ABB i-bus KNX BCI/S Boiler/Chiller Interface

Similar documents
ABB i-bus KNX HCC/S Heating/cooling circuit controller

ABB i-bus KNX Analogue Actuator, 4-fold, MDRC, 0-10 V, 0-20 ma AA/S 4.1.2, 2CDG110202R0011

ABB i-bus KNX AC/S Application Controller

ABB i-bus KNX Switch Actuator, x-fold, 10 A, MDRC SA/S x , 2CDG11015xR0011

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011

ABB i-bus KNX Logic Controller ABA/S 1.2.1, 2CDG110192R0011

ABB i-bus KNX Fan Coil Actuator, PWM, MDRC FCA/S , 2CDG110195R0011

ABB i-bus KNX Switch Actuator, Current Detection, x-fold, 16/20 A, C-Load, MDRC SA/S x , 2CDG1101xxR0011

ABB i-bus KNX Weather Unit, 1-fold, MDRC WZ/S , 2CDG110184R0011

ABB i-bus KNX IP Router, MDRC IPR/S 3.1.1, 2CDG110175R0011

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2TAZ710xx1R2161

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011

ABB i-bus KNX Fan Coil Actuators FCA/S Product Manual

ABB i-bus KNX Fan Coil Actuators FCA/S Product Manual

PRODUCT MANUAL. ABB i-bus KNX SV/S KNX-Power Supplies

ABB i-bus KNX Switch Actuator, x-fold, 6 A, MDRC SA/S x.6.1.1, 2CDG x R0011

Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

ABB i-bus KNX KNX/EnOcean Gateway EG/A , 2CDG R0011

ABB i-bus KNX Binary Inputs BE/S Product Manual

Operating voltage Maximum

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

ABB i-bus KNX Thermoelectric Valve Drive, 230 V TSA/K 230.2, 2CDG R0011

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

Switching relay CT-IRE with 1 c/o (SPDT) contact

Boxed interface relays and optocouplers R600 Boxed slim relays, optocouplers and accessories

Messaging module CP-C MM

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Accessories for pluggable interface relays CR-P Sockets

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

ABB i-bus KNX Blind/Roller Shutter Actuators JRA/S Product Manual

Intrusion Detection Technology SafeKey Switching Module SSM/A, SSM/U Product Manual

AI561 Analog Input Module

Electronic timer CT-ERD ON-delayed with 1 c/o contact Data sheet

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Pluggable interface relays CR-P Pcb relays

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Datasheet RCUXXYY EAE KNX Room Control Unit RCUXXYY DT R1.0. General Description. EAE Technology Page 1/10

Electronic timer CT-VWD Impulse-ON with 1 c/o contact Data sheet

Device technology. Supply Bus voltage V DC. Current consumption via bus. Accuracy in the range 300 1,000 ppm 1,000 2,000 ppm 2,000 5,000 ppm

PHOENIX CONTACT Features

Power supply CP-D 12/2.1 Primary switch mode power supply

Power supply CP-E 48/1.25 Primary switch mode power supply

TEPI11 P/I signal converter

ABB i-bus KNX Blind/Roller Shutter Actuator JRA/S Product Manual

RTU500 series Data Sheet Power Supply CP-E 24/2.5

Redundancy unit CP-A RU

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

Power supply CP-E 24/0.75 Primary switch mode power supply

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Redundancy unit CP-D RU Accessory for CP range power supplies (e.g. switch mode power supplies CP-D range)

Thermistor motor protection relay CM-MSS.11

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

DI572 Digital Input Module

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Pluggable interface relays CR-M Miniature relays

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

DI561 Digital Input Module

TU531, TU532 Terminal Unit

ABB i-bus KNX Blower/Fan Coil-Actuator LFA/S 1.1, LFA/S 2.1. Product Manual. Intelligent Installation Systems ABB

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

Thermistor motor protection relays CM-MSS.32 and CM-MSS.33

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

ABB i-bus EIB / KNX Blower/Fan Coil-Aktuator LFA/S 1.1, LFA/S 2.1. Product Manual. Intelligent Installation Systems ABB

TF501, TF521 Terminal Bases

Three-phase monitoring relay

DC562, digital input/output module,

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

Buffer module CP-B 24/20.0, ultra-capacitor based Accessory for power supplies (e.g. switch mode power supplies CP range)

ABB i-bus KNX SUG/U 1.1 Split Unit Gateway Product Manual

Electronic timer CT-ARS.11

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

DC561, digital input/output module,

Power supply CP-E 24/10.0 Primary switch mode power supply

Power supply. Interface technology in modular housing DIN rail devices, IM series. Features

Linienkoppler S KNX. Line coupler S KNX. Line coupler S KNX Status: March 16 (Subject to change) Page 1 of 29

Thermistor motor protection relay CM-MSS.31

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Thermistor motor protection relay CM-MSS.41

Pluggable interface relays and optocouplers CR-P Pcb relays, optocouplers and accessories

DX561 Digital Input/Output Module

AX521 Analog Input/Output Module

Electronic timer CT-ERS.21

AO523 Analog Input Module

QUINT-PS/ 1AC/24DC/ 5

Electronic timer CT-ERD.12

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

Electronic timer CT-AHD.22

Bus Connection Unit 560BCU04

AO561 Analog Output Module

ST 200 M data sheet System pro M compact miniature circuit breakers for supplementary protection acc. to UL 1077

Product and Applications Description. Application Programs. Example of Operation. Installation Instructions. load circuit AC 230/400V L1 L2 L3 N

Accessories for pluggable interface relays CR-P, CR-M Pluggable function module

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Transcription:

ABB i-bus KNX BCI/S 1.1.1 Boiler/Chiller Interface Description of product The boiler/chiller interface is a modular DIN rail component that acts as an interface to the heating/cooling system generator. Via a relay output it is possible to enable or switch on and off the generator, the analog output can be used specify set the setpoint temperature via a 0-10 V input on the generator. Two binary inputs are available to monitor the status of the generator via floating contacts and report it to the KNX bus. In addition, the supply and return flow temperatures are measured via analog inputs. The pump can be switched on or enabled via a relay. In addition, three binary inputs are available for monitoring the pump function. The device is powered via the ABB i-bus KNX and requires no additional auxiliary voltage. The device is ready for operation after connecting the bus voltage.

Dimension drawing 105 2CDC072026F0017 2 2CDC508254D0211 Rev. A BCI/S 1.1.1

Connection N L1 / U n1 A U n2 B C a b U n1,u = 24-230 V ~ I n1,i n2= 6A 1 2 5 6 7 8 3 4 9 10 0V 0-10V 10 11 11 12 13 14 15 16 17 c d e f g 2CDC072044F0017 LEGEND 1Label carrier 2KNX programming LED (red) 3KNX programming button 4KNX connection 5Cover cap 6Binary inputs (c, d, e, f, g) c, d, e: Binary inputs for pump f, g: Binary inputs for generator 7Relay output A (pump) 8Relay output B (generator/enable) 9Boiler/chiller 10 Analog output C (setpoint encoder boiler/chiller) 11 Temperature inputs (a, b) BCI/S 1.1.1 2CDC508254D0211 Rev. A 3

Operating and display elements Button/LED Description LED indicator Assignment of the physical address On: device is in programming mode Technical data Supply Bus voltage 21 32 V DC Current consumption, bus Power loss, bus Power loss, device KNX connection Relay 5 A < 12 ma Maximum 250 mw Maximum 3 W 0.25 W Connections KNX Via bus connection terminal Inputs/outputs 0.6 W Via screw terminals Connection terminals Screw terminal Screw terminal with universal head (PZ1) Screw terminal 1 0.2 2.5 mm 2 stranded, 2 x (0.2 2.5 mm 2 ) Screw terminal 2 0.2 4 mm 2 solid, 2 x (0.2 4 mm 2 ) Ferrule without plastic sleeve 0.25 2.5 mm 2 Ferrule with plastic sleeve 0.25 4 mm 2 TWIN ferrules 0.25 4 mm 2 Ferrule contact pin length Tightening torque Grid 6.35 At least 10 mm Maximum 0.6 Nm Protection degree IP 20 According to EN 60529 Protection class II According to EN 61140 Isolation category Overvoltage category III according to EN 60664-1 Pollution degree II according to EN 60664-1 SELV KNX safety extra low voltage SELV 24 V DC 4 2CDC508254D0211 Rev. A BCI/S 1.1.1

Technical data Temperature range Operation - 5 +45 C Transport -25 +70 C Storage -25 +55 C Ambient conditions Maximum air humidity 95 %, no condensation allowed Atmospheric pressure Atmosphere up to 2,000 m Design Modular DIN rail component (MDRC) Modular installation device Design Housing/color pro M Plastic, gray Dimensions Dimensions 90 x 105 x 63.5 mm (H x W x D) Mounting width in space units Mounting depth 6x modules of 17.5 mm 63.5 mm Mounting 35 mm mounting rail According to EN 60715 Mounting position Weight Fire classification Any 0.24 kg Flammability V-0 as per UL94 Approvals KNX certification According to EN 50491 CE marking Certification According to EN 60669 In accordance with the EMC and Low Voltage Directives BCI/S 1.1.1 2CDC508254D0211 Rev. A 5

Software Device type Heating/cooling circuit controller BCI/S 1.1.1 Application Boiler/chiller interface/ * Maximum number of group objects 42 Maximum number of group addresses 255 Maximum number of assignments 255 * = Current version number of the application. Please refer to the software information on our website for this purpose. Generator output (analog) Rated values Quantity 1, non-floating, short-circuit proof Control signal 0 10 V DC Signal type Analog Output load > 10 kohm Output tolerance ± 10 % Current limitation Up to 1.5 ma Pump and generator outputs (relay 5 A) Rated values Quantity 2 (1 x pump, 1 x generator) U n rated voltage I n rated current (per output pair) 250 V AC (50/60 Hz) Switching currents AC3* operation (cos φ = 0.45) According to EN 60947-4-1 Service life Switching times AC1* operation (cos φ = 0.8) According to EN 60947-4-1 Fluorescent lighting load AX According to EN 60669-1 Minimum switching capacity at 20 ma Minimum switching capacity at 10 ma Minimum switching capacity at 7 ma DC switching capacity, resistive load, at 5 A Mechanical service life Electrical service life of switching contacts according to IEC 60947-4-1 Maximum relay position changes per output and minute if only one relay is switched 5 A 5 V AC 12 V AC 24 V AC 24 V DC > 10 7 cycles > 10 6 cycles > 500 6 2CDC508254D0211 Rev. A BCI/S 1.1.1

Inputs Rated values Quantity 10 For temperature measurement Quantity 2 For contact scanning Quantity 5 Contact scanning Scanning current 1 ma Scanning voltage 12 V Resistance Selection User-defined PT 1000 2-conductor technology PT 100 2-conductor technology KT 1 k KTY 2 k NI 1 k NTC 10 k NTC 20 k Cable length Between sensor and device input Max. 100 m, one-way Ordering details Device type Product Name Order No. bbn 40 16779 EAN Weight 1 pcs. [kg] BCI/S 1.1.1 Boiler/chiller interface 2CDG110222R0011 01165 5 0.210 1 Packaging [pcs.] NOTE Please refer to the BCI/S 1.1.1 Boiler/Chiller Interface product manual for a detailed description of the application. It is available free of charge at www.abb.com/knx. ETS and the current version of the device application are required for programming. The latest version of the application and corresponding software information is available for download from www.abb.com/knx. After import into ETS, it appears in the Catalogs window under Manufacturers/ABB/Heating, ventilation, air conditioning/primary systems. The device does not support the locking function of a KNX device in ETS. Using a BCU code to inhibit access to all the project devices has no effect on this device. Data can still be read and programmed. BCI/S 1.1.1 2CDC508254D0211 Rev. A 7

ABB STOTZ-KONTAKT GmbH Eppelheimer Straße 82 69123 Heidelberg, Germany Telefon: +49 (0)6221 701 607 Telefax: +49 (0)6221 701 724 E-Mail: knx.marketing@de.abb.com Further Information and Local Contacts: www.abb.com/knx Copyright 2018 ABB. We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of this contents - in whole or in parts - is forbidden without prior written consent of ABB AG. Order Number 2CDC508254D0211 Rev. A (11.2018)