STEP-PS/1AC/24DC/1.75

Similar documents
PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

MINI-PS AC/10-15DC/8

PHOENIX CONTACT - 07/2006

PHOENIX CONTACT - 01/2007

TRIO-DIODE/12-24DC/2X10/1X20

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

QUINT-PS-3x AC/24DC/10

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

TRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.:

QUINT-BUFFER/24DC/24DC/40

STEP-PS/1AC/24DC/2.5. Extract from the online catalog. Order No.: DIN rail power supply of 24 V DC/2.5 A, primary switched, single phase.

QUINT-PS/ 1AC/24DC/ 5

ASI QUINT /2.4 EFD

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

QUINT-PS AC/24DC/10

QUINT-PS/24DC/48DC/ 5

1-Phase Power Supply, Primary Switch Mode for Use in Potentially Explosive Areas QUINT-PS AC/24DC/5/EX

QUINT-PS/ 1AC/24DC/20/CO

Power supply CP-C 24/5.0

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

Redundancy Module QUINT-DIODE/40

Extract from the online catalog

RTU500 series Data Sheet Power Supply CP-E 24/2.5

Power Supply HARTING pcon

Power supply CP-E 48/1.25 Primary switch mode power supply

QUINT-DC-UPS/24DC/10. Extract from the online catalog. Order No.:

QUINT-DC-UPS/24DC/40. Extract from the online catalog. Order No.:

Power supply CP-E 24/0.75 Primary switch mode power supply

Power supply CP-E 24/10.0 Primary switch mode power supply

Power Supply HARTING pcon

Easy Analog RNB130. Technical Information. Primary switched-mode power supply

QUINT-DC-UPS/24DC/10. Extract from the online catalog. Order No.:

Uninterruptible power supply - TRIO-UPS/1AC/24DC/

DC/DC converters - QUINT-PS/24DC/24DC/

onlinecomponents.com

Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/40

MINI MCR-SL-UI-2I(-SP)(-NC)

Redundancy unit CP-A RU

MINI MCR-SL-PT100-UI-200

EMD-SL-LL-230. Electronic monitoring relay for level monitoring of conductive liquids. INTERFACE Data sheet _en_04. 1 Description.

Power supply CP-D 12/2.1 Primary switch mode power supply

MINI MCR-SL-PT100-UI(-SP)(-NC)

MINI MCR-SL-CVS NC

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

Output Voltage* (nom.)(adjustable)

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

FL MC 2000E (SM40) LC

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

MINI MCR-SL-UI-REL(-SP)

Power supply CP-C 24/5.0

ETD-BL-1T-OFF-CC- 10S

PI-EX-ME-2NAM/COC-24VDC

PHOENIX CONTACT - 12/2007

PI-EX-ME-2NAM/COC-120VAC

Buffer module CP-B 24/20.0, ultra-capacitor based Accessory for power supplies (e.g. switch mode power supplies CP range)

Industrial Power Supplies

Output Voltage* (nom.)(adjustable)

PHOENIX CONTACT Features

PHOENIX CONTACT - 11/2008

Rhino PSM Power Supplies. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

24V 100W 1 Phase PMC-24V100W1AA

AO561 Analog Output Module

AI561 Analog Input Module

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

PHOENIX CONTACT - 05/2007

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

ABL1REM24100 regulated SMPS - single phase V input - 24 V output W

Contact protection relay

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

Switched-Mode Power Supplies. 5, 12, 18, 48 VDC Output

20A DRR Module / 40A DRR Module

Chrome DIN Rail Power Supply 5V 7.5W 1 Phase (Class II & NEC Class 2) / DRC-5V10W1AZ

DC561, digital input/output module,

Industrial Power Supplies

DC562, digital input/output module,

PSR-PS21. SIL coupling relay. Data sheet. 1 Description

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

ABL1RPM24100 regulated SMPS - single phase V input - 24 V output W

MACX MCR-EX-SD LP(-SP)

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

ABL1REM24025 regulated SMPS - single phase V input - 24 V output - 60 W

DX561 Digital Input/Output Module

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

Chrome DIN Rail Power Supply 24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1AZ

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

Electronic timer CT-ERD.12

SITOP power supply. LOGO!Power. Overview. Safety instructions. Description, device design, dimension drawing. Mounting/removal 3

PHOENIX CONTACT - 01/2008

Chrome DIN Rail Power Supply 24V 10W 1 Phase (Class II & NEC Class 2) / DRC-24V10W1A

Transcription:

Primary-switched power supply, 1 AC, output current 1.75 A INTERFACE Data Sheet 103506_en_00 1 Description PHOENIX CONTACT - 05/2008 Features STEP POWER power supply units for building automation The new STEP POWER generation of compact power supply units is particularly suitable for installation distributors and flat control panels thanks to its design. The power supply units are available with 24 V DC output voltage in four performance classes and widths and with the special voltages 5, 12, 15 and 48 V DC. Their high degree of efficiency and the low standby losses make for high power efficiency. Easy assembly on the DIN rail or panel Maximum energy efficiency thanks to low idling losses Quick startup with LED function monitoring High operating safety due to long mains buffering under full load and high MTBF (> 500,000 h) Can be used worldwide in all industrial sectors due to a wide-range input and an international approval package Wide temperature range of -25 C to 70 C Parallel connection possible for increased performance and redundancy DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. DANGER The device contains dangerous live elements and high levels of stored energy. Never carry out work when the power is turned on. Make sure you always use the the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf.

2 Table of contents 1 Description...1 2 Table of contents...2 3 Ordering data...3 4 Technical data...3 5 Structure...6 6 Block diagram...7 7 Safety notes...7 8 Installation...8 9 Installation position...8 10 Mounting on DIN rails...9 Assembly...9 Removing...9 11 Connection to various systems...9 12 Input... 10 Protection of the primary side...10 Recommended backup fuse for mains protection...10 13 Output... 10 Protection of the secondary side...10 14 Signaling... 11 15 Function... 11 Output characteristic curve...11 Thermal behavior...11 Parallel operation...12 Redundant operation...12 Increased performance...12 103506_en_00 PHOENIX CONTACT 2

3 Ordering data Description Type Order No. Pcs. Pkt. Primary-switched power supply, 1 AC, output current 1.75 A STEP-PS/1AC/24DC/1.75 2868648 1 4 Technical data Input data Input nominal voltage range AC input voltage range DC input voltage range AC frequency range DC frequency range Current consumption Inrush current limitation I 2 t Power failure bypass Typical response time Protective circuitry Input fuse, integrated 100 V AC... 240 V AC 85 V AC... 264 V AC 95 V DC... 250 V DC 45 Hz... 65 Hz 0 Hz Approx. 0.6 A (120 V AC) Approx. 0.3 A (230 V AC) < 15 A (typical) < 0.6 A 2 s > 25 ms (120 V AC) > 150 ms (230 V AC) < 0.5 s Transient surge protection Varistor 3.15 A (slow-blow, internal) Recommended backup fuse for mains protection 6 A (characteristic B) 10 A (characteristic B) 16 A (characteristic B) Output data Nominal output voltage 24 V DC ±1% Setting range of the output voltage 22.5 V DC... 29.5 V DC (> 24 V constant capacity) Output current 1.75 A (-25 C... 70 C) 1.9 A (-25 C... 40 C) 3.75 A (maximum output current) Derating Above 55 C: 2.5% per Kelvin Control deviation < 1 % (change in load, static 10%... 90%) < 2 % (change in load, dynamic 10%... 90%) < 0.1 % (change in input voltage ±10%) Power loss nominal load max. 5 W Maximum power dissipation idling 0.7 W Efficiency > 89 % (for 230 V AC and nominal values) Ascent time < 0.5 s (U OUT (10%... 90%)) Residual ripple < 35 mv PP (with nominal values) Peak switching voltages < 35 mv PP Connection in parallel Yes, for redundancy and increased capacity Connection in series No Surge protection against internal surge voltages Yes, limited to approx. 35 V DC Resistance to reverse feed Max. 35 V DC Signal output DC OK active Status display "DC OK" LED green / U OUT > 21.5 V: LED lights up 103506_en_00 PHOENIX CONTACT 3

General data Insulation voltage input/output 4 kv AC (type test) 2 kv AC (routine test) Insulation voltage input / PE 3.5 kv AC (type test) 2 kv AC (routine test) Insulation voltage output / PE 500 V DC (routine test) Degree of protection IP20 Class of protection II MTBF > 500 000 h in acc. with IEC 61709 (SN 29500) Housing material polycarbonate Foot latch material Plastic POM Dimensions W / H / D (state of delivery) 54 mm / 90 mm / 61 mm Weight 0.2 kg Ambient conditions Ambient temperature (operation) -25 C... 70 C (> 55 C derating) Ambient temperature (storage/transport) -40 C... 85 C Max. permissible relative humidity (operation) 95 % (at 25 C, no condensation) Vibration (operation) < 15 Hz, amplitude ±2.5 mm in acc. with IEC 60068-2-6 15 Hz... 150 Hz, 2.3g, 90 min. Shock 30g in all directions in acc. with IEC 60068-2-27 Pollution degree in acc. with EN 50178 2 Climatic class 3K3 (in acc. with EN 60721) Standards Electrical for Machinery EN 60204 Safety transformers for power supply units IEC 61558-2-17 Electrical safety (of information technology equipment) IEC 60950/VDE 0805 (SELV) Electronic equipment for use in electrical power installations EN 50178/VDE 0160 (PELV) SELV IEC 60950 (SELV) and EN 60204 (PELV) Safe isolation DIN VDE 0100-410 DIN VDE 0106-1010 Protection against electric shock DIN 57100-410 Protection against electric shock, basic requirements for safe isolation in DIN VDE 0106-101 electrical equipment Limitation of mains harmonic currents EN 61000-3-2 Certificate CB Scheme Approvals UL approvals UL Listed UL 508 UL/C-UL Recognized UL 60950 103506_en_00 PHOENIX CONTACT 4

Conformance with EMC directive 2004/108/EC Noise immunity according to EN 61000-6-2 Electrostatic discharge EN 61000-4-2 Housing Level 3 Contact discharge ± 6 kv (Contact discharge) Discharge in air ± 8 kv (Air discharge) Comments Criterion B Electromagnetic HF field EN 61000-4-3 Housing Level 4 Frequency range 80 MHz... 3000 MHz Field intensity 10 V/m Comments Criterion A Fast transients (burst) EN 61000-4-4 Input 4 kv (level 4 - asymmetrical) Output 2 kv (Level 3 - asymmetrical) Comments Criterion B Surge current loads (surge) EN 61000-4-5 Input 4 kv (asymmetrical: Conductor to ground) 2 kv (symmetrical: Conductor to conductor) Output 2 kv (level 3 - asymmetrical: conductor to ground) 1 kv (Level 3 - symmetrical: Conductor to conductor) Comments Conducted interference EN 61000-4-6 Input/output Frequency range Voltage Comments Voltage dips EN 61000-4-11 Input Comments Emitted interference in acc. with EN 61000-6-3 Criterion B Level 3 - asymmetrical 10 khz... 80 MHz 10 V Criterion A (mains buffering > 20 ms) Criterion A Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1 Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) class B used in industry and residential area / EMC 1 103506_en_00 PHOENIX CONTACT 5

5 Structure 4 5 2 1 AC input 2 DC output 3 "DC OK" LED 4 Potentiometer 22.5 V DC... 29.5 V DC 5 Universal snap-on foot for EN DIN rails and for wall mounting 1 STEP-PS/1AC/24DC/1.75 Order-No.: 2868648 INPUT AC: 100-240V 50-60Hz 0.85-0.4A 85-264V ~ 95-250V Operational Voltage: OUTPUT DC: -26 24V 1.75A TEMPERATURE (>55 C/>131 F Derating:2,5%/k) -25.70 C -15.158 F Industrial APPROVALS UL LISTED Control 43KA Information Technology Read manual No. 9038813 before connecting to mains www.interface.phoenixcontact.com 3 [mm 2 ] AWG [Nm] solid stranded Torque Input 0.2-2.5 0.2-2.5 24-12 0.6-0.8 Output 0.2-2.5 0.2-2.5 24-12 0.6-0.8 Input data Input nominal voltage range 100 V AC... 240 V AC AC input voltage range 85 V AC... 264 V AC DC input voltage range 95 V DC... 250 V DC AC frequency range 45 Hz... 65 Hz DC frequency range 0 Hz Input fuse, integrated 3.15 A (slow-blow, internal) Recommended backup fuse for mains protection 6 A (characteristic B) 10 A (characteristic B) 16 A (characteristic B) Type of connection Screw connection Stripping length 6.5 mm Output data Nominal output voltage 24 V DC ±1% Setting range of the output voltage 22.5 V DC... 29.5 V DC (> 24 V constant capacity) Output current 1.75 A (-25 C... 70 C) 1.9 A (-25 C... 40 C) 3.75 A (maximum output current) Type of connection Screw connection Stripping length 6.5 mm 103506_en_00 PHOENIX CONTACT 6

6 Block diagram L () N (-) 7 Safety notes DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. DANGER The device contains dangerous live elements and high levels of stored energy. Never carry out work when the power is turned on. WARNING Before startup please ensure: The mains connection has been carried out by a competent person and protection against electric shock is guaranteed! The device can be disconnected outside the power supply unit in accordance with the regulations as in EN 60950 (e.g. through primary side line protection)! All feed lines are sufficiently protected and dimensioned! All output lines are dimensioned according to the maximum output current of the device or separately protected! Sufficient convection is guaranteed! CAUTION The power supply units are built-in devices. The device may only be installed and put into operation by qualified personnel. The corresponding national regulations must be observed. 103506_en_00 PHOENIX CONTACT 7

8 Installation ATTENTION In order to ensure sufficient convection, we recommend a minimum vertical distance of 30 mm to the other devices. STEP-PS/1AC/24DC/1.75 Order-No.: 2868648 INPUT AC: 100-240V 50-60Hz 0.85-0.4A 85-264V ~ 95-250V Operational Voltage: OUTPUT DC: -26 24V 1.75A TEMPERATURE (>55 C/>131 F Derating:2,5%/k) -25.70 C -15.158 F Industrial APPROVALS UL LISTED Control 43KA Information Technology The power supply unit can be snapped onto all DIN rails as per EN 60715; it can also be mounted on walls. The device must be mounted vertically (connecting terminals above or below). Read manual No. 9038813 before connecting to mains www.interface.phoenixcontact.com 9 Installation position 54 55 44 150 90 30 22.5-29.5V 30 Output DC 24 V 1.75 A L() N(-) 50 61 103506_en_00 PHOENIX CONTACT 8

10 Mounting on DIN rails Assembly To mount on an EN DIN rail, snap the device straight onto the DIN rail. If the power supply unit is to be fastened directly onto an even surface, press the orange base latch upward and down. Place a washer between the pulled-out base latch and the even surface (max. outer diameter 8.5 mm, max. thickness 1.3 mm, e.g., spring washer for M4 in acc. with DIN 127-B or toothed lock washer in acc. with DIN 6797). Then fasten the device with two screws (max. thread diameter 4 mm, max. head diameter 8.5 mm). Removing To dismantle from the EN DIN rail, press the orange base latch outward and pull the device off of the DIN rail. In the case of wall mounting, loosen the screws and press the base latch inwards again. 11 Connection to various systems TN-S TN-C TT it L N PE L PEN L N L1 L2 L3 L N - L N L N - - L N - The 100 V AC... 240 V AC connection is made using the L and N screw connections. The device can be connected to 1-phase AC networks or to two of the phase conductors of three-phase systems (TN, TT or IT networks in acc. with VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC...240 V AC. For operation on two of the phase conductors of a three-phase system, an isolating facility for all poles must be provided. 103506_en_00 PHOENIX CONTACT 9

12 Input CAUTION If an internal fuse is triggered, there is most probably a malfunction in the device. In this case, the device must be inspected in the factory! STEP-PS/1AC/24DC/1.75 Order-No.: 2868648 INPUT AC: 100-240V 50-60Hz 0.85-0.4A 85-264V ~ 95-250V Operational Voltage: OUTPUT DC: -26 24V 1.75A TEMPERATURE (>55 C/>131 F Derating:2,5%/k) -25...70 C -15.158 F Industrial APPROVALS UL LISTED Control 43KA Information Technology Read manual No. 9038813 before connecting to mains www.interface.phoenixcontact.com Protection of the primary side The device must be installed in acc. with the regulations as in EN 60950. It must be possible to disconnect the device using a suitable isolating facility outside the power supply. The primary side line protection, for example, is suitable. For device protection, there is an internal fuse. Additional device protection is not necessary. Recommended backup fuse for mains protection Power circuit-breaker 6 A, 10 A or 16 A, characteristic B (or identical function). Connect a suitable fuse upstream for DC applications! 13 Output STEP-PS/1AC/24DC/1.75 Order-No.: 2868648 INPUT AC: 100-240V 50-60Hz 0.85-0.4A 85-264V ~ 95-250V Operational Voltage: OUTPUT DC: -26 24V 1.75A TEMPERATURE (>55 C/>131 F Derating:2,5%/k) -25.70 C -15.158 F Industrial APPROVALS UL LISTED Control 43KA Information Technology Read manual No. 9038813 before connecting to mains www.interface.phoenixcontact.com CAUTION Make sure that all output lines are dimensioned according to the maximum output current or are separately protected. The cables on the secondary side must have sufficiently large cross sections in order to keep the voltage drops on the lines as low as possible. The connection is made using the "" and "-" screw connections on the screw connection of the DC output. At the time of delivery, the output voltage is 24 V DC. The output voltage can be set on the potentiometer. Protection of the secondary side The device is electronically protected against short circuit and idling. In the event of a malfunction, the output voltage is limited to 35 V DC. 103506_en_00 PHOENIX CONTACT 10

14 Signaling The "DC OK" LED enables evaluation of the function of the power supply directly on site. State 1 State 2 "DC OK" LED ON OFF Cause Output voltage > 21.5 V Output voltage < 21,5 V or no voltage at the output Meaning Output voltage and output current OK The device is in operation, but there is a fault in the consumer, the current consumption is greater than I 1 or the output is short circuited. The device is out of operation because there is no mains voltage, the fuse on the primary side has been triggered, or the device is faulty. 15 Function Output characteristic curve The power supply works with a power reserve as shown in the U/I characteristic curve in the figure. At ambient temperatures T AMB < 40 C, I 1 is available continuously. At higher temperatures, it's available for a few minutes. In the event of a secondary-side short circuit or overload, the output current is limited to I MAX. Thereby, the module does not switch off, but rather supplies a continuous output current. The secondary voltage is reduced here until the short circuit is eliminated. The U/I characteristic curve with the power reserve ensures that both high inrush currents of capacitive loads as well as consumers with DC/DC converters in the primary circuit can be supplied. U N = 24 V I N = 1,75 A P N = 42 W I 1 = 1,9 A P 1 = 46 W I MAX = 3,75 A (U OUT = 0 V) U [V] OUT U N P N P 1 I N I 1 I MAX I OUT [A] Thermal behavior Output current [A] I N 0 0 20 40 60 Ambient temperature [ C] With an ambient temperature of up to 55 C, the device supplies the continuous output current of I N. In the case of ambient temperatures above 55 C, the output current must be reduced by 2.5% per Kelvin increase in temperature. The device does not switch off at ambient temperatures of 70 C or thermal overload. The output capacity is reduced as far as necessary to provide device protection. After it has cooled down, the output capacity is increased again. 103506_en_00 PHOENIX CONTACT 11

Parallel operation Devices of the same type can be connected in parallel to enable both redundancy and an increase in efficiency. No other alignment is necessary when in the state of delivery. If the output voltage is adjusted, a uniform distribution of power is guaranteed by setting all parallel operated power supply units to exactly the same output voltage. To ensure symmetrical distribution of power, we recommend designing all cable connections from the power supply unit to a busbar of the same length and with the same conductor cross section. The system makes it advisable to install a protective circuit at the output of each device when more than two power supply units are connected in parallel (e.g. decoupling diode or DC fuse). This prevents high reverse feed currents in the event of a secondary device fault. Redundant operation I N I N Σ =I N Redundant circuits are suitable for the supply of systems which make especially high requirements on the operational safety. If a fault occurs in the primary circuit of the first power supply unit, the second device automatically takes over the entire power supply, without interruption, and vice versa. For this reason, the power supply units to be connected in parallel are dimensioned in such a way that the total current requirement of all consumers can be completely covered by one power supply unit. 100% redundancy makes external decoupling diodes necessary (QUINT-DIODE/40, Order No. 2938963)! I N I N Increased performance For n parallel connected devices, the output current can be increased to n x I N. Parallel connection to increase efficiency is used for the expansion of existing systems. It is advisable to use parallel connection if the power supply unit does not cover the current requirement of the most powerful consumer. Otherwise the consumers should be spread among individual devices independent of one another. A maximum of five devices can be connected in parallel! Σ =2xI N 103506_en_00 PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany Phone: 49-(0) 5235-3-00 12 PHOENIX CONTACT P.O.Box 4100 Harrisburg PA 17111-0100 USA Phone: 717-944-1300 www.phoenixcontact.com