Replacement of MS6-SV-1/2-E-ASIS-

Similar documents
Special SoftMotion settings/homing issues for CPX-CEC-M1-V3

Application Note Commissioning VTEM connected to Beckoff PLC via CPX-FB38 bus node

Application Note. Modbus on CMMP-AS- -M3/M0. Connection and configuration of the motor controller CMMP-AS- -M3/M0 within a Modbus/TCP network.

CECC-LK as IO-Link Master connected to Balluff RFID Device and data carriers

Application Note. CECC-LK as IO-Link Master Connected to SDAT

YJKP - Logging functionalities

YJKP with Mitsubishi Q series PLC control via Modbus TCP

CPX-FB36 in Ethernet/IP Mode

Servo Press Kit YJKP - Integration of host function blocks in Allen Bradley (Studio 5000 Logix Designer V26.01)

Application Note. Control Via Ethernet (CVE) How to Read or Write: -Target Position -Velocity -Actual Position -Save All Objects CMMO-ST

Configuration of CMMT-AS- -EC/PN to run 3rd party motor

How to setup Travel to fixed stop with CMMT-AS-PN by using the SINA_POS / telegram 111

IO-Link parameter description

Application Note I-Port event/error list

CPX-HART with Rockwell Logix and EtherNet/IP

CMMT-AS-PN controlled by SINAPOS functions block with Siemens S controller

Application Note Designer Studio

Servo press kit YJKP - Host interface

Servo Press Kit YJKP - Description of host function blocks in Allen Bradley (Studio 5000 Logix Designer V26.01)

IO-Link parameter description

IO-Link parameter description

Compact performance. Brief description. CPV valve terminal with AS-Interface type CPV..-GE- ASI-8E8A-Z M8. English e [ ]

Motion Terminal VTEM. Description. Motion App #02. Proportional directional control valve [ ]

AS-i Safety Relay Output Module with Diagnostic Slave

Controller CMXH. Description STO. Safe Torque Off (STO) [ ]

AS-i Safety Relay Output Module with Diagnostic Slave

Operating Manual -ENGLISH- Page 1 KWG-ISO

Motion Terminal VTEM. Description. Motion App #04. Model-based proportional pressure regulation [ ]

Temposonics Magnetostrictive Linear Position Sensors

ISG Isolated DIN Rail Mount Signal Conditioner Issue: Revision A Technical User Manual

Original operating instructions Safety relay with relay outputs G1501S / / 2016

SCHMIDT Sensor interface PROFIBUS Instructions for use

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

System CPX-E. IO-Link master module CPX-E-4IOL- Description. Protocol IO-Link. Function Parameterisation [ ]

Date Revision Change(s) 29/07/ First version

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. Control Cabinet Inverter MOVITRAC B Functional Safety

User's Manual. english

Application Note. a HART Tool-routing with Emerson AMS HART over TH LINK PROFIBUS for Asset Management 1.0.0

Original operating instructions Fail-safe inductive sensor GI711S / / 2010

Operating instructions. Switching amplifier DN0210 DN / / 2015

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Application note. WAGO-I/O-SYSTEM 750 DALI Multi-Master Module Configuration of a DALI Lighting System via WAGO- I/O-PRO V2.

Festo Motion Terminal (VTEM)

Operation Manual for Sensor Interface LCV-USB2

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

B63/ NS MS. EtherNet/IP LINK

BIC 1B0-ITA50-Q40KFU-SM4A4A BIC 1B0-IT005-Q40KFU-SM4A4A BIC 2B0-ITA50-Q40KFU-SM4A5A. User s Guide

English. Operating Manual. Conductive point level switch MLR120. Retain for later reference. Companies / brands of GHM

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

Fieldbus Independent I/O Modules 4 AI Pt100/ RTD , (/xxx-xxx) Manual

Position sensor PO1 series 20

Draft sensor KMB series 30

PKP Prozessmesstechnik GmbH. Borsigstrasse 24. D Wiesbaden-Nordenstadt. Tel: / Fax: / Operating manual PSA06

Operating Instructions

Flow sensors SFAB Key features

BNI IOL K023 BNI IOL K023. User s Guide

Fieldbus Independent I/O Modules 8 DI DC 24 V 3.0 ms, Manual

Control D. Controller Module for Proportional Valve Control. Installation Manual

Modbus RTU Protocol description

BNI USB A501. User s Guide

MSI-RM2 Safety Relays

Accessories for Sunny Central COMMUNICATION CABINET (COM-C)

ISO INTERNATIONAL STANDARD. Safety of machinery Safety-related parts of control systems Part 1: General principles for design

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

Communication Interface for SMA Inverters SMA BLUETOOTH PIGGY-BACK

AS-i 3.0 PROFIBUS Gateways with integrated Safety Monitor

Smart High-Side Power Switch for Industrial Applications One channel: 1 x 1 Ω

G3B/G3BD. Model Number Structure. Ordering Information. Solid State Relays Model Number Legend. List of Models

English. Operating manual. Universal transmitter UT125. Save for later reference. Companies / brands of GHM

BNI IOL K023 BNI IOL K023. User s Guide

Application Note. WAGO-I/O-SYSTEM 750 Connecting energy meters with M-Bus interface to the WAGO-I/O-SYSTEM

Operating Instructions

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. MOVITRAC MC07B Functional Safety

V E2B Snap-in I/O Module

Binary output and supervision 520CSD01 Data sheet

TG basic 1. Appliance tester for testing protective measures in accordance with DIN VDE (DIN EN 62638)

Manual. Decentralized Drive Control MOVIFIT FDC-SNI Connection to PROFIBUS/DeviceNet with UFF41B Fieldbus Gateway

Software WINDY BOY Setup Tool

Valve and Case Expansion Monitor Specifications

Operating Manual. English. Digital-Analog Converter DACON8-UMB.

Documentation KM2042. Sixteen channel digital output module with D-Sub Connector. Version: Date:

Position transmitter SDAT-MHS e [ ]

Operating instructions for AX5801. TwinSAFE drive option card for the AX5000 servo drive. Version: Date:

SNO 4003 K plus. Areas of application for the unit. Connection circuit diagrams. Intended use. Competent persons. Equipment and functional description

SMVector Additional I/O Module Installation and Operation Manual

to 12a Added Standard and Electrical requirements for UL table 1.1

efesotomasyon.com - Klockner Moeller - inverter User Manual CAN-Monitor

Drive Technology \ Drive Automation \ System Integration \ Services. Manual. MOVITRAC MC07B Functional Safety

System manual AS-i safety monitor AC041S /00 05/2013

Setpoint Isolators. Technical Manual. HA Issue Parker SSD Drives, a division of Parker Hannifin Ltd. WARRANTY

Control unit IndraDrive Commissioning Linear axis LDx with IndraDrive control unit

IO-Link System Description Technology and Application

Operating instructions. Standstill monitor A / / 2011

CPX-E-CEC-... Controller. Description Function, Parameterisation [ ]

Documentation EM2042. Sixteen Channel Digital Output Module with D-Sub Connector. Version: Date:

AS-i Safety Output Module, IP20

SIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006

Terminal CPX. Electrical interface CPX CTEL 4 M12 5POL. Description. CTEL master module. I-Port a [ ]

ecomat 100 type R 360 Use as safety controller

Transcription:

Application Note Replacement of MS6-SV-1/2-E-ASIS- AG by MS6-SV-1/2-E-10V24-AD1 How to replace MS6-SV-E-ASIS with MS6-SV-E-... MS6-SV-1/2-E- ASIS-AG; MS6-SV-1/2-E- ASIS-AG 100178

Title... Replacement of MS6-SV-1/2-E-ASIS- by MS6-SV-1/2-E-10V24-AD1 Version... 1.10 Document no.... 100178 Original...en Author... Festo Last saved... 30.11.2018 Copyright Notice This documentation is the intellectual property of Festo AG & Co. KG, which also has the exclusive copyright. Any modification of the content, duplication or reprinting of this documentation as well as distribution to third parties can only be made with the express consent of Festo AG & Co. KG. Festo AG & Co KG reserves the right to make modifications to this document in whole or in part. All brand and product names are trademarks or registered trademarks of their respective owners. Legal Notice Hardware, software, operating systems and drivers may only be used for the applications described and only in conjunction with components recommended by Festo AG & Co. KG. Festo AG & Co. KG does not accept any liability for damages arising from the use of any incorrect or incomplete information contained in this documentation or any information missing therefrom. Defects resulting from the improper handling of devices and modules are excluded from the warranty. The data and information specified in this document should not be used for the implementation of safety functions relating to the protection of personnel and machinery. No liability is accepted for claims for damages arising from a failure or functional defect. In other respects, the regulations with regard to liability from the terms and conditions of delivery, payment and use of software of Festo AG & Co. KG, which can be found at www.festo.com and can be supplied on request, shall apply. All data contained in this document do not represent guaranteed specifications, particularly with regard to functionality, condition or quality, in the legal sense. The information in this document serves only as basic information for the implementation of a specific, hypothetical application and is in no way intended as a substitute for the operating instructions of the respective manufacturers and the design and testing of the respective application by the user. The operating instructions for Festo products can be found at www.festo.com. Users of this document (application note) must verify that all functions described here also work correctly in the application. By reading this document and adhering to the specifications contained therein, users are also solely responsible for their own application. (Festo AG & CO. KG, D-73726 Esslingen, 2018) Internet: http://www.festo.com E-Mail: service_international@festo.com

Table of contents 1 Description... 5 1.1 Intended Use... 5 1.2 Reasonably Foreseeable Misuse... 5 1.3 Environment (Electromagnetic Compatibility, EMC)... 5 1.4 User Groups... 5 1.5 Task... 6 1.6 Limitations... 6 1.7 Proposal for alternative feedback and diagnostic signals... 6 1.8 Electrical circuit with cable plug NECA-S1G9-P9-MP1... 7 1.9 Electrical circuit with cable plug NECA-S1G9-P9-MP3 / NECA-S1G9-P9-MP5... 7 1.10 Hardware Components... 7 Application Note MS6-SV-1_2-E-ASIS-AG_en 1.10 Seite 3 von 7

Index of revisions Author: Festo AG & Co.KG Name of manual: Soft-start and exhaust valve. Replacement of MS6-SV-1/2-E-ASIS-AG by MS6-SV-1/2-E-10V24- AD1 Filename: MS6-SV-1_2-E-ASIS-AG_en.docx Consec. Description Index of revisions Author Date of amendment No. 1 Creation of the document 1 ADD 23.10.2018 Translation of original instruction. Application Note MS6-SV-1_2-E-ASIS-AG_en 1.10 Seite 4 von 7

1 Description 1.1 Intended Use This document describes the replacement of an MS6-SV-1/2-E-ASIS-AG by an MS6-SV-...-E-10V24... in conjunction with the AS-i Safety output module BWU2045 from Bihl + Wiedemann. The safety functions described in the operating instructions of the MS6-SV-...-E-10V24... can be implemented. In the application software of the functional control and the application software of the Safety Relay, adaptations of the software are probably required which are not included in this document. These software modifications must be created and checked in relation to the specific application. Notes: - If the application software of the safety relay is changed, verification and validation of the changes in the machine is required. - The operating instructions for the devices used must be observed. 1.2 Reasonably Foreseeable Misuse This application note is not realized with the described components. It is used to implement safety functions that are not specified in the MS6-SV-...-E- 10V24... operating instructions. For the replacement of the MS6-SV-1/2-E-ASIS-AG no sufficient risk assessment, verification and validation is done. There is no safety concept for the machine. The suitability of this application note for the application is not verified. 1.3 Environment (Electromagnetic Compatibility, EMC) Industry. This application note applies to machines which are assumed to be connected directly to a power supply network which is powered by its own high-voltage or medium-voltage distribution transformer intended for the power supply of a factory or similar installation. The environments covered by this application note are industrial environments within buildings. Industrial environments are characterized by the presence of one of the following conditions: Industrial, scientific and medical equipment is available; Large inductive or capacitive loads are switched frequently; The current intensities and the associated magnetic field strengths are high. 1.4 User Groups This document is only suitable for persons with sufficient expertise for machine safety based on EN ISO 12100 and EN ISO 13849. In addition, the following qualifications are required in the project team: Specialist in pneumatics Specialist in electrical engineering Specialist for the programming of control systems and safety switching devices A specialist is a person who, based on his professional training, knowledge and experience, as well as knowledge of the relevant standards, can assess the work carried out and recognize possible dangers. In order to assess the professional training, a multi-year activity can also be used in the work area concerned. [According DIN VDE 1000-10:2009-01] Application Note MS6-SV-1_2-E-ASIS-AG_en 1.10 Seite 5 von 7

1.5 Task Due to the planned phase-out of the MS6-SV-...-E-ASIS-... an alternative solution with the MS6-SV-...-E-10V24- AD1 and the AS-i Safety output module BWU2045 from Bihl+Wiedemann is proposed. The circuits described here and the procedure described are recommendations which do not exclude other possibilities. 1.6 Limitations By using the AS-i Safety output module BWU2045 not all functionalities of the MS6-SV-...ASIS-... can be reproduced. The following data can no longer be accessed: Feedback and diagnostic signals (cyclical digital data) Input and output pressure via the ASI bus (cyclical analogue values) 0...1200 for 0 bar to 12 bar at address A15...A0 1.7 Proposal for alternative feedback and diagnostic signals If feedback and diagnostic signals are required, the following options are available: - For feedback and diagnostic signals (cyclic digital data) It is recommended to configure the MS6-SV-1/2-E-10V24-... with a pressure sensor AD1. The pressure sensor AD1 and the feedback contact 3/4 can be used to distinguish between "pressurized" and "error". Status of valve Pressure sensor Signal contact 3/4 Activation for pressurisation by means of EN1 and EN2 Activation for exhaust by means of EN1 and EN2 Closed Open Open Closed Malfunction (red LED flashing) Open Open Table 1.6: Status of valve - For inlet and outlet pressure via the ASI bus (cyclic analog values) It is recommended to configure the MS6-SV-1/2-E-10V24-... with a pressure sensor AD3. If the pressure sensor AD3 is used, the analogue signal (4-20mA) can additionally supply the pressure value of P2. This digital data or analog values can be transmitted back via a suitable ASi input module. If the signals are only used as diagnostic signals for monitoring the safety function, a standard ASi input module (no safety-related characteristic values) is normally sufficient if the switching times of the MS6-SV are monitored by the safety PLC. Application Note MS6-SV-1_2-E-ASIS-AG_en 1.10 Seite 6 von 7

1.8 Electrical circuit with cable plug NECA-S1G9-P9-MP1 The multi-pin plug socket NECA-S1G9-P9-MP1 expects 2 signals with +24V DC at pins 1 and 2, these can be static or dynamic. For a more detailed description of the signals, please see the MS6-SV-...-E-10V24... operating instructions. 1.9 Electrical circuit with cable plug NECA-S1G9-P9-MP3 / NECA-S1G9-P9-MP5 The multi-pin plug socket NECA-S1G9-P9-MP3 / NECA-S1G9-P9-MP5 expects 1 signal with 0V DC at pin 1 and +24V DC at pin 2, these can be static or dynamic. For a more detailed description of the signals, please see the MS6-SV-...-E-10V24... operating instructions. 1.10 Hardware Components Component Order No. Type Part Number / Remarks Qty. Mssr. T1 Safety Switching Device BWU 2045 BWU 2045 1 Bihl + Wiedemann V1 Valve MS6-SV-1/2-E-.. MS6-SV-1/2-E-10V24-AD1 562580 1 Festo Application Note MS6-SV-1_2-E-ASIS-AG_en 1.10 Seite 7 von 7