Electrical actuators

Similar documents
Electromotoric actuators

Electromotoric actuators

Electromotoric actuators

Electrical Actuators

Electrical Actuators

Electromotoric actuators

Electrical Actuators

Electromotoric actuators

Electromotoric actuators

Electromotoric actuator

SAX.. ACVATIX Electromotive actuators for valves. with a 20 mm stroke

Heating Circuit Controller

Overview of types. Technical data

Immersion Temperature Sensors

Heating Circuit Controller

TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O

Products no longer available

AV24-MFT AV24-MFT2 AV24-MFT2-C105. Power consumption In operation For wire sizing N 1700 N Control Control signal Y Operating range

Extension module for lighting control

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

RF adapter plugs, dimming

Electromotive actuators for combi valves

Radiator Valves. Building Technologies HVAC Products. NF norm, for 2-pipe heating systems

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

ERF910. RF Repeater. Synco living

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

Power supply module, bus connection module

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

See «Overview of types» 90 s / 60 mm 150 s / 100 mm Manuelle Auslösung der Adaption durch Drücken der Taste «Adaption» oder mit dem PC-Tool

Room unit with PPS2 interface

Actuators for modulating control AME 13SU, AME 23SU - safety function (spring up)

Products no longer available

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

Rotary version, three-position control

ASI Systems ML5740A Series

Modulating controlled actuator AME 11

Air damper actuators

SRQ24A. Technical data. Safety notes. Rotary actuator for ball valves Torque 16Nm Nominal voltage AC/DC 24V Control: Open-close Running time 9s

Electric Actuators Type 5824 (without fail-safe action) Type 5825 (with fail-safe action)

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

ASI Systems ML5720A Series

Room controller STRA-17

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency. Draft

HERZ Actuator 7708, 7990

Modulating controlled actuators AME 10, AME 20, AME 30 AME 13, AME 23, AME 33 - with DIN EN certified safety function (spring down)

3-PORT SEAT VALVES PN16 WITH EXTERNALLY THREADED CONNECTIONS STAZ-16, STBZ-16, STCZ-53 DATASHEET

Room Temperature Controller

Electromotoric actuators for stroke valves

Room Temperature Controller

Radiator Lockshield Valves ADN.. AEN..

Communication module to connect M-bus devices to POL6xx.xxx controllers.

Semi flush-mounted room temperature controllers with LCD

VAV compact controller GDB181.1E/3 GLB181.1E/3

Semi flush-mounted room temperature controllers with LCD

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Rotary actuators for ball valves

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

Web interface BACnet/IP

Non-communicating room controllers

Universal Controller

Use. Functions. OpenAir TM. Linear version, modulating, AC 24 V

RТTH DUAL ROOM SWITCH

QVE3000.0xx QVE3100.0xx. Flow sensor. for liquids in DN10 25 pipes

Semi Flush-mount Room Temperature Controllers with LCD

Room unit with PPS2 interface

VAV compact controller

Product and functional description

TXM1.8RB. TX-I/O Blinds module

Non-communicating room controllers

RMZ792. Bus Operator Unit. Building Technologies HVAC Products. Synco 700

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

Resistance measuring module

2-PORT SEAT VALVES PN16 WITH FLANGED CONNECTIONS STAZ-16, STBZ-16, STCZ-52 DATASHEET

ML7421A,B Electric Linear Valve Actuators

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Room Temperature Controllers

Temperature Controller

OEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers

Electrical actuator AME 855

Actuators for modulating control AME 55, AME 56

Operating instructions. Speed monitor D / / 2014

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

VAV modular controller

Room Temperature Controller with 7-Day Time Switch, LCD and opt. Remote Temperature Sensor

24V, Motorized Actuators

Room automation station

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

AVM 321, 322: Valve actuator

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Room controller. For chilled ceiling and radiator applications CC-02 with Konnex bus communications (S-mode and LTE mode)

Actuators for three point control AMV 655 without safety function AMV 658 SU, AMV 658 SD with safety function (spring up/down)

Actuators AMV 655, 658 and 659 can be controlled by electronic controllers with 3-point output.

Airflow Pressure Sensor

Electromotoric actuators Torques up to 60 Nm Running times ¹) s. ¹) Predefined by the basic unit (LMV5...)

Transcription:

4 893 SSA without auxiliary switch Electrical actuators SSA1 with auxiliary switch for radiator valves, MiniCombiValves (MCV) and small valves SSA31 SSA81 SSA61 Use SSA31 operating voltage AC 230 V 3-position control signal SSA81 operating voltage AC 24 V 3-position control signal SSA61 operating voltage AC / DC 24 V DC 0 10 V control signal ominal force 100 Automatic identification of valve stroke Direct mounting with coupling nut, no tools required Basic types complete with plug-in connecting cable, length 15 m Optional cable types Cable length 15 m, 25 m and 45 m Halogen-free cables 25 m cables with Batigyr connector Manual override and position indication Parallel connection of multiple actuators possible Auxiliary switch integrated in SSA311 and SSA811 actuators Optional tamper-proof fitting to prevent dismantling For radiator valves, VD, VE, VU and MiniCombiValves, VPD, VPE For small valves, VD1 CLC For radiator valves with M30 x 15 screwed fitting, nominal closing dimension 116 mm and a 25 mm nominal stroke (without adapter) Also for use with third-party valves in conjunction with AV-type adapter For modulating or 3-position control in heating systems, chilled ceilings and terminal units CE14893en 29042008 Building Technologies HVAC Products

Type summary Type reference SSA31 SSA31/00 1) SSA311 SSA81 SSA81/00 1) SSA811 Operating voltage AC 230 V AC 24 V Run time at 50 Hz Control signal 150 s 3-position Connecting cable 15 m Auxiliary switch no cable 15 m es 15 m no cable 15 m es SSA61 15 m AC / DC 24 V 34 s DC 010 V SSA61/00 1) no cable For available cable lengths or terminal block connectors refer to "Accessories", page 3 1) Accessories Type reference AS3L15 AS3L25 AS3L45 AS8L15 AS8L25 Description Connecting cable 15 m Connecting cable 25 m Connecting cable 45 m Connecting cable 15 m Connecting cable 25 m AS8L25B Connecting cable 25 m with Batigyr connector AS8L45 Connecting cable 45 m AS8L45HF Connecting cable 45 m, halogen-free, VDE 0207-24 AS6L15 AS6L25 Connecting cable 15 m Connecting cable 25 m AS6L45 Connecting cable 45 m AS6L45HF Connecting cable 45 m, halogen-free, VDE 0207-24 AS98 AS99 AS100 1) AL40 Retaining screw for terminal block connectors Operating voltage AC 230 V AC 24 V AC / DC 24 V Terminal block connector for 3-position actuators SSA81/00 Terminal block connector for DC 0 10 V modulating actuators SSA61/00 Tamper-proof fitting to prevent dismantling of actuators Adapter type for third-party valves Adapter type for third-party valves AV51 Beulco old (M30x10) AV56 iacomini Control signal 3-position DC 010 V AV52 Comap AV57 Herz AV53 Danfoss RA- (RA2000) AV58 Oventrop old (M30x10), till 2002 AV54 Danfoss RAVL AV59 Vaillant AV55 Danfoss RAV AV60 TA, till 2002 1) o adapter required for type TBV-C AV61 Markaryd (MMA) Ordering Delivery Example When ordering, please give quantity, product name and type reference 2 actuators SSA81/00 without cable and 2 connecting cables AS8L45 Actuators, valves and accessories are packed separately Equipment combinations 2/8 Type reference Valve type k vs [m 3 /h] V & [l/h] P class Data sheet VD, VE, VU Radiator valves 009 141 2105, 2106 VPD, VPE MCV radiator valves 25 483 P 10 2185 VD1 CLC Small valves 025 260 2103 For other radiator valves with type AV adapters refer to "Type summary / accessories" Radiator valves (M30 x 15) from other manufacturers, without adapter: Heimeier Crane D981 TA-Typ TBV-C Oventrop M30 x 15 (from 2001) M Junkers Honeywell-Braukmann Cazzaniga Beulco (new) k vs = nominal flow rate of cold water (530 C) through the fully open valve (H 100) at a differential pressure of 100 kpa (1 bar) V & = ominal volume flow at 05 mm stroke Building Technologies Electrical actuators CE14893en HVAC Products 29042008

Valves from other manufacturers To ensure trouble-free operation of third-party valves with the SSA actuator, the valves must satisfy the following requirements: F x 90187 y Threaded connections with coupling nut M30 x 15 ominal force F 100 Dimension x x > 90 mm Dimension y y 145 mm Function / mechanical design A M30 x15 AB When the actuator is driven by DC 0 10 V control voltage or by a 3-position signal, it produces a stroke which is transmitted to the valve stem The description of operation in this document applies to the valve versions which are fully open when de-energized (O) 3-position control signal SSA31 / SSA81 Voltage at 1: Stem retracts Valve opens Voltage at 2: Stem extends Valve closes o voltage at 1 and 2: Actuator maintains its current position DC 010 V control signal SSA61 The valve opens / closes in proportion to the control signal at At DC 0 V, the valve is fully closed (A AB), stem extended When power supply is removed, the actuator maintains its current position Features and advantages Plastic housing Locking-proof, maintenance-free gear train Manual override with hexagonal socket wrench 3 mm Reduced power consumption in the holding positions Load-dependent switch-off in the event of overload and in stroke end positions Parallel operation of 6 SSA31, 24 SSA81 and 10 SSA61 possible, provided the controllers output is sufficient Terminal block connectors for customer made cables available (only for use with AC 24 V and AC / DC 24 V actuators) Connecting cables with AC 24 V and AC 230 V connectors cannot be mixed up Halogen-free cables available 4893Z16 Accessories Adapter type AV for third-party valves Adapter types AV51 to AV61 are available for mounting the SSA actuators on thirdparty radiator valves as shown under "Type summary/accessories", page 2 Tamper-proof fitting AL40 01422 4893Z15 01417 01414 1x 1x a b a b tighten gently Building Technologies Electrical actuators CE14893en HVAC Products 29042008 3/8

Retaining screw AS98 4864Z02 Type AS98 to secure the cable connector b c d The cable connector snaps into position, but can be additionally secured with the retaining screw 4864Z03 Terminal block connectors AS99 AS100 4864Z04 For special cable lengths of the AC / DC 24 V actuators Type AS99 for 3-position actuators SSA81/00 Type AS100 for DC 0 10 V modulating actuators SSA61/00 The terminal block connectors are supplied complete with mounting instructions (74 319 0385 0) otes Engineering Mounting Caution Caution The actuators must be electrically connected in accordance with local regulations (refer to "Connection diagrams", page 7) Regulations and requirements to ensure the safety of people and property must be observed at all times! The permissible temperatures (refer to "Technical data", page 6) must be observed The connecting cable of the actuator may come into contact with the hot valve body, provided the temperature of the valve body does not exceed 80 C Actuator types SSA 311 and SSA811 have a built-in auxiliary switch The switch cannot be fitted in other actuators later Mounting instructions (Ref 74 319 0497 0) are enclosed in the product packaging The actuator and valve are assembled with the coupling nut; no tools or adjustments are required The actuator must be fitted in position 1 with the power disconnected (refer also to "Manual override", page 5): Position the actuator and tighten the coupling nut manually Do not use any tools such as wrenches Avoid lateral pressure or (cable) tension on the mounted actuator! In the case of actuators without a connecting cable (SSA/00), the separately ordered terminal block connector and connecting cable must be fitted Orientation 90 90 4362Z01 Commissioning When commissioning, check the wiring and the functioning of the actuator and auxiliary switch, if fitted Actuator stem extends (from position 1 to 0): Valve closes Actuator stem retracts (from position 0 to 1): Valve opens 4/8 Building Technologies Electrical actuators CE14893en HVAC Products 29042008

Self-calibration Caution ote: Correct calibration is only possible with valve stroke > 15 mm During commissioning and whenever 100 % the operating voltage is switched on, the SSA61 runs a self-calibration routine (Valve stroke 0 Max stroke Setpoint) t 0 % ever intervene manually in this 75 s process Power O The second or third attempt at calibration occurs automatically after an 8-minute delay After three failed calibration attempts the actuator stem remains in the extended position and the radiator valves are closed For valves with strokes < 15 mm, the actuator/valve combination locks after three failed calibration attempts The new Siemens type VD, VE and VU radiator valves have in all 15 mm stroke 4893Z18 Operation Manual override ote A 3 mm hexagonal socket wrench can be used to move the actuator to any position between 0 and 1 However, if a control signal from the controller is present, then this takes priority in determining the position To retain the manually set position, unplug the connecting cable or switch off the operating voltage and the control signal 3 mm B A 1 3 mm 0 1 0 3 mm 4893Z09 4893Z10 A (, 1) B (2) 4893Z17 Position indicator in position 1: Valve open Position indicator in position 0: Valve closed Maintenance Repair! The actuators are maintenance-free When carrying out service work on the plant, following must be noted: Turn power off (eg remove the plug) If necessary, disconnect electrical connections from the terminals The actuator must be commissioned only with a correctly mounted valve in place! SSA actuators cannot be repaired; the complete unit must be replaced Disposal The device must not be disposed of together with domestic waste This applies in particular to the PCB Legislation may demand special handling of certain components, or it may be sensible from an ecological point of view Current local legislation must be observed Warranty The technical data given for these applications is valid only when the actuators are used with the Siemens valves listed under "Equipment combinations", page 2 The use of the SSA actuators in conjunction with third-party valves invalidates any warranty offered by Siemens Building Technologies / HVAC Products 5/8 Building Technologies Electrical actuators CE14893en HVAC Products 29042008

Technical data Power supply Operating voltage Voltage tolerance SSA31 SSA81 SSA61 AC 230 V ± 15% AC 24 V ± 20% AC 24 V or DC 24 V ± 20% ± 25% Frequency 50 / 60 Hz Max power consumption 6 VA 08 VA 25 VA Fuse for incoming cable 2 A, quickblow Control Control signal 3-position DC 010 V Input impedance for DC 010 V > 100 kohm Parallel operation (number of actuators) 1) max 6 max 24 max 10 Functional data Run time for 25 mm stroke at 50 Hz 150 s 34 s ominal stroke 25 mm (max 55 mm) ominal force 100 Perm temperature of medium in the connected valve 1110 C (190 C for MCV-radiator valves) Electrical connections Connecting cable of basic types 15 m 3-core to E 60320 / IEC 60227 orms and standards Meets requirements for CE marking: EMC directive 2004/108/EC Immunity E 61000-6-2 Industrial 2) Low voltage directive Emission E 61000-6-3 2006/95/EC Electrical safety E 60730-1 Residential Protection class to E 60730 II III Contamination level E 60730, Class 2 Housing protection Upright to horizontal IP40 to E 60529 Environmental compatibility ISO 14001 (Environment) ISO 9001 (Quality) S 36350 (Environmentally compatible products) RL 2002/95/E (RoHS) Dimensions / weight Dimensions refer to "Dimensions", page 8 Housing colors Auxiliary switch Coupling thread to valve Coupling nut M30 x 15 Weight with / without auxiliary switch Base Cover Mounted in SSA311 and SSA811 Switching point adjustable Factory setting 50% Switching capacity 1 change-over switch 0100 % max AC 250 V, 1 A (05 A) 04 kg / 035 kg RAL 7035 light gray RAL 9003 signal white 1) Provided the controller output is sufficient 2) 160 VA transformer (eg Siemens 4AM3842-4T00-0EA0) for AC 24 V actuators eneral ambient conditions Operation E 721-3-3 Transport E 721-3-2 Storage E 721-3-1 Environmental conditions Class 3K3 Class 2K3 Class 1K3 Temperature +1+50 C 25+70 C 5+50 C Humidity 585 % rh < 95 % rh 595 % rh 6/8 Building Technologies Electrical actuators CE14893en HVAC Products 29042008

Connecting cable SSA31 4864Z12en 7 6 4 white black blue 2 1 Control signal CLOSE (AC 230 V) Control signal OPE (AC 230 V) eutral SSA81 4864Z13en 7 6 1 orange violet red 2 1 Control signal CLOSE (AC 24 V) Control signal OPE (AC 24 V) System potential (AC 24 V) SSA61 4864Z14en 8 2 1 grey black red 0 Control signal DC 010 V (AC 24 V) System neutral ( DC 24 V) System potential AC 24 V (+ DC 24 V) Connection terminals AS99 for SSA81 2 1 4864Z15 Control signal CLOSE Control signal OPE System potential AC 24 V AS100 for SSA61 0 4864Z16 System neutral Control signal DC 010 V System potential AC / DC 24 V Terminals for auxiliary switches SSA311, SSA811 Q14 Q12 Q11 80125 Factory setting: 050 % Q11 Q12 50 %1 Q11 Q14 The switching point can be adjusted by turning the switching cam with a screwdriver (see Mounting Instructions) Connection diagrams SSA31 L AC 230 V () 2AF (L) Q1 Q2 (1) (2) 1 2 4864A01 Controller Actuator L System potential AC 230 V System neutral 1, 2 Control signal OPE, CLOSE Q1, Q2 Controller contacts Building Technologies Electrical actuators CE14893en HVAC Products 29042008 7/8

SSA81 SP AC 24 V 2AF () Q1 (0) (1) 1 2 Q2 (2) 4864A02 Controller Actuator SP, System potential AC 24 V S, 0 System neutral 1, 2 Control signal OPE, CLOSE Q1, Q2 Controller contacts S SSA61 SP (+) AC 24 V (DC 24 V) 2AF () () (0) 4864A03 SP, S, 0 Controller Actuator System potential AC 24 V System neutral Control signal 0 S (-) Dimensions Dimensions in mm Actuator without auxiliary switch SSA31 SSA81 SSA61 77 725 48 M30 x 1,5 9 83 4893M01 Actuator with auxiliary switch SSA311 SSA811 985 895 48 M30 x 1,5 9 83 4893M02 8/8 2005 2008 Siemens Switzerland Ltd Subject to alteration Building Technologies Electrical actuators CE14893en HVAC Products 29042008