I/O module, analogue outputs and universal inputs

Similar documents
I/O module, digital and universal inputs, modu530

I/O module, universal, digital, S0 inputs, modu533

modu : Local override and indicating units

I/O module, digital outputs (relays), modu550

I/O module, digital outputs (open collector), modu551

EY-IO 534: I/O module, analogue inputs with galvanic isolation, modu534

EY-EM : Remote I/O module, ecolink

EY-RU : Room operating unit, ecounit

EY-RU : Room operating unit, ecounit

EY-AS 524, 525: Modular automation station, modu524/525

EY-AS 525: Modular automation station, modu525

EY-AS 524, 525: Modular automation station, modu524/525

EY-RU : Room operating unit, ecounit

EYE 200: DDC single-room controller, ecos200

EY-RU : Room operating unit, ecounit

modunet292: novanet-ethernet interface

EY-AS 521: Compact automation station, modu521

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

ecounit : Room operating unit with EnOcean wireless technology

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

EY-RC 208, 209: Room automation stations, ecos208, 209

EY-RU 355: Room operating unit, ecounit355

EY-RC 500: Room automation station, ecos500

EY-SU 358: Push-button unit for room operating unit, ecounit358

Sauter Systems

Content. Product Description

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A)

EY-WS 500: Web server for moduweb Vision and moduweb500 BACnet networks

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02

Operating instructions. Speed monitor D / / 2014

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Extension module for lighting control

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

Non-communicating room controllers

Operating instructions. Switching amplifier DN0210 DN / / 2015

TM5C12D6T6L compact I/O expansion block TM5-24 I/0-12 DI - 6 DO transistor - 4 AI - 2 AO

MINI MCR-SL-UI-REL(-SP)

PHOENIX CONTACT - 01/2007

EYL230: nova230, Compact universal automation station

Data Sheet T 6493 EN. TROVIS 6400 Automation System TROVIS 6493 Compact Controller. For panel mounting (front frame 48 x 96 mm/1.89 x 3.

RTU500 series Data Sheet Power Supply CP-E 24/2.5

The Tracker 220 Series A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement

EY-RU : Room operating unit with EnOcean wireless technology, ecounit

SSR - Supplies - Relays

TM3TM3 module TM3-2 temperature inputs and 1 analog output

AV24-MFT AV24-MFT2 AV24-MFT2-C105. Power consumption In operation For wire sizing N 1700 N Control Control signal Y Operating range

Priva Blue ID Analogue output module with manual override AO2m/AO4m

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO

AVM321S, 322S: Actuator SAUTER vialoq AVM 1000 with SAUTER Universal Technology (SUT )

TM3TI4 module TM3-4 inputs temperature

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

TRACKER 220 SERIES. Digital Panel Indicators. A Complete Range of Universal Input Digital Panel Indicators for Temperature and Process Measurement

Operating instructions. Standstill monitor A / / 2011

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

AVM 321, 322: Valve actuator

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

Controller module. Brief description. Features. Block structure. Page 1/7. Data Sheet

EY-RU : Room operating unit with EnOcean wireless technology, ecounit

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

Universal Controller

OP10. Pre-programmed, configurable controller for simple applications

Products no longer available

Compact Universal Controllers

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Automation stations compact model

Indicomp 4 Bargraph Indicator

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

EXOcompact. Third generation freely programmable controllers

AVF 125S: SUT valve actuator with spring return

Priva Blue ID Digital input module DI4/DI8/DI16

SX90 Process Controller

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX

QUICK START GUIDE. vau4/3. Frequency converter. operating instructions /12

TM3AI4 module TM3-4 analog inputs

ACTIONI/Q Q498. DC Powered DC Input Field Configurable Isolator with Math Functions

Technical Data. C-DIAS-MULTI l/o MODULE CIO 013

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

MINI MCR-SL-PT100-UI-200

MID approval no. DE-08-MI004-PTB004 Date of release

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Non-communicating room controllers

EY-RC 311: Programmable controller, ecos311

LLR-MOD Modbus Light Level and Occupancy Sensor

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

Product and Function Description

Product and functional description

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

Electronic Temperature Controller. Instruction Manual Version

Operating Manual FPGA-based High-Speed Micro-PLC

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

Electrical Actuators

Priva Blue ID C-Line Mix input/output module MX34

Transcription:

SAUTER EY-modulo 5 PDS 92.061 en Product Data Sheet EY-IO570 modu570: I/O module, analogue outputs and universal inputs How energy efficiency is improved SAUTER EY-modulo 5 technology: modular, fast and universal Areas of application Control via standardised signal (0...10 V), acquisition of digital (alarm/status) and analogue inputs (Ni/Pt1000, U/I/Pot) in technical installations, e.g. HVAC. Features Pluggable element for extending the modu525 automation station 4 outputs 8 inputs Modular design (baseplate/electronics) Power supply from modu525 automation station Direct inscription on front Part of the SAUTER EY-modulo 5 family of systems Can be equipped with a local override/indicating unit Technical description 4 analogue outputs (0...10 V) 8 universal inputs (Ni/Pt1000, U/I/R, DI) Products Type EY-IO570F001 I/O module, analogue outputs and universal inputs Technical data Electrical supply Installation Power supply from modu525 via I/O bus Fitting on top-hat rail Power consumption 1) up to 1.5 VA/0.80 W Dimensions W H D (mm) 42 170 115 Dissipated power up to 0.80 W Weight (kg) 0.285 Current consumption 2) up to 50 ma Standards, guidelines and directives Version Degree of protection IP 30 (EN 60529) Analogue outputs 4 (push-pull) Protection class I (EN 60730-1) Load up to 2 ma Environmental class 3K3 (IEC 60721) Universal inputs 8 CE conformity as per Analogue Ni/Pt1000, U/I/R, Pot EMC Directive 2004/108/EC EN 61000-6-1 Digital DI (approx. 3 Hz) EN 61000-6-2 EN 61000-6-3 Interfaces, communication EN 61000-6-4 Connection, modu6.. (LOI) 6-pole, integrated Connection, I/O bus 12-pole, integrated Additional information Connection terminals 24, 0.5...2.5 mm² Fitting instructions for electronics MV P100001574 Fitting instructions for baseplate MV P100001575 Permitted ambient conditions Material declaration MD 92.061 Operating temperature 0 45 C Storage and transport temperature 25 70 C Dimension drawing M11416 Humidity 10 85% rh Wiring diagram A10510 no condensation 1) On the primary side of modu525 base station (230 V~) 2) Supply from modu525 base station Accessories Type Local override and indication devices (LOIs) EY-LO630F001 EY-LO670F001 16 LED indicators, bi-colour 4 setpoint adjusters (A-0 100%), 8 LEDs for operation/indicating Components 0920360003 24 V I/O module baseplate (pack of three) 0929360570 Module electronics modu570 8 UI/4 AO 24 V www.sauter-controls.com 1/5

Engineering notes The I/O module modu570 generally consists of two components: the baseplate, in which the I/O bus system and connection terminals are integrated, and the actual I/O module electronics. Installation & assembly The baseplate of the I/O module is fitted to a top-hat rail (EN 60715) inside a motor control centre and connected on one side directly with the I/O bus of the modu525 automation station or modules. This connection work must be done only when there is no voltage. The baseplate contains the 'bus module' that is responsible for the voltage supply and continuous communication. This ensures that disturbances due to a malfunction or partial defect of the electronic component do not affect the functionality of other modules in the sequence. I/O module pcbs can be inserted in and removed from the baseplate whilst the automation station is in operating mode. I/O module pcbs should be inserted and removed only when the basis station is switched off for reasons of plant safety and to avoid input/output malfunctions. Labelling concept The I/O module can be labelled by means of a paper insert behind the transparent cover on the front side. Perforated labelling templates are available for this purpose. These labels are normally inscribed using text generated from within CASE Suite and are printed out on normal DIN A4 paper using generic printers. Assigning modules to an automation station The I/O module's electronic hardware has pin coding so that only the correct baseplate can be used. The modu525 automation station detects whether or not a module baseplate is plugged into the I/O bus. CASE Suite is used to assign the baseplate number and module types of I/O modules to the automation station. This information is stored permanently in the automation station. LED display/function The I/O module is equipped with a system LED that indicates the following operating conditions: System LED LED I/O Bus Condition Indicator sequence No name green, continuously lit Module in operation green, pulsating Module not assigned to base station red, pulsating fast AS in configuration, update or download mode red, flashing Module incorrectly assigned or internal error alternating green - red - off lamp test active (display type has priority) no display no voltage supply of function The I/O module has a total of 4 analogue outputs and 8 universal inputs. Outputs Number of outputs 4 Type of outputs Analogue outputs 0(2)...10 V= Load up to 2 ma per output Return conductor connected to earth Updated 100 ms Resolution 13 bits The output voltage is measured between the relevant output terminal (a0...a3) and an earth terminal. The outputs are designed as push-pull outputs with active sink capability. A load of 2 ma can be applied to each output. The sum of all outputs should not exceed 20 ma. The outputs are protected against static discharges, but not against the presence of direct or alternating currents! Universal inputs Number of inputs 8 (UI) Type of inputs Ni1000 (DIN 43760) (software coding) Pt1000 (EN 60751) Voltage measurement (U) Current measurement (I) only on channels u8, u9. Potentiometer input (Pot) Resistance (R) Protection against extraneous voltage Ni/Pt/U/R/Pot/DI ± 30 V / 24 V~ (without damage) I (channel u8, u9) +12 V / 0,3 V (without damage) Reference Uref 1.23 V (terminal 22) Scan rate 100 ms Scan rate 500 ms Resolution Channels u8, u12 Channels u9, u10, u11, u13, u14, u15 14 bits Measuring ranges Voltage (U) 0 (2)...10 V, 0 (0.2)...1 V Current (I) 0 (4)...20 ma Potentiometer (Pot) 0...1 (100%) with 3-line connection (1 2.5 k ) Reference Uref 1.23 V (terminal 22) > 1 k, max. load 10 ma Resistance (R) 200...2,500 Temperature Ni1000 50...+150 C Pt1000 50...+150 C Digital input Potential-free contacts, wired to earth Pulse counter Opto-coupler, transistor (open collector) approx. Iout = 1.2 ma max. 3 Hz (100 ms update interval) max. 0.5 Hz (500 ms update interval) Digital input (DI fixed) Protection against extraneous voltage Ni/Pt/U/R/Pot/DI < 24 V~/30 V (without destruction) I (channel u12, u13) +12 V/ 0.3 V (without destruction) Reference Uref 1.23 V (terminal no. 22) Temperature measurement (Ni/Pt) The Ni/Pt1000 sensors are connected using the two-wire method between one of the input terminals for universal inputs (channel u8...u15) and an earth terminal. Inputs do not require calibration and can be used directly. A corresponding line resistance of 2 is pre-compensated as standard. With the corresponding line resistance of 2 (cable cross-section: 1.5 mm²), the connection cable may be a maximum of 85 m in length. Greater line resistances can be compensated using the software. The measuring voltage is pulsed so that the sensor does not heat up (IMeas approx. 0.3 ma). 2/5 www.sauter-controls.com

Voltage measurement (U) The voltage to be measured is connected between one of the input terminals for universal input (channel u8...u15) and an earth terminal. The signal must be potential-free. The two measurement ranges with or without offset 0 (0.2)...1 V and 0 (2)...10 V are selected by means of the software. The input's internal resistance Ri (burden) is 9 M. Current measurement (I) The current can only be measured on two inputs. The voltage to be measured is connected between one of the two input terminals for universal input (channel u8, u9) and an earth terminal. The current signal must be potential-free. The measurement ranges with or without offset 0 (4)...20 ma are selected by means of the software. The internal resistance Ri of the maximum input current must be restricted to 50 ma. The internal resistance Ri is < 50. Potentiometer measurement (Pot) The potentiometer is connected between one of the input terminals for universal inputs (channel u8...u15), an earth terminal and the terminal Uref (reference voltage). So as not to overload the reference outputs, the lowest potentiometer value should be at least 1 k. The reference output is not short-circuit-proof. The upper value of 2.5 k is predefined to guarantee stable, interference-free measurement. Note: In order to maintain the measuring accuracy, earthing connections should be occupied only with the same type of input. To obtain an ideal connection, it is recommended to connect one of the I/O module's earthing terminals direct (short) to the automation station or to a corresponding cabinet terminal. Digital inputs (DI with UI) The AS also uses the universal inputs to record binary information. This information (alarm/status) is connected between an input terminal (u8...u15) and an earth terminal. The station applies a voltage of approx. 13 V to the terminal. This usually corresponds to INACTIVE (bit = 0) for an open contact. When a contact is closed it is ACTIVE (bit = 1) and 0 V are applied, whereby the current flow equates to approx. 1 ma. Brief temporary changes of at least 20 ms are buffered between the station's polling enquiries and are then processed in the next cycle. Each input can be defined via software configuration as an alarm or status input. Digital inputs can be displayed on a local indicating unit (e.g. modu630). Technical specifications of inputs and outputs Universal input Measuring range Resolution Accuracy of measuring span plus measurement value Ni/Pt1000 50 +150 C < 0.05 K ± 0.5% 0.5% U (0/0.2 1 V) 0.02...1.1 V < 0.1 mv ± 0.5% 0.5% U (0/2..0.10 V) 0.15...10.2 V < 1 mv ± 0.5% 0.5% I (0/4...20 ma) 0.02...22 ma < 0.02 ma ± 1% 2% R 200...2500 < 0.1 ± 0.2% 1% Pot (> 1 k ) 1 100% < 0.5% ± 1% 1% Analogue output Correcting range Pitch error AO (0/2 10 V) 0.01 10.2 V < 2 mv 1% 1% Binary input (0-I) Switching threshold, active Switching threshold, inactive Switching hysteresis Universal input (UI) > 3 V < 1.5 V > 0.4 V Channel and terminal occupancy Terminals modu570 Channel Wiring diagram Signal GND Analogue output (0 10V) 0 a0 2 1 1 a1 4 3 2 a2 6 5 3 a3 8 7 Universal input 8 u8 13 9 (Ni/Pt1000/U/R/Pot) 9 u9 14 10 u10 15 16 Current measurement only on channels 8,9 or 11 u11 17 18 or terminals 13, 14 12 u12 19 20 13 u13 21 14 u14 23 15 u15 24 Reference voltage 1.23 V 22 Connecting a local override unit The I/O module modu570 can be supplemented using a modu670 override/indicating unit (LOI: Local Override and Indication Device) to enable the direct control of output signals and the display of digital inputs. The function complies with the EN ISO 16484-2:2004 standard relating to local priority override/indicating units. The modu630 local indicating unit can also be used. The unit can be installed and removed during ongoing operations (hot-plug capable) without impeding any functions of the automation station or I/O module. www.sauter-controls.com 3/5

Detailed information on control functions and LED display can be referenced from PDS 92.081 EY-LO6. All the LEDs (red and yellow) will start to flash if an incompatible override unit is connected; there is no danger of destroying the I/O module. Note: Check all control positions (Auto) prior to installation to avoid unintended signal emissions. When the unit is removed all outputs are operated using the automatic values of the automation station or I/O module. In keeping with the applicable standard, the local override and indication devices allow the restricted operation of plant components without involving the automation station intended for the application. Outputs from automation stations or I/O modules that are in manual operating mode may temporarily change value during a user program download. The local override unit can be used to control analogue outputs directly in the automation station without a user application (CASE Engine). Accessories EY-LO630F001 Single unit for indicating I/O modu530 or AS modu525 data points 16 LED LED indicators, bi-colour green/red (freely configurable for event/alarm) EY-LO670F001 Single unit for overriding and indicating I/O modu570 or AS modu525 data points 8 LED LED indicators, bi-colour green/red (freely configurable for event/alarm) 4 slide Setpoint adjuster 0 100%, yellow indicates manual operation switches with LED display LED indicator, red, (freely configurable for event/alarm) Wiring diagram a0 a1 a2 a3 01 03 05 07 09 11 02 04 06 08 10 12 4 x AO 0(2) 10 V 8 x UI Ref 13 15 17 19 21 23 14 16 18 20 22 24 u8 u9 u10 u11 u12 u13 u14 u15 A10510a 4/5 www.sauter-controls.com

Dimension drawing 42 115 Printed in Switzerland M11416 85 170 85 Fr. Sauter AG Im Surinam 55 CH-4016 Basle Tel. +41 61-695 55 55 Fax +41 61-695 55 10 www.sauter-controls.com info@sauter-controls.com www.sauter-controls.com 71920610035/5 02