FX2-CHILLER. Digital Control. Operations Manual

Similar documents
FX 2 Instruction Manual

ARCTIC AIR DC OLED. Digital Control Operations Manual

FX-2 Control Board ASY-360-XXX Setup and Configuration Guide

INTRODUCTION. FX-1 Operations Manual. Standard Features. Optional Features. Read This Manual Completely Before Proceeding!

FX-2 Control Board ASY-360-XXX Setup and Configuration Guide

R & D SPECIALTIES SERIES 100 RO CONTROLLER USERS MANUAL. 2004, by R & D Specialties, Inc. All Rights Reserved.

AirNet. CAN to Ethernet Adapter Setup Manual

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

AirNet CAN Bus Implementation Revision /6/2018

TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company

OK - Functions of the buttons. = "Arrow up" = ON / OFF. = Enter. = Temperature. ="Arrow down" = Preset time / Start time.

4-step Chiller and Heat Pump Controller

Millennium Simplicity Elite Parameter Points and Quirks

Wiring Diagrams UNITS WITH STARTING SERIAL NUMBER 3507Q

This document describes the features and functional specifications of the ECONO3 air conditioner controller.

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

Wiring Diagrams DIAGRAM INDEX. POWER SCHEMATICS Unit 30GXN,R Voltage Figure Number

ADVANCED TECHNICAL MANUAL AAC1 SMALL SYSTEM CONTROL CONSOLE. Redefine your comfort zone.

32MP Gateway. Overview and Configuration Manual

Component Troubleshooting

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

Xpander Desktop Elite Gen 3 User Guide

Brivis Touch. Owner s Manual

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins

BB5-Lite TECHNICAL MANUAL

DEKKER KNOWLEDGE DATABASE KNOWLEDGE IS POWER

Dryer. M720 Programming and Operation Manual. July 15, 2015 Revision 1.51

Product Manual 8330GMX

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

Product Manual Pushbutton Station for Modicon Programmable Controller MODBUS Interface

INSTALLATION, OPERATION & MAINTENANCE CRFF Series Wall Control Console. ECM Motors. ACC1-25 (Part # ) Revision:

Temperature controller Ducted systems

MODELS: STEAM FIRED YPC-ST-14SC & YPC-ST-16SL Thru YPC-ST-19S

HCS-3600 / 3602 / 3604 Laboratory Grade & High RFI Immunity Switching Mode Power Supply with Rotary Encoder Control

The PanasonicVRF Driver

TECHNICAL MANUAL WATER 300 C 5300 CV/06-00 GB

IPS INTELLIGENT PUMP STARTER

UNIT CONTROLLER 7 (UC7) Operation & Installation. Hydronic Units

Installation and Operation Manual SPC1

Smartstart Control Module

FC-DIN DIN-Rail Mount Fan Speed Controller

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

CommandCenter Operator Panel

VLT 2800 DRIVE SPECIFICATIONS

Installation and Operation Manual DPC1

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

SMARTSTART MOTOR STARTERS

ESC 201. Installation and Operating Instructions Manual. SG Jan 2015

Series SD-3PB Digital THERMOSTAT + TIMER

User Guide. FreeCool : Free Cooling unit V1.1 ENGY-SVU001A-GB

BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL

CO2 Controller Operating Instructions Models: RAD-0501, RAD-0501A, RAD-0501E 1. Product Description

ZONETOUCH DAMPER CONTROL SYSTEM Operation Manual

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

Measure & Control Temperature & CO2 levels with analog & digital I/O

Brushless DC Motor Controller Product Specification Assembly 025F0219

Touchpad User Guide. National Sales. Product Support. Freecall: Ph:

V0STAT51P-2 Programmable Wired Controller

Digital Thermostat for drum heaters Model HCL 5536

Microprocessor based Temperature / CO2 Controller c/w 365 Day Time Switch & Modbus Communication.

Installation Manual. 1.Included Accessories. System Controller SC-201-6M INT. Requests to Installers *SHA8754 C*

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers

Instruction Manual HID-2

Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification. Assembly 025F0348

Operations Manual HP2000. With 9100 Controller. Self-Heated Oxygen Measurement System

USER S MANUAL. DAS-G01 The Power of Tomorrow

NTP-5521/5531/5561 SWITCHING MODE POWER SUPPLY

Xpander Rack Mount 16 5U Gen 3 with Redundant Power [Part # XPRMG3-1625URP] User Guide

RTD-W Installation Instructions

Installation Manual. 65 Interactive LED/LCD. Model: HILF65101 (64.56 )

Brushless DC Motor Controller Product Specification Assembly 025F0200

7. PCB AND FUNCTIONS

INSTRUCTION MANUAL MODEL 8081 DIGITAL RECORDER

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller

Touchpad User Guide (Model: C-LCD-122-TL)

Autoranging True RMS Multimeter User Manual

PAS 9406/AMP ENGINEERING SPECIFICATION

JOCKEY FIRE PUMP CONTROL MODEL: FPC Series

TF243 Series Digital Thermostat Fan Coil Unit Control

MPC-3000 Field Technical Manual

Xpander Rackmount Elite Gen 3.0 User Guide

BACnet MS/TP Interface User s Guide

Total Sense Digital Control MODEL TSC-350. User Instructions Adjusting System and Control Settings (For Installer Only)

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide

Room Controllers. SC3000 Relay Pack

ETM-2050/ETM-2051 Service Manual

RBC-AMT32E / RBC-AMS41E

E-ACLM-V E-ACLM-P12/8/18 AC LINE MONITORS Installation and Operation Manual

February Instruction Manual. TURBO V80 controller. Model Model I. )

OPERATION & SERVICE MANUAL VC1100 Series MDB-120 Controller Software 120 Volts, 60 HZ 230 Volts, 50 HZ

Owner s Manual. Digital Player Addendum. For Heat Siphon Swimming Pool Heat Pumps

Application program: description and examples

INSTRUCTION MANUAL IM253 R0. AquaStart COMBINATION SOFT STARTERS START-UP MANUAL

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

ICON SERIES IDRIVE. Intelligent Constant Pressure. Water Supply Controller User Manual. idrive

Multi-Unit Controller Installation Manual

WavePRO Wireless Programmable T2500 Thermostat & R2500 Receiver OPERATING MANUAL. Model K

Fermostat Users Manual

UNIT CONTROLLER 8 (UC8) Modbus RTU communications

Transcription:

FX2-CHILLER Digital Control Operations Manual Micro Air Corporation Phone (609) 259-2636 124 Route 526 www.microair.net Allentown NJ 08501 Fax (609) 259-6601

Introduction: The FX2-CHILLER digital control operates onboard tempered water equipment to provide closed loop water temperature control. The FX2-CHILLER digital control is designed to operate with central type tempered water marine air-conditioning systems. Features include: High visibility Organic Light Emitting Diode display (OLED) offers superior visual characteristics compared to LCD displays. Variable brightness adjustment and automatic screen saver. Four position menu navigation switch featuring a joystick style interface with push on / push off control. The display is compatible with Vimar and Gewiss frames. Visual symbols enable the viewer to see the operating status at a glance. Easily programmed for customized operation. Built in options for fault protection help aid trouble diagnosis and prevent system damage. Universal 115/230 VAC 50/60 Hz power supply. FXII Chiller Revision: 05 March 25, 2013 2

Before you start: 1. Applying power: When power is first applied, the display will show the software revision, and then return to the last state the unit was in when power was removed. On/Off Button Mode Select Button Up Button Service Button (Unmarked) Down Button 2. Joystick operation: The four position joystick may be tapped up, down, right, left or in the center to make changes to the operation of the control. Gently tap this switch to operate it. Excessive force will damage the switch. 3. Operating states: Pressing the joystick in the center will toggle between OFF and ON. When the display is OFF the display will appear dark**. When the display is ON, the display shows the operating screen**. See operating screens for an example. Switch between these states by pressing and releasing the On/Off button. **Unless screen saver is active. See screen saver for details. Operating Screens Screen Saver If no buttons are pressed for two minutes, the display will enter the screen saver mode. The display will dim and icons will scroll across the screen. To exit this mode, just tap any button. FXII Chiller Revision: 05 March 25, 2013 3

Operating Screen Water Inlet Temperature Water Outlet Temperature Temperature Set Point Operating Status Icon Heating or Cooling Mode Selection To change from heating to cooling or cooling to heating, tap the mode select button. Set the desired loop water temperature by tapping the up or down button. The system will provide cooling or heating as selected. Operation The control will automatically operate the circulating pump, sea water pump, compressor and heater or valve as necessary. Inlet temperature must be more than two degrees from the set point for operation to occur. In heat mode, temperatures must be below set point and in cool mode temperatures must be above the set point. Temperatures must be above 33 F for any operation. Operating output conditions are indicated in the icon at the center of the display. CW is the closed circulating water loop. When the pump is on, the icon will animate and show water flow in the system. If the flow switch opens, or the pump is off, the pipe will appear empty. This is the compressor symbol. When the compressor is running, the symbol will look like an operating piston. SW is the sea water pump. When the pump is on, the symbol will animate and show the pump operating and water flowing. When the sea water pump is off, the pipe will appear empty and the pump will not spin. This is the electric heat symbol. This symbol will appear in heat mode in place of the compressor if the optional electric heater is installed and selected in the programmable parameters. The animation will look like heat rising from the element when the heater is on. FXII Chiller Revision: 05 March 25, 2013 4

System Status Screen AC Line voltage System Current High Freon Pressure Switch (CLosed or OPen) Low Freon Pressure Switch (CLosed or OPen) System Frequency Flow Switch (CLosed or OPen) Viewing System Status In the ON state, press and hold the Mode select button for three seconds. The display will indicate AC line voltage, System current, AC Line frequency, and High and Low pressure switch status and Flow switch status. After one minute without a button press, the display will return to the operating screen. Viewing Fault History Fault message history may be viewed by pressing and holding the service button for three seconds with the display in the operating screen. Scroll from message to message by tapping the up and down buttons. The past eight fault messages, numbered from 1 to 8 can be viewed with the most recent numbered 1. Multiple faults of the same type will not be listed separately unless they occur more than one hour from the first fault. To clear the history log, the screen must show the operate screen. Press and hold the service button for 10 seconds. The history log will appear then the displayed fault will disappear indicating the log is cleared. Fault Messages The following fault messages will be shown on the display in the event of a problem. Compressor and electric heat operation is prevented for two minutes after a fault occurs. Following this two minute period, the control will restart in the last mode of operation. Pressing the on / off button twice will return the display to the operating screen but operation will not resume for two minutes. Repeated faults are an indication of a problem and should be checked by a qualified service person. LOCKOUT Four of the same faults occurred in less than 1 hour from the first fault. The display will show the fault that caused the lockout followed by the word LOCKOUT. Press the On/Off button twice on the display to clear a lockout. HIGH FREON PRESSURE: Indicates the high pressure switch connected to the High/Low Freon jack is open. If the switch resets, the compressor will restart within two minutes. LOW FREON PRESSURE: Indicates low pressure switch connected to the High/Low Freon jack is open for over 10 minutes. The LP jumper (JP7) on the FX2 power supply must be cut to enable this option. LOW AC VOLTAGE: The AC line voltage was below the voltage set in the programmable parameters for more than 10 minutes. FXII Chiller Revision: 05 March 25, 2013 5

OVER CURRENT: The total system run current exceeded the limit set in the programmable parameters. Systems may start with currents exceeding the limit but must be below the limit within two seconds after the start of the compressor. FREEZE FAULT: The closed circulating loop water temperature at the water outlet sensor is below 34 F. This fault causes an immediate lockout for system protection. FLOW SWITCH OPEN: The closed circulating water loop flow switch connected to the service input is open for more than 10 seconds. When this fault occurs, all outputs will shut down for two minutes then restart. SENSOR TROUBLE WATER IN: The sensor connected to the ALT AIR jack (Loop water in) has failed or is disconnected. SENSOR TROUBLE WATER OUT: The sensor connected to the OUTSIDE jack (Loop water out) has failed or is disconnected. HIGH LIMIT: Closed circulating loop water outlet temperature has exceeded the limit set in the programmable parameters. KLIXON OPEN: EasyStart has detected a problem with the compressor most likely an open compressor overload protector. EasyStart will wait 3 minutes before attempting a restart. Systems without EasyStart should set the program parameter Starter Present to NO to prevent this error. COMPRESSOR STALLED: EasyStart has detected a problem with the compressor most likely a stalled compressor. EasyStart will wait 3 minutes before attempting a restart. Systems without EasyStart should set the program parameter Starter Present to NO to prevent this error. FXII Chiller Revision: 05 March 25, 2013 6

Program Parameters: There are eleven programmable parameters with their factory defaults described in this section. The table below defines the parameter descriptions along with the permitted values and default settings. To enter the program mode first put the unit in the off state. Press and hold the joystick in the center for 3 seconds. Use the fan button to advance to the next parameter and the mode button to go back to the last parameter. Use the up and down buttons to change the parameters value. Exit the program mode when finished by pressing and releasing the On/Off button or wait 60 seconds for the display to exit. Note: program mode can also be entered by pressing the following sequence of buttons: Mode, Up, Down, Mode in the off mode. Description Default Value Display brightness 15 4=Minimum 15=Maximum Screen Saver Brightness 4 0=Minimum 8=Maximum Staging Delay 15 or 45* 5-135 Seconds Current Limit 35 0-35 Amps (0 is disabled) Low AC Line Detection Off 75-100 or 175-200 VAC High Limit Threshold 130 100-135 F System Units F F or C Cycle Sea Pump Cycled Sea Pump Cycled or Continuous Reverse Cycle Heat Reverse Cycle Heat Electric Heat or Reverse Cycle Heat Purge Air in System No Yes or No Starter Present No Yes or No Reset Parameters No No or Yes If JP8 is removed, Staging Delay default will be 45 seconds. Parameter description: o Display brightness: Display brightness can be set from 4 (dim) to 15 (bright) to suit room lighting. Brightness will change as the number is changed. o Screen saver brightness: Number values from 0 (dim) to 8 (bright) can be set to suit room brightness. The unit will operate as described in the screen saver section. o Staging delay: The compressor staging delay is provided for multi system installations where more than one system is operating from the same power source. Set the Staging delays at different intervals so only one compressor starts at a time when power is applied. o Current limit: The system current limit can be set from 0 to 35 Amps maximum running current. Systems may start at higher FXII Chiller Revision: 05 March 25, 2013 7

currents but running currents must be less than the set point. To disable this fault set the limit to 0. o Low AC line detection: When set, if the AC line voltage remains below the set value for 10 minutes, the control will turn off the compressor or heater and indicate Low AC. Voltages may be set between 75 and 100 VAC for 120 volt systems, and 175-200 VAC for 208-230 VAC systems. o High Limit Threshold: Set this parameter to monitor water outlet temperature. Temperatures may be selected between 100 F and 135 F. o System units: Degrees Fahrenheit ( F) or degrees Celsius ( C) can be selected o Cycled Sea Pump: This setting will turn on the sea pump with the compressor. This parameter may be changed to run the Sea Pump continuously. o Electric Heat/ Reverse Cycle Heat: Set this parameter only if the system is equipped with an electric heater. If the heater current will exceed 10 Amps, a contactor must be connected to the valve output to use this feature. o Purge Air in System: This parameter allows the user to operate the circulating pump for one hour while the system is being filled so air can be removed. Set the parameter to YES and press the On/Off button. The display will go blank then the screen saver will appear with PURGING AIR on the screen. The circulating loop water pump will run for 1 hour then turn off. To exit this function, press the On/Off button. Flow faults are disabled while Purge Air is active. Flow switch status may be viewed in the system status screen. See Viewing System Status for details. o Starter Present: Set this parameter to YES only if the EasyStart option board is installed on top of the FXII power supply. This option must be set for No for ALL other systems including EasyStart systems where the EasyStart option board is NOT installed on the FXII power supply such as those systems with EasyStart in an external box. o Reset parameters: To reset all parameters to factory defaults, select YES and then exit the program mode by pressing the joystick center button. The display will show EEPROM RESET then the display will go blank indicating the unit is OFF. Staging two compressors in a system: In some applications, two compressors may be necessary to handle the cooling or heating load. On these systems, remove jumper JP8 from one of the two power supplies. (see Wiring Diagram and Configuration for jumper location details). With JP8 removed, the second unit will operate at a different default set point and staging delay. Defaults: JP8 In: Cool 42 F, Heat 110 F, Staging Delay 15 Seconds JP8 Out: Cool 44 F, Heat 108 F, Staging Delay 45 Seconds FXII Chiller Revision: 05 March 25, 2013 8

Specifications Set point range Cool Mode 38 F-58 F or 3.3 C-14.4 C Heat Mode 95 F to 120 F or 35 C to 48.9 C Sensor accuracy 2 F at 77 F Low voltage limit 115 VAC units Low voltage limit 230 VAC units Line voltage limit Frequency Fan output MAX (Connect to Sea Water Pump) Valve output MAX (Connect to optional electric heater) Circulating Pump output MAX Compressor output 75VAC 175VAC 240VAC 50 or 60 Hz 4 Amps 10 Amps ¼ HP at 115 VAC ½ HP at 230 VAC 1HP at 115 VAC 2HP at 230 VAC Minimum operating temperature 0 F Maximum operating temperature 180 F Maximum RH conditions Maximum length of the display cable Maximum length of the sensor cable 99% Non-condensing 75 Feet 50 Feet FXII Chiller Revision: 05 March 25, 2013 9

PCB-360-00F and Earlier FXII Chiller Revision: 05 March 25, 2013 10

PCB-360-00G and later wiring diagram and configuration FXII Chiller Revision: 05 March 25, 2013 11

Updates: From To Reason Rev 3 Rev 4 Add parameter in FRM278B16 for Starter Present. Rev 4 Rev 5 Add fault descriptions for EasyStart and update wiring for 360 rev G boards COPYRIGHT 2008 Micro Air Corporation, All Rights Reserved No part of this publication may be reproduced, translated, stored in a retrieval system, or transmitted in any form or by any means electronic, mechanical, photocopying, recording or otherwise without prior written consent by Micro Air Corporation. Every precaution has been taken in the preparation of this manual to insure its accuracy. However, Micro Air Corporation assumes no responsibility for errors and omissions. Neither is any liability assumed nor implied for damages resulting from the use or misuse of this product and information contained herein. FXII Chiller Revision: 05 March 25, 2013 12