the ICM400 shall be performed by trained technicians only. Adhere to all local and national electric codes. Disconnect all power to the system before making any connections.

Installation 1. Using (2) #8 screws, mount the ICM400 in a cool, dry, easily accessible location in the control panel enclosure. 2. Connect voltage as shown in Figure 1 (below). Leave existing line and load side connections intact on the contactor. Note: Load side monitoring is optional (unit may be used to monitor line side only). 3. Wire the contactor and control voltage monitoring as in Figures 2 and 3 (below). Note: Load/line wire must be rated for 3-phase voltage rating, 20ga minimum. 4. Upon application of power, the ICM400 will be online and will begin to monitor the system. Figure 1 Incoming 3-phase voltage from load or back side of contactor (optional) LOAD 3 LOAD 2 LOAD 1 LINE 3 Incoming 3-phase LINE voltage from line or 2 front side of contactor LINE (190-600 VAC) 1 Terminals 1 and 3 are the control signal input terminals There must be a voltage present on terminals 1 and 3 for the relay output terminals 4 and 6 to close; this voltage can be supplied from a thermostat, pressure switch, etc. When the voltage on these terminals is re-applied, the unit will not re-energize until the lockout delay (.1 to 5 minutes) time has elapsed 6 5 4 Figure 3 3 1 Contactor Coil Contactor Voltage (18-240 VAC) 6 5 4 * Switch can be a thermostat, pressure switch, etc. Control Voltage (18-240 VAC) Figure 2 Short pins when using 24 VAC control voltage with anticipator type thermostat Terminals 4 and 6 are dry, normally open contacts Terminals 4 and 6 are closed when power is within specifications Terminals 4 and 6 open when there is a fault condition or loss of control signal 3 1

3-Position Reset Switch Operation Choose from three, easy-to-select reset mode positions to best meet the needs of your system. The modes of operation for each position are described below. Position 1: FULL MANUAL RESET (MAN-MAN) Manual control reset required on both the front (line) and back (load) side of system. Used for highly critical loads. System will not reset until fault is corrected and manually reset by personnel. After a front side fault the unit will restart only if all of the following conditions are met: The Reset Mode switch is moved to the AUTO-AUTO position After a back side fault the unit will restart only if all of the following conditions are met: The Reset Mode switch is moved to the AUTO-AUTO position Position 2: FULL AUTOMATIC RESET (AUTO-AUTO) Control automatically resets front (line) and back (load) sides of system. Used on less critical loads. Helps eliminate unnecessary service calls. After a front or back side fault, the unit will restart only if all of the following conditions are met: Position 3: AUTO FRONT/MANUAL BACK RESET (AUTO-MAN) Automatic reset on the front (line) side only. Back (load) side requires manual reset. Typically used with reliable power supply. Back side faults require service evaluation and manual reset. After a front side fault the unit will restart only if all of the following conditions are met: After a back side fault the unit will restart only if all of the following conditions are met: The Reset Mode switch is moved to the AUTO-AUTO position

ICM400 Setup Voltage Adjust: Set knob to match 3-phase voltage of system Fault Interrogation (in seconds): Set to the amount of time for the ICM400 to analyze a non-critical fault* before de-energizing the load ** Recommended: 7 to 8 seconds Lockout Time Delay (in minutes): Set to the amount of time between the de-energizing of the load and the ICM400 attempting to re-energize the load ** Recommended: 4 minutes % Voltage Unbalance: Set to the amount of allowable voltage unbalance between the 3-phase lines ** Recommended: 4 to 5% * Non-critical faults are faults such as high/low voltage and phase unbalance. Critical faults are phase loss and phase reversal. When a critical fault is detected, the load is de-energized immediately. ** For best recommendations, consult manufacturer of motor/compressor. ICM400 Wiring Diagrams 2-Pole Contactor LOAD LOAD LOAD 3 2 1 L03 LINE LINE LINE 3 2 1 LI3 LI2 LI1 3-Pole Contactor LOAD LOAD LOAD 3 2 1 LINE LINE LINE 3 2 1 LI3 LI2 LI1 Control Voltage Control Voltage L01 L02 * Thermostat, pressure switch, etc. L0AD L01 L02 L03 * Thermostat, pressure switch, etc. L0AD

Typical System Diagram Line Voltage Control Transformer * Thermostat * Install jumper for 24 VAC anticipator type thermostats. Contactor Compressor

Problem LED Status Corrective Action Load will not energize All LEDs are OFF Check incoming power and/or control voltage input Load turns ON and OFF The load short-cycles when the thermostat is repeatedly opened and closed (thermostat bounce) Troubleshooting Front fault LED ON Front fault LED ON High or low LED ON Slowly turn the Voltage Unbalance knob to maximum (25%): If a fault condition continues, check for phase loss with voltmeter If a fault condition still exists, reverse any two of the phases on the line side of the ICM400* Turn the Voltage Adjust knob up or down very slowly until either High or Low voltage LED turns off Lockout LED ON Turn Lockout Time Delay knob to.1 minutes; set reset switch to the AUTO-AUTO position Front fault LED ON after the load is OFF Back fault LED ON Lockout LED ON Back fault LED ON Slowly adjust the Voltage Unbalance knob to a higher percentage Check for voltage unbalance, phase loss or phase reversal on the load side of the ICM400 Reconnect the control input as outlined in the (see Typical System Diagram (see Page 4) * Only swap phases during initial setup, not after the ICM400 has been in operation without errors. Note: After troubleshooting, reset all adjustment knobs and switches to motor/ compressor manufacturer s recommendations.

ONE-YEAR LIMITED WARRANTY The Seller warrants its products against defects in material or workmanship for a period of one (1) year from the date of manufacture. The liability of the Seller is limited, at its option, to repair, replace or issue a non-case credit for the purchase prices of the goods which are provided to be defective. The warranty and remedies set forth herein do not apply to any goods or parts thereof which have been subjected to misuse including any use or application in violation of the Seller s instructions, neglect, tampering, improper storage, incorrect installation or servicing not performed by the Seller. In order to permit the Seller to properly administer the warranty, the Buyer shall: 1) Notify the Seller promptly of any claim, submitting date code information or any other pertinent data as requested by the Seller. 2) Permit the Seller to inspect and test the product claimed to be defective. Items claimed to be defective and are determined by Seller to be non-defective are subject to a $30.00 per hour inspection fee. This warranty constitutes the Seller s sole liability hereunder and is in lieu of any other warranty expressed, implied or statutory. Unless otherwise stated in writing, Seller makes no warranty that the goods depicted or described herein are fit for any particular purpose. 7313 William Barry Blvd., North Syracuse, NY 13212 (Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276 www.icmcontrols.com LIA152-2