DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

Similar documents
DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

PROTECT Electronics Co. Ltd

Residual overvoltage relay

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Feeder protection relay SPAA 121 C. Product Guide

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

Arc protection relay. Features Three-phase overcurrent function. Application

High impedance protection relay

MiCOM P521. Fast Feeder Differential Protection

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

RT4F-110V/25A RECTIFIER

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

RT4F-120V/20A-WAC RECTIFIER

RT4F-48V/50A-WAC RECTIFIER

MiCOM P521. Fast feeder differential protection

MiCOM P521. Fast Feeder Differential Protection. Protection Relays. MiCOM P521 CUSTOMER BENEFITS

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

2H34. Definite Time Frequency Relay with ROCOF. Features. Operation. Application

RT4B-110V/12A RECTIFIER

Bus Bar Protection Relay B-PRO 4000

MiCOM P111. Three phase and earth fault overcurrent relays

Synchro-check relay. Application

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D

Arc protection relay. Features Three-phase overcurrent function. Application

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

Protection Relays PHASE & RESIDUAL OVERCURRENT

2T105. Multi Range Digital Setting Time Delay Relay. Features. Application. Operation

SE-701 MANUAL GROUND-FAULT MONITOR

TWO-WINDING TRANSFORMER DIFFERENTIAL

FL MC 2000E (SM40) LC

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

MiCOM P122C Time-Overcurrent Protection

Reyrolle Protection Devices. 7SG117 Argus 7 Synchronising Relay. Answers for energy

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

TM221M16R controller M IO relay

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

Communication with EuroProt-IED Multifunctional intelligent devices

Contact protection relay

02/11/2015

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

2V67 Four Stage Over / Under Voltage Relay

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

This data sheet is only valid in association with the IL SYS INST UM E user manual.

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

DRS-LA413. Circuit Breaker Failure Relay. Operating Principle DRS-LA413. Operating Principle. Revision: 2 from Dwg.No.: DIL

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

Siprotec 7ST61 / 7ST63

DIGITAL RELAY OF PROTECTION AND AUTOMATION SERIES PC83 AND PC830

NPI800 NPI800R. First Handling Guide. Phase and earth overcurrent relay

TM221ME32TK controller M IO transistor PNP Ethernet

TM221M16TG controller M IO transistor PNP spring

Feeder protection relay

Binary output and supervision 520CSD01 Data sheet

Substation Automation Products. High impedance differential busbar protection REB650 Relion 650 series

Iso DIN. User Manual. 1 channel Earth Fault Monitoring

ATV310HU30N4E variable speed drive ATV310-3 kw - 4 hp V - 3 phase

TM221CE40T controller M IO transistor PNP Ethernet

PGR-3200 MANUAL INSULATION MONITOR

TM221CE24R controller M IO relay Ethernet

General information. Display. Supply voltage. Input current. Encoder supply. Output current

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

Directional or Non-Directional Earth-Fault Relay REJ 527. Product Guide

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

SEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay

MID approval no. DE-08-MI004-PTB004 Date of release

TM241C40R controller M IO relay

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators

Feeder protection relay SPAA 341 C. Product Guide

For Transmission, Distribution and Machinery protection.

Advant OCS. The Compact and Cost Effective Advant Controller. Advant Controller 210. Open Control System

SM100. On-Line Switchgear Condition Monitoring

Accessories / 7XV5662

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

2V67-S Four Stage Over / Under Voltage Relay

EARTH-FAULT AND SHORT-CIRCUIT INDICATOR TYPE EKL8001 / EKL8002 surface mounted

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

ES Energy Saver Product Ranges 90Amp 6000Amp

TM241CE40R controller M IO relay Ethernet

General information. Display. Supply voltage. Input current. Encoder supply. Output current

TM221CE40R controller M IO relay Ethernet

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

TM221ME16T controller M IO transistor PNP Ethernet

Microprocessor protection and automation devices

RM4JA01F current measurement relay RM4-J - range ma V AC

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

TM241C40U controller M IO transistor NPN

Protection relays.

Reyrolle Protection Devices. 7SG21 DDB20 Multi Range Digital Setting Time Delay Relay. Energy Management

RM4JA31M current measurement relay RM4-J - range ma V AC

100% electricity. Automatic transfer switch controllers ATL series

MiCOM P220, P225 and P226C

Transcription:

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description contains special data of this type. General and common features of EuroProt family can be found in the EuroProt system information sheet. Accordingly it is proposed to study both this short description and system information sheet too, in order to understand the device entirely. Application field The DGSZV-EP type digital galvanic longitudinal differential protection of can be applied in electric power generating plants, transmission and distribution substations of the electric power system to quick and selectively protect high or medium voltage lines or cables against phase or ground faults. There are basically three versions: a three phase version for effectively grounded networks, a two phase device to protect medium voltage compensated or isolated networks against phase faults, in medium voltage resistance grounded or compensated network with neutral resistor for increasing the earth fault current, against phase and ground faults. The protection needs a single-phase, three wires, galvanic connection between the devices of both ends of the line. The connection is continuously supervised, in case of failure an alarm signal is generated, and disables or submits a trip command, according to the parameter setting..

Main features The DGSZV-EP type digital galvanic longitudinal differential protection is member of the numeric device family of PROTECTA Co. Ltd., called EuroProt. The protection contains a differential measuring element of a percentage bias characteristic with settable basic sensitivity ( I), an overcurrent function measuring in two phases (I>(t) and I>>(t)), four basic and two additional, free applicable timers (T1, T2). The stages of the galvanic longitudinal differential protection and overcurrent functions can be enabled independently of each other. The parameters for the differential protection, the current and the voltage elements and the timers can be set independently. The length of the single phase, three line, galvanic connection between the devices at both ends, in case of copper conductor may be maximum 10 km, the cross-section must be at least 1,5 mm 2. The three phase basic version of the device can be applied connected to two phases, or two phases + Io as well. The trip command can depend on undervoltage state. The phase selection is decided by the undervolatge function, but it is not absolutely necessary. The characteristics with two knee points can be set as needed, the biasing is made with the average of absolute value of currents at both ends. I d I be 100 % 400 300 f3=200% INTERNAL FAULT f3=500% f1=200% 200 f3=1000% f2=50% I 1 current at the own side I 2 current at the opposite side I = s I I 1 + 2 I I 1, n 2, n 100 % 2 f2=20% 100 f1=50% EXTERNAL FAULT 50 20 Is f1=20% 100 200 300 400 500 600 The trip characteristics of the digital galvanic longitudinal differential protection The operating time of the differential protection is approx. 35 ms. Software characteristics: built-in self-check functions, digital event recorder for 50 events, and an event sequence recorder with 1 ms time resolution for maximum 300 events, analog event records with current data, two additional timers (T1 and T2) in connection with the software matrix, the rows of the matrix (the relay-functions) can be latched. Hardware characteristics: numerical type, with own A/D converter, digital signal processor (DSP) and separate main processor, 8 opto-coupler inputs, 16 output contacts, the type of the contacts (NC or NO) can be selected individually for each contacts when ordering, versions for 19" rack cabinet mounting or housed in relay case (semi-flush mounting or hinged type). Communication: 2x16 character LCD display for setting the functions, displaying messages and reading event records, on-line screen on external PC to make commissioning and testing easier, external communication interface, can be set for RS 232 or for fibre optic cable,

optional interface module with IEC 870 protocol for SCADA systems, the set parameters can be saved and downloaded, real time clock handling with the aid of RAM with battery, (which can be synchronised via optical fibre cable connected to external PC, to the SCADA system, or through an optical cable). Working principle The DGSZV-EP device is a fully microprocessor based construction, the functions and their versions are realised basically on software. The device contains a 87C196 type 16 bit micro-controller. The program is stored in the internal EPROM of the controller, the message text for the display is stored in EPROM as well. The parameter setting is loaded in EEPROM. Events are recorded in battery supplied RAM. The man-machine interface consists of a keyboard with six push-buttons, above it the two row, 2 x 16 character LCD display, seven LEDs and two SW pushbuttons. With the help of an external PC and communication software the handling of the device is easier. The analog current and voltage inputs are connected via inductive internal measuring transformers and low-pass filters to the multiplexer then to the A/D converter, where all current and voltage signals are sampled in every 0,5 ms. The sampled values of the 16 bit A/D converter are passed via high speed CAN bus to the CPU. The central processor communicates via parallel bus with the optocoupler inputs and with the relay drivers. The protection contains a two stage definite time overcurrent protection for all the three phases. The time delay of all stages can be set independently. The two overcurrent stages contain RMS algorithm, the setting of the stages is independent of each other. The longitudinal differential protection function compares currents of the own end and that of the far end, composed of the weighted (2x, 3x, 1x) three phase currents or composed of two weighted phase currents and the zero sequence current (See Figure below), and decides if the fault is inside the protected section and a trip command is issued, or the fault is outside, when no trip command is generated. The algorithm compares 10 subsequent sampled values, then the comparison is repeated one period later. If the evaluation shows twice difference, the trip command is generated. The Id trip signal is composed of the vector difference of the single phase currents of the two sides, the restraint current is the average of the measured individual currents. As because of the presence of the intermediate current transformers and the connecting pilot cable, the saturation effects can be expected at smaller currents, the f3 knee point of the characteristics must be set lower, than that of the usual differential protection (see Figures). One branch of the pilot cable is for the current proportional to the own current, the second is for that of the opposite line side, the third branch is for the sum of these currents (Id). I R 1 I S,3I 0 I> Scheme of the longitudinal differential protection 3 I T common (Id) own side opposite side protection at the opposite side

The pilot cable is supervised in the operating current range by a sensitive differential function. The disabling (and the safety trip command if this is set by parameters) is delayed, if there is no deviation, a drop delay is set. The trip command can depend of voltage precondition, in this case the protection submits warning signal only. The longitudinal distance protection function, if voltage precondition is set, is blocked by the open signal of the miniature circuit breakers in the voltage transformer's secondary circuit. The galvanic longitudinal differential protection contains intermediate current transformers, and depending on the turns ratios of the mixing current transformers - at the rated current 5 A and 1 A as well - the current in the pilot cable is between 20 ma and 40 ma. One branch of the pilot cable is for the current proportional to the own current, the second is for that of the opposite line side, the third branch is for the sum of these currents (Id). In case of load current, or in case of external faults this branch has double current sum. This makes possible a quick and simple supervision. Technical data Rated secondary current, I n 1A or 5 A Rated voltage (line), U n 100V or 200 V Rated frequency 50 Hz or 60 Hz Overload capacity, voltage circuit, thermal, continuous 2xU phase =2xU n / 3 current circuit, thermal, continuous 1 s 4xI n 100xI n (if I n = 1 A) 50xI n (if I n = 5 A) Dynamic current limit 100xI n Accuracy, current relays (above 50 % I n ) ± 2 % Accuracy timers, with 10 ms steps with 1 s steps ± 3 ms ± 12 ms Reset ratio, current relays 95 % Number of output relays 12 print relays Type of contacts (NO / NC): Output contacts, electrical data: rated switching voltage continuous load current making current DC breaking capability at 220 V, at pure conductive load at load of L/R = 40 ms option at load of L/R = 40 ms Auxiliary DC voltage (the same supply unit) voltage tolerance Permissible ambient temperature Insulation test (IEC 255) Disturbance test (IEC 255) Electrostatic discharge (ESD, IEC 801-2) Burst test (IEC 801-4) to be selected at ordering, factory setting 1 NC 11 NO 250 V 8 A 16 A 0,25 A 0,14 A 4 A 220 V or 110 V 88...310 V 0...50 C 2 kv, 50 Hz 5 kv, 1,2/50 µs 2,5 kv, 1 MHz 8 kv 2 kv Setting ranges Basic setting (Id>f1*Ibe)[f1] 10...200 %, step: 2 % Slope of section 2. (Id>f2*Is)[f2] 40...80 %, step: 2 % Slope of section 3. (Id>2Is-f3*Ibe)[f3] 50...2000 %, step: 10 % Voltage condition [U>/Un] 20...100 %, step: 5 % The tertiary rated current at the own side (Iset[own]rated.) 0,2 A fix The tertiary rated current at the opposite side (Iset[opp]rated.) 0,2 A fix Delay of signalling cable error 0...64000 ms, step 10 ms

Low set overcurrent function, I> / In[AV] 50...2500 %, step: 5 % High set overcurrent function, I>> / In[AV] 50...2500 %, step: 5 % CT rated primary current, In[AV] 50...2500 A, step: 25 A External communication type RS 232 or fibre optic cable Serial communication Baud rate 150...19200 Baud Optical fibre cable operation mode Radial or loop Daily automatic self-check time 23 hours 59 min.(step 1 min) Automatic self-check block setting 60 min Design, size An EuroProt device is always rack mounted, it has two design forms. One of the form is suitable to be mounted into standard 19" cabinet frame, this form is also suitable to be mounted directly to a relay panel with flash mounted form. The other form is a relay panel mounted device with raised-hinged form. Outline size of 19"cabinet frame mounted device: Width Height Depth 483 mm 132,5 mm 201 mm Outline of the panel mounted device with raised-hinged form: Weight: 8 kg. Width Height Depth 490 mm 250 mm 250 mm Options The device can be extended by optional units: digital disturbance recorder (see separate information sheet), SCADA connection (see EuroProt system information sheet), output relays with 4 A breaking capability. Information required with order Protection type [DGSZV-EP], Protection case type [19" cabinet frame mounted device, or panel mounted device Rated current [1 A, 5 A], Rated voltage [100 V, 200 V], Output relay contact type [NC or NO, if deviates from the Technical Data], Options if needed