White Paper October 2009

Similar documents
DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

glossary GE Digital Energy Power Quality Surge Protective Devices (SPDs)

White Paper Surge Protective Devices in Automatic Transfer Switches

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD)

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS

SECTION TRANSIENT VOLTAGE SURGE SUPPRESSION

GUIDE TO VERIFYING SURGE PROTECTIVE DEVICES INSTALLED IN LIGHTNING PROTECTION SYSTEM INSTALLATIONS ARE COMPLIANT WITH UL 96A.

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

File E Project 08NK November 24,2009 REPORT TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7)

UL 508 A standard-compliant design of industrial control panel

The following standards are the basis of design, manufacture, and test of SPD equipment: Guide for Surge Voltages in Low-Voltage AC Power Circuits

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

File E Project 08NK October 2, 2009 REPORT SURGE PROTECTIVE DEVICES (VZCA) GE Zenith Controls Bonham, TX

Secondary Surge Arrester Instruction Manual Page 1 of 5

TDX Series. Transient Discriminating TM TVSS

SECTION SURGE PROTECTIVE DEVICES

Dirty Power... A Guide to Surge Suppression & Filtering. Surge & Signal Protection for Business-Critical Continuity. EmersonNetworkPower.

White Paper Surge Current Characteristics: 570 Hybrid Surge Protective Device

2008 Code Changes for Power Distribution

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

INTRODUCTION TO SPECIFYING SURGE PROTECTION SURGE PROTECTION NOTE 1 INTRODUCTION TERMS PROBABILITY OF SURGES APPEARING:

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

GE Digital Energy. Power Quality

B. System Design and Performance Requirements

UL2930 Healthcare Facility Outlet Assemblies UL1449 Heavy Duty Surge Protection Devices. Wiring Device-Kellems

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

Current Regulatory and Industry Updates for Surge Protective Devices (SPD)

US Catalog March Surge protective devices (SPDs) UL range

BSPD Surge Protective Devices

Overcurrent and Overvoltage Protection Changes in the 2008 NEC Code. www. ElectricalPartManuals. com

Liebert TVSS: The First Line of Defense - Product Overview. Jim Tiesi

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs)

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Surge Protection Devices for. Facility Engineers And Electricians. Today s Information. History of SPD Protection. Why Specify an SPD?

MICHIGAN DEPARTMENT OF TRANSPORTATION

Low Voltage and Medium Voltage Surge Protection

CPS block & CPS nano UL rd Ed. Surge protective devices (SPD)

Figure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters.

Surge Protection for Surveillance Systems

ENGR. MARITES R. PANGILINAN, P.E.E.

OPERATOR S MANUAL ATE 1/2 RACK POWER SUPPLY AUTOMATIC TEST EQUIPMENT MODEL

2.1. SPD, Power Conditioning, PF Capacitors and Harmonic Filters. Contents Description. Introduction. Surge Protection and Power Conditioning

GE TR7000 Series Wall Mounted Surge Protective Device (SPD)

NEC 2008 Code Changes Top 20 Revisions. By: Rafi Wartan, PE, LEED AP


Surge Protective Devices. STV25K Series. Instruction Manual

Stalking the Elusive and Somewhat Strange PV System

THE SURGE PROTECTION SOLUTION

Mitigation of Voltage Swells I

UL508Afor Panel Builders Getting Started

MICHIGAN DEPARTMENT OF TRANSPORTATION

Surge Protection Systems Performance and Evaluation

BUSSMANN. North American UL Type 1, 2 and 4, and data signal surge protective devices SERIES. Application note 3193

Presenter Information

ALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD

In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect.

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Spacing Requirements for Power Distribution and Terminal Blocks

Quantum Chargers Enhanced AC Line Transient Immunity

Specifications, Installation, and Operating Instructions

PQ ANALYZER PROCUREMENT SAMPLE SPECIFICATION

AC Surge Protection Devices

Surge & Filter Protection Addressing your industrial power quality needs.

Surg Sur e P ot r ection

Grid to Chip Surge Protection Product Catalog

Surgelogic Surge Protective Device I-Line Plug-On Unit Series

Datasheet Stock No: RS Pro

Manufactured Home Production by Product Mix ( )

Lightning & Surge Protection

Electrical Service Change-Tn Neenah

OPERATOR S MANUAL ATE 1/2 RACK POWER SUPPLY AUTOMATIC TEST EQUIPMENT MODEL

OVRH catalog Surge protective devices

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

SECTION ELECTRIC METERING

White Paper National Electrical Code (NEC) Requirements for Surge Protective Devices

More Questions from Inspectors Numerous PV Systems Pose Issues

Application Note. Table 1. Test requirements by equipment type

Application Techniques CENTERLINE 2100 Motor Control Centers

Circuit Protection Methods

NEMA 1 / IP40 metal housing. Compact design

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

FORM FOR PROPOSAL FOR 2014 NATIONAL ELECTRICAL CODE

AN4275 Application note

Each VariSTAR Type AZU arrester must pass the following production tests: 100% Physical Inspection 100% Leakage Current Test 100% RIV Test

UL 508A Industrial Control Panels Eaton. All Rights Reserved.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

ITS Heartland: Overview of Transient Overvoltage Surge Protection in ITS/Traffic Systems

SECTION PANELBOARDS. A. NECA (National Electrical Contractors Association) -Standard of Installation

Introduction. Upon completion of Basics of Surge Protection, you should be able to:

NEMA ANSI C New Surge Protection for LED Roadway and Area Lighting. Overview of NEMA ANSI C Threat to LED Lighting

After the storm leaves the area, you pat yourself on the back for protecting your data and equipment. The worry is over. Or is it?

Transcription:

ANSI /UL1449 Third Edition Safety Standard (New UL and NEC standards means new performance levels, test procedures and markings to products and manufacturers) White Paper October 2009 The past two years have seen many changes in codes and standards of surge protective devices (s). The specific standards are from Underwriters Laboratories (UL), and the National Fire Protection Association (NFPA). The changes in the two standards are widespread, but they primarily affect the application of the, not the performance or safety of the devices. Underwriters Laboratories Underwriters Laboratories (UL) Standard for Safety, Transient Voltage Surge Suppressors (UL 1449) has undergone a number of changes and will continue to drive application changes throughout the industry. This includes a change in nomenclature from transient voltage surge suppressors (TVSS) to surge protective devices (s) and recognition of the standard by the American National Standard Institute (ANSI) [1]. The adoption of the third edition of UL 1449 also affects performance testing methodologies, ratings, and the appropriate application of s. As with previous changes of the UL standard, there are no grandfather clauses and all s must be retested, recertified and compliant by September 2009 [1]. Unlike the introduction of UL 1449 second edition and subsequent amendments, the latest changes do not dramatically affect the product safety of an, but are intended to clarify performance testing, ratings, and applications of an. Location Types Previous versions of UL 1449 only identified two types of s: permanently connected or cordconnected. Permanently connected s can be applied to many locations: service entrance, distribution panels, or end-use equipment. Permanently connected s are installed by electricians or technicians. Cord-connected s could be located anywhere within a facility as long as there was an outlet. Cord-connected s can be applied 10 meter from service entrance at locations close to the service entrance, branch panel locations, or end-use equipment through standard electrical outlets. In addition to UL 1449, another class of s, denoted as surge arresters and classified by UL as OWHX, were tested to an outdated revision of an IEEE standard. The third edition of UL 1449 has combined all categories of s into a formalized classification for use in specific applications. The types identified are Type 1, Type 2, Type 3, and Type 4 [1]. Each type can consist of permanently connected or cord-connected s, but each type has consistent testing and application requirements. Type 1 s were formally denoted as Secondary Surge Arresters (SSA) and are intended to be installed between the secondary side of the service transformer and the primary side of the service entrance disconnect (Figure 1). s intended for application in a Type 1 location are required to have overcurrent protective devices either installed internally to the, or are included with the Type 1. While Type 1 s are primarily intended for installation before the main service disconnect, Type 1 s can be installed in Type 2 and Type 4 locations: distribution panels, end-use equipment, etc.

Type 2 s are intended to be connected on the secondary side of the main service disconnect (Figure 1) [1]. While some Type 2 s will have internal overcurrent protective components, Type 2 s can rely on the service entrance overcurrent disconnect device for overcurrent protection. Type 2 s can be installed in service equipment, distribution panels, end-use equipment. Type 2 s are permanently connected. TYPE 1 Type 3 s are intended to CB6 CB7 connected at least 10 meters (33 feet) from the service entrance; this Panel PS- 21 does not include the length of the conductors [1]. Based on the PDU 11 definition of a Type 3, these devices are cord-connected devices, and are intended to be used in end- equipment locations. Type 3 s can rely on external overcurrent TO IT EQUIPMENT TO HVAC SYSTEM protective devices for overcurrent protection. Type 3 s that are cord-connected are required to comply with leakage current requirements to ensure unwanted (objectional) currents are not injected on the ground conductor. Type 4 s are component or assembly devices [1]. Type 4 s are incomplete in their construction, or the safety testing (e.g. limited-current abnormal overvoltage test, intermediate current test, etc) and are intended to be tested in the final assembly. Type 4 s that are incomplete in construction or testing has the identifying information denoted in the requirements section of the manufacturer s UL report. Unfortunately, there is no documentation of the additional testing requirements for a Type 4 on the labeling or installation instructions. Type 4 component s range from single components (MOVs, SADs) to complex devices intended for installation into distribution equipment (panelboards, switchboards, etc). Voltage Protection Rating One of the primary ratings of an has been the surge voltage rating (SVR), which has been used to determine the protection an can provide. This SVR has changed from the first edition of UL 1449 to the second edition of UL 1449. To avoid confusion of the SVR in the marketplace, the third edition of UL 1449 has changed the nomenclature and testing of the protection rating of an. s tested in accordance to the third edition of UL 1449 will now be marked with a voltage protection rating (VPR). All s will be tested on three samples of all declared modes of the to the Institute of Electrical and Electronic (IEEE) combination wave at rated voltage [1]. The IEEE combination wave consists of an open circuit voltage and a short circuit current. The amplitude of the open circuit voltage of the 1.2/50 µs waveform is 6 kv, and the amplitude of the 8/20 µs short circuit current is 3 ka [2]. All measurements for parallel s are achieved by measuring the let-through voltage of the at a distance of 150 mm (6 inches) from the exit of the conductors from the enclosure [1]. FIGURE 1 LOCATIONS BY UL 1449 TYPES PRIMARY POWER UPS 11 CB1 ATS 1 CB4 CB3 CB2 CB5 ALTERNATE POWER G Greater than 10 m from service disconnect TABLE 1 VOLTAGE PROTECTION RATING (VPR) 330 400 500 600 700 800 900 1000 1200 1500 1800 2000 2500 3000 4000 5000 6000

Once the has completed the voltage protection testing, it must undergo the nominal discharge current test. If the successfully completes the test sequence, the per mode average of the letthrough voltages measured are compared to a predetermined list of values (Table 1). The voltage protection rating (VPR) of the is the value that is greater than the measured averages. The VPR is part of the UL marking requirements and is marked on the. Nominal Discharge Current The nominal discharge current is a new part of the testing regime and was adopted from the IEC standards for s, with some differences [3]. The nominal discharge current test is part of the voltage protection rating test, and is a measure of the s endurance capability. The nominal discharge current uses the 8/20 µs current waveform, which has a rise time from ten to ninety percent (t r ) of 8 µs, and a time from initialization to the fifty percent decay point (t d ) of 20 µs (Figure 2) [4]. manufacturers designate the amplitude of the nominal discharge current that the is to be tested to. The nominal discharge current test is only applicable to Type 1 and Type 2 s. The nominal discharge current for Type 1 s is 10 ka or 20 ka [2]. For Type 2 s, the nominal discharge currents are 3 ka, 5 ka, 10 ka, or 20 ka [2]. Short Circuit Current (Amperes) FIGURE 2 20 ka 8/20 µs NOMINAL DISCHARGE CURRENT The test methodology consists of Three(3) groups of Five(5) impulses for a total of 10000 fifteen (15) impulses. At the completion of each applied impulse, the maximum continuous operating voltage (MCOV) shall 5000 be applied within 1 sec to the for 1 minute. After each group of tests, the 0 can rest for up to thirty minutes. At the completion of the nominal discharge current Time (seconds) test, the is subjected to the maximum continuous operating voltage (MCOV) and for verification of the voltage protection rating. The maximum continuous operating voltage (MCOV) is applied for fifteen minutes. The voltage protection rating is verified by applying the IEEE combination wave to the and measuring the let-through voltage. The value of the nominal discharge current obtained through testing is required to be marked on the data label of the product. This is identified by the abbreviation I N. National Electric Code The Occupational Safety & Health Administration (OSHA), an organization under the Department of Labor, is the department within the US federal government responsible for workplace safety. One aspect of workplace safety is the safe use and application of electricity and electrical equipment. Workplace safety is achieved through a partnership between OSHA and the individual States. The States are responsible for determining standards that will ensure workplace safety. Each State determines what standards and revisions are appropriate, and the timeline for reviewing such standards. In some States, the responsibility for the adoption of workplace safety has been delegated to local municipalities. For electrical safety, all States and Municipalities have adopted the National Electric Code, which is developed by the National Fire Protection Association (NFPA). The revision cycle of the National Electric Code occurs every three years (e.g. 2002, 2005, 2008, etc.). However, not all States and Municipalities have adopted the same version of the National Electric Code (Figure 3). States such as Massachusetts, North Carolina, Arkansas, Ohio, New Mexico, Colorado, Wyoming, Idaho, Montana and Oregon has adopted the 2008 revision of the National Electric Code. Tennessee remains the only state to utilize the 2002 revision of the National Electric Code. States such as Nevada, Arizona, Texas, Oklahoma, Illinois, Maryland, and Iowa have delegated standards responsibility to the local level. The remaining states still utilize the 2005 revision of the National Electric Code. 20000 15000 000.0E+0 10.0E-6 20.0E-6 30.0E-6 40.0E-6 50.0E-6

The 2005 revision of the National Electric Code had two types of s: secondary surge arresters (SSAs), transient voltage surge suppressors (TVSSs). The application requirements of SSAs were detailed in Article 280, whereas the application requirements of TVSSs were detailed in Article 285. The requirements for both SSA and TVSS devices rated for use on systems of 1,000 volts or less were nearly identical. However, the testing methodologies utilized by Underwriters Laboratories were not. Article 285 The adoption of the Standard for Safety, Surge Protective Devices by UL and American National Standards Institute (ANSI) required changes to the National Electric Code. Unlike many changes to the National Electric Code, which requires changes to product safety standards, the product safety standard is necessitating the change to the National Electric Code. The two sections of the National Electric Code associated with s are Article 280 and Article 285. Article 280 of the 2008 revision of the National Electric Code is for surge arresters over 1,000 volts. Article 285 in the 2008 revision of the National Electric Code provides the requirements for connecting all surge protective devices (s) rated 1,000 volts or less to the electrical distribution system of a facility. The location of s ranges from the secondary terminals of the service transformer to end-use equipment. FIGURE 3 ADOPTION OF NATIONAL ELECTRIC CODE IN UNITED STATES Local Codes NFPA 70-2002 NFPA 70-2005 NFPA 70-2008 The changes between the 2005 and the 2008 revision of Article 285 of the National Electric Code are minor. Items that are the same between the two revisions are: Article 285.3 s shall not be used on ungrounded, impedance grounded, or corner grounded systems unless approved for use, Article 285.4 Where used, s shall be connected to each ungrounded conductor, Article 285.5 s shall be Listed, Article 285.6 s shall be marked with a short circuit current rating (SCCR), and shall not be installed at a point on the system where the available fault current exceeds the SCCR of the, Article 285.11 s can be connected indoors or outdoors, and shall be inaccessible to unqualified persons, Article 285.12 Conductors used to connect the to the system shall be as short as possible, Article 285.26 Conductors used to connect the to the system shall be greater than 14 AWG copper, or 12 AWG aluminum, and Article 285.27 s shall be permitted to be connected between any two conductors of the system: grounded, ungrounded, or grounding conductors. Connection of the grounded and grounding conductors shall only be interconnected during a surge Changes or additions to the 2008 revision of the National Electric Code are associated with the three types and their applicable locations of use, as defined by the Standard for Safety, Surge Protective Devices. Article 285.23 identifies the applicable installation locations for a Type 1. Type 1 s are permitted to be installed on the supply side or the line side of the service disconnect. When Type 1 s are installed on the supply side of the service disconnect, the grounding conductor of the shall be connected to either the grounded service conductor, the grounding electrode conductor, the grounding electrode for the service, or the grounding terminal in the service equipment.

Article 285.24 identifies the application requirements and installation locations for a Type 2. Type 2 s are permitted to be installed only on the load side of the service disconnect overcurrent device. In installations with multiple buildings or structures, a Type 2 can only be installed downstream of the first overcurrent device. Similarly, on separately derived systems, Type 2 s must be connected on the load side of the first overcurrent device. Article 285.25 identifies the application requirements and installation locations for a Type 3. Type 3 s must be located on the load side of the service disconnect overcurrent device, on the load side of branch circuit overcurrent protection, and at least 10 meters (30 feet) of conductor distance from the service disconnect. Conclusion Recent changes in the Underwriter Laboratories (UL) Standard for Safety, Surge Protective Devices, UL 1449 third edition has mandated changes to the 2008 revision of the National Electric Code. The UL 1449 third edition will become effective in 2009 September, requiring all s to be evaluated to the new standard. However, most State codes and subsequently, Code Inspectors will not be ready to apply these changes. The changes in the UL and NFPA documents will provide additional information on the application of s. There will also be changes related to the performance measurements of an ; although they are not significant. The areas of performance that will be noticeable are the new voltage protection rating (VPR), and the nominal discharge current. Since the surge current that is used to determine the VPR has increased from 500 amperes to 3,000 amperes, VPR levels will increase. Data labels will also have a nominal discharge current (I N ) of up to 20 ka. In some cases, the nominal discharge current rating will be the maximum surge rating of the device. In others cases, additional testing to other standards will be performed by the manufacture to determine the maximum capabilities of the. However, the impact of both documents on the marketplace will be small to manufacturers that had already meet UL s Standard for Safety, Transient Voltage Surge Suppressors, UL 1449 second edition, and were able to document their products clamping characteristics and surge current capabilities. References 1. Underwriters Laboratories (2006), Standard for Safety, Surge Protective Devices, ANSI/UL 1449, third edition, Northbrook, IL USA 2. Underwriters Laboratories (1996), Standard for Safety, Transient Voltage Surge Suppressors, UL 1449, second edition, Northbrook, IL USA 3. International Electrotechnical Commission (). 4. National Fire Protection Association (2004), Lightning Protection Systems, NFPA 780, Quincy, MA USA 5. National Fire Protection Association (2008), National Electric Code, NFPA 70, Quincy, MA USA

100 Emerson Parkway Binghamton, NY 13905 P (607) 721 8840 P (800) 288 6169 F (607) 722 8713 E contactsurge@emerson.com WP-30016 Rev. 8 1/13