RS-485 Modbus RTU Networking FCU Thermostats with 0(2)-10 VDC Fan Output

Similar documents
RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

BACnet MS/TP Gateways for Mega Controls Modbus RTU Networking Devices

BACnet-over-Ethernet (BACnet TCP/IP) Gateways for Modbus RTU Devices

BACnet Product Overview

Field selectable application type and room module series, via dip-switches on controller

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

TC-9102 Terminal Controller

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

BA/BS4S Temperature Sensor Installation & Operating Instructions

RCF-230CAD. Room controller with communication for fancoil applications with two analogue V DC outputs

FCU-MULTI Modbus Fan Coil Unit Controller

FX Input/Output (I/O) Modules XM07 and XM14

RCF-230CAD. Communicating room controller for fan-coil applications with two analogue V DC outputs

Networkable Dual Duct VAV Controller Specification and Installation Instructions

RCF-230CD. Communicating room thermostat for fan-coil applications with on/off outputs

FCU-4 FAN COIL CONTROLLER

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

BACnet Flow Controller for Fan Filter Units

Temperature controller Ducted systems

TC-8900 Controller Units with PM-8900 Power Modules

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

FXVMA Variable Air Volume (VAV) Box Controller

S66 Series Electronic Fan Speed Control

RCF-230CTD. Room controller for fan-coil applications with outputs for two thermal or one 3-position actuator or function for an electric heater

isma-b-fcu FCU Hardware User Manual Global Control 5 Sp. z o.o. Warsaw, Poland

TM-2100 Series Room Command Module

BAPI-Stat 4MB Modbus Temp or Temp/Humidity Sensor

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

clarity 3 Programmable Controller

FX06 Field Controller

Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit

MANUAL INSTALLATION. Multi-Variable Monitor. MVM Series. Issue Date: 02/07/ Price Industries Limited. All rights reserved.

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

THERMOSTATS & CONTROLLERS

IntesisBox PA-AW-MBS-1 v.2.0

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

Measure & Control Temperature & CO2 levels with analog & digital I/O

TM-2100 Series Room Command Module

RCM Room Command Module New Style

MOD-RI Room Interface Modules with Modbus

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

HARDWARE GUIDE. VAV Zone Controller C1000 Series. Specifications and Operational Guide

CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers)

Room controller STRA-17

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

P216. Condenser fan speed controller. Product bulletin. Features

Evolution TH. Pre-configured controller with display, clock and communication. Evolution. Applications. TH version. Sensors

FX-2 Control Board ASY-360-XXX Setup and Configuration Guide

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

TF243 Series Digital Thermostat Fan Coil Unit Control

LLR-MOD Modbus Light Level and Occupancy Sensor

SE7600E Series Application Guide

RWD68U Universal Controller

Pre-programmed room controller with display and communication

Underfloor Controllers

Starzone 4000 Master Control Panel Figure 2.1 Master Control Panel

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Carbon Monoxide Sensor - ModBus

Linear Actuators (235N)

Supplementary operating instructions for your air curtain system Controller TMC 500

Medium User Interface (MUI) Version 3

HLS34 Modbus FCU/VAV Controllers installation instructions

SE7600E Series Application Guide

M1000 INTELLIGENT ZONE CONTROL SYSTEM

P216 Series Condenser Fan Speed Controller

VA-7700 Series. Electric Valve Actuators. Product Bulletin

PROLON INSTALLATION AND START UP GUIDE

CONTROLLER INSTALLATION OPERATION & QUICK START

System Controls Suggested Specification

FCU-4 FAN COIL CONTROLLER

Richmond Heights. Smart Wi-Fi Capacitive Touch With Dual Protocols Universal Controller. Go Green

RC-CDTO. Pre-programmed room controller with display, communication and three-point control

Fast Route to Reliable Energy Savings ZIP Economizer

ECL Comfort V a.c. and 24 V a.c.

I ntroduction. RA Fast Running Electric Actuator. Features and Benefits

Andover ContinuumTM. b3850 Series Terminal Controllers

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

HygroClip M22 Series. 2-wire loop powered humidity temperature transmitters INSTRUCTION MANUAL

Series P215DP Single/Dual Pressure Input Condenser Fan Speed Controllers For Single Phase Motors (incl. built-in RFI suppression filter)

Millennium Simplicity Elite Parameter Points and Quirks

Modular Room Control (MRC) Series Expansion Board

clarity 3 VAV Programmable Controller

2.) Cabinet setup and preset data shall, as standard, be fully user programmable on a per cabinet or system wide basis.

Zone Pressure Touch Sensor - Standard Range

Transmitters RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P LCD

Communicative controller for VAV systems

Tempco Instruction Manual

Siemens BACnet Programmable TEC Constant Volume

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

BAC-9000 Series VAV Controller Installation Guide

Siemens BACnet Programmable TEC Unit Conditioner Controller

CDR Room CO 2 and Temperature Sensor with Modbus

EZ-ZONE. EZ-ZONE ST Integrated Control Loop Makes Solving the Thermal Requirements of Your System Easy

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

Transcription:

NTAF Series Issue Date March 1, 2018 RS-485 Modbus RTU Networking FCU Thermostats with 0(2)-10 VDC Fan Output Features Ultra slim wall-mount unit to match any décor Supports Modbus RTU protpcol Supports standalone operation on RS-485 communication failure Large easy-to-read Liquid Crystal Display (LCD), with LED backlight A stylish bi-directional rotating dial and two compact touch keys to provide ease of operation Choice of constant display of ambient temperature or temperature set point value Output relays employed for direct connection of valve actuators for 2- wire on-off and 3-wire floating control Configurable operating parameters 2-wire on-off, 3-wire floating and 0 (2)-10 VDC output models available 0(2)-10 VDC fan output in a maximum of 7 steps plus auto mode Adjustable proportional band for proportional/3-wire floating models Adjustable integral time for 0(2)-10 VDC and 3-wire floating output models Choice of valve stroke time for 3- wire floating output models Field adjustable high and low occupied set point limit settings Choice to retain last entered settings on power resumption Dual-output models with auto cooling/heating changeover (deadband operation) and manual override Adjustable 1 to 5 K deadband for dual-output models Choice of operating sequence for dual-output models Unoccupied mode capability with field adjustable cooling and heating set points, for energy savings Choice of unoccupied mode activation in operating mode only or in both standby and operating modes Choice of fan action in unoccupied mode Field recalibration capability of measured temperature Continuous or auto fan operation External and seasonal changeover temperature sensor capability Window mode operation Optional infra-red remote control unit Optional special faceplate color available on request General The NTAF Series RS-485 networking room thermostats use the communication technologies of Modbus RTU protocol to monitor and supervise BLDC motor-driven fan coil units in the heating, ventilating and air-conditioning industry, and employ a simple master/ slave protocol. All NTAF Series thermostats are slaves in this protocol, and can be under the control of a Mega Controls BACnet gateway, of either BMG or BMGE Series, called the master. The BMGs and BMGEs are native BACnet devices and communicate using the BACnet MS/TP or BACnet-over-Ethernet protocol. Net 2 port of the BMG master and all slaves are daisy-chained through a RS- 485 Modbus RTU network. The maximum number of NTAF slaves in a Modbus RTU network is 32. Each BMG has 2 addresses. Net 2 address is always 0 which is the address of the Modbus RTU network. Net 1 address is the MAC address of the BACnet MS/TP network which is also set up for a maximum of 32 devices in a trunk cable length not exceeding 1000 m. The BMG gateway spontaneously detects the presence of slaves that go online in its NET 2 network. If more than 32 BMGs are needed in the system, an additional BACnet system device is required for the second BACnet MS/TP network. Each BMGE gateway is available with two RS-485 networks. Each network can support up to 32 NTAF Series Modbus RTU devices. The BMGE gateway spontaneously detects the presence of slaves that go online in its NET 1 and NET 2 networks. The NTAF Series thermostats cover a wide range of fan coil applications, including 2 and 4-pipe fan coils and direct connection to BLDC motor-driven fans. Temperature sensing can be from a built-in room sensor or a remote sensor. The 0(2)-10 VDC and 3-wire floating thermostats adopt true proportionalintegral (PI) control algorithm. The microprocessor combines a proportional plus integral (PI) algorithm with advanced adaptive control logic. The proportional component of the algorithm adjusts the control output in response to changes in the measured temperature. The integral component of the algorithm adjusts the control output to eliminate offset (difference between the set point and the actual temperature). This provides precise and stable control under various system capacity and varying load conditions without the need for tuning or calibrating the control algorithm in the field. The digital display of ambient temperature, set point and operating mode provides the user with an attractive and functional thermostat that is easy to use. A fan-speed control touch key allows control of a variable-speed fan in the form of step outputs in 0(2)-10 VDC values. The speed control key has a maximum of 8 positions: Steps 1 to 7 plus Auto. In the step positions, the fan runs continuously at a speed corresponding to the selected fixed voltage output. In the Auto mode, the fan speed is temperature dependent and controlled automatically in 3 steps from lowest to highest speed. Through the parameter setup menu, the default number of steps as well as default fan output range can be changed from 3 to 7 and from 0-10 to 2-10 VDC respectively. When operating in auto fan mode, the ambient temperature controls both the valve output and fan output simultaneously but uses different algorithms. A bi-directional rotating dial allows change of settings such as temperature set point values. Ordering To order, specify complete model numbers. Copyright Mega Controls Limited www.megacontrols.com 1

Specifications Product model numbers See Fig.2: NTAF Series Model Number Selection Guide Power requirements 110-230 V, +10% and -15%, 50/60 Hz Operating temperature differential Fixed at 1 K for both cooling and heating modes (for both 2-wire and 3-wire on-off models) 0(2)-10 VDC output impedance Minimum 10,000 Ω Temperature display range 5-35 º C in 0.5 K increments: accuracy ±1 K (41-95ºF in 0.5 R increments, accuracy ±1 R) Temperature set point range 5-35 º C in 0.5 K increments, initial factory setting at 22 º C (41-95ºF in 0.5 R increments) Offset adjustment of temperature +2, +1, 0, -1 and -2 K (+2, +1, 0, -1 and -2 R) throughout the range, factory setting 0 indication (field recalibration) Deadband of dual-output models Adjustable 1 to 5 K between cooling Mode and heating Mode, factory set at 3 K(3 R) Valve stroke time for 3-wire floating Accumulatively 10 to 240 s maximum in one direction, in steps of 10 s; factory setting 120 s models Proportional band for PI control Adjustable 1 to 10 K in 1 K increments, factory setting 5 K Integral time for PI control Adjustable 0 to 30 minutes in 1 minute increments, factory setting 15 minutes. Setting = 0 means integral time being turned off. Auto fan temperature differential Fan step output changes at 2 K increments from lowest to highest speed, only Steps 2, 4 and 7 are available in auto fan mode; auto fan operation in heating mode depends on choice of auto fan action. Sensing element NTC thermistor, 10 kω@25ºc; accuracy ±0.5 K@25ºC Unoccupied mode Input signal from external voltage-free contact; choice of unoccupied mode activation: in operating mode only or in both standby and operating Unoccupied temperature set point range Field adjustable 5-35ºC in 1 K increments, separately for cooling and heating; Factory settings: 16ºC for heating and 26ºC for cooling RS-485 communication speed Baud rate fixed at 19,200 bps Device MAC addressing 01-32 via parameter setup menu, factory default setting 255 (displays as FF on thermostat screen) Proprietary Modbus RTU network guide- Maximum 32 devices and maximum 1,000 m cable length Enclosure Material: Self-extinguishing, molded ABS Finish: Off white housing and dark grey faceplate Electrical ratings Valve output relays 110-230 V, 3 A resistive, 1 A inductive, 50/60 Hz Total rating 110-230 V, 5 A maximum, 50/60 Hz Ambient/Storage temperature limits 0 to 50 o C / -30 to 50 o C, 10% to 90% RH non-condensing Connectors Non-removable line-voltage terminal blocks and removable low-voltage wire plugs Power wires Wire size 1 mm 2 or 18 AWG solid copper recommended Sensor wires 22 AWG twisted shielded pair double-insulated cable Accessories and options See Figure 8: Optional Accessories Agency approval CE Mark compliant to EMC and Low Voltage Directives pending Shipping weight 0.2 kg (0.44 lb) Dimensions See Figure 7: Dimensions in mm The performance specifications above are nominal and subject to tolerances and application variables of generally acceptable industry standards. The Manufacturer shall not be liable for damages resulting from misapplication or misuse of its products. Figure 1: Display Control Unit and LCD Layout 2 NTAF Series Modbus RTU Networking FCU Thermostats Product Bulletin

Figure 2: NTAF Series Digital Room Thermostat Model Number Selection Guide NTAF 1 R Product Type Separator Control Type Options NTAF = NTAF Series 1 = Single 2-wire on-off output, cool only or heat only R = with infra-red Digital Room 1M = Single 2-wire on-off output, manual cool/heat changeover receiver Thermostats 1A = Single 0-10 VDC output, cool only or heat only for RCU-1 1AM = Single 0-10 VDC output, manual cool/heat changeover B = without buzzer for 1F = Single 3-wire floating output, cool only or heat only key touch sounding 1FM = Single 3-wire floating output, manual cool/heat changeover W = with white color 2 = Dual 2-wire on-off outputs, manual or Auto cool/heat faceplate changeover 2AH = 0-10 VDC cooling output and 2-wire on-off output, manual or Auto cool/heat changeover Figure 3: Jumper Settings The models NTAF-2 can be re-configured in the field to various model numbers by a qualified servicing agent, if necessary, by changing the jumper positions of JP2 and JP3. The locations of these jumpers can be found after removing the thermostat cover from its baseplate. Jumper Settings of JP2 and JP3 Model Number JP2 JP3 NTAF-1 Cut Cut NTAF-2 Uncut Uncut NTAF-1F Cut Uncut NTAF-1A Uncut Cut Jumper Settings of JP1 and JP4 Jumper Cut Uncut JP1 JP4 With External Sensor For 2-10 VDC Output With Builtin Sensor For 0-10 VDC Output Note: JP4 is available in 0-10 VDC/2-10 VDC output models only. Factory setting is 0-10 VDC. Figure 5: Thermostat Errors Reporting Figure 4: 0(2)-10 VDC Fan Output Table Step Output Value for 0-10 VDC Range (VDC) Output Value for 2-10 VDC Range (VDC) 0 0 2 1 1.43 3.15 2 2.86 4.29 3 4.29 5.43 4 5.72 6.57 5 7.15 7.71 6 8.58 8.85 7 10 10 When the following errors are reported on the LED display unit, these errors will prevent the thermostat from normal operation and all thermostat functions will be locked out: E-1 EEPROM read/write error E-2* Temperature sensor open-circuited E-3 Temperature sensor short-circuited * If jumper JP1 is cut open and external sensor is used, E-2 means the external sensor may have been disconnected from Terminals SR1 and GND. Check the external sensor s connectivity and resistive value. If E-2 error is still reported, return the thermostat to the manufacturer for repair. When the error E-1 or E-3 is reported or when the error E-2 is reported without jumper JP1 being cut and external sensor being installed, return the thermostat to the manufacturer for repair. Auto In auto mode, the fan will run in only 3 steps, i.e. Steps 2, 4 and 7 as default. Number of steps can be changed via parameter setup menu. Figure 6: Wiring Diagrams and Application Notes Wiring and Application Notes Cut jumper JP1 open if an external sensor is wired to SR1 and GND. Run the wiring away from any electrical motors or power wiring. Failure to do so may result in poor thermostat performance due to electrical noise. Cut jumper JP4 open if 2-10 VDC proportional output is required. 22 or 24 AWG twisted shielded pair double-insulated cable is recommended as remote sensor wiring and its length must not exceed 25 m. Do not bundle and run power wiring and remote sensor wiring in the same conduit. The seasonal changeover sensor should be wrapped around the supply water pipe when associated with a water system. When the changeover sensor temperature exceeds 30 ºC, the thermostat enters into heating mode. External seasonal changeover sensor or switch is applicable to heat only or cool only 2-pipe models only. Unoccupied contact closure activates unoccupied mode. Window contact closure activates thermostat lockout mode. Hidden-line wiring for Terminal 4 of CN6 is applicable to dual on-off output models only. The thermostat outputs are designed for controlling zone valves. If used for controlling electric heaters, external contactors must be used. NTAF Series Modbus RTU Networking FCU Thermostats Product Bulletin 3

Figure 7: Dimensions in mm Figure 8: Optional Accessories Remote Control Unit Bottom View Description Remote control unit Probe temperature sensor Duct temperature sensor With infra-red receiver capability Without buzzer capability With white-color faceplate Part No. RCU-1 TE10-1 TE10-2 NTAF-xxR NTAF-xxB NTAF-xxW Figure 9: Mounting Details Back View Front View Mounting The thermostat can be flush mounted or secured to a standard European 75 x 75 x 47 mm (strongly recommended) electrical box. Two mounting screws are included. Network, Cabling & Step-down Transformer Requirements To ensure network stability and reliable communications, particularly at high speeds on a BACnet MS/TP or Modbus RTU network for a number of devices, it is imperative that the following network, cabling step-down transformer requirements are adhered to: Item Cabling Topology Maximum Nodes Terminator Cable Shielding Description It is recommended to use networking cabling that matches the following specifications: Balanced 100 to 120 ohms nominal impedance, 22 or 24 AWG Twisted Shielded Pair (TSP) Cable Nominal capacitance of 52 pf/m or lower Nominal velocity of propagation of 66% or higher Terminating the shield to ground at one end only for each isolated segment will prevent ground loops in the shield and drain RF energy to ground. Grounding at the BACnet router or controller is preferred. Ensure the BACnet MS/TP or Modbus RTU network cable is installed as a daisy chain from one device to the next. The maximum number of devices is 32 per BACnet MS/TP or Modbus RTU network. A terminator of 120-ohm impedance must be installed at each end of each BACnet MS/TP or Modbus RTU network segment, or two per network. Ensure that this requirement is not overlooked in laying out the network architecture and when ordering product. Use a shielded, twisted pair cable for communications. Never directly ground wire in more than one point on the shield. Doing so can induce large currents and result in communication problem. Repeater A repeater is not necessary unless the network is extended beyond 1,000 m. Step-down Transformer A separate isolated double-wound transformer is recommended for supplying 24 VAC power to each BMG or BMGE. If and when the same transformer is shared with other devices, observe the polarities of the power supply of all devices including the BMG or BMGE. 4 NTAF Series Modbus RTU Networking FCU Thermostats Product Bulletin

Figure 10: Network Configuration BACnet MS/TP Network Notes: 1. Ensure the recommended balanced cable is used. 2. Ensure the cable is installed as a daisy chain from one device to the next (1,000 m maximum) and the shield is grounded at one single point of the network only. 3. Ensure a MS/TP terminator is installed on each end of a MS/TP network. 4. The maximum nodes per MS/TP network is 32. Modbus RTU Network Notes: 1. Ensure the recommended balanced cable is used. 2. Ensure the cable is installed as a daisy chain from one device to the next (1,000 m maximum) and the shield is grounded at one single point of the network only. 3. Ensure a terminator is installed on each end of each Modbus RTU network. 4. The maximum nodes per Modbus RTU network is 32 To BACnet MS/TP Network Supervisor With BMG BACnet MSTP Gateway BMG BMG With BMGE BACnet-over-Ethernet Gateway BMGE NTAF NTAF NTAF NTAF BMGE NTAF Series Modbus RTU Networking FCU Thermostats Product Bulletin 5

WARNING Incorrect wiring connection may cause permanent equipment damages to the thermostat. Connections of Sensors and Contacts Piping Notes: 1. On a single on-off output unit, V1 can be either a 2-wire spring-return cooling or heating valve. 2. On a dual on-off output unit, V1 must be a 2-wire spring-return cooling valve and V2 a 2-wire springreturn heating valve. 3. V3 must be a 3-wire floating valve. In cooling mode, Terminal 3 output opens valve on temperature rise and Terminal 4 output closes valve on temperature drop. The action in heating mode is reversed. 4. On a single 0(2)-10 VDC output unit, V1+ can be either a 0(2)-10 VDC cooling or heating valve. 5. On a dual 0-10 VDC plus on-off output unit, V1+ must be a 0-10 VDC cooling valve and H an electric heating contactor. Wiring Diagram for Single and Dual 2-Wire On-Off Valve Outputs Wiring Diagram for Single 3-Wire Floating Valve Output V1 and V2 are 2-wire on-off spring-return valves Wiring Diagram for Single 0(2)-10 VDC Valve Output V3 is a 3-wire floating valve Wiring Diagram for Dual 0(2)10 VDC Cooling Valve Output and Line-Voltage Heating Output V1+ is a 0(2)-10 VDC valve V1+ is a 0(2)-10 VDC cooling valve and V2 is an electric heating contactor 6 NTAF Series Modbus RTU Networking FCU Thermostats Product Bulletin

Operation Notes User Operating Mode LCD shows ambient temperature constantly except when set point adjustment is being made. Press the system key Ф to enter into the desired operating mode: Cool or Heat-Auto-Fan Only-Off, etc. Press the fan key to change the fan speed mode: 1-2-3-4-5-6-7-Auto, etc. Increase or decrease temperature set point by rotating the adjustment dial clockwise or counter-clockwise. When the dial is rotated, the LCD shows the existing set point setting. In unoccupied mode, the factory temperature set points are 26 o C for cooling and 16 o C for heating. In heating mode, the fan speed can be set at Off or Step 2, depending on setup menu setting, when temperature is satisfied. Unoccupied mode can be activated in the following manner when the unoccupied contact closes: For Models 1, 1A and 1F, the unoccupied cooling or heating mode is determined by the status of the SR2 seasonal changeover sensor and the valve output is activated according to the measured temperature. For Models 1M, 1AM and 1FM, while in unoccupied mode, the valve output is never activated. For Model 2 and 2AH, the unoccupied cooling or heating mode is always determined by the measured temperature and valve output is also activated according to the measured temperature. Unoccupied mode activation in operating mode only or in both standby and operating mode will be determined by activation setting in setup menu. When unoccupied mode is activated, all keys are locked out and no settings can be entered. When the window contact is closed, the window function enabled mode is activated and locks out all thermostat functions and displays the window icon on the LCD. This function has a higher priority than the unoccupied mode. Parameter Setup Mode The thermostat allows authorized service agent to change a number of operating parameters in the field. Refer to the parameter setup manual for details. Error reporting All valve and fan outputs will be shut down when error is reported. Mega Controls Limited Room 1521A, Star House, 3 Salisbury Road, Tsimshatsui, Kowloon, Hong Kong Phone: +852 6281 1320 Fax: +852 3741 7084 E-mail: sales@megacontrols.com Website: www.megacontrols.com NTAF, 18-03(Mega) NTAF Series Modbus RTU Networking FCU Thermostats Product Bulletin 7