MONITORING ABSTRACT KEYWORDS. TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017

Similar documents
White Paper. AC Surge Protection. Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems

Quality assurance Test Facilities for Gapless ZnO Surge Arresters in High Voltage Division of CPRI, Bengaluru

Fundamentals of Thyristor Overvoltage Circuit Protection

Today, utilities are focusing on improving or maintaining

AC Power Quality and Protection

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

Surge & Filter Protection Addressing your industrial power quality needs.

Timothy Cox Application and Support Engineer Dynamic Ratings Australia

Redundant Bus Protection Using High-Impedance Differential Relays. Josh LaBlanc

Capacitor Test System

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment

ELG4125: System Protection

Manual for overvoltage protection for LED luminaires rev 1

The following standards are the basis of design, manufacture, and test of SPD equipment: Guide for Surge Voltages in Low-Voltage AC Power Circuits

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Figure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters.

Lightning Surge Response Improvement by Combinations of Varistors and Gas Discharge Tubes

Each VariSTAR Type AZU arrester must pass the following production tests: 100% Physical Inspection 100% Leakage Current Test 100% RIV Test

35 kv Class M.O.V.E. DirectConnect elbow arrester

ALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD

National Standard of The People s Republic of China

PHASETRONICS. SCR Power Control Specialists. EP1 Series Power Control Single Phase SCR Amps OPERATION & SERVICE MANUAL

Surge Current Capacities

2 Principle of lightning protection

Presented by: Ron Hotchkiss Chairman, IEEE PES Surge Protective Devices Committee

Providing the missing piece in your Condition Based Monitoring platform

glossary GE Digital Energy Power Quality Surge Protective Devices (SPDs)

Lightning Surge Response Improvement by Combinations of Varistors and Gas -Discharge -Tubes

ITU-T Recommendations and the Resistibility of Telecommunication Equipment

METAL OXIDE VARISTORS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Series Wall Mounted Low and Medium Exposure Surge Protective Devices (SPDs)

Mitigation of Voltage Swells I

GE Digital Energy. Power Quality

Using the Bitronics 70 Series to Improve Local Monitoring and Control

Electromagnetic Compatibility ( EMC )

Systems which use a conventional POTS subscriber line to dial a compatible system and transfer digital data.

GLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc.

ENGR. MARITES R. PANGILINAN, P.E.E.

Type VRLTC tap changer

Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV Version 3.3

M ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS

Data Sheet. Surge protection devices - A technical overview

ELECTROM INSTRUMENTS

We put the now in knowledge Today s solutions built on a century of innovation and expertise

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

QUALITROL QTMS Transformer Monitoring System

Surge Protector. Esma Khatun

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation

Identify and understand the operation of common bus. After this presentation you will be able to: Identify common bus arrangements

Installation Instructions

Central Power Research Institute, Medipally PO, Uppal, Hyderabad, Telangana. Discipline Electrical Testing Issue Date

OVP2. The Over-Voltage Protector 2 (OVP2) Technical Literature

www. ElectricalPartManuals. com

HV-CS kv Edge Mount Triaxial Jack

Ethernet Protection A Whole Solution Han Zou, ProTek Devices

SAMPLE. MOVs are sometimes referred

Type Code No. Weight Packaging [g] [pcs]

TDX Series. Transient Discriminating TM TVSS

Integrating Monitoring and Diagnostic Equipment on Aging Transformers

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

"Powering and Protecting Networks and Equipment Connected to It" Jim Pelegris ITW/LINX

17 th Edition (BS 7671:2008) incorporating Amendment No 1

CONTENTS 3 EN :2006

Deploying surge protective devices (SPDs) in photovoltaic systems. Technical Information

Ferraz Shawmut TPMOV Principles and Operation

Suppressing Transients: A New Approach

Low Voltage and Medium Voltage Surge Protection

SURGE PROTECTION OPTION

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Innovative Technology TVSS Products

MDSP-Series 90kA, 150kA, 300kA Modular Distribution Surge Protector Type 2 Class II Surge Arrester

BS th Edition wiring regulations Furse overview

Tel: Web: Lightning and surge protection help pages

White Paper Surge Protective Devices in Automatic Transfer Switches

16-Channel Input Digital Input Termination Card

ENhanced TEChnology. Solid insulated vacuum recloser for power distrbution system thru 15kV, 27kV, 38kV V 3.1

Motor Surge Suppressors and Cable Considerations

Hazardous Area Protection

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

Surge Protection. The effects of transient voltages on business and the benefits of installing Surge Protection Devices

White Paper Surge Current Characteristics: 570 Hybrid Surge Protective Device

Digital On-Load Tap Changer Voltage Controller TAPCON 250 Operating Instructions (short version) BA 289

AN579 Application note

Small Power Station Surge Protection Analysis and Plan

Overvoltage Protection Devices

PHOTOVOLTAIC PLANTS Comprehensive lightning protection

After the storm leaves the area, you pat yourself on the back for protecting your data and equipment. The worry is over. Or is it?

SSV-T and SSC-T High Drop-out Relay. Range amps amps amps amps. Operating Frequency: Temperature Error:

HyperLink Brand Weatherproof PTZ Camera Lightning and Surge Protector Model: AL-VDP Series

Basic HEMP Protection Means for a Power Substation: A Quick Guide

S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

Power Quality of Commercial Buildings - Advanced

Introduction to Surge Protection

OVERVOLTAGE PROTECTIVE DEVICE AND METHOD OF OVERVOLTAGE PROTECTION

LIGHTNING PROTECTION of SCADA AND TELEMETRY SYSTEMS

Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers

ENhanced TEChnology. Solid insulated vacuum recloser for power distribution system thru 15kV, 27kV, 38kV. Ver.

Transcription:

MONITORING The difference between safe and reliable on-line bushing monitoring and false alarms often lays in the quality of the sensor design and the installation procedure ABSTRACT On-line monitoring has proven to be an effective technology to detect deteriorating high voltage bushings and prevent failures. While there is much focus placed on the monitor and the data it provides, the sensors used to transmit the signals are often overlooked. An on-line bushing monitoring program is only as good as the quality and reliability of the sensors used to provide the signals. Many problems and false alarms can be avoided by using a properly designed sensor and making sure it is correctly installed. This article will discuss what to consider when selecting a bushing sensor and how to install the sensor properly. KEYWORDS open circuit protection, transient surge protection, moisture ingress, power factor 102 TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017

Mark TOSTRUD Bushing sensors and their role in reliable on-line bushing monitorings 1. Introduction Although bushing manufacturers continue to improve the quality and reliability of their product, the 2015 CIGRE Transformer Reliability Study shows that bushing failures continue to be one of the leading causes of transformer failures around the globe. The study also shows that bushing failures were the cause of over one third of the transformer failures involving fires or explosions. Due to the financial impact a catastrophic transformer failure can have, many utilities are turning to on-line bushing monitoring to identify deteriorated bushings earlier and prevent transformer failures [1]. On-line bushing monitoring systems have been successfully used by the utility industry for over 20 years. They have a proven track record for being able to identify degrading bushings early in the failure process. By providing early warning, users have additional time to plan and schedule an outage to replace the bushings. While there are many users that have successful on-line bushing monitoring programs, some users cite problems with false alarms from the monitor. While there can be multiple reasons for a false alarm, sensor related problems are one of the more common complaints. The use of properly designed sensors and correctly installing the sensors can improve the reliability of the on-line monitoring system. This article will discuss the different styles of bushing sensors available on the market today, the protection the sensors must provide to prevent equipment damage and protect utility personnel, and the installation procedures that can help to prevent false alarms. 2. Sensor design IEEE Standard C57.19.100, IEEE Guide for Application of Power Apparatus Bushings offers the following guidance when selecting a bushing monitoring system/ sensor: Bushing monitors are installed on bushing cap taps to allow for on-line testing and monitoring. These [devices] allow for continuous monitoring or periodic testing of bushings without removing the bushing from service. Since the monitors replace the existing cap tap cover, the user should insure proper fit of the monitor to prevent moisture ingress into the cap tap. A voltage is then brought from the monitor to an accessible area of the transformer to perform the monitoring. The user should consult with the manufacturer of the monitor to determine the voltage levels that are normally expected and the maximums that could be reached should the device fail. Operational guide When installing a bushing monitor, maintaining the ground connection is of utmost importance www.transformers-magazine.com 103

MONITORING 4. Sensor protection 4.1 Open circuit protection Figure 1. Resistive style bushing sensor The sensor must provide redundant overvoltage and overcurrent surge protection from damaging the bushing and monitoring system lines can then be developed by the user to determine the level of safety requirements and experience of personnel who should have access to the devices. [2] 3. Sensor types 3.1 Resistive Resistive style sensors, Fig. 1, utilize resistors connected between the bushing tap and ground as the primary method to limit the voltage from the test tap. Should the resistors fail, metal oxide varistors (MOVs) or similar overvoltage protective devices, limit the voltage output from the tap to acceptable levels. Current limiting resistors in series with the MOVs can help to prevent MOV failures. Since the test tap of the bushing is solidly grounded through resistors, this type of sensor closely matches the original bushing design where the C2 capacitance is grounded when in service through the tap cover. To protect against overcurrent, gas discharge tubes or similar surge protection devices are used. The resistor (RS) is used to limit the test tap voltage. The resistor(s) may be located in the bushing monitor or in the bushing sensor. Locating the resistor(s) in the bushing monitor allows for standardization of the bushing sensor design. Since the sensor design is not dependent on the size of the resistor required, the same sensor can be used for almost all system voltages and bushing C1 capacitance values; the exception being extra high voltage systems (EHV) where additional protection elements are often required [2, 3, 4, 5]. 3.2 Capacitive Capacitive style sensors, Fig. 2, utilize a capacitor, CS, in parallel with the C2 capacitance of the bushing. The sensor capacitor (CS) forms a voltage divider with the C1 capacitance of the bushing. The capacitor is sized to limit the voltage present in the tap. If the capacitor CS is located in the sensor body, the size of the capacitor must be considered in addition to the type of test tap adapter when ordering the bushing sensor. Should the capacitor CS fail, MOVs or similar overvoltage protection is provided to limit the voltage level to acceptable levels [2, 4, 6]. Some capacitive style sensor manufacturers rely on active electronic circuits to provide an alternative ground path should the voltage in the tap rise to unacceptable levels. The use of passive electronic components is generally recommended due to their high reliability and the simplicity of the design. 3.3 MOV MOV style sensors, Fig. 3, rely solely on arrestors to limit the voltage level from the tap to acceptable levels. Since this type of sensor provides only one layer of protection, it is not commonly found today. The ANSI type test taps used on bushings require the tap to always be grounded during operation. The loss of the ground connection will result in high voltage at the tap. To prevent generating high voltage, the tap cover grounds the test tap to the flange of the bushing. When installing a bushing monitor, it is extremely important that the monitor maintain this ground connection. Without proper protection, failure to maintain this ground connection will result in high voltage not only at the test tap, but also in the transformer cabinet and at the monitoring equipment. The maximum voltage present in an ungrounded test tap is dependent on the ratio of the C1/C2 capacitances of the bushing (cable capacitance and system burden effects are assumed to be minimal) as shown in equation (1). Let us consider a high voltage bushing applied on a 500 kv system with a C1 capacitance of 300 pf and a C2 capacitance of 3000 pf: C1 Open circuit voltage = VOC =VØ-G (C1+C2) = 500 kv. 300 = = 26.2 kv (1) 3 (300+3000) In the worst case for a bushing where C1 = C2, an ungrounded test tap could float to ½ the line to ground voltage of the system. To prevent high voltage at the tap and to prevent overstressing the C1 insulation system of the bushing, the sensors connected to the test tap must: have open circuit protection to protect operating personnel from electric shock and to maintain a safe operating voltage at the monitor; protect the bushing insulation system and the test tap from overvoltage in case of an open circuit between the sensor and the monitor; and provide a reliable current output with minimal phase shift from the test tap for the monitoring system. All bushing monitor manufacturers provide some form of open circuit protection in their sensors. However, the maximum voltage output under open circuit conditions will vary. At a minimum, the bushing sensor should limit the open circuit voltages to the lower of the manu 104 TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017

facturers specified test tap voltage or to a low voltage (50-300 VAC) as defined by OSHA 1910.303. Voltages in this range are commonly found in transformer control cabinets and hence will allow electrical personnel to follow their general safe work practice of avoiding contact with the electrical parts operating at this voltage when working in the cabinet. Maintaining an extra low voltage (<50 VAC) during an open circuit can further reduce the hazards to utility personnel. If subject to long duration overvoltage conditions which exceed the design specifications, overvoltage protective devices can fail. Current limiting resistors can help to prevent the failure of MOVs. Back up protection or redundant overvoltage protection devices are recommended since the sensors must maintain a ground connection at the test tap to prevent hazardous overvoltage from occurring. While maintaining this ground connection is necessary for all bushing types, manufacturers may not recommend on-line bushing monitoring due to the concern that the sensor may not maintain this ground connection. However, a properly designed sensor that utilizes redundant protective devices and failsafe protection can minimize these concerns [2, 3, 7, 8, 9]. 4.2 Transient surge protection In addition to overvoltage protection, the bushing sensor should also provide overcurrent protection against lightning and switching surges. The overcurrent protection required is dependent on the rate of voltage rise. Using the standard 1.2/50 μsec pulse, commonly specified for surge withstand protection, would result in a surge current of 125 amps for an indirect 500 kv lightning strike as shown in equation (2). I = dv C1 = 300. 10 dt -12. 500,000 1.2. = 10-6 = 125 amps (2) Figure 2. Capacitive style bushing sensor The use of passive electronic components for protection is recommended due to their high reliability and simple design be designed for lightning stroke currents of at least 10 ka. Using a larger stroke current capability will increase the life expectancy of the surge protective devices (SPD). Lightning related surges will have higher voltage with a shorter duration rise time, while switching related surges will have lower voltages and longer duration. Both need to be considered when designing the transient surge protection of the sensor. While the maximum expected current surge is only a few thousand amps, higher levels of protection are achievable and should be considered [7, 8, 9]. IEEE C37.90.1 and IEC 60255-26 provide guidance on transients and other electrical disturbances that are commonly found in high voltage substations. The standards define the surge withstand capabilities that are required for relays and relay systems. While these standards do not apply directly to bushing monitors and sensors, the fast transient and oscillatory waveform tests described in these standards are typical of the disturbances that bushing monitoring systems are exposed to [10, 11, 12]. Hence, bushing monitor manufacturers should design their equipment to meet the surge withstand capabilities specified in these standards. 5. Sensor installation Moisture ingress through to the test tap has always been a concern with high voltage bushings. Changes in C2 power factor due to moisture ingress is often listed as one of the leading reasons why utilities replace bushings on transformers. With Designing for surges with a shorter rise time than the typical 1.2x50 μsec waveform will result in a more robust sensor design and help to eliminate premature sensor failures. The same 500 kv lightning strike with a 0.1 μsec rise time would result in 1500 amps of surge current. IEEE 62.41 recommends that surge suppressors (applicable for sensing circuits) Figure 3. MOV style bushing sensor www.transformers-magazine.com 105

MONITORING Figure 4. Bushing test tap with moisture ingress due to an improper sealing gasket Since the sensor replaces the existing test tap cover, the user should insure proper fit of the sensor to prevent moisture ingress into the test tap an on-line monitor, moisture problems in the test tap can impact the magnitude and phase angle of the leakage current making it appear that the problem is in the bushing C1 insulation. Preventing moisture ingress, like that shown in Figure 4, re quires the following elements: 1. A properly designed cover or sensor that fits snug and firm to the test tap 2. A conductive thread lubricant to prevent damage to the thread during installation 3. A properly sized O-ring or similar gasket material which allows for the correct seal and gasket crush 4. A compatible O-ring lubricant to improve the seal and prevent damage to the gasket during installation 5. Filling the test tap with oil or a dielectric grease to provide additional protection from moisture ingress Most bushing manufacturers recommend filling the test tap with oil or a dielectric grease to help prevent moisture ingress. Hence, the sensor design must be compatible with mineral oil and capable of being operated with a wet or dry test tap. Following these simple and effective means of preventing moisture ingress can lead to years of trouble-free operation [3, 5]. Improper installation can have a significant impact on the readings from the bushing monitor and trigger false alarms. Figure 5 shows data from an online bushing monitor before and after repair of moisture ingress/contamination in the test tap of the X2 bushing. The figure shows the change in the phase angle of the X2 bushing leakage current compared to the reference bushing X1. Under ideal conditions, a 120-degree phase angle would be expected. If the system voltages are stable, an increase in the angle indicates an in crease in the power factor of the X2 bushing. In this example, the phase angle of the bushing leakage current often exceeded 124 degrees and at times exceed ed 125 degrees. Had this been an actual problem in the C1 insulation of the bush ing, this would have been equivalent to an increase in the C1 power factor of the bushing from 0.35 % to over 7 %. The problem resulted in frequent alarms from the bushing monitor whenever the imbalance Figure 5. Data from a bushing monitor before and after repair of corrosion due to moisture ingress 106 TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017

Improper installation can have a significant impact on the readings from the bushing monitor and trigger false alarms current exceeded 4 %. The utility downloaded the data from the monitor and noticed the erratic signals in the X2 bushing leakage current. After discussing the problem with the monitor manufacturer, a physical inspection of the test tap was performed. Figure 6 shows the corrosion in the test tap and on the spring connection due to improper installation. The contractor failed to follow the instructions for the bushing and monitor during the installation. The moisture and corrosion in the test tap had a significant impact on the power factor readings of the X2 bushing and resulted in alarms from the monitor. Conclusion On-line bushing monitoring can be an effective tool to help utilities prevent transformer and bushing failures, and better manage their aging infrastructure. To be successful in the use of on-line bushing monitoring, the design of the bushing sensors and the installation procedures should not be overlooked. The sensor must provide redundant open circuit (overvoltage) and transient (overcurrent) surge protective elements to protect the bushing and monitoring system from damage. The level of overvoltage protection, along with the design of the circuit, should be considered. Overvoltage protection which uses current limiting resistors in series with the protective device(s) can help to ensure long term safe and reliable operation. Overcurrent protection of at least 10 ka per IEEE 62.41 should be provided. Bushing monitoring systems should be designed to meet the surge withstand capabilities per C37.91.1 and IEC 60255-2 6. Most bushings require that the test tap remain grounded when in service. Since these circuits also protect utility personnel from hazardous overvoltage conditions being present in the transformer cabinet, the reliability of these circuits is of utmost importance. Due to the critical nature of this protection, sensors that offer failsafe protection, in addition to overvoltage and overcurrent protection are recommended. The failsafe protection, as the name implies, will short the test tap to ground at the test tap should the primary protection fail. Proper installation procedures are also required to prevent false alarms. Installation procedures should consider the fit of the sensor adapter to the test tap; the size and type of gasket material used; the lubrication of the gasket(s); and filling the test tap with mineral oil or a dielectric grease to prevent moisture ingress. References [1] Cigre Bulletin 642, Transformer Reliability Survey, Working Group A2.37, December 2015 [2] IEEE Standard C57.19.100-2012, IEEE Guide for Application of Power Apparatus Bushings [3] Type BAU Bushing Sensor Manual, Dynamic Ratings [4] Testing Power Factor and Capacitance on Energized Bushings, Free Standing CT and CCVTs, Weideman Solutions Seminar, San Antonio, TX, 2005 [5] Doble IDD Bushing Users Guide, Doble Engineering Company [6] User Manual for TBS Sensors, Eaton Electrical Predictive Diagnostics Figure 6. Corrosion found in the test tap after removing the transformer from service [7] IEEE Standard C62.41.1-2002, IEEE Guide on the Surge Environment in Low-Voltage (1000 V and less) AC Power Circuits [8] IEEE Standard C62.41.2-2002, IEEE Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and less) AC Power Circuits [9] IEEE Standard C62.45-2002, IEEE Recommended Practice on Surge Testing for Equipment Connected to Low- Voltage (1000 V and less) AC Power Circuits [10] IEEE Standard C37.90.1, IEEE Standard for Surge Withstand Capability (SWC) Tests for Relays and Relay Systems Associated with Electrical Power Apparatus [11] IEC Standard 60255-26, Measuring relays and protection equipment Part 26: Electromagnetic compatibility requirements Author Mark Tostrud is the Technology Officer for Dynamic Ratings, Inc. Prior to his present position, Mark was a Construction & Maintenance Supervisor at We Energies. During his 19 years at We Energies, Mark led the implementation of many of the condition based monitoring programs for We Energies substation equipment. Mark is a past officer of the Doble Oil Committee, and was an active member on various Doble Committees and Subcommittees including the Transformers, Insulating Materials, DGA of LTCs and others. Mark is a registered professional engineer in the State of Wisconsin. www.transformers-magazine.com 107