SIPLUS CPU 313C-2DP. Function

Similar documents
General information. Supply voltage

Product type designation. General information. Supply voltage

Product type designation. General information. Supply voltage. Input current

Product type designation. General information. Supply voltage. Input current. Power loss

General information. Supply voltage. Input current

CPU 317F-2 DP. Page 1603 Mar 2008 Siemens ITS

Product type designation. General information. Supply voltage. Input current. Power losses

Parameterizable properties The S7 configuration as well as the properties and response of the CPUs can be parameterized using STEP 7:

General information. Engineering with. Supply voltage. Load voltage L+ Input current. Power losses. Memory. Work memory.

Programming package STEP 7 V5.2 SP1 or higher with HSP 0126

CPU 319F-3 PN/DP. Page 1682 Mar 2008 Siemens ITS

General information. Supply voltage. Input current

General information. Supply voltage. Input current

General information. Supply voltage. Input current

General information. Supply voltage. Input current

6ES7151-8AB01-0AB0. 5/18/2011 Siemens Industry IA/DT/BT Service&S. siemens.com/ww/llisapi.dll?func=csl 1/10 ET200S, IM151-8 PN/DP CPU, 192 KB

CPU 412H. Function. Parameterizable properties

SIMATIC S7-400, CPU KB WORKING MEMORY (384 KB CODE, 384 KB DATA) 1. INTERFACE MPI/DP 12 MBIT/S 2.IF PROFIBUS DP, 3.

Product type designation. General information. Supply voltage

Product type designation. General information. CiR - Configuration in RUN. Supply voltage. Input current. Power loss. Memory

100 ms. 30 µs; Time per I/O byte. 24 V DC No; Power supply via system power supply. Not relevant for 400 series (300 series set)

Product type designation. General information. CiR - Configuration in RUN. Input current. Power loss. Memory

Product type designation. General information. CiR - Configuration in RUN. Supply voltage. Input current. Power loss. Memory

Supply voltage. Input current. Power loss. Memory. Battery. CPU processing times

CPU 412. Function. Programmable properties

64 kbyte ; 64 KB / 21K instructions RAM (integrated) Yes ; 4 KB: bit memory, counter, times and data

General information. CiR - Configuration in RUN. Supply voltage. Input current. Power loss. Memory

General information. Supply voltage

General information. Display. Control elements. Supply voltage

General information. Configuration control. Display. Control elements. Supply voltage

General information. Configuration control. Display. Control elements. Supply voltage. Input current. Power. Power loss

Data sheet CC 03, Commander Compact (603-1CC21)

Data sheet CPU 115 (115-6BL02)

Data sheet VIPA CPU 115DP (115-6BL22)

General information. Configuration control. Display. Control elements. Supply voltage

CPU 224. The compact high-performance CPU With 24 inputs/outputs on board Expandable with up to 7 expansion modules Design

General information. Display. Control elements. Supply voltage

General information. Configuration control. Control elements. Supply voltage. Input current. Power. Power loss. Memory

General information. Display. Control elements. Supply voltage

General information. Configuration control. Display. Control elements. Supply voltage. Input current. Power. Power loss

General information. Configuration control. Display. Control elements. Supply voltage. Input current. Power. Power loss

Product type designation

General information. Display. Supply voltage

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Supply voltage. Input current. Encoder supply. Memory

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current. Encoder supply. Power losses

General information. Display. Supply voltage

SIMATIC. ET 200S IM CPU Interface Module. Introduction. New features 2. Technical specifications 3. Product Information 06/2007 A5E

General information. Display. Supply voltage. Input current. Encoder supply. Output current. Power loss. Memory

General information. Display. Supply voltage

Supply voltage. Input current. Encoder supply. Memory SIMATIC S7-200, CPU 221 COMPACT UNIT, DC POWER SUPPLY 6 DI DC/4 DO DC, 4 KB CODE/2 KB DATA,

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage. Input current

General information. Supply voltage. Input current. Encoder supply. Power loss. Memory

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage. Input current

General information Engineering with Programming package. Display with display

Commander compact. Commander compact Lines displays. System SLIO. System 100V. Lines displays Commander compact 603-1CC CC21.

Data sheet CPU 013C (013-CCF0R00)

Central processing units CPU 221, CPU 222, CPU 224, CPU 224 XP, CPU 224 XPsi, CPU 226

General information. Configuration control. Display. Control elements. Supply voltage

CPU 1214C. Overview. Design. The compact CPU 1214C has:

Data sheet CPU 315SB/DPM (315-2AG12)

Data sheet CPU 315SB/DPM (315-2AG12)

6ES7212-1BD30-0XB0. permissible range, lower limit (DC) permissible range, upper limit (DC)

Multi Panel options. SIMATIC WinAC MP 2/169

Data sheet VIPA CPU 214PG (214-2BE03)

Data sheet CPU 315SN/NET (315-4NE12)

Data sheet VIPA CPU 214NET PG (214-2BT13)

Data sheet VIPA CPU M13C (M13-CCF0000)

Data sheet CPU 315SN/NET (315-4NE12)

Data sheet CPU 315SN/PN ECO (315-4PN33)

IM IM in the RS485 variants features: 9-pin Sub-D socket for connection to PROFIBUS DP

Data sheet CPU 015PN (015-CEFPR01)

Data sheet CPU 015PN (015-CEFPR00)

Data sheet SLIO CPU 015PN (015-CEFPR01)

SIMATIC S /4 Central processing units 4/4 Compact CPUs 4/21 Standard CPUs 4/43 Technology CPUs 4/51 Fail-safe CPUs

SIMATIC PC-based controller

System description SLIO

SIMATIC S /2 3/4 3/22 SIPLUS 3/26 3/33 SIPLUS

Product Information on the Manual

SIMATIC S /2 Introduction

EM 253 POSITIONING MODULE

Distributed I/Os SIMATIC ET 200

Operating and Monitoring Systems

Transcription:

SIPLUS CPU 313C-2DP Function Password protection; a password concept protects the user program from unauthorized access. Block encryption; the functions (FCs) and function blocks (FBs) can be stored in the CPU in encrypted form by means of S7-Block Privacy to protect the know-how of the application. Diagnostics buffer; the last 500 error and interrupt events are stored in a buffer for diagnostic purposes, of which 100 are stored retentively. Maintenance-free data backup; the CPU automatically saves all data (up to 64 KB) in case of a power failure so that the data are available again unchanged when the power returns. Parameterizable properties The S7 configuration as well as the properties and response of the CPUs can be parameterized using STEP 7: General; definition of the name, system ID and location ID MPI multi-point interface; determining station addresses Page 1491 Mar 2008 Siemens ITS

Startup; definition of the startup characteristics of the CPU and the monitoring time Cycle/clock memory; specification of the maximum cycle time and load. Setting of the clock memory address. Retentivity; definition of the number of retentive bit memories, counters, timers and data blocks Time-of-day interrupts; setting of start date, start time and periodicity Cyclic interrupts; setting of periodicity System diagnostics; determining handling and scope of the diagnostic messages Clock; setting the type of synchronization in the AS or on the MPI Protection level; specifying the access rights to program and data Communication; reservation of connection resources PROFIBUS DP master/slave interface; user-oriented address allocation for distributed I/O. Parameterizing the operating mode and configuring the transfer areas in the case of PROFIBUS DP. Parameterizing the time synchronization Digital inputs/outputs; Page 1492 Mar 2008 Siemens ITS

setting of addresses, input delay and process interrupt Integrated function "counting"; setting the addresses, parameter assignment of the modes "continuous counting", "single counting", "periodic counting", "frequency measurement" and "pulse width modulation" Integrated "Rules" function Display and information functions Status and error indications; LEDs indicate e.g. hardware, programming, time or I/O errors, as well as operating states such as RUN, STOP and start-up. Test functions; the PG is used to indicate signal states during program execution, to modify process variables independently of the user program and to output the contents of stack memories. Information functions; you can use the PG to obtain information about the storage capacity and operating mode of the CPU as well as the current loading of the main and load memories as well as current cycle times and diagnostic buffer contents in plain text. Integrated communication functions PG/OP communication Global data communication Page 1493 Mar 2008 Siemens ITS

S7 basic communication S7 communication (server only) Routing Data record routing Integrated functions Counters; 3 counters (up to 30 khz) with directionally-dependent comparators and to directly connect 24 V incremental encoders 3 channels for frequency measurement; frequency measurement (up to max. 30 khz) enables, for example, speed measurement of a shaft with speed range monitoring or throughput measuring (parts per measuring time) with range monitoring. Period measurement; 3 channels. The period duration of the counting signal can be measured up to a counting frequency of 1 khz. Pulse width modulation; 3 outputs for direct control of valves, final controlling elements, switching devices, heating equipment, etc., switching frequency 2.5 khz. The period length can be set and the pulse-pause ratio can be changed while running. Alarm inputs (all digital inputs); the alarm inputs enable the detection of process events as well as the rapid triggering of responses. Technical specifications Page 1494 Mar 2008 Siemens ITS

Technical specifications 6ES7 313-6CG04-0AB0 Product version Hardware product version 01 Firmware version V3.3 General information associated programming package STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP 203 Supply voltage 24 V DC Input current Current consumption (rated value) 800 ma Current consumption (in no-load operation), 110 ma typ. Inrush current, typ. 5 A I²t 0.7 A² s Power losses Power loss, typ. 9 W Memory Work memory integrated 128 Kibyte expandable Size of retentive memory for retentive 64 Kibyte Page 1495 Mar 2008 Siemens ITS

data blocks Load memory pluggable (MMC) pluggable (MMC), max. Data management on MMC (after last programming), min. Backup present without battery CPU-blocks Number of blocks (total) 8 Mbyte 10 a ; Guaranteed by MMC (maintenance-free) ; Program and data 1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used. DB Number, max. 1 024; Number range: 1 to 16000 Size, max. 64 Kibyte FB Number, max. 1 024; Number range: 0 to 7999 Size, max. 64 Kibyte FC Number, max. 1 024; Number range: 0 to 7999 Size, max. 64 Kibyte OB Size, max. 64 Kibyte Page 1496 Mar 2008 Siemens ITS

Nesting depth per priority class 16 additional within an error OB 4 CPU processing times for bit operations, min. 0.07 µs for word operations, min. 0.15 µs for fixed point arithmetic, min. 0.2 µs for floating point arithmetic, min. 0.72 µs Counters, timers and their retentivity S7 counter Number 256 Retentivity adjustable 0 lower limit 255 upper limit Z 0 to Z 7 preset Counting range 0 lower limit 999 Page 1497 Mar 2008 Siemens ITS

upper limit IEC counter present Type Number S7 times Number 256 Retentivity adjustable lower limit upper limit preset Time range lower limit upper limit IEC timer present Type SFB Unlimited (limited only by RAM capacity) 0 255 retentivity 10 ms 9 990 s SFB Page 1498 Mar 2008 Siemens ITS

Number Unlimited (limited only by RAM capacity) Data areas and their retentivity retentive data area, total All, max. 64 KB Flag Number, max. 256 byte Retentivity available ; MB 0 to MB 255 Retentivity preset MB 0 to MB 15 Number of clock memories 8; 1 memory byte Data blocks Retentivity adjustable ; via non-retain property on DB Retentivity preset Local data per priority class, max. 32 Kibyte; Max. 2048 bytes per block Address area I/O address area Inputs 2 048 byte Outputs 2 048 byte of which, distributed 2 030 byte Inputs 2 030 byte Outputs Process image Inputs, adjustable 2 048 byte Page 1499 Mar 2008 Siemens ITS

Outputs, adjustable 2 048 byte Inputs, default 128 byte Outputs, default 128 byte Default addresses of the integrated channels 124.0 to 125.7 Digital inputs 124.0 to 125.7 Digital outputs Digital channels integrated channels (DI) 16 integrated channels (DO) 16 Inputs 16 256 Outputs 16 256 Inputs, of which central 1 008 Outputs, of which central 1 008 Analog channels Integrated channels (AI) 0 Integrated channels (AO) 0 Inputs 1 015 Outputs 1 015 Inputs, of which central 248 Outputs, of which central 248 Hardware configuration Page 1500 Mar 2008 Siemens ITS

Racks, max. 4 Modules per rack, max. 8; In rack 3 max. 7 Expansion devices, max. 3 Number of DP masters integrated 1 via CP 4 Number of operable FMs and CPs (recommended) FM 8 CP, point-to-point 8 CP, LAN 6 Time of day Clock Hardware clock (real-time clock) battery-backed and synchronizable Deviation per day, max. 10 s; Typ.: 2 s Backup time 6 wk; (at 40 C ambient temperature) Behavior of the clock following POWER- Clock continues running after POWER OFF ON Behavior of the clock following expiry of backup period Operating hours counter Number 1 Number/Number range 0 Clock continues to run with the time at which the power failure occurred Page 1501 Mar 2008 Siemens ITS

Range of values 0 to 2^31 hours (when using SFC 101) Granularity 1 hour retentive ; Must be restarted at each restart Clock synchronization supported to MPI, master to MPI, slave to DP, master ; With DP slave only slave clock to DP, slave in AS, master in AS, slave Digital inputs Number/binary inputs 16 of which, inputs usable for technological 12 functions Input characteristic curve acc. to IEC 1131, Type 1 Number of simultaneously controllable inputs horizontal installation 16 up to 40 C, max. 8 up to 60 C, max. Page 1502 Mar 2008 Siemens ITS

vertical installation up to 40 C, max. Technological functions shielded, max. Unshielded, max. Standard DI shielded, max. Unshielded, max. Input voltage Rated value, DC for signal "0" for signal "1" Input current for signal "1", typ. Input delay (for rated value of input voltage) for standard inputs Parameterizable 8 100 m; at maximum count frequency not allowed 1 000 m 600 m 24 V -3 to +5 V 15 to 30 V 8 ma ; 0.1 / 0.3 / 3 / 15 ms (You can reconfigure the input delay of the standard Page 1503 Mar 2008 Siemens ITS

Rated value for counter/technological functions at "0" to "1", max. inputs during program runtime. Please note that under certain circumstances your newly set filter time may not be effective until the next filter cycle.) 3 ms 16 µs; Minimum pulse width/minimum pause between pulses at maximum counting frequency Cable length Cable length, shielded, max. 1 000 m; 100 m for technological functions Cable length unshielded, max. 600 m; For technological functions: Digital outputs Number/binary outputs 16 of which high-speed outputs 4; tice: You cannot connect the fast outputs of your CPU in parallel Functionality/short-circuit strength ; Clocked electronically Response threshold, typ. 1 A Limitation of inductive shutdown voltage to L+ (-48 V) Lamp load, max. 5 W Controlling a digital input Output voltage for signal "1", min. L+ (-0.8 V) Page 1504 Mar 2008 Siemens ITS

Output current for signal "1" rated value for signal "1" permissible range, min. for signal "1" permissible range, max. for signal "1" minimum load current for signal "0" residual current, max. Parallel switching of 2 outputs for increased power for redundant control of a load Switching frequency with resistive load, max. with inductive load, max. on lamp load, max. of the pulse outputs, with resistive load, max. Aggregate current of outputs (per group) horizontal installation up to 40 C, max. up to 60 C, max. vertical installation up to 40 C, max. 500 ma 5 ma 0.6 A 5 ma 0.5 ma 100 Hz 0.5 Hz 100 Hz 2.5 khz 3 A 2 A 2 A Page 1505 Mar 2008 Siemens ITS

Load resistance range lower limit 48 Ω upper limit 4 kω Cable length Cable length, shielded, max. 1 000 m Cable length unshielded, max. 600 m Encoder Connectable encoders 2-wire BEROS 1.5 ma permissible quiescent current (2-wire BEROS), max. Interfaces Number of USB interfaces 0 1st interface Type of interface Integrated RS 485 interface Physics RS 485 Isolated Power supply to interface (15 to 30 V 200 ma DC), max. Functionality MPI DP master DP slave Page 1506 Mar 2008 Siemens ITS

Point-to-point connection MPI Services PG/OP communication Routing Global data communication S7 basic communication ; Only server, configured on one side S7 communication ; (but via CP and loadable FBs) S7 communication, as client S7 communication, as server Transmission rate, max. 187.5 kbit/s 2nd interface Type of interface Integrated RS 485 interface Physics RS 485 Isolated Power supply to interface (15 to 30 V 200 ma DC), max. Page 1507 Mar 2008 Siemens ITS

Functionality MPI DP master DP slave PROFINET IO Controller PROFINET IO Device PROFINET CBA DP master Services PG/OP communication Global data communication S7 basic communication S7 communication S7 communication, as client S7 communication, as server Equidistance mode support ; I blocks only ; (only server; connection configured at one end) Page 1508 Mar 2008 Siemens ITS

Isochronous mode SYNC/FREEZE Activation/deactivation of DP slaves 8 Number of DP slaves that can be simultaneously activated/deactivated, max. ; As subscriber Direct data exchange (slave-to-slave communication) DPV1 Transmission rate, max. 12 Mbit/s Number of DP slaves, max. 124 Address area 2 Kibyte Inputs, max. 2 Kibyte Outputs, max. User data per DP slave 244 byte Inputs, max. Page 1509 Mar 2008 Siemens ITS

Outputs, max. DP slave Services PG/OP communication Global data communication S7 basic communication S7 communication S7 communication, as client S7 communication, as server Direct data exchange (slave-to-slave communication) DPV1 GSD file 244 byte ; (only server; connection configured at one end) The latest GSD file is available on the Internet (http://www.siemens.com/profibusgsd) Page 1510 Mar 2008 Siemens ITS

Transmission rate, max. 12 Mbit/s Automatic baud rate search ; only with passive interface Transfer memory 244 byte Inputs 244 byte Outputs Address area, max. 32 User data per address area, max. 32 byte Communication functions PG/OP communication Data record routing Global data communication supported Number of GD loops, max. 8 Number of GD packets, max. 8 Number of GD packets, transmitter, max. 8 Number of GD packets, receiver, max. 8 Size of GD packets, max. 22 byte Size of GD packet (of which consistent), 22 byte max. S7 basic communication supported User data per job, max. 76 byte Page 1511 Mar 2008 Siemens ITS

User data per job (of which consistent), max. S7 communication supported as server as client User data per job, max. User data per job (of which consistent), max. S5-compatible communication supported Number of connections usable for routing S7 message functions Number of login stations for message functions, max. Process diagnostic messages simultaneously active Alarm-S blocks, max. 300 Test commissioning functions Status/control Status/control variable Variables 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server) ; Via CP and loadable FB 180 Kibyte; With PUT/GET 240 byte; as server ; via CP and loadable FC 4; max. 8; Depending on the configured connections for PG/OP and S7 basic communication Inputs, outputs, memory bits, DB, times, counters Page 1512 Mar 2008 Siemens ITS

Number of variables, max. 30 of which status variables, max. 30 of which control variables, max. 14 Forcing Forcing Force, variables Inputs, outputs Number of variables, max. 10 Status block ; Up to 2 simultaneously Single step Number of breakpoints 4 Diagnostic buffer present Number of entries, max. 500 adjustable 100; Only the last 100 entries are retained Of which powerfail-proof Number of entries readable in RUN, max. 499 ; From 10 to 499 adjustable 10 preset Integrated Functions Number of counters 3; See "Technological Functions" manual Page 1513 Mar 2008 Siemens ITS

Counter frequency (counter) max. 30 khz Frequency measurement Number of frequency meters 3; up to 30 khz (see "Technological Functions" manual) controlled positioning Integrated function blocks (closed-loop ; PID controller (see "Technological control) Functions" manual) PID controller Number of pulse outputs 3; Pulse width modulation up to 2.5 khz (see "Technological Functions" Manual) Limit frequency (pulse) 2.5 khz Galvanic isolation Galvanic isolation digital inputs Galvanic isolation digital inputs between the channels between the channels and the backplane bus Galvanic isolation digital outputs Galvanic isolation digital outputs between the channels between the channels, in groups of 8 between the channels and the backplane bus Permissible potential difference Page 1514 Mar 2008 Siemens ITS

between different circuits Isolation Isolation checked with Ambient conditions Operating temperature Min. 0 C max. 60 C Configuration Configuration software STEP 7 STEP 7 Lite programming Programming language LAD FBD STL SCL 75 VDC / 60 VAC 600 V DC ; STEP 7 V5.5 + SP1 or higher or STEP 7 V5.3 + SP2 or higher with HSP 203 Page 1515 Mar 2008 Siemens ITS

CFC GRAPH HiGraph Command set see instruction list Nesting levels 8 Know-how protection User program protection/password protection Block encryption ; With S7 block Privacy Dimensions Width 80 mm Height 125 mm Depth 130 mm Weight Weight, approx. 500 g Page 1516 Mar 2008 Siemens ITS