32MP Gateway Overview and Configuration Manual
32MP Gateway Overview and Configuration Manual
This document is the property of Carrier Corporation and is delivered on the express condition that it is not to be disclosed, reproduced in whole or in part, or used for manufacture by anyone other than Carrier Corporation without its written consent, and that no right is granted to disclose or so use any information contained in said document. Carrier reserves the right to change or modify the information or product described without prior notice and without incurring any liability. 1993, Carrier Corporation
Manual Revisions The 32MP Gateway Overview and Configuration Manual is catalog number 808-824 Rev. 11/93. This manual replaces the 32MP Gateway Overview and Configuration Manual (808-824) 9/92. The following changes were made since the last revision. Section/Chapter Overview Changes On Pages 5 and 10 under the topics BEST Program Access, added the following: BEST IV can write data to only those points that are accessible to the Data Tranfer function. To see the list of point names that Data Transfer can access, refer to Table 1 on Page 9. Configuration 1. Modified the last paragraph on Page 11 of the Points Screen section to read: The commands can come from an operator, or from other devices on the CCN, such as the CHILLERVISOR System Manager, Data Transfer, or BEST IV. 2. In the Points Screen section, stated that the following points could be used in conjunction with BEST IV: Chiller Start/Stop LCW Control Point Demand Limit Compressor Ontime Remote Contacts Input Spare Sensor 2, Spare Sensor 3, Spare Sensor 4 BEST Program Access In the General Information section, deleted the following sentence from the first paragraph: BEST cannot write to data in the Gateway. iii
iv
Contents Overview... 1 About this Manual... 1 Introduction... 2 32MP Gateway Hardware... 2 32MP Gateway Functions... 4 Program Enable/Disable... 4 Elapsed On-time Tracking... 4 Remote Contact Start/Stop... 4 Shutdown and Communication Alarms... 5 BEST Program Access... 5 CHILLERVISOR System Manager Support... 5 Operator Interface... 5 Network Functions... 8 Data Collection... 8 Data Transfer... 8 BEST Program Access... 9 Configuration... 11 General Information... 11 Points Screen... 11 Service Configuration Screen... 21 Configuration Screen... 31 Maintenance Screen... 41 Alarm Configuration Screen... 48 BEST Program Access... 51 General Information... 51 v
Configuration Sheets... 59 Tables Table 1 Point Names and Types for Data Collection and Transfer... 9 Table 2 Table 3 Table 4 Table 5 Table 6 Table 7 Table 8 Table 9 Points Screen (Single Compressor)... 51 Points Screen (Dual Compressor)... 52 Service Configuration Screen (Single Compressor)... 53 Service Configuration Screen (Dual Compressor)... 54 Configuration Screen (Single Compressor)... 55 Configuration Screen (Dual Compressor)... 56 Maintenance Screen (Single Compressor)... 57 Maintenance Screen (Dual Compressor)... 58 Figures Figure 1 32MP Gateway... 3 Figure 2 32MP Gateway Points Screen (Single Compressor)... 12 Figure 3 Figure 4 Figure 5 32MP Gateway Points Screen (Dual Compressor)... 13 32MP Gateway Service Configuration Screen (Single Compressor)... 22 32MP Gateway Service Configuration Screen (Dual Compressor)... 23 vi
Figure 6 Figure 7 Figure 8 Figure 9 32MP Gateway Configuration Screen (Single Compressor)... 32 32MP Gateway Configuration Screen (Dual Compressor)... 33 32MP Gateway Maintenance Screen (Single Compressor)... 41 32MP Gateway Maintenance Screen (Dual Compressor)... 42 Figure 10 Alarm Configuration Screen... 48 vii
viii
Overview
Overview About this Manual The purpose of this manual is to provide information on the 32MP Gateway s hardware, functions, and configuration. This manual is divided into four sections. The Overview section gives a detailed description of the 32MP Gateway hardware and functions. The Configuration section presents 32MP Gateway screens as they are displayed at the Building Supervisor and gives specific information about each item on the screen. This section provides a crossreference between Building Supervisor displays and the 3200MP Controller information contained in the following start-up, operation and maintenance instructions available through Carrier Literature Distribution: 19DK (531-919) 19DM (531-962) 19DR with DM Compressor (531-926) 19DR with DK Compressor (531-928) 19EB (531-910) 17DK (531-708) 17DM (531-707) 17DR with DM Compressor (531-704) 17DR with DK Compressor (531-717) 3200MP Controller Retrofit (808-009) 3200MP Expanded Services Panel II Start-up, Operation and Maintenance Instructions (533-211) also applies to the listed equipment. The BEST Program Access section provides a list of table, point, and decision numbers that can be used in BEST programs. The Configuration Sheets section provides a copy of the 32MP configuration sheets. 1
Introduction The 32MP Gateway is a component of the Carrier Comfort Network (CCN) CHILLERVISOR system. The 32MP Gateway integrates a centrifugal chiller into the Carrier Comfort Network (CCN). The chiller must be equipped with a 3200MP Controller and an ESP-II Expanded Services Panel. The 32MP Gateway can be used with both single and dual compressor chillers. A single 32MP Gateway provides interface functions for one chiller. A CCN Building Supervisor communicating through a 32MP Gateway can be used to configure certain ESP-II and 3200MP Controller parameters, and to display current operating conditions of the chiller connected to them. The Building Supervisor also annunciates alarms and displays alarm messages generated by the 32MP Gateway. BEST, Carrier s custom programming language, can access points and decisions in a 32MP Gateway. BEST programs, which reside in a FID, can read data from 32MP Gateway parameters displayed on the points, service configuration, configuration, and maintenance screens. 32MP Gateway Hardware The 32MP Gateway is a CCN CIO (Communications Input/Output) Module equipped with specialized software that enables it to perform its interface functions. The 32MP Gateway is shown in Figure 1. COMM1 is the 32MP Gateway s connection to the CCN Communication Bus. The bus can operate at 1200, 2400, 4800, or 9600 bits per second (bps). It typically operates at 9600 bps. A 32MP Gateway can reside on any CCN Communication Bus, 0-239, and can be assigned any system element number, 1-239. The 32MP Gateway s default address is Bus 0, System Element 85. COMM2 is the Gateway s connection to the 3200MP Controller Communication Bus. The 3200MP Controller Communication Bus operates at 1200 bps. For this reason, COMM2 also operates at 1200 bps. 2
The Network Configuration Tool (NCT) may be used to change the 32MP Gateway s bus and system element numbers and the baud rate of COMM1 if necessary. Figure 1 32MP Gateway 3
32MP Gateway Functions The 32MP Gateway s primary function is to integrate a centrifugal chiller equipped with a 3200MP Controller and an ESP-II panel into the Carrier Comfort Network II. Other 32MP Gateway functions include: Program enable/disable Elapsed on-time tracking Remote Contacts Start/Stop Shutdown and communication alarms BEST program access CHILLERVISOR System Manager (CSM) support Each function is described in detail below. Program Enable/ Disable On initial power up, the 32MP Gateway automatically determines whether it is connected to a single or dual compressor chiller. Because of this, a Building Supervisor cannot display 32MP Gateway data if the gateway is not connected to a functional 3200MP Controller Communication Bus. Two switches on the 3200MP Controller allow the user to enable and disable the 32MP Gateway manually. The two switches are the Local/Remote switch on the 3200MP s Setpoint/Display Board, and the Panel/Remote switch on the ESP-II panel. The 32MP Gateway s ability to write to the 3200MP/ESP-II software is disabled when either switch is not in the Remote position. If the switches are in the Local or Panel modes, chiller parameters can be displayed, but configuration changes cannot be made. Elapsed On-time Tracking Remote Contact Start/Stop The 32MP Gateway accumulates up to 32,767 hours of elapsed ontime for its chiller. The accumulated on-time value is displayed on the Building Supervisor s points screen, and may be modified by an operator using the Building Supervisor. The 32MP Gateway and the ESP-II panel each include a remote contact option that, when enabled, allows the chiller to be stopped and started by contact closure input from a field-installed remote start relay. Because the gateway supercedes the ESP-II panel in initiating the chiller's starts and stops, it automatically disables the panel's remote contacts option. The panel's option can be enabled, 4
but it will be disabled by the gateway as soon as the panel is returned to remote mode. Because of this, when enabling, disabling, or checking the status of the remote contact option the user should do so at the 32MP Gateway, not at the ESP-II panel. Shutdown and Communication Alarms BEST Program Access CHILLERVISOR System Manager Support The 32MP Gateway generates two types of alarms. A CHILFAIL alarm is generated if a 3200MP Controller shutdown fault occurs. The 3200MP status code is included in this alarm message. A CHILCOMM communication error alarm is generated in the event of a communication failure between the 32MP Gateway and the 3200MP Controller/ESP-II. If the communication failure is with the 3200MP within the chiller or with the cable from the chiller to the 32MP Gateway, a code value of 1 is included with this alarm message. If the communication failure is with the ESP-II within the chiller, a code value of 2 is included with this alarm message. When alarms occur, they are annunciated at the Building Supervisor and the alarm messages are placed into its alarm file. BEST programs, which reside in a FID, can access 32MP Gateway points and decisions. BEST can read data from 32MP Gateway parameters displayed on the points, service configuration, configuration, and maintenance screens through the appropriate tables. BEST IV can write data only to those points that are accessible by the Data Transfer function. To see the list of point names that are accessible by Data Transfer, refer to Table #1 on Page 9. The CHILLERVISOR System Manager (CSM) is a device that coordinates chillers equipped with 32MP Gateways. It can coordinate the operation of up to eight centrifugal chillers. The 32MP Gateway contains a dedicated internal data structure that can be accessed by the CSM. For specific information regarding the CSM, refer to the CSM Overview and Configuration Manual (808-625). Operator Interface The Building Supervisor is the primary operator interface to the 32MP Gateway. Once a 32MP Gateway is connected to a 3200MP Controller Communication Bus and a CCN Communication Bus, an operator at a Building Supervisor can add it to the Carrier Controls List and upload the data from the 32MP Gateway to the Building Supervisor s database. 5
An operator working at a Building Supervisor can then: display a list of 32MP Gateway points that shows current conditions at the chiller and the last five shutdown codes. modify selected points and return them to local control. display configuration and maintenance screens and change 3200MP Controller configuration data. create graphics. There are eight screens associated with the 32MP Gateway: Points screen Service configuration screen Configuration screen (CONFIG1) Maintenance screen Alarm configuration screen (ALRM-CFG) Runtime Equipment Part Configuration screen (RUN-POC1) Consumable Equipment Part Configuration screen (CONS- POC1) Controller Identification screen (CTLR-ID) The Points screen displays the current status of chiller parameters such as status codes, setpoints, and operating temperatures. The status of selected points can be modified by the operator using the Building Supervisor s Force function. The force can be removed using the Auto function. Note that the Auto function removes only the SUPVSR force message from the Building Supervisor screen. The value entered remains in effect at the 3200MP/ ESP-II. From the Points screen, an operator can modify the values of the following points: Chiller Start/Stop Leaving Chilled Water (LCW) Control Point Demand Limit Compressor On-time Remote Contact Input 6
Note: Due to the nature of communications between the 32MP Gateway and the 3200MP Controller/ESP-II combination, it can take up to thirty seconds for the modified value to be displayed on the Building Supervisor screen. The Service configuration screen displays service parameters read by the 32MP Gateway from the configuration (DIP) switches located on the 3200MP Controller. Service parameters include machine, starter, and sensor types. The Configuration screen allows an operator to enter data used by the 3200MP s reset, restart, and remote contacts options. The table named CONFIG1 is selected to display this screen. The Maintenance screen displays the current status of the 3200MP Controller s inputs and outputs. The Alarm configuration screen is displayed by selecting the table named ALRM-CFG. This screen is a listing of 32MP Gateway alarm configuration decisions such as Alarm System Name and Re- Alarm Time. Specific information on each item displayed on the Points, Service Configuration, Configuration, Maintenance, and Alarm Configuration screens is provided in the Configuration section beginning on Page 11. The Runtime and Consumable Equipment Part Configuration screens are displayed by selecting the tables named RUN-POC1 and CONS-POC1. If 32MP Gateway points are to be used in conjunction with the Runtime and Consumable supervisory parts of a CCN Data Collection Option, this is where the point names and types of those points are entered. See Page 8 for more information on Data Collection. The Controller Identification screen lists 32MP Gateway controller parameters such as device name, description and location, and software and assembly part numbers. The table named CTLR-ID is selected to display this screen. 7
The 32MP Gateway can display units in either imperial or metric format when used with the Building Supervisor III. Data from gateways used with the Building Supervisor II can be displayed in imperial units only. Network Functions Data Collection The CCN network functions that are relevant to a 32MP Gateway are the Data Collection and Data Transfer Options, and BEST programs. The CCN Data Collection Option can be used to collect data from the 32MP Gateway points listed in Table 1. Points must be specified by name and type when configuring the Data Collection Option s supervisory part. Consumable and Runtime point names and types must also be configured in the 32MP Gateway s equipment parts (CONS-POC1 and RUN-POC1). For more information on the Data Collection Option, refer to the Data Collection Option Overview and Configuration Manual (808-556). Consumable and Runtime equipment part configuration sheets can also be found in that manual. Data Transfer The CCN Data Transfer Option can be used to transfer data from or to the 32MP Gateway points listed in Table 1. To transfer data from the 32MP Gateway, the point names given in Table 1 must be configured in the Source Variable Name decisions at the Data Transfer Option. These point names must also be used when transferring data to the Gateway. A data transfer to a point results in a controller force on that point. For this reason, it is recommended that caution be used when transferring data to the 32MP Gateway. Data should not be transferred to the spare sensor points. For more information on the Data Collection Option, refer to the Data Transfer Option Overview and Configuration Manual (808-557). 8
Table 1 Point Names and Types for Data Collection and Transfer Description Type Point Name Point Chiller Start/Stop CHIL_S_S Discrete LCW Control Point LCW_STPT Analog Demand Limit DEM_LIM Analog Compressor Ontime ONTIME Analog Remote Contacts Input REM_CON Discrete Spare Sensor 2 SPARE2 Analog Spare Sensor 3 SPARE3 Analog Spare Sensor 4 SPARE4 Analog BEST Program Access BEST programs, which reside in a FID, can access 32MP Gateway points and decisions. BEST can read data from 32MP Gateway parameters displayed on the points, service configuration, configuration, and maintenance screens. Each item displayed is indexed by a table number corresponding to the screen on which it appears, and by point or decision number. Section 3 of this manual contains a complete list of table, point, and decision numbers. Note: With the exception of the points listed in Table 1 above, the points listed in Section 3 can only be accessed by table and index number. In BEST programs the CONNECT statement is used to access 32MP Gateway parameters. Use the following format to read any 32MP Gateway point or decision: CONNECT var AS A DECISION TO table, index IN number where var is a user-defined name for the point or decision. table is a number corresponding to the 32MP Gateway screen on which the point or decision appears. index is a number corresponding to the 32MP Gateway point or decision. 9
number is a 32MP Gateway s system element number on a CCN Communication Bus. BEST IV can write data to only those points that are accessible to the Data Transfer function. To see the list of point names that Data Transfer can access, refer to Table 1 on Page 9. When using BEST IV to write to points, use this statement format to connect to variables: CONNECT var AS A type TO point IN element USING SAFETY LIMITS low, high Note: The format shown above can only be used for the points listed in Table 1. All other points must use the format shown on the previous page. Remember that the other points can only be read by BEST, not written to by BEST. For more information on BEST, refer to the CCN BEST IV Programmer's Reference Manual (808-699). 10
Configuration
Configuration General Information This section shows single and dual compressor 32MP Gateway screens displayed at the Building Supervisor. Specific information regarding individual parameters is given following each screen. Wherever possible, this section provides cross-reference to related Carrier documentation: 3200MP Controller Retrofit Startup, Operation, and Maintenance Manual 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions 17-series and 19-series Startup, Operation and Maintenance Manuals Title and catalog numbers for these documents are listed on Page 1 of this manual. Points Screen The Points menu item is used to select the Points screen. The Points screen displays current conditions at the chiller and the last five shutdown codes. The Building Supervisor or Service Tool s force operation can be used to modify the values of selected 32MP Gateway points. Transmitting a force command to one of these points causes its value to change and the SUPVSR force message to be displayed on screen with the point. Using the Auto operation removes the SUPVSR force message from the screen. The point does not return to the value it had before being forced. Of the 32MP Gateway points that can be modified, only Compressor On-time displays a dynamic value. The other modifiable points only change their values when commanded to. The commands can come from an operator, or from other devices on the CCN, such as CHILLERVISOR System Manager, Data Transfer, or BEST IV. 11
12 Figure 2 32MP Gateway Points Screen (Single Compressor)
Figure 3 32MP Gateway Points Screen (Dual Compressor) 13
The points screen for a 32MP Gateway installed on a single compressor chiller is shown in Figure 2. The points screen for a 32MP Gateway installed on a dual compressor chiller is shown in Figure 3. Specific point information follows. Chiller Status Code Lead Compressor Status Code Lag Compressor Status Code Maintenance Manual: Diagnostic Codes These points display current status code numbers. The Chiller Status Code point appears on the single compressor points screen only. The Lead and Lag Compressor Status Code points appear on the dual compressor points screen only. Note: When the operator uses the ESP panel to place a chiller in its local test mode, a status code of 164 appears on the Building Supervisor screen. The ESP panel screen, however, displays the test mode information. Display Units Diagnostic code numbers Chiller Start/Stop The function of this point is analogous to that of the manual start/stop switch located on the 3200MP Controller s Setpoint/Display panel. This allows an operator (or external software such as the CSM or writing to this variable with the Data Transfer Option) to start and stop the chiller. This point also provides an indication of the chiller s current commanded status for the operator. This point can be modified by the operator, and can be used in conjunction with the Data Collection and Data Transfer Options, and BEST IV. For information on Data Transfer, refer to the Data Transfer Option Overview and Configuration Manual (808-557). The Remote Contact option is disabled when this point is forced. Display Units Stop Start 14
LCW Control Point Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying ESP Chilled Water Control Point This point displays the value of the Leaving Chilled Water Control Point currently in effect at the 3200MP Controller. This value defaults to the one entered by means of the Thermostat control on the Setpoint/Display panel, unless that value is overwritten either from the ESP-II panel or by the Chilled Water Reset option. This point can be modified by the operator, and can be used in conjunction with the Data Collection and Data Transfer Options and BEST IV. Display Units Degrees Demand Limit Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying Basic 3200MP Demand Limit Setpoint This decision displays the value of the Demand Limit setpoint. This value will be the same as the one entered by means of the Electrical Demand control on the 3200MP Controller s Setpoint/ Display panel, unless that value has been overwritten from the ESP-II panel. This point can be modified by the operator, and can be used in conjunction with the Data Collection and Data Transfer Options, and BEST IV. Display Units Percent kw Leaving Chilled Water Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying Machine Operating Parameters This is the current Leaving Chilled Water temperature. Display Units Degrees 15
Evaporator Refrigerant Trippoint Maintenance Manual: Safety Controls Analog Safety Control Limits; Capacity Overrides The chiller will shut down if the evaporator refrigerant temperature goes below the value displayed. This provides freeze protection for the chiller barrel. Display Units Degrees Evaporator Refrigerant Condenser Refrigerant Maintenance Manual: Safety Controls Analog Safety Control Limits; Capacity Overrides Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying Machine Operating Parameters These are the current evaporator and condenser refrigerant temperatures. Display Units Degrees Compressor Ontime At the time of installation the value of this point should be modified using the Building Supervisor s Force operation to correspond to the value displayed by the ontime indicator mounted on the chiller control panel. The Auto operation should then be used to remove the Force, allowing the point s value to increment. This value will increment up to 32,767 hours, then reset to 0 and continue. This point can be used in conjunction with the Data Collection and Data Transfer Options, and BEST IV. Display Units Hours 16
Remote Contacts Input Maintenance Manual: Remote Start/Stop Controls This decision displays the current status of the remote start contacts input. If the Remote Contacts Option is enabled on the Configuration screen and the status of this point is on, the chiller will start. When Chiller Start/Stop is forced, the Remote Contacts Option is disabled. This point can be modified by the operator, and can be used in conjunction with the Data Collection and Data Transfer Options, and BEST IV. Display Units Open = Remote start contacts open Closed = Remote start contacts closed Compressor Motor Load Compressor A Motor Load Compressor B Motor Load Maintenance Manual: Capacity Overrides The values displayed here are internally calculated values that the 3200MP Controller uses to correct differences in motor power factors at various loads. Compressor Motor Load is calculated by multiplying Compressor Motor Current by Amps Correction Factor. The Compressor Motor Load point appears on the single compressor points screen only. The Compressor A and B Motor Load points appear on the dual compressor points screen only. Display Units Percent Compressor Motor Current Compressor A Motor Current Compressor B Motor Current Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying Machine Operating Parameters These are compressor motor currents expressed as a percentage of RLA (Rated Load Amps). 17
The Compressor Motor Current point appears on the single compressor points screen only. The Compressor A and B Motor Current points appear on the dual compressor points screen only. Display Units Percent Motor Winding Motor A Winding Motor B Winding Maintenance Manual: Capacity Overrides Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying Machine Operating Parameters These are the current motor winding temperatures. The Motor Winding point appears on the single compressor points screen only. The Motor A and B Winding points appear on the dual compressor points screen only. Display Units Degrees Compressor Discharge Compressor A Discharge Compressor B Discharge Maintenance Manual: Analog Safety Control Limits Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying Machine Operating Parameters These are the current compressor discharge temperatures. The Compressor Discharge point appears on the single compressor points screen only. The Compressor A and B Discharge points appear on the dual compressor points screen only. Display Units Degrees 18
Thrust Bearing Thrust Bearing A Thrust Bearing B Maintenance Manual: Analog Safety Control Limits Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying Machine Operating Parameters These are the current thrust bearing temperatures. The Thrust Bearing point appears on the single compressor points screen only. The Thrust Bearing A and B points appear on the dual compressor points screen only. Display Units Degrees Spare Sensor 1 Maintenance Manual: Control Wiring Schematic Optional Sensor #1 Display Units Degrees Spare Sensor 2 Spare Sensor 3 Spare Sensor 4 Maintenance Manual: Control Wiring Schematic Optional Sensors #2, #3, #4 These spare points are provided as options and could be used to read any 5K thermistor sensor. Possible uses could be for condensor water or chilled water header supply and return temperatures. These points can be used in conjunction with the Data Collection and Data Transfer Options, and BEST IV. Note: Display Units Exercise care if using Data Transfer to transfer data into these points, as the Data Transfer Option only updates data once per minute. Degrees 19
Shutdown Code 1 Shutdown Code 2 Shutdown Code 3 Shutdown Code 4 Shutdown Code 5 Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying Stored Shutdown Status Codes Shutdown Code 1 shows the most recent shutdown code, Shutdown Code 2 the next most recent, Shutdown Code 3 the next, etc. The codes are explained in the 3200MP Expanded Services Panel Startup, Operation and Maintenance Instructions. Display Units Shutdown code number Control Voltage Reference: 3200MP Expanded Services Panel Start-up, Operation and Maintenance Instructions: Displaying Machine Operating Parameters This point displays the present control voltage. Display Units Volts (Vac) Starts In 6 Hours Maintenance Manual: Compressor Starts Reminder This is the number of times that the chiller has been commanded to start in the last six hours. Display Units Number of starts Compressor B Is Lead Reference: 17-series and 19-series Startup, Operation and Maintenance Manuals: Analog Expansion Board This point indicates the status of the Lead Compressor Selection switch on the Analog Expansion Board mounted inside the 3200MP Controller. This point appears on the dual compressor points screen only. Display Units No = Compressor B is lag Yes = Compressor B is lead 20
Remote Mode Enabled Maintenance Manual: Setpoint/Display Board This indicates the current status of the Local/Remote switch on the Setpoint/Display panel. Both the Local/Remote on the Setpoint/Display panel and the Panel/ Remote switch on the ESP-II panel must be set to the Remote position for the 32MP Gateway to process configuration changes. Display Units No = Local Yes = Remote Lag Disable Switch Set Reference: 17-series and 19-series Startup, Operation and Maintenance Manuals: Configuration (DIP) Switch Settings - Lag Compressor Enable/Disable This indicates the current position of the Lag Compressor Enable/ Disable switch, located at the 3200MP Controller. This point appears on the dual compressor points screen only. Display Units No = Lag enabled Yes = Lag disabled Service Configuration Screen The service configuration screen is selected by the operator at a Building Supervisor to display chiller service parameters, set by configuration (DIP) switches located on the 3200MP Controller s processor board. Service parameters cannot be changed from the Building Supervisor. The Service-Config menu item is used to select this screen. The service configuration screen for a 32MP Gateway installed on a single compressor chiller is shown in Figure 4. The service configuration screen for a 32MP Gateway installed on a dual compressor chiller is shown in Figure 5. Specific decision information follows. 21
22 Figure 4 32MP Gateway Service Configuration Screen (Single Compressor)
Figure 5 32MP Gateway Service Configuration Screen (Dual Compressor) 23
DM Compressor Maintenance Manual: Compressor Type Display Units No = not DM Yes = DM Machine Type Is CB Maintenance Manual: Machine Type This decision appears on the single compressor Service Configuration screen only. Display Units No = not CB (gear driven chiller) Yes = CB (non-gear driven chiller) Leaving Chilled Water (LCW) Deadband Maintenance Manual: LCW Deadband Display Units Degrees Leaving Chilled Water (LCW) Proportional Band Maintenance Manual: LCW Proportional Band Display Units Degrees Line Frequency Maintenance Manual: Line Frequency Display Units Hz Full Voltage Starter Type Maintenance Manual: Starter Type Display Units No = reduced voltage Yes = full voltage 24
Motor Sensor Type Maintenance Manual: Motor Winding Sensor Type Display Units Analog Discrete Thrust Sensor Type Maintenance Manual: Thrust Bearing Sensor Type This decision appears on the single compressor service configuration screen only. Display Units Analog Discrete Brine Medium Maintenance Manual: Chilled Medium Display Units No = Water Yes = Brine Fahrenheit Temperature Maintenance Manual: LCD Temperature Readout Display Units No = Degrees C Yes = Degrees F Chiller Controller ID Maintenance Manual: Controller Identification Number Display Units Chiller numbers 25
Compressor A Capacity Reference: 17-series and 19-series Startup, Operation and Maintenance Manuals: Relative Capacity of Compressor A This decision appears on the dual compressor service configuration screen only. Display Units Percent Y Degrees Selection Reference: 17-series and 19-series Startup, Operation and Maintenance Manuals: Y (degrees) This decision appears on the dual compressor service configuration screen only. Display Units Degrees X Minutes Selection Reference: 17-series and 19-series Startup, Operation and Maintenance Manuals: X (minutes) This decision appears on the dual compressor service configuration screen only. Display Units Minutes Local Ramp Rate Maintenance Manual: Ramp Loading Rate Display Units Degrees per minute Impeller Diameter Impeller Diameter A Impeller Diameter B Maintenance Manual: DM Compressor Identification Code Impeller Diameter decision is on the single compressor service configuration screen only. Impeller Diameter A and B decisions are on the dual compressor service configuration screen only. Display Units Inches 26
Switch Bank 3, Switch Positions: 2 3 4 5 1.442 = Off Off Off Off 1.303 = On Off Off Off 1.212 = Off On Off Off 1.142 = On On Off Off 1.056 = Off Off On Off 0.975 = On Off On Off 0.845 = Off On On Off 0.756 = On On On Off 1.712 = Off Off Off On 1.556 = On Off Off On 0.674 = Off On Off On 0.601 = On On Off On 1.012 = Off Off On On 1.789 = On Off On On Diffuser Width Diffuser Width A Diffuser Width B The values displayed in these decisions indicate the diffuser wall widths, in inches. The Diffuser Width decision appears on the single compressor service configuration screen only. The Diffuser Width A and B decisions appear on the dual compressor service configuration screen only. Display Units Inches 27
Switch Switch Function Switch Width Bank Position Settings (Inches) 2 5-8 Diffuser Width 5 6 7 8 4 1-2 Diffuser Width A 1 2 5 1-4 Diffuser Width B 1 2 3 4 6 6-7 Diffuser Width B 6 7 Off On Off On Off Off.44 On On Off On Off Off.45 Off Off On On Off Off.46 On Off On On Off Off.47 Off Off Off Off Off Off.48 Off On On On Off Off.49 On On On On Off Off.50 Off Off Off Off On Off.51 On Off Off Off On Off.52 Off On Off Off On Off.53 On On Off Off On Off.54 On Off Off Off Off Off.55 Off Off On Off On Off.56 On Off On Off On Off.57 Off On On Off On Off.58 On On On Off On Off.59 Off On Off Off Off Off.60 Off Off On Off Off Off.61 Off Off Off On On Off.62 On Off Off On On Off.63 Off On Off On On Off.64 On On Off On On Off.65 On On Off Off Off Off.66 Off Off On On On Off.67 On Off On On Off On.68 On Off On Off Off Off.69 Off On On On On Off.70 On On On On On Off.71 Off Off Off On Off Off.72 Off Off Off Off Off On.73 On Off Off Off Off On.74 (continued) 28
Switch Switch Function Switch Width Bank Position Settings (Inches) 2 5-8 Diffuser Width 5 6 7 8 4 1-2 Diffuser Width A 1 2 5 1-4 Diffuser Width B 1 2 3 4 6 6-7 Diffuser Width B 6 7 Off On Off Off Off On.75 Off On On Off Off Off.76 On On Off Off Off On.77 Off Off On Off Off On.78 On Off On Off Off On.79 Off On On Off Off On.80 On On On Off Off On.81 Off Off Off On Off On.82 On On On Off Off Off.83 On Off Off On Off On.84 Off On Off On Off On.85 On On Off On Off On.86 Off Off On On Off On.87 On Off On On Off On.88 Off On On On Off On.89 On On On On Off On.90 On Off Off On Off Off.91 Off Off Off Off On On.92 On Off Off Off On On.93 Off On Off Off On On.94 On On Off Off On On.95 Off Off On Off On On.96 On Off On Off On On.97 Off On On Off On On.98 On On On Off On On.99 Off Off Off On On On 1.0 On Off Off On On On 1.01 Off On Off On On On 1.02 On On Off On On On 1.03 Off Off On On On On 1.04 On Off On On On On 1.05 Off On On On On On 1.06 On On On On On On 1.07 29
Lag Shutdown Table Reference:17-series and 19-series Startup, Operation and Maintenance Manuals: Lag Turn-Off % Corrected Amps The Lag A and B Shutdown Table decisions (on the configuration screen) can be used to override the value entered at the 3200MP Controller s configuration switches. Refer to Page 38 of this manual for information regarding those decisions. This decision appears on the dual compressor service configuration screen only. Display Units 0 = Lag turn-off correction disabled 1 = Turn off lag sooner 2 3 4 5 = Normal setting 6 7 8 = Turn off lag later Amps Correction Factor Amps Correction Factor A Amps Correction Factor B Reference: 17-series and 19-series Startup, Operation and Maintenance Manuals: Compressor Motor Amps Correction Factor The Amps Correction Factor decision appears on the single compressor service configuration screen only. The Amps Correction Factor A and B decisions appear on the dual compressor service configuration screen only. Display Units 1 = Increase 2 3 4 5 6 7 8 = Decrease 30
Compressor Selection Factor Reference: 17-series and 19-series Startup, Operation and Maintenance Manuals: Compressor Selection Factor Display Units Switch Bank 4, Switch Positions: 3 4 5 1 = Off Off Off 2 = On Off Off 3 = Off On Off 4 = On On Off 5 = Off Off On 6 = On Off On 7 = Off On On 8 = On On On Configuration Screen The configuration screen is displayed by the operator at a Building Supervisor to configure reset and demand limit types, and chiller options. The table named CONFIG-1 is selected to display this screen. The configuration screen for a 32MP Gateway installed on a single compressor chiller is shown in Figure 6. The configuration screen for a 32MP Gateway installed on a dual compressor chiller is shown in Figure 7. Specific decision information follows. 31
32 Figure 6 32MP Gateway Configuration Screen (Single Compressor)
Figure 7 32MP Gateway Configuration Screen (Dual Compressor) 33
Temperature Reset Type Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Leaving Chilled Water Temperature Reset Allowable Entries 0 = chilled water reset options disabled 1 = reset based on cooler temperature difference 2 = reset based on a 4-20 ma input signal 3 = reset based on a remote temperature sensor input 4 = return chilled water temperature control Degrees Reset for Temperature 1 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on Cooler Temperature Difference Reset Temperature A This decision is used when the Temperature Reset Type decision is set to 1. Allowable Entries -30 to 30 degrees F (-34 to -1 degrees C) Reset 1 Temperature 1 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on Cooler Temperature Difference Delta-T for Reset Temperature A This decision is used when the Temperature Reset Type decision is set to 1. Allowable Entries 0 to 20 degrees F (-18 to -7 degrees C) 34
Degrees Reset for Temperature 2 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on Cooler Temperature Difference Reset Temperature B This decision is used when the Temperature Reset Type decision is set to 1. Allowable Entries -30 to 30 degrees F (-34 to -1 degrees C) Reset 1 Temperature 2 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on Cooler Temperature Difference Delta-T for Reset Temperature B This decision is used when the Temperature Reset Type decision is set to 1. Allowable Entries 0 to 20 degrees F (-18 to -7 degrees C) Reset 2 Degrees for ma 1 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on a 4-20 ma Input Signal Reset Temperature A This decision is used when the Temperature Reset Type decision is set to 2. Allowable Entries -30 to 30 degrees F (-34 to -1 degrees C) 4-20 ma Point 1 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on a 4-20 ma Input Signal Input Signal A This decision is used when the Temperature Reset Type decision is set to 2. Allowable Entries 4 to 20 ma (dc) 35
Reset 2 Degrees for ma 2 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on a 4-20 ma Input Signal Reset Temperature B This decision is used when the Temperature Reset Type decision is set to 2. Allowable Entries -30 to 30 degrees F (-34 to -1 degrees C) 4-20 ma Point 2 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on a 4-20 ma Input Signal Input Signal B This decision is used when the Temperature Reset Type decision is set to 2. Allowable Entries 4 to 20 ma (dc) Reset 3 Degrees for RT1 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on a Remote Temperature Sensor Input Reset Temperature A The decision is used when the Temperature Reset Type decision is set to 3. Allowable Entries -30 to 30 degrees F (-34 to -1 degrees C) Remote Temperature Point 1 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on a Remote Temperature Sensor Input Remote Temperature A This decision is used when the Temperature Reset Type decision is set to 3. Allowable Entries -20 to 240 degrees F (-29 to 116 degrees C) 36
Reset 3 Degrees for RT2 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on a Remote Temperature Sensor Input Reset Temperature B This decision is used when the Temperature Reset Type decision is set to 3. Allowable Entries -30 to 30 degrees F (-34 to -1 degrees C) Remote Temperature Point 2 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Chilled Water Reset Based on a Remote Temperature Sensor Input Remote Temperature B This decision is used when the Temperature Reset Type decision is set to 3. Allowable Entries -20 to 240 degrees F (-29 to 116 degrees C) Reset 4 ECW Setpoint Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Return Chilled Water Temperature Control Entering Temperature Control Point This decision is used when the Temperature Reset Type decision is set to 4. Allowable Entries 0 to 120 degrees F (-18 to 49 degrees C) Demand Limit Type Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Power Demand Limit Allowable Entries 0 = demand limit options disabled 1 = demand limit based on contact closure 2 = demand limit based on a 4-20 ma input signal 37
Demand 1 for Contact 1 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Power Demand Limit Based on Contact Closure Switch A Demand Limit This decision is used when the Demand Limit Type decision is set to 1. Allowable Entries 40 to 100 percent Demand 1 for Contact 2 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Power Demand Limit Based on Contact Closure Switch B Demand Limit This decision is used when the Demand Limit Type decision is set to 1. Allowable Entries 40 to 100 percent Demand 1 for Contact 3 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Power Demand Limit Based on Contact Closure Switch C Demand Limit This decision is used when the Demand Limit Type decision is set to 1. Allowable Entries 40 to 100 percent Demand 2 for Milliamp 1 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Power Demand Limit Based on 4-20 ma Input Signal Demand Limit A This decision is used when the Demand Limit Type decision is set to 2. Allowable Entries 40 to 100 percent 38
4-20 Milliamp Point 1 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Power Demand Limit Based on 4-20 ma Input Signal Input Signal A This decision is used when the Demand Limit Type decision is set to 2. Allowable Entries 4 to 20 ma (dc) Demand 2 for Milliamp 2 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Power Demand Limit Based on 4-20 ma Input Signal Demand Limit B This decision is used when the Demand Limit Type decision is set to 2. Allowable Entries 40 to 100 percent 4-20 Milliamp Point 2 Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Power Demand Limit Based on 4-20 ma Input Signal Input Signal B This decision is used when the Demand Limit Type decision is set to 2. Allowable Entries 4 to 20 ma (dc) Automatic Restart Option Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Automatic Restart After Power Failure Allowable Entries Disable Enable Remote Contacts Option Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Remote Contact Start/Stop The 32MP Gateway and the ESP-II panel each include a remote contacts option that, when enabled, allows the chiller to be stopped 39
and started by contact closure input from a field-installed remote start relay. Because the gateway supercedes the ESP-II panel in initiating the chiller's starts and stops, it automatically disables the panel's remote contacts option. The panel's option can be enabled, but it will be disabled by the gateway as soon as the panel is returned to remote mode. Because of that, when enabling, disabling, or checking the status of the remote contacts option the user should do so at the 32MP Gateway, not at the ESP-II panel. Allowable Entries Disable Enable Remote Ramp Rate Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Ramp Loading Rate Adjustment Allowable Entries 0 to 8 (code numbers) Lag A Shutdown Table Lag B Shutdown Table Reference: 3200MP Expanded Services Panel Start-up, Operation, and Maintenance Instructions: Dual Compressor Chiller Lag Compressor Turn-Off Correction This decision allows the 32MP Gateway to override 3200MP Controller DIP switch settings. An entry of 0 here allows the DIP switch configuration to be used. These decisions appear on the dual compressor configuration screen only. Allowable Entries 0 = Correction override disabled (DIP switch settings enabled) 1 = Turn lag off sooner 2 3 4 5 = Normal setting 6 7 8 = Turn lag off later 40
Maintenance Screen The maintenance screen is displayed by the operator at a Building Supervisor to display the status of inputs and outputs wired to the 3200MP Controller and diffuser wall position (DM machines only). The Maintenance menu item is used to select this screen. The maintenance screen for a 32MP Gateway installed on a single compressor chiller is shown in Figure 8. The maintenance screen for a 32MP Gateway installed on a dual compressor chiller is shown in Figure 9. Specific decision information follows. Figure 8 32MP Gateway Maintenance Screen (Single Compressor) 41
42 Figure 9 32MP Gateway Maintenance Screen (Dual Compressor)
Oil Pressure Switch Input Maintenance Manual: Start-up Sequence Oil Pressure Switch; Control Wiring Schematic Oil Pressure Display Units Close = pressure Open = no pressure Condenser Pump Relay Output Maintenance Manual: Start-up Sequence Condenser Water Pump Relay; Control Wiring Schematic CDW Pump Start Display Units Off = de-energized On = energized Condenser Flow Switch Input Maintenance Manual: Start-up Sequence Condenser Flow Switch; Control Wiring Schematic CDW Flow Display Units Close = flow Open = no flow Tower Fan Relay Output Maintenance Manual: Start-up Sequence Tower Fan Relay; Control Wiring Schematic Tower Fan Enable Display Units Off = de-energized On = energized Purge Pump Relay Output Maintenance Manual: Excessive Purge Pump Run Time; Control Wiring Schematic Purge Pump Display Units Off = de-energized On = energized 43
Purge Switch Input Maintenance Manual: Excessive Purge Pump Run Time; Control Wiring Schematic Purge Display Units Close = pump on Open = pump off Alarm Relay Output Maintenance Manual: Control Wiring Schematic Alarm Display Units On = alarm limits exceeded Off = normal operation Spare Protection Limit Input Maintenance Manual: Spare Safety Inputs; Control Wiring Schematic Spare Display Units Close = normal operation Open = alarm limits exceeded Compressor 1CR Output Compressor A 1CR Output Compressor B 1CR Output Maintenance Manual: Start-up Sequence 1CR Relay; Control Wiring Schematic Compressor Start Output The Compressor Start Relay Output decision appears on the single compressor maintenance screen only. The Compressor A and B Start Relay Output Decisions appear on the dual compressor maintenance screen only. Display Units Off = de-energized On = energized 44
Compressor 1CR Aux Contact Compressor A 1CR Aux Contact Compressor B 1CR Aux Contact Maintenance Manual: Start-up Sequence 1CR Auxiliary Contact; Control Wiring Schematic Compressor Start Input The Compressor 1CR Start Input decision appears on the single compressor maintenance screen only. The Compressor A and B 1CR Start Input decisions appear on the dual compressor maintenance screen only. Display Units Close = not starting Open = start-up in progress Compressor Aux Run Contact Compressor A Aux Run Contact Compressor B Aux Run Contact Maintenance Manual: Control Wiring Schematic Compressor Run The Compressor 1CR Run Input decision appears on the single compressor maintenance screen only. The Compressor A and B 1CR Run Input decisions appear on the dual compressor maintenance screen only. Display Units Close = running Open = not running Compressor Start Circuit Volt Compressor A Start Circuit Volt Compressor B Start Circuit Volt Maintenance Manual: Control Wiring Schematic Compressor Run The Compressor High Pressure Input decision appears on the single compressor maintenance screen only. The Compressor A and B High Pressure Input decisions appear on the dual compressor maintenance screen only. Display Units Yes = normal operation No = alarm limits exceeded when running 45
Motor Temperature Switch Input Motor A Temperature Switch Input Motor B Temperature Switch Input Maintenance Manual: Control Wiring Schematic Motor (Discrete) The Compressor Winding Temperature Input decision appears on the single compressor maintenance screen only. The Compressor A and B Winding Temperature Input decisions appear on the dual compressor maintenance screen only. Display Units Close = normal operation Open = alarm limits exceeded Guide Vane Increase Guide Vane A Increase Guide Vane B Increase Maintenance Manual: Control Wiring Schematic Vane Open The Guide Vane Increase decision appears on the single compressor maintenance screen only. The Guide Vane A and B Increase decisions appear on the dual compressor maintenance screen only. Display Units Off = guide vane stationary On = guide vane opening Guide Vane Decrease Guide Vane A Decrease Guide Vane B Decrease Maintenance Manual: Control Wiring Schematic Vane Close The Guide Vane Decrease decision appears on the single compressor maintenance screen only. The Guide Vane A and B Decrease decisions appear on the dual compressor maintenance screen only. Display Units Off = guide vane stationary On = guide vane closing 46
Diffuser Wall Increase Diffuser Wall A Increase Diffuser Wall B Increase Maintenance Manual: Control Wiring Schematic Diffuser Wall The Diffuser Wall Increase decision appears on the single compressor maintenance screen only. The Diffuser Wall A and B Increase decisions appear on the dual compressor maintenance screen only. Display Units Off = diffuser wall stationary On = diffuser wall opening Diffuser Wall Decrease Diffuser Wall A Decrease Diffuser Wall B Decrease Maintenance Manual: Control Wiring Schematic Diffuser Wall The Diffuser Wall Decrease decision appears on the single compressor maintenance screen only. The Diffuser Wall A and B Decrease decisions appear on the dual compressor maintenance screen only. Display Units Off = diffuser wall stationary On = diffuser wall closing Impeller Displacement Input Maintenance Manual: Control Wiring Schematic Impeller Displacement This decision appears on the single compressor maintenance screen only. Display Units Close = normal operation Open = alarm limits exceeded 47
Figure 10 Alarm Configuration Screen Alarm Configuration Screen The alarm configuration screen is displayed by the operator at a Building Supervisor to configure alarm parameters such as system names and re-alarm times. The table named ALARM-CFG is selected to display this screen. The alarm configuration screen is shown in Figure 10. Specific decision information follows. Alarm Control This decision defines the CCN system elements that will process 32MP Gateway alarms. Allowable Entries 0 = Alarm processing disabled 64 = Autodial Gateways 128 = Local Building Supervisors 192 = Local Building Supervisors and Autodial Gateways 208 = Local Building Supervisors, Autodial Gateways, and Alarm Printer Interface Module 48
Alarm Equipment Priority This is used to define the priority of 32MP Gateway alarms. A priority of 0 is the highest priority and a priority of 7 is the lowest priority. A priority of 4 is reserved for chiller alarms. It is therefore recommended that you do not change the value of this decision. Allowable Entries 0 to 7 priority numbers Communication Failure Retry Time This decision defines the interval between alarm retries. If an alarm sent by the 32MP Gateway is not acknowledged by a network alarm acknowledger, the same alarm will be sent again following the amount of time entered in this decision. Allowable Entries 1 to 240 minutes Re-alarm Time This is the interval between re-alarms sent by the 32MP Gateway. As long as the alarm condition that initially caused an alarm exists, the 32MP Gateway will continue to retransmit the alarm at regular intervals. The interval between retransmissions is the amount of time entered in this decision. Re-alarming will stop when the alarm condition returns to normal. Allowable Entries 1 to 255 minutes Alarm System Name This decision is used to identify the system element generating an alarm. In the case of the 32MP Gateway, the default name 32MPGTWY will appear in the alarm message displayed at Building Supervisors. In a multiple chiller system this name can be changed to identify the gateway serving each individual chiller. 32MPGW-1 and 32MPGW-2 might be used, for example. Allowable Entries Up to 8 alphanumeric characters 49
50
BEST Program Access
BEST Program Access General Information BEST programs can read data from each item displayed on the 32MP Gateway s points, service configuration, configuration, and maintenance screens through the appropriate tables. This section provides a list of table, point, and decision numbers used in BEST programs. Further information regarding a BEST program s access to 32MP Gateway parameters can be found on Pages 5 and 9 of this manual. Table 2 Points Screen (Single Compressor) Description Index Range Table Number Chiller Status Code 1 1-99 17 Chiller Start/Stop 2 0,1 17 LCW Control Point 3-20 - 120 17 Demand Limit 4 40-100 17 Leaving Chilled Water 5-20 - 240 17 Evaporator Ref. Trippoint 6-20 - 35 17 Evaporator Refrigerant 7-20 - 240 17 Condenser Refrigerant 8-20 - 240 17 Compressor Ontime 9 0-32,767 17 Remote Contacts Input 10 0,1 17 Compressor Motor Load 11 0-255 17 Compressor Motor Current 12 0-255 17 Motor Winding 13-20 - 240 17 Compressor Discharge 14-20 - 240 17 Motor Thrust Bearing 15-20 - 240 17 Spare Sensor 1 16-20 - 240 17 Spare Sensor 2 17-20 - 240 17 Spare Sensor 3 18-20 - 240 17 Spare Sensor 4 19-20 - 240 17 Shutdown Code 1 20 40-99 17 Shutdown Code 2 21 40-99 17 Shutdown Code 3 22 40-99 17 Shutdown Code 4 23 40-99 17 Shutdown Code 5 24 40-99 17 Control Voltage 25 0-255 17 Starts in 6 Hours 26 0-6 17 Remote Mode Enabled 27 0,1 17 51
Table 3 Points Screen (Dual Compressor) Description Index Range Table Number Lead Compressor Status Code 1 1-99 17 Lag Compressor Status Code 2 1-99 17 Chiller Start/Stop 3 0,1 17 LCW Control Point 4-20 - 120 17 Demand Limit 5 40-100 17 Leaving Chilled Water 6-20 - 240 17 Evaporator Ref. Trippoint 7-20 - 35 17 Evaporator Refrigerant 8-20 - 240 17 Condenser Refrigerant 9-20 - 240 17 Compressor Ontime 10 0-32767 17 Remote Contacts Input 11 0,1 17 Compressor A Motor Load 12 0-255 17 Compressor B Motor Load 13 0-255 17 Compressor A Motor Current 14 0-255 17 Compressor B Motor Current 15 0-255 17 Motor A Winding 16-20 - 240 17 Motor B Winding 17-20 - 240 17 Compressor A Discharge 18-20 - 240 17 Compressor B Discharge 19-20 - 240 17 Thrust Bearing A 20-20 - 240 17 Thrust Bearing B 21-20 - 240 17 Spare Sensor 1 22-20 - 240 17 Spare Sensor 2 23-20 - 240 17 Spare Sensor 3 24-20 - 240 17 Spare Sensor 4 25-20 - 240 17 Shutdown Code 1 26 40-99 17 Shutdown Code 2 27 40-99 17 Shutdown Code 3 28 40-99 17 Shutdown Code 4 29 40-99 17 Shutdown Code 5 30 40-99 17 Control Voltage 31 0-255 17 Starts in 6 Hours 32 0-6 17 Compressor B Is Lead 33 0,255 17 Remote Mode Enabled 34 0,1 17 Lag Disable Switch Set 35 0,255 17 52
Table 4 Service Configuration Screen (Single Compressor) Description Index Range Table Number DM Compressor 1 0,255 19 Machine Type Is CB 2 0,255 19 LCW Deadband 3 1,2 19 LCW Proportional Band 4 5,15 19 Line Frequency 5 60,50 19 Full Voltage Starter Type 6 0,255 19 Motor Sensor Type 7 255,0 19 Thrust Sensor Type 8 255,0 19 Brine Medium 9 0,255 19 Fahrenheit Temperature 10 0,255 19 Chiller Controller ID 11 0-7 19 Local Ramp Rate 12 2.25-10.5 19 Impeller Diameter 13 0,255 19 Diffuser Width 14 0.48-1.07 19 Amps Correction Factor 15 0-7 19 Compressor Selection Factor 16 0-7 19 53
Table 5 Service Configuration Screen (Dual Compressor) Description Index Range Table Number DM Compressor 1 0,255 19 LCW Deadband 2 1,2 19 LCW Proportional Band 3 5,15 19 Line Frequency 4 60/50 19 Full Voltage Starter Type 5 0,255 19 Motor Sensor Type 6 255,0 19 Brine Medium 7 0,255 19 Fahrenheit Temperature 8 0,255 19 Chiller Controller ID 9 0-7 19 Compressor A Capacity 10 50 60 19 Y Degrees Selection 11 1-30 19 X Minutes Selection 12 1-60 19 Local Ramp Rate 13 2.25-10.5 19 Impeller Diameter A 14 0.255 19 Diffuser Width A 15 0.48-1.07 19 Impeller Diameter B 16 0,255 19 Diffuser Width B 17 0.48-1.07 19 Lag Shutdown Table 18 0-7 19 Amps Correction Factor A 19 0-7 19 Amps Correction Factor B 20 0-7 19 Compressor Selection Factor 21 0-7 19 54
Table 6 Configuration Screen (Single Compressor) Description Index Range Table Number Temperature Reset Type 1 0-4 16 Reset 1 Temperature 1 2-30 - 30 16 Degrees Reset for Temp 1 3 0-20 16 Reset 2 Temperature 2 4-30 - 30 16 Degrees Reset for Temp 2 5 0-20 16 Reset 2 Degrees for ma 1 6-30 - 30 16 4-20 ma Point 1 7 4-20 16 Reset 2 Degrees for ma 2 8-30 - 30 16 4-20 ma Point 2 9 4-20 16 Reset 3 Degrees for RT1 10-30 - 30 16 Remote Temperature Point 1 11-20 - 240 16 Reset 3 Degrees for RT2 12-30 - 30 16 Remote Temperature Point 2 13-20 - 240 16 Reset 4 ECW Setpoint 14 0-120 16 Demand Limit Type 15 0-2 16 Demand 1 Contact 1 16 40-100 16 Demand 1 Contact 2 17 40-100 16 Demand 1 Contact 3 18 40-100 16 Demand 2 for ma 1 19 40-100 16 4-20 ma Point 1 20 4-20 16 Demand 2 for ma 2 21 40-100 16 4-20 ma Point 2 22 4-20 16 Auto Restart Option 23 0,1 16 Remote Contacts Option 24 0,1 16 Remote Ramp Rate 25 0-7 16 55
Table 7 Configuration Screen (Dual Compressor) Description Index Range Table Number Temperature Reset Type 1 0-4 16 Reset 1 Temperature 1 2-30 - 30 16 Degrees Reset for Temp 1 3 0-20 16 Reset 2 Temperature 2 4-30 - 30 16 Degrees Reset for Temp 2 5 0-20 16 Reset 2 Degrees for ma 1 6-30 - 30 16 4-20 ma Point 1 7 4-20 16 Reset 2 Degrees for ma 2 8-30 - 30 16 4-20 ma Point 2 9 4-20 16 Reset 3 Degrees for RT1 10-30 - 30 16 Remote Temperature Point 1 11-20 - 240 16 Reset 3 Degrees for RT2 12-30 - 30 16 Remote Temperature Point 2 13-20 - 240 16 Reset 4 ECW Setpoint 14 0-120 16 Demand Limit Type 15 0-2 16 Demand 1 Contact 1 16 40-100 16 Demand 1 Contact 2 17 40-100 16 Demand 1 Contact 3 18 40-100 16 Demand 2 for ma 1 19 40-100 16 4-20 ma Point 1 20 4-20 16 Demand 2 for ma 2 21 40-100 16 4-20 ma Point 2 22 4-20 16 Auto Restart Option 23 0,1 16 Remote Contacts Option 24 0,1 16 Remote Ramp Rate 25 0-7 16 Lag A Shutdown Table 26 0-7 16 Lag B Shutdown Table 27 0-7 16 56
Table 8 Maintenance Screen (Single Compressor) Description Index Range Table Number Diffuser Wall Position 1 0-7 18 LCW Pump Relay Output 2 0,255 18 LCW Flow Input 3 0,255 18 Oil Pump Relay Output 4 0,255 18 Oil Pressure Switch Input 5 0,255 18 Cond. Pump Relay Output 6 0,255 18 Condenser Flow Switch Input 7 0,255 18 Tower Fan Relay Output 8 0,255 18 Purge Pump Relay Output 9 0,255 18 Purge Pump Switch Input 10 0,255 18 Alarm Relay Output 11 0,255 18 Spare Protection Limit Input 12 0,255 18 Compressor 1CR Output 13 0,255 18 Compressor 1CR Aux Contact14 0,255 18 Compressor Aux Run Contact 15 0,255 18 Comp. Start Circuit Volt 16 0,255 18 Motor Temp. Switch Input 17 0,255 18 Guide Vane Increase 18 0,255 18 Guide Vane Decrease 19 0,255 18 Diffuser Wall Increase 20 0,255 18 Diffuser Wall Decrease 21 0,255 18 Impeller Displacement Input 22 0,255 18 57
Table 9 Maintenance Screen (Dual Compressor) Description Index Range Table Number Diffuser Wall A Position 1 0-7 18 Diffuser Wall B Position 2 0-7 18 LCW Pump Relay Output 3 0,255 18 LCW Flow Input 4 0,255 18 Oil Pump Relay Output 5 0,255 18 Oil Pressure Switch Input 6 0,255 18 Cond. Pump Relay Output 7 0,255 18 Cond. Flow Switch Input 8 0,255 18 Tower Fan Relay Output 9 0,255 18 Purge Pump Relay Output 10 0,255 18 Purge Switch Input 11 0,255 18 Alarm Relay Output 12 0,255 18 Spare Protection Limit Input 13 0,255 18 Comp. A 1CR Output 14 0,255 18 Comp. A 1CR Aux Contact 15 0,255 18 Comp. A Aux Run Contact 16 0,255 18 Comp. A Start Circuit Volt 17 0,255 18 Motor A Temp. Switch Input 18 0,255 18 Guide Vane A Increase 19 0,255 18 Guide Vane A Decrease 20 0,255 18 Diffuser Wall A Increase 21 0,255 18 Diffuser Wall A Decrease 22 0,255 18 Comp. B 1CR Output 23 0,255 18 Comp. B 1CR Aux Contact 24 0,255 18 Comp. B Aux Run Contact 25 0,255 18 Comp. B Start Circuit Volt 26 0,255 18 Motor B Temp. Switch Input 27 0,255 18 Guide Vane B Increase 28 0,255 18 Guide Vane B Decrease 29 0,255 18 Diffuser Wall B Increase 30 0,255 18 Diffuser Wall B Decrease 31 0,255 18 58
Configuration Sheets
59
60
61