BACnet P.I.C.S. For RDT900 configurable controllers. Protocol Implementation Conformance Statement

Similar documents
BACnet IP Enabled InFusion Controller Bacnet-IP-IC BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

Wireless Pneumatic Thermostat BACnet Gateway PICS. Document No rev 01

BACnet Protocol Implementation Conformance Statement (PICS) MULTICAL 62/601/602/6L2/6M2/801

ANNEX A - PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE) (This annex is part of this Standard and is required for its use.

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

MULTICAL 403 MULTICAL 603

Functional Specifications Gateway

BACnet Protocol Implementation Conformance Statement (PICS) Product Discription V1.0

BACnet Protocol Implementation Conformance Statement

Distech Controls Application Specific Controllers PICS

Modular Series BACnet Protocol Implementation Conformance (PIC) Statement A6V Building Technologies

BACnet RIB June 24, 2016

PXC Compact Unitary Equipment Controller BACnet Protocol Implementation Conformance Statement

DS-RP-A AE-N-I-B DM-DCC-B DS-RP-B AE-ACK-B DM-PT-A DS-RPM-B AE-ASUM-B DM-PT-B DS-WP-A AE-INFO-B DM-TS-A DS-WP-B DM-DDB-B DM-UTC-B

BACnet RIB Jan

Integration Specification Sheet

BACnet RIB March,

homelynk/spacelynk BACnet Protocol Implementation Conformance Statement

BACnet RIB July 1, 2014

HMS-1655 BACnet MS/TP Protocol Implementation Conformance Statement

BTL Listed March 2013

Zoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement

TRIDIUM NIAGARA AX 3.8

BACnet RIB July,

EC-Net AX /NIAGARA AX Framework 3.5 BACNET PICS

Protocol Implementation Conformance Statement (PICS)

Climatix VVS11 BACnet Protocol Implementation Conformance Statement (PICS) Basic documentation

Additional BACnet Interoperability Building Blocks Supported (Annex K):

BACnetRIB June 24, 2016

Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement

Input/Output Module (IOM) Series Protocol Implementation Conformance Statement

EC-Net AX 3.6 BACnet PICS

Product Implementation Conformance Statement bcx1-r

Honeywell Novar XIO Remote I/O Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement

Vitogate 300. BACnet Protocol Implementation Conformance Statement (PICS)

BCM-ETH BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

BACnet Protocol Implementation Conformance Statement

Sales and Engineering Data Sheet ED

EC-Net AX 3.6 BACnet PICS

CALEC ST with BACnet MS/TP

Date: Vendor Name: Product Name: Product Model Number: Applications Software Version: Firmware Revision: BACnet Protocol Revision:

Universalgateway. BACnet Protocol Implementation Conformance Statement. Version: 2016, October 17

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement Automated Logic G5RE

Protocol Implementation Conformance Statement (PICS)

! BACnet Operator Workstation (B-OWS)! BACnet Advanced Operator Workstation (B-AWS)! BACnet Operator Display (B-OD)

Climatix BACnet Protocol Implementation Conformance Statement (PICS)

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)

Terminal Equipment Controller (TEC) Protocol Implementation Conformance Statement

Synergy Network Controller

BACnet IP GOLD RX/PX/CX/SD, GENERATION C/D Applicable to program version 5.15 and newer versions

TB7300 Series Fan Coil Unit Communicating Thermostats BACnet Protocol Implementation Conformance Statement (PICS)

PICS_EE10D // v1.0 / Technical data subject to change. PICS EE10D BACnet Protocol Implementation Conformance Statement

Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE , BACnet

MicroTech II Multiple Air Handler Controller

PICS EE160D & EE210D BACnet Protocol Implementation Conformance Statement

SITRANS F. Ultrasonic Flowmeters SITRANS F US Clamp-on Communications Module. Introduction 1. F US Clamp-on Communications Module Kit 2

Swegon GOLD BACnet PICS Version E BACnet Protocol Implementation Conformance Statement

Building Operation. Vendor ID 10

Product Implementation Conformance Statement bcx1-cr

BACnet Protocol Implementation Conformance Statement

PICS_EE800D // v1.2 / Technical data subject to change. PICS EE800D BACnet Protocol Implementation Conformance Statement

BACnet/IP Advanced Application Field Equipment Controllers Protocol Implementation Conformance Statement

Desigo V5 BACnet Protocol Implementation Conformance Statement (PICS) Basic documentation

BACnet Protocol Implementation Conformance Statement

BACnet protocol implementation conformance

BACnet Protocol Implementation Conformance Statement

NB-GPC Family Protocol Implementation Conformance Statement (PICS)

Omni BEMS Controllers PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS)

Desigo V5.1 BACnet Protocol Implementation Conformance Statement (PICS) Basic documentation

Product Implementation Conformance Statement bcx-4040

MatrixBBC. Protocol Implementation Conformance Statement (PICS) Product Description: BACnet Standardized Device Profile:

IntesisBox BACnet IP Server Notifier ID3000 and Morley DXc fire panel series. User Manual r1.1 eng

BACnet Protocol Implementation Conformance Statement Unitary Protocol Converter (UPC)

QC BAC-BOX PIC STATEMENT

Protocol Implementation Conformance Statement (Normative) BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement Automated Logic Corporation LGR25, LGR250, LGR1000

entelibus CPU Engine (eb-eng) Firmware

PICS EE850D & EE820 BACnet Protocol Implementation Conformance Statement

PXC Compact Series on BACnet/IP

Neutrino-GLT Server BACnet TM Protocol Implementation Conformance Statement (PICS) Version 3

Advanced Application Field Equipment Controllers Protocol Implementation Conformance Statement Code No. LIT Issued December 5, 2014

Proposed Addendum bd to Standard , BACnet - A Data Communication Protocol for Building Automation and Control Networks

BACnet protocol implementation conformance statement (PICS)

FX Server BACNET AWS Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement OEMPrtl Pro

Desigo PXC3 and DXR2 Automation Stations BACnet Protocol Implementation Conformance Statement (PICS) Basic documentation

BACnet protocol implementation conformance statement (PICS)

1. BACnet Protocol Implementation Conformance Statement

Field Equipment Controllers Protocol Implementation Conformance Statement

PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE) (This annex is part of this Standard and is required for its use.)

NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement (PICS)

BACnet Gateway for VRF System UTY-VBGX

Transcription:

BACnet P.I.C.S. Protocol Implementation Conformance Statement For RDT900 configurable controllers ENGLISH Code 148RDT900SAU page 1 of 28

page 2 of 28

Important Read this document thoroughly before installation and before use of the device and follow all recommendations; keep this document with the device for future consultation. Only use the device in the way described in this document; do not use the same as a safety device. Disposal The device must be disposed of in compliance with local standards regarding the collection of electric and electronic equipment. page 3 of 28

(This annex is part of this Standard and is required for its use.) BACnet Protocol Implementation Conformance Statement Date: 23-02-2018 Vendor Name: Sauter Italia S.p.A. Product Name: Flexotron 900 Product Model Number: RDT921, RDT940 Application Software Version: 1.0.0 Firmware Revision: 3.3 BACnet Protocol Revision: 1.10 page 4 of 28

Product Description: RDT900 controllers are fully programmable I/O controllers for use in HVAC&R fields and Building Automation System applications. All variants are conform to the BACnet Application Specific Controller (B-ASC) profile: BACnet Standardized Device Profile (Annex L) BACnet Operator Workstation (B-OWS) BACnet Advanced Operator Workstation (B-AWS) BACnet Operator Display (B-OD) BACnet Building Controller (B-BC) BACnet Advanced Application Controller (B-AAC) BACnet Application Specific Controller (B-ASC) BACnet Smart Sensor (B-SS) BACnet Smart Actuator (B-SA) BACnet Interoperability Building Blocks Supported (Annex K): Data Sharing Designation BIBB Annex K DS-RP-B Read Property-B K.1.2 DS-RPM-B Read Property Multiple-B K.1.4 DS-WP-B Write Property-B K. 1.8 DS-WPM-B Write Property Multiple-B K.1.10 DS-COV-B Change Of Value-B K.1.12 Device & Network Management DM-DDB-B I Am K.5.2 DM-DDB-B Who Is K.5.2 DM-DOB-B I Have K.5.4 DM-DOB-B Who Has K.5.4 DM-DCC-B Device Communication Control K.5.4 DM-TS-B Time Synchronisation-B K.5.12 page 5 of 28

DM-RD-B Reinitialize Device-B K.5.16 Alarms and Events AE-N-I-B Notification Internal-B K.2.2 AE-ACK-B Acknowledge-B K.2.5 AE-INFO-B Information-B K.2.11 Schedules Trends Segmentation Capability: Able to transmit segmented messages Window Size Able to receive segmented messages Window Size Supported Data Link Layer and Routing Options: BACnet MS/TP Data Rates: Options: BACnet IP Ethernet, ISO 8802-3 ARCNET, ANSI/ATA 878.1 LonTalk TP/FT-10 LonTalk IP Point-To-Point, EIA 232 BACnet/ZigBee (ANNEX O) Other: 9600 baud 19200 baud 38400 baud 76800 baud BBMD, Foreign Device page 6 of 28

Networking Options: Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices? Yes No Does the controller support registrations to BBMD as Foreign Device? Yes No Does the BBMD support network address translation? Yes No Network Security Options: Non-secure Device - is capable of operating without BACnet Network Security Secure Device - is capable of using BACnet Network Security (NS-SD BIBB) Multiple Application-Specific Keys: Supports Encryption (NS-ED BIBB) Key Server (NS-KS BIBB) Character Sets Supported: Indicating support for multiple character sets does not imply that they can all be supported simultaneously. ISO 10646 (UTF-8) IBM /Microsoft DBCS ISO 8859-1 ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS X 0208 page 7 of 28

Supported BACnet Object Types (Summary): An object type is supported if it may be present in the device. The objects checked are currently supported by this product family. See the appropriate object type section in this document for details. Object Supported Create Delete Notes Accumulator Analog Input NO NO Analog Output NO NO Analog Value NO NO Averaging Binary Input NO NO Binary Output NO NO Binary Value NO NO Calendar Not requested for B-ASC profile Command Device NO NO Event Enrollment File Loop Multistate Input Multistate Output Multistate Value NO NO Notification Class Not requested for B-ASC profile Schedule Not requested for B-ASC profile Trend Log Event Log page 8 of 28

Device Address Binding: Support of static device binding (this is currently necessary for two-way communication with MS/TP slaves and certain other devices): Yes No Analog Input Property Data type R W Storage Configurab. In Uni-Pro Default Note Object_Identifier BACnetObjectIdentifier X Object_Name CharacterString X X F Y Object_Type BACnetObjectType X Description CharacterString X X F Y Present_Value float X X R Status_Flags BACnetStatusFlags X Event_State BACnetEventState X Reliability BACnetReliability X Out_Of_Service bool X X R Units BACnetEngineeringUnits X F Y 95 Min_Pres_Value float X X F Y -32700 Range AI Max_Pres_Value float X X F Y 32700 Range AI COV_Increment Float X X F Y 0 Time_Delay (*) Unsigned X X F Y 0 Notification_Class (*) Unsigned X X F Y NONE High_Limit (*) float X X F Y 0 Low_Limit (*) float X X F Y 0 page 9 of 28

Deadband (*) Float X X F Y 0 Limit_Enable (*) Unsigned X X F Y 0,0 see Tab.2 Event_Enable (*) Unsigned X X F Y 0,0,0 see Tab.3 Acked_Transitions (*) BACnetEventTransitionBits X R 0,0,0 see Tab.3 Notify_Type (*) BACnetNotifyType X X F Y alarm alarm,event Event_Time_Stamps (*) BACnetARRAY[3] of BACnetTimeStamp X R The property PRESENT_VALUE is usually read-only, unless OUT_OF_SERVICE is set to TRUE: in this situation the physical input is disconnected than the application and the PRESENT_VALUE, as well as the property RELIABILITY, can be written for testing purposes. (*) These properties are supported only if the specific object implements Intrinsic Reporting page 10 of 28

Analog Output Property Data type R W Storage Configurab. In Uni-Pro Default Note Object_Identifier BACnetObjectIdentifier X Object_Name CharacterString X X F Y Object_Type BACnetObjectType X Description CharacterString X X F Y Present_Value float X X R Status_Flags BACnetStatusFlags X Event_State BACnetEventState X Reliability BACnetReliability X Out_Of_Service bool X X Units BACnetEngineeringUnits X F Y 95 Min_Pres_Value Float X X F Y -32700 Range AI Max_Pres_Value Float X X F Y 32700 Range AI Priority_Array Float[16] X R Relinquish_Default Float X X R COV_Increment Float X X F Y 0 Time_Delay (*) Unsigned X X F Y 0 Notification_Class (*) Unsigned X X F Y NONE High_Limit (*) Float X X F Y 0 Low_Limit (*) Float X X F Y 0 page 11 of 28

Deadband (*) Float X X F Y 0 Limit_Enable (*) Unsigned X X F Y 0,0 see Tab.2 Event_Enable (*) Unsigned X X F Y 0,0,0 see Tab.3 Acked_Transitions (*) BACnetEventTransitionBits X R 0,0,0 see Tab.3 Notify_Type (*) BACnetNotifyType X X F Y alarm alarm,event Event_Time_Stamps (*) BACnetARRAY[3] of BACnetTimeStamp X R When OUT_OF_SERVICE is TRUE or when the output is forced with an OVERRIDE operation, the physical output is disconnected than the application. The PRIORITY_ARRAY is an array of 16 items. The BACnet variables should be forced (Override) with different priority levels. The value with the highest priority will be used to command the output. To remove that forced value it is necessary to do the Relinquish with the same priority. If all the level are released (NULL), the PRESENT_VALUE will became the RELINQUISH_DEFAULT value. (*) These properties are supported only if the specific object implements Intrinsic Reporting page 12 of 28

Analog Value Property Data type R W Storage Configurab. In Uni-Pro Default Note Object_Identifier BACnetObjectIdentifier X Object_Name CharacterString X X F Y Object_Type BACnetObjectType X Description CharacterString X X F Y Present_Value Float X X R Status_Flags BACnetStatusFlags X Event_State BACnetEventState X Reliability BACnetReliability X Out_Of_Service Bool X X Units BACnetEngineeringUnits X F Y 95 Priority_Array Float[16] X R Relinquish_Default Float X X R COV_Increment Float X X F Y 0 Time_Delay (*) Unsigned X X F Y 0 Notification_Class (*) Unsigned X X F Y NONE High_Limit (*) Float X X F Y 0 Low_Limit (*) Float X X F Y 0 Deadband (*) Float X X F Y 0 Limit_Enable (*) Unsigned X X F Y 0,0 see Tab.2 page 13 of 28

Event_Enable (*) Unsigned X X F Y 0,0,0 see Tab.3 Acked_Transitions (*) BACnetEventTransitionBits X R 0,0,0 see Tab.3 Notify_Type (*) BACnetNotifyType X X F Y alarm alarm,event Event_Time_Stamps (*) BACnetARRAY[3] of BACnetTimeStamp X R The PRIORITY_ARRAY is an array of 16 items. The BACnet variables should be forced (Adjust) with different priority levels. The value with the highest priority will be used by the application. To remove that forced value it is necessary to do the Relinquish with the same priority. If all the level are released (NULL), the PRESENT_VALUE will became the RELINQUISH_DEFAULT value. (*) These properties are supported only if the specific object implements Intrinsic Reporting page 14 of 28

Binary Input Property Data type R W Storage Configurab. In Uni-Pro Default Note Object_Identifier BACnetObjectIdentifier X Object_Name CharacterString X X F Y Object_Type BACnetObjectType X Description CharacterString X X F Y Present_Value BACnetBinaryPV X X R Status_Flags BACnetStatusFlags X Event_State BACnetEventState X Reliability BACnetReliability X Out_Of_Service Bool X X R Polarity BACnetPolarity X X F Y 0 0,1 Inactive_Text CharacterString X X F Y inactive Active_Text CharacterString X X F Y active Change_Of_State_Time BACnetTimeStamp X R Change_Of_State_Count Unsigned X X R Time_Of_State_Count_Reset BACnetTimeStamp X R Time_Delay (*) Unsigned X X F Y 0 Notification_Class (*) Unsigned X X F Y NONE Alarm_Value (*) BACnetBinaryPV X X F Y 1 0,1 Event_Enable (*) Unsigned X X F Y 0,0,0 see Tab.3 page 15 of 28

Acked_Transitions (*) BACnetEventTransitionBits X R 0,0,0 see Tab.3 Notify_Type (*) BACnetNotifyType X X F Y alarm alarm,event Event_Time_Stamps (*) BACnetARRAY[3] of BACnetTimeStamp X R The property PRESENT_VALUE is usually read-only, unless OUT_OF_SERVICE is set to TRUE: in this situation the physical input is disconnected than the application and the PRESENT_VALUE, as well as the property RELIABILITY, can be written for testing purposes. By default, the PRESENT_VALUE returns the string INACTIVE_TEXT in case of logic value low and ACTIVE_TEXT in case of high. (*) These properties are supported only if the specific object implements Intrinsic Reporting page 16 of 28

Binary Output Property Data type R W Storage Configurab. In Uni-Pro Default Note Object_Identifier BACnetObjectIdentifier X Object_Name CharacterString X X F Y Object_Type BACnetObjectType X Description CharacterString X X F Y Present_Value BACnetBinaryPV X X R Status_Flags BACnetStatusFlags X Event_State BACnetEventState X Reliability BACnetReliability X Out_Of_Service Bool X X R Polarity BACnetPolarity X X F Y 0 0,1 Inactive_Text CharacterString X F Y inactive Active_Text CharacterString X F Y active Change_Of_State_Time BACnetTimeStamp X R Change_Of_State_Count Unsigned X X R Time_Of_State_Count_Reset BACnetTimeStamp X R Priority_Array Unsigned [16] X R Relinquish_Default BACnetBinaryPV X X R Time_Delay (*) Unsigned X X F Y 0 Notification_Class (*) Unsigned X X F Y NONE Feedback_Value (*) BACnetBinaryPV X X F Y 1 0,1 page 17 of 28

Event_Enable (*) Unsigned X X F Y 0,0,0 see Tab.3 Acked_Transitions (*) BACnetEventTransitionBits X R 0,0,0 see Tab.3 Notify_Type (*) BACnetNotifyType X X F Y alarm alarm,event Event_Time_Stamps (*) BACnetARRAY[3] of BACnetTimeStamp X R When OUT_OF_SERVICE is TRUE or when the output is forced with an OVERRIDE operation, the physical output is disconnected than the application. The PRIORITY_ARRAY is an array of 16 items. The BACnet variables should be forced (Override) with different priority levels. The value with the highest priority will be used to command the output. To remove that forced value it is necessary to do the Relinquish with the same priority. If all the level are released (NULL), the PRESENT_VALUE will became the RELINQUISH_DEFAULT value. By default, the PRESENT_VALUE returns the string INACTIVE_TEXT in case of logic value low and ACTIVE_TEXT in case of high. (*) These properties are supported only if the specific object implements Intrinsic Reporting page 18 of 28

Binary Value Property Data type R W Storage Configurab. In Uni-Pro Default Note Object_Identifier BACnetObjectIdentifier X Object_Name CharacterString X X F Y Object_Type BACnetObjectType X Description CharacterString X X F Y Present_Value BACnetBinaryPV X X R Status_Flags BACnetStatusFlags X Event_State BACnetEventState X Reliability BACnetReliability X Out_Of_Service bool X X R Inactive_Text CharacterString X X F Y inactive Active_Text CharacterString X X F Y active Change_Of_State_Time BACnetTimeStamp X R Change_Of_State_Count Unsigned X X R Time_Of_State_Count_Reset BACnetTimeStamp X R Priority_Array Unsigned [16] X R Relinquish_Default BACnetBinaryPV X R Time_Delay (*) Unsigned X X F Y 0 Notification_Class (*) Unsigned X X F Y NONE Feedback_Value (*) BACnetBinaryPV X X F Y 1 0,1 Event_Enable (*) Unsigned X X F Y 0,0,0 see Tab.3 page 19 of 28

Acked_Transitions (*) BACnetEventTransitionBits X X R 0,0,0 see Tab.3 Notify_Type (*) BACnetNotifyType X X F Y alarm alarm,event Event_Time_Stamps (*) BACnetARRAY[3] of BACnetTimeStamp X R The PRIORITY_ARRAY is an array of 16 items. The BACnet variables should be forced (Adjust) with different priority levels. The value with the highest priority will be used by the application. To remove that forced value it is necessary to do the Relinquish with the same priority. If all the level are released (NULL), the PRESENT_VALUE will became the RELINQUISH_DEFAULT value. By default, the PRESENT_VALUE returns the string INACTIVE_TEXT in case of logic value low and ACTIVE_TEXT in case of high. (*) These properties are supported only if the specific object implements Intrinsic Reporting page 20 of 28

Multi State Value Property Data type R W Storage Configurab. In Uni-Pro Default Note Object_Identifier BACnetObjectIdentifier X Object_Name CharacterString X X F Y Object_Type BACnetObjectType X Description CharacterString X X F Y Present_Value Unsigned X X R Status_Flags BACnetStatusFlags X Event_State BACnetEventState X Reliability BACnetReliability X Out_Of_Service Bool X X R Number_Of_States Unsigned X F Y 1 <=16 State_Text BACnetARRAY[N] of CharacterString X F Y str null N = 16 Priority_Array Unsigned [16] X R Relinquish_Default Unsigned X X R Time_Delay (*) Unsigned X X F Y 0 Notification_Class (*) Unsigned X X F Y NONE Alarm_Values (*) Unsigned X X F Y 0 <= N_O_S Fault_Values (*) Unsigned X X F Y 0 <= N_O_S page 21 of 28

Event_Enable (*) Unsigned X X F Y 0,0,0 see Tab.3 Acked_Transitions (*) BACnetEventTransitionBits X X R 0,0,0 see Tab.3 Notify_Type (*) BACnetNotifyType X X F Y alarm alarm,even t Event_Time_Stamps (*) BACnetARRAY[3] of BACnetTimeStamp X R The PRIORITY_ARRAY is an array of 16 items. The BACnet variables should be forced (Adjust) with different priority levels. The value with the highest priority will be used by the application. To remove that forced value it is necessary to do the Relinquish with the same priority. If all the level are released (NULL), the PRESENT_VALUE will became the RELINQUISH_DEFAULT value. (*) These properties are supported only if the specific object implements Intrinsic Reporting page 22 of 28

Device Property Data type Man/OPT R W Storage Configurab. In Uni-Pro Default Note Object_Identifier BACnetObjectIdentifier R X X Object_Name CharacterString R X X F Y prj Name Object_Type BACnetObjectType R X System_Status BACnetDeviceStatus R X R OPERATIONAL L I A Vendor_Name CharacterString R X F Y Vendor_Identifier Unsigned R X F Y 630 Model_Name CharacterString R X F Y CPro3 Firmware_Revision CharacterString R X F Y Ver/Rev Application_Software_Revisio n CharacterString R X F Y Prj/Ver Location CharacterString O X X F Y strnull Description CharacterString O X X F Y strnull Protocol_Version Unsigned R X F Protocol_Revision Unsigned R X F Protocol_Services_Supported Bitstring R X F Protocol_Object_Types_Supp orted Bitstring R X F Object_List BACnetObjectIdentifier R X F Max_Apdu_Length_Accepted Unsigned R X F Segmentation_Supported BACnetSegmentation R X F NO page 23 of 28

Local_Time Time O X R from RTC Local_Date Date O X R from RTC Apdu_Timeout Unsigned R X X F Y 3 sec Number_Of_Apdu_Retries Unsigned R X X F Y 1 Max_Master Unsigned O X X F Y 127 1-127 Max_Info_Frames Unsigned O X X F Y 3 1-5 Device_Address_Binding BACnetObjectIdentifier R X Database_Revision Unsigned R X F Y Ver Active_Cov_Subscriptions Unsigned O X Receive_Message_Count Unsigned O X R Transmit_Message_Count Unsigned O X R Error_Message_Count Unsigned O X R Property Data type MS/TP IP R W Storage Configurab. In Uni-Pro Default Note Device ID Unsigned R R X X F Y 127 1..24bit-1 MAC Address Unsigned R X X F Y 127 1-127 Baud Rate Unsigned R X X F Y 38400 9600 19200 38400 76800 Adjust Priority Unsigned R R X X F Y 16 1..16 page 24 of 28

Override Priority Unsigned R R X X F Y 8 1..16 BACnet Port Number Unsigned R X X F Y 0xBAC0 BBMD IP Address R X X F Y 0.0.0.0 BBMD Port Number Unsigned R X X F Y 0xBAC0 Time To Live Unsigned R X X F Y 300 >=15 sec NOTE: Storage R means that all the writeable values will be storage non volatile, so will be lost after power cycle of the controller. NOTE: Some properties like MAX_MASTER, MAX_INFO_FRAMES, are related only to the MSTP protocol, others like BBMD and Time To Live only to IP protocol. Tab. 1 BACnetEngineeringUnits (see ANSI/ASHRAE Standard 135-2010) Tab. 2 BACnetLimitEnable ::= BIT STRING { lowlimitenable (0), highlimitenable (1) } Tab. 3 BACnetEventTransitionBits ::= BIT STRING { to-offnormal (0), to-fault (1), to-normal (2) } Tab. 4 BACnetEventState ::= ENUMERATED { normal (0), fault (1), offnormal (2), high-limit (3), low-limit (4), life-safety-alarm (5),... } page 25 of 28

Appendix A : Restrictions All strings are restricted to 25 characters. Unsigned values are limited to 65535. The max number of states in Multistate objects is 16 states. The max number of COV subscription is 10 If the precision of the value written to PRESENT_VALUE is greater than the precision of the variable in the application, the controller will truncate the value to the application precision. MAX_INFO_FRAMES is limited to 1. NUMBER_OF_APDU_RETRIES is restricted to the range 0..3 The max number of the Reception List is 5. Only some objects have the Intrinsic Reporting properties supported. page 26 of 28

RDT900 configurable controllers PICS ver. 1.0 EB - 2/18 Code 148RDT900SAU This document is exclusive property of SAUTER ITALIA; SAUTER ITALIA does not assume any liability regarding possible errors stated. The customer (manufacturer, installer or final user) assumes all liability regarding configuration of the device. SAUTER ITALIA does not take any responsibility for damages coming by the non-observance of additional information. SAUTER ITALIA reserves the right to make any change without prejudice the basic safety and operating features. page 27 of 28

SAUTER Italia S.p.A. Via dei lavoratori 131, 20092Cinisello Balsamo (Mi) ITALIA Tel. 02 280 48 1 Fax 02 280 48 280 info.sede@it.sauter-bc.com www.sauteritalia.it page 28 of 28