Installation & Operation Guide

Similar documents
Installation & Operation Guide

Installation & Operation Guide

Installation and Operation Guide

Installation and Operation Guide. KMD 5559 CommTalk

BAC-9000 Series VAV Controller Installation Guide

Installation and Operation Guide. BAC-5841/5842 UFAD and BAC / VAV Advanced Application Controllers, 8 x 8

Digital Lighting Systems, Inc.

Digital Lighting Systems, Inc.

Installation and Operation Guide

7" Touch Screen Display

Custom Controller Installation Instructions

ETM-2050/ETM-2051 Service Manual

EX-RC1 Remote I/O Adapter

XT-9100 Technical Bulletin

Quick Start Installation Guide

TPE 1464 Series Pressure Transducer

NSD/M1 Installation Instructions

THE CTB08D LIGHT CONTOLLER

TRC-190 User s Manual

Ethernet Adapter Installation Instructions

Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.

6222 Two Door Module Technical Operations Manual

Rev Cutler-Hammer Smart Breaker Panel Control Manual

CA-A480-A Elevator Controller. Reference & Installation Manual

TRC-190 User s Manual

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

Digital Lighting Systems, Inc. PD216. Two Channel Dimmer and Switch Packs PROTOCOL USER'S MANUAL. PD216-UM Rev. E - 02/03

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

Installation and Getting Started Guide. HP ProCurve 600/610 External Power Supplies. PoE. Power over Ethernet Devices

SNAP-IT-1U Installation Guide

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

CC186 AND CC186/2 STAND-ALONE OR SYSTEM CLOCK

SCC5-RM. Coloronix, Inc West Jefferson Boulevard Los Angeles, California (323)

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

WIRING INSTRUCTIONS FOR HENRY SIGNS CONCERNING THE JOHN HANCOCK SIGN

EP/2 Installation Instructions

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

NCH-1000 (Multiple Breaker Types) Installation Instructions

Infosystem Remote Touchscreen Installation Instructions

STATUS Shiloh Road Alpharetta, Georgia (770) FAX (770) Toll Free

OilCop Component Wiring Installation Manual

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

Manual Simatek Control Unit GFC 32

Digital Lighting Systems, Inc. CD400-DMX DMX512 Four Channel Dimmer and Switch module

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

DESIGN GUIDE FOR INFINITY SYSTEMS

FX-2 Control Board ASY-360-XXX Setup and Configuration Guide

Rack Input Module Installation Instructions

Manual Control Unit GFC 32

ETM-2040 Service Manual

Installation Guide max. Modular RJ-45 Jack. Four-pin EIA-485 PC Data Port

Installation Guide (3/6 Outputs)

R & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.

Installation Guide. Room Temperature Sensors. Mounting. Location and Cover Removal (All) STE-6011 Only. STE-6010/6013/6015 Only

Control Techniques Variable-Speed Drive (VSD) Interface to E2 v and Above

Digital Lighting Systems, Inc.

Carbon Monoxide Sensor - ModBus

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual

Dim levels for each system output may be controlled by any of the following methods:

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007

Ink-Dot Series II Driver

High Power over Ethernet Midspans PD Port Model PD Port Model

NSI DIGITAL DIMMING SYSTEM DDS 5300 / 5600 DIMMER PACK

X47.CE Product Guide

OPLC Installation Guide

Andover Continuum Infinet II i2865/866 VAV Controllers with Built-in Actuator

Modular Room Control (MRC) Series Expansion Board

1 Description. 2 Specifications. Product Installation Document. Honeywell 12 Clintonville Road Northford, CT

USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10

ADAPTER CARDS TRADITIONAL STANDALONE. DATA SHEET page 1/14. Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Rev CH Breaker Gateway Installation and Operation Manual

22 Digital Inputs, including 2 Analog, 2 HSC/Shaft-encoder inputs 16 Transistor Outputs

Application Engineering

M-SWITCH SWITCH INPUT IN GAS CONTROL SYSTEM INSTALLATION OPERATION AND MAINTENANCE MANUAL

Installation and Configuration Guide

Channel Switch CS. General Operating, Maintenance and Installation Manual

Andover ContinuumTM Infinet II

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

PROLON INSTALLATION AND START UP GUIDE

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

Delta Controls. Wiring and Installation Guidelines

Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

ACS-30-EU-MONI-RMM2-E

180 Series Keypad. Handbook. Revision 2.1

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

500 Business Center Drive Pittsburgh, PA USA CAGE 1BGJ7. SwitchMaster R5000 Series Ultra-Compact Ganged A/B Switching System

CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE

EasyIO FC20 User Reference v1.3. EasyIO FC 20 DDC User Reference V1.3

INSTALLATION INSTRUCTIONS

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L M O N I T O R E D DEVICE

OZONE SWITCH Model OS-6. OS-6 Features

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

TARA CONTROLS AGC-5. UCI Random Start USER S GUIDE. With Optional Warning Flashes for the Hearing Impaired. TARA CONTROLS by Cartessa Corporation

Trouble Shooting Leveling Control Box Electric Jacks. Touch Pad LED Probable Cause Solution

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Transcription:

& Operation Guide KMD-7301/7301C Direct Digital Controller For Air Handling Applications 880-019-02C

KMD 7301 and KMD 7301C Direct Digital Controller & Operation Guide Introduction This section provides a brief overview of the KMD-7301 and the KMD-7301C Direct Digital Controllers. Review this material before you attempt to install the controller. Illustration 1 shows the major controller components and their locations. RS-485 Terminal Fuse Lamps Input Terminal PC/Modem Connector 4.374 Status LEDs Network On/Off Switch AC Power Terminal Output Terminal 1.416 6.786 Illustration 1. Controller Components Illustration 2 shows the connectors in greater detail. RS-485 B A (Ground reference; universal inputs) IN 4 IN 3 IN 2 IN 1 Inputs (Ground reference; universal outputs) Neutral Neutral 24 VAC Power Inputs Outputs Output 4 Output 3 Output 2 Triac Return Triac Output Illustration 2. Connector Detail 2

B A ~ KMD 7301 and KMD 7301C Direct Digital Controller & Operation Guide This section provides important instructions and guidelines for installing the KMD-7301/7301C Controllers. Carefully review this information prior to attempting installation. Mounting Use the four mounting holes to securely mount the controller using #6 hardware inside a UL-approved Enclosed Energy Management Equipment Panel or other suitable protective enclosure. Refer to Illustration 3. 6" IN1 IN2 IN3 IN4 RDY COM ON OFF LAMPS 4" 24VAC PWR T1 RET O2 O3 O4 Illustration 3. Mounting Hole Locations Input Connections Universal Inputs RS-485 Inputs Wiring connections are made depending on the intended application. Observe the following guidelines. (Refer to Illustration 2.) Connect device inputs to the input terminal connections for inputs 1 4. Connect all grounds to the common reference terminal. If input pull-ups are required, refer to Configuration later in this section. Make connections to a network using the RS-485 connector. If the Controller is at the End-of-Line, refer to Configuration after connections are completed. Detail The End-of-Line connection will have only one wire attached to the A and B terminals. For reliable operation, use Belden cable model #82760 or equivalent (18 gauge, twisted, shielded, 50 picofarads or less) for all network terminal block connections. 3

KMD 7301 and KMD 7301C Direct Digital Controller & Operation Guide Connect the nodes of the network in a daisy-chain arrangement. This means: Connect the A terminal in parallel with all other A terminals. Connect the B terminal in parallel with all other B terminals. Connect the shields of the cable together at each controller. Connect the shields to an earth ground only at one end of the segment; tape back the shield ground at the other end. Connecting Outputs Configuration One Triac and three Universal Outputs are available for output connections. The Triac output is labeled as T1 and the Universal Outputs are labeled O2 O4 on the output terminal block. Use the RET connection for the Triac return only; connect the Universal Outputs to the common terminal. Configuration settings may be required for the inputs or the RS-485 connection. If you must activate or de-activate pull-ups on the inputs or set the end-of-line termination for the RS-485 connection, refer to Illustration 4 to locate the switches for these settings. End of line switches Input pull-up switches 1 M A RST WD FL Illustration 4. Configuration Switch Locations Proceed as follows: 1. Remove the screw at the center of the controller that secures the cover, then remove the cover. 2. Locate the appropriate switch (see Illustrations 4 and 5). 4

KMD 7301 and KMD 7301C Direct Digital Controller & Operation Guide Power Connection ON CTS 1 2 ON OFF ON RS-485 Input Pull-Ups Illustration 5. Configuration Switches 3. Set the switches as follows: If the RS-485 connection is the End-of-Line controller, verify that both switches on the RS-485 switch are in the ON position. Otherwise, the switches remain in the OFF position. If one or more inputs require a pull-up, verify that the appropriate switch is set to the ON position. If no pull-up is required, move the switch to the OFF position (away from the ON side of the terminal block). 4. After you set the switches, replace the controller cover and secure it with the screw you removed earlier. Connect the 24 VAC supply voltage to the power terminal block on the lower left side of the controller. Two neutral and one hot connection are available. Power is applied to the controller when the power supply (or transformer) is plugged in, there is no Power On/Off switch. Illustration 6 shows a typical connection diagram for the controller. CTS 1 2 3 4 FROM PREV. DEVICE "A" FROM PREV. DEVICE "B" TO NEXT DEVICE "A" TO NEXT DEVICE "B" SPACE$TP SETPT$TP MIXED$TP KMD-7301 FAN COOL$VLV HEAT$VLV OUT$DMPR B A IN1 IN2 IN3 IN4 OUT1 TRIAC TRIAC RET OUT2 OUT3 OUT4 SERIES 24VAC FAN START CIRCUIT 24VAC 120VAC A B C 24 VAC RET. STE-5112-10 0-10 VDC OUT4 MEP-1272 KMC LINK N.O. CTE-3017 STE-5200 SERIES THERMOSTAT OPTION IN1 IN2 OA LINK N.C. H C C C DIS. STE-1414 OUT2 T SP STE-52XX APPLICATION DRAWING FOR KMD-7301 AHU WITH 10VDC HWV AND CWV AND OPTIONAL ECONOMIZER 0-10VDC VALVE ACTUATORS OUT3 Illustration 6. Typical Controller Application Diagram 5

KMD 7301 and KMD 7301C Direct Digital Controller & Operation Guide Configuration Prior to operating the controller, it must be configured using the Hardware Configuration Manager (HCM) application supplied with WinControl. Refer to the WinControl XL User s Manual for additional information. Note: All controllers on the same network must be configured for the same baud rate. Programming Refer to the KMC Digital Applications Manual for information on how to program the controller. Operation Controls and Indicators Network ON/OFF Status LEDs Isolation Lamps Once configured, programmed and powered up, the controller requires very little user intervention. The following sections describe the controls and indicators found on the card. The network ON/OFF switch is located below the phone jack on the left side of the controller. Use this switch to enable or disable the RS-485 network connection. Alternately, you may remove the RS-485 terminal block from the card to completely isolate the card from the network without disrupting network communications to other controllers. Two Status LEDs are located on the left side of the controller above the power connector terminal. They are used to indicate the following: RDY This LED flashes rapidly whenever the controller is operating normally. You can consider this the same as a power LED. COM This LED indicates when the controller is transmitting over the RS-485 network connection. Two Isolation Lamps are located near the Network ON/OFF switch. These lamps serve three functions: Removing the lamps will open the RS-485 circuit and isolate the controller from the network. 6

KMD 7301 and KMD 7301C Direct Digital Controller & Operation Guide Resetting the Controller If one, or both, lamps are lit, it indicates the network is improperly phased. This means that the ground potential of the controller is not the same as other controllers on the network If the voltage or current on the network exceeds safe levels, the lamps operate as fuses to protect the controller from damage. If the controller appears to be operating incorrectly, or is not responding to commands, you may need to reset the controller. Note Resetting the controller will restore the factory default configuration. It may be necessary to re-configure the controller with HCM to establish normal communications and operation. Re-programming may also be required. To reset the controller, proceed as follows. 1. Remove the screw at the center of the controller that secures the cover, then remove the cover. 2. Locate the jumper block next to the input pull-up switches (see Illustration 7). M A RST WD FL Illustration 7. Reset Jumper Block 3. Power off the controller. 4. Place a short on the RST jumper. 5. Power up the controller. Wait until the RDY LED flashes normally. 6. Power off the controller. 7. Remove the short from the RST jumper. 8. Replace the controller cover. 9. Power up the controller and re-configure it if necessary. 7

KMD 7301 and KMD 7301C Direct Digital Controller & Operation Guide Disclaimer The material in this document is provided for information purposes only. The contents and the product(s) described herein are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this document. Important Notices The KMC logo is a trademark of KMC Controls, Inc. 2003, KMC Controls, Inc. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of KMC Controls, Inc.Printed in U.S.A. Technical Support If you have any questions about this technical document or need additional details, please call KMC Controls technical services at 574-831-5250 or e-mail us at techs@kmccontrols.com. KMC Controls, Inc. P.O. Box 497 19476 Industrial Drive New Paris, IN 46553 U.S.A. TEL: 574.831.5250 FAX: 574.831.5252 E-mail: info@kmccontrols.com 8 880-019-02B