SERIES. ProVu PD6200 Analog Input Rate/Totalizer. Quick Start Guide. MeterView Pro. 233 South Street Hopkinton MA USA

Similar documents
Helios PD Large Display Meter Quick Start Guide

Trident & Trident X2 PD765

PROVU PD6000 Analog Input Process Meter Instruction Manual

Helios Large Display Analog Input Rate/Totalizer

PROVU PD6300 Pulse Input Rate/Totalizer Instruction Manual

Helios Large Display Analog Input Meter

PD6300 Pulse Input Rate/Totalizer Instruction Manual

Precision Digital Corporation 233 South Street Hopkinton MA USA Tel (800) Fax (508)

PROVU PD6001 Analog Input Feet & Inches Meter Instruction Manual

PROVU PD6060 Dual-Input Process Meter Instruction Manual

Helios Large Display Strain Gauge Meter

High Voltage DC Meter

Precision Digital Corporation 233 South Street Hopkinton MA USA Tel (800) Fax (508)

PROVU Batch Controllers PD6210 Analog Input & PD6310 Pulse Input

Analog Panel Meter Series APM Instruction Manual

PROVU PD7000 Temperature Meter Instruction Manual

ProtEX-MAX PD Explosion-Proof Pulse Input Rate/Totalizer Instruction Manual

YPP6200 Analog Input Rate/Totalizer Instruction Manual

PD6300 Pulse Input Rate/Totalizer Instruction Manual

Helios Large Display Temperature Meter

PD6000 Analog Input Process Meter Instruction Manual

ProtEX-MAX PD Explosion-Proof Process Meter Instruction Manual

Communications and Displays. SITRANS RD300 - Dual-Input Process Meter Operating Instructions 02/2014

BD300 Analog Input Process Meter Instruction Manual

Analog Panel Meter Series APM Instruction Manual

HIGH-VOLTAGE DC METER

Viatran DL Series Analog Input Process Meter Instruction Manual

YPP6300 Pulse Input Rate/Totalizer Instruction Manual

Pulse Panel Meter Series PPM Instruction Manual

DDMC Meter / Controller

ProtEX PDD6800 Series Demonstrators

SPECIFICATIONS SPECIFICATIONS. Input VDC. NEMA 4X/IP65 front VDC option. Temp SPECIFICATIONS

PD6000 Analog Input Process Meter Instruction Manual M387

PRECISION DIGITAL CORPORATION Since 1974 Dual-Line Large Display

ProtEX-MAX PD Explosion-Proof Strain Gauge, Load Cell & mv Meter Instruction Manual

ProtEX-MAX PD Explosion-Proof Analog Input Batch Controller Instruction Manual

Serial Communication Converters & Adapters Instruction Manual

PDW30 Point-to-Point Wireless Bridge Installation Guide

Multi Process Meter Series MPM Instruction Manual

Plus-X IIU / ICRU Installation Guide

Javelin D Model PD644 Instruction Manual

ProtEX-MAX PD Explosion-Proof Pulse Input Batch Controller Instruction Manual

YPP6060 Dual-Input Process Meter Instruction Manual

PD6210 / PD6310. PROVU Dual-Line 6-Digit Batch Controllers BATCH CONTROL. PRECISION DIGITAL CORPORATION SERIES

Process & Temperature Digital Panel Meter

DP6060. Dual-Input Process Meter

PD Helios Dual-Line 6-Digit Temperature Meter. Actual Size Digit

Trident and Trident X2 Digital Process and Temperature Panel Meter

YPP6060 Dual-Input Process Meter Instruction Manual

CATALOG SHORT FORM. Digital Indicators & Controllers. th ANNIVERSARY PRECISION DIGITAL CORPORATION Since 1974

PD6210 / PD6310. PROVU Dual-Line 6-Digit Batch Controllers. Batch control SERIES. Precision Digital Corporation

Instruction Manual July sitrans RD200

PD ProtEX-MAX Analog Input Feet & Inches Meter. IECEx MAX

PD765 TRIDENT. Trident Series Process & Temperature Meters.

ScanView EX Software Programming Software for PD6730X & PD6830X Modbus Scanners

ProtEX-MAX PD WM Explosion-Proof NTEP Certified Batch Controller Instruction Manual

Helios Large Display Modbus Scanner

Introduction to The PROVU &ProtEX-MAX Great New Features!

PD6200 / PD6300. PROVU Dual-Line 6-Digit Flow Rate/Totalizers SERIES. Precision Digital Corporation

dual-line 6-dIGIt process MeteR

Snooper Model PD865 Modbus Serial Input Instruction Manual

PD7000. PROVU Dual-Line 6-Digit Temperature Meter SERIES.

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

PD ProtEX-MAX Strain Gauge, Load Cell & mv Meter. Strain gauge. IECEx MAX

PD8-6200/PD ProtEX-MAX TM Dual-Line 6-Digit Flow Rate/Totalizers. IECEx. Precision Digital Corporation

CATALOG. Digital Indicators & Controllers. Simplifi ed information where and how you want it. Short Form. predig.com/videos

Temperature Meter Model Instruction Manual

Modbus Digital Display

PD ProtEX-MAX TM Explosion-Proof Process Meter. IECEx MAX

LAUREL ELECTRONICS, INC.

DIGITAL METERS Universal Analog Input Process Meter With Rate/Totalizer/Batch Control Features Instruction Manual

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications

GTWIN 1.1 CONTROL TECHNOLOGY CORPORATION. GTWIN 2.8 Quick Start. MGT Panel & GTWIN Quick Start Guide

LLC-E-BA Industrial Batch Controller v1.3

PD Helios Strain Gauge, Load Cell & mv Meter. Strain gauge. Actual Size Digit

PD765 TRIDENT. Trident Series Process & Temperature Meters.

PD Large Display Dual-Line 6-Digit Process Meter. process. Actual Size Digit

FEM-03. Opera on & Installa on Manual FLOW MONITOR. Rev. 2

PD Large Display Feet & Inches Process Meter. Feet & Inches process. Actual Size Digit

PD Large Display Dual-Line 6-Digit Process Meter. process. Actual Size Digit

DIGITAL PROCESS CONTROLLER

PROVU PD6080/PD6081 Modbus Scanner Instruction Manual

Plus-X 300. Installation and Operation Manual

PD8-6262/PD ProtEX-MAX TM Dual-Input Rate/Totalizers. flow rate/total. IECEx. Isolated ma Transmitter Power Supply

PD6262 / PD6363 SERIES. PROVU Dual-Input Rate/Totalizers. flow rate/total. Precision Digital Corporation

Process & Temperature Meter LI5X Instruction Manual

INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx

PD6262 / PD6363. PROVU Dual-Input Rate/Totalizers. flow rate/total SERIES. Precision Digital Corporation

PD6262 / PD6363. PROVU Dual-Input Rate/Totalizers. flow rate/total SERIES. Precision Digital Corporation

DPS3311 Series wall mount Programmable Process Monitor

IPM500 Series QuickStart Manual

PRECISION DIGITAL CORPORATION Since CATALOG. level temperature pressure.

DPM-100 Modbus Display Instruction Manual

ProtEX-MAX PD8-765 Explosion-Proof Process & Temperature Meter Instruction Manual

Safety. 2. Configuration - Operation 2.1 RTD Selection 2.2 Driver Test Header. 3. Diagnostics 3.1 ph Input 3.2 Temperature Input

PD6000. PROVU Dual-Line 6-Digit Process Meter. SERIES

DATA ACQUISITION Hints and Tips

LAUREL. Laureate Pulse or Analog Input Batch Controller Automatic batch control for repetitive liquid fill operations ELECTRONICS, INC.

LAUREL ELECTRONICS, INC.

DNP 3.0 Serial (RS232/RS485) and Ethernet (TCP/IP) SCADA Interface for TPSD/A36D Chargers with S2A-205T Option 21P or 57T or 57U. Setup Instructions

Transcription:

ProVu PD6200 Analog Input Rate/Totalizer MeterView Pro USB Install Thank you for your purchase of the ProVu PD6200 rate/totalizer. This quick start guide will briefly describe some of the common setup procedures for this meter. This guide includes: Installing MeterView Pro... 2 Basic Wiring for ProVu Meter... 3 Program and Scale the Input... 4 Program Relays for Automatic Reset... 6 Program 4-20 ma Analog Output... 7 Return Meter to Factory Defaults... 8 For additional information about the ProVu PD6200 rate/totalizer not covered in this quick start guide, please consult the instruction manual included on the CD or available at www.predig.com. PR VU SERIES 2016 Precision Digital Corporation. All rights reserved. Menu Button Use this button to access Programming Mode and to return to Run Mode. Note: If you think you have made a mistake while programming the meter, use this button to return the meter to Run Mode without saving. Right/F1 Button Use this button to change the selected digit while inputting a numeric value in Programming Mode. Up/F2 Button Use this button to increment the selected digit while inputting a numeric value in Programming Mode. Enter/F3 Button Use this button to access or accept a menu item while in Programming Mode. 233 South Street Hopkinton MA 01748-2208 USA Tel. (508) 655-7300 www.predig.com

Installing MeterView Pro The meter can be programmed using MeterView Pro. This software can be installed on any Microsoft Windows (2000/XP/Vista/7/8/10) computer by connecting to the meter s onboard USB. The meter is powered by the USB connection, so there is no need to wire anything prior to programming the meter. Connect the provided USB cable to the meter and the computer as shown. The computer will automatically install the driver software it needs to talk to the meter. Note: Only one meter may be connected at a time. Attaching multiple meters will cause a conflict with the meter software. Once the driver is installed, an AutoPlay dialog should appear for the drive MAINSTAL. Click Open folder to view files. If the computer does not display an AutoPlay dialog for the drive MAINSTAL, you should open My Computer and double-click on the drive labeled MAINSTAL. Double-click on the file named MAStart. If there is an update available, click the Update button to install the new version. Otherwise, click Configure to begin programming your meter. The program will open a few windows and install two programs on your computer. Simply follow the onscreen instructions until you see one of the dialogs in step 4. Note: If you receive a User Account Control warning, click Yes. Note: When you update your MeterView Pro software, you will be asked if you want to update the setup files located on the meter itself. This way, you will always have the most current version on the meter for future installs. 2 Note: The remainder of this guide will explain how to configure your meter using either the MeterView Pro software or the configuration menus in the meter itself. It is only necessary to perform one of these operations in order to configure the meter for a desired setting.

Basic Wiring for ProVu Meter The connectors label, affixed to the top of the meter, shows the location of all available connectors. Connect your wires to the provided connectors and plug into the meter as indicated. 4-20 ma Input Wiring Wiring for a 4-20 ma input using either an external power supply or self powered transmitter. 5 6 - + External Power Supply 2-Wire 4-20 ma Transmitter 5 6 - + 2-Wire 4-20 ma Self-Powered Transmitter Wiring for a 4-20 ma input using internal power supply. 5 6 5 6 4-20 ma Output Wiring 1 Active (Self-Powered) RELAY1 3 2 1 24 V MA OUT I- I+ R 3 2 1 4-20 ma Input Remote Display, Chart Recorder, Etc. Passive (Externally Powered) RELAY1 3 2 1 4-20 ma Input Meter Relay Connections 2 RELAY4 RELAY3 6 5 4 3 2 1 NO NC C NO NC C + - 24 V MA OUT I- I+ R 3 2 1 - + 12-35 VDC Power Supply RELAY2 RELAY1 6 5 4 3 2 1 NO NC C NO NC C 2-Wire 4-20 ma Transmitter 0-10 V Input Wiring 3-Wire 4-20 ma Transmitter Signal C R C R AC and DC Loads Protection Power Connection Low Voltage DC Loads Protection 5 6 5 6 POWER - + Voltage Signal 3-Wire Voltage Transducer Signal F4 Digital Input Connection 5 6 AC or DC POWER Required External Fuse: 5 A max, 250 V Slow Blow For additional wiring diagrams, consult the PD6200 instruction manual located on the included CD or available online at www.predig.com. 1 ProVu models with 4-20 ma output option (PD6200-XX3/5/7) 2 ProVu models with relay option (PD6200-XX2/4/5/7) 3

Program and Scale the Input Program the ProVu meter to accept an analog input and display a value. When the meter is receiving the low end of the input, it will display the low end of the display range; when receiving the high end of the input, it will display the high end of the display range. The input values (InP 1 & InP 2) can be changed if needed, but the default values are sufficient for most flowmeters. For example: If the meter were setup to accept a 4-20 ma input and display the flow of a pipe whose rate of flow is between 0 and 100 gal/s, the transmitter would send a 4 ma signal when there is zero flow and a 20 ma signal when there is maximum flow. The meter should be programmed to interpret these inputs on a display range of 0-100, so that at 4 ma the meter will display 0 and at 20 ma the meter will display 100. ======== MeterView Pro Software ======== On the Setup tab, under Input Type, select the desired input. 3 Under Scale Values, enter the desired low and high display values in the Display column. 5 Press to select either nma (milliamps) or volt the total (Totalizer) menu (volts) and press to accept. and press to accept yes (enable). 5 6 Press to display the dec pt (Decimal Point) menu and press 4 On the Programming tab, select the desired decimal point location for Rate, Total and Grand Total. 4 Under Totalizer Options, select the appropriate time base for your rate measurement (such as gallons per second). 6 Select whether the Click the Send total should reset automatically Meter Data button or manually. If Auto is selected, to send your programmed settings to the use the Time Delay field below to enter the meter. amount of time (in seconds) until it resets. ======== Meter Configuration Menus ======== Press to enter Programming Mode, press the Input (Input) menu. to access the SEtup (Setup) menu. to access. Press to select the parameter for which you want to assign the decimal point and press.

7 desired decimal point location is displayed and press to accept. Continue to assign decimal points to subsequent parameters. 9 Press to access the ProG (Program) menu. InCAL (Input Calibration). the SCALE (Scale) menu. 11 12 Press three Press three times, until dis 1 (Low Display Value) is displayed. which digit times, until dis 2 (High Display Value) is displayed. is selected and to increment the digit. selected and to increment the digit. Press Press when done. and saved will display momentarily. 13 14 Press to select t tb (Total Time Base). Note: The time base for rate can be in units per second, per minute, per hour, or per day. the appropriate time base and press to accept. 15 16 Press until an t CF (Total Conversion Factor). appropriate decimal point location for Note: The conversion factor for total calculation is the conversion factor is displayed and press the number by which the rate will be multiplied before being added to the total. to accept. 17 18 selected and to the t rst (Total Reset) menu. increment the digit. Press when done. Press to select either nman (Manual) or Note: The default conversion factor is 1.0, which Auto (Automatic) and press to accept. means that the rate will be multiplied by 1.0 Press to return the meter to Run Mode. before being added to the total. Note: If Auto (Automatic) is chosen, an additional menu will be displayed: t dly (Time Delay), which is the delay time before the total is reset. A relay assigned to total will reset the total Note: Time base, conversion factor and reset may also be set for the grand total. These menus are Gt tb, Gt CF, and Gt rst and are accessible directly following the total menus. value once its set point has been reached. 8 10 5

Program Relays for Automatic Reset Program the ProVu meter to turn on the relays at programmable set points and turn off the relays at reset points. Note: Only relays assigned to rate (Rate) will require a reset point value; total and grand total only require set points. If the set point is higher than the reset point, the relay will be a high alarm. If the set point is lower than the reset point, the relay will be a low alarm. ======== MeterView Pro Software ======== 1 2 On the Relays tab, in Select Auto from the the desired relay section, assign the relay Note: See PD6200 Action drop down list. to a desired parameter Instruction Manual for details on additional relay actions. (i.e. rate, total, grand total, or Modbus ). Enter the set and reset point values in the provided fields. ======== Meter Configuration Menus ======== Press to Press until enter Programming the relay (Relay) Mode, press to menu is displayed access the SEtup (Setup) menu. and then press to access. the ASSiGn (Relay relay number you Assignment) menu. wish to assign a parameter is displayed (ASiGn 1-8) and then press to access. 5 6 appropriate parameter (i.e. rate, total or grand total) is displayed and then press to accept. Continue to assign additional relays to subsequent parameters. 6 Click the Send Meter Data button to send your programmed settings to the meter. appropriate relay number is displayed (rly 1-8) and then press to access.

7 Press to accept the Act (Relay Action) Auto (Automatic menu. Reset). 9 10 the set (Relay Set Point) menu. selected and to increment the digit. Press 11 12 the rst (Relay Reset Point) menu. Note: The reset point menu will only be displayed if the relay has been assigned to rate. Total and grand total relays do not have reset points. when done. selected and to increment the selected digit. Press when done to accept the new set point value. Press to return to Run Mode. Note: If you need to program more relays, simply repeat steps 6-12 for each additional relay. Up to eight (8) relays can be installed on the ProVu meter. Consult the ProVu PD6200 Instruction Manual for information on additional relay action types. Program 4-20 ma Analog Output Program the ProVu meter to output an analog signal based on its display value. This signal is commonly output to a PLC or chart recorder. Note: By default, the analog output will transmit the rate value as it is displayed on the meter. It is possible to output the total, grand total or some other value. Please refer to Program Analog Output Source on the following page for information on changing the output parameter. ======== MeterView Pro Software ======== On the Setup tab, under Analog Out Scale, enter your desired display values in the provided fields. Click the Send Meter Data button to send your programmed settings to the meter. ======== Meter Configuration Menus ======== 8 Press to enter Press until Programming Mode the aout (Analog and press to Output) menu is access the SEtup (Setup) menu. displayed and then press to access. 7

3 4 the dis 1 (Display 1) menu. This is the display value at which the low range of the output will be transmitted. 5 the Out 1 (Output 1) menu. This is the output signal which represents dis 1. 7 Press and hold until the meter flashes reset (Reset). Immediately press 8 selected and to increment the digit. Press accept the new display value. 6 The default value of 04.000 (4 ma) should be sufficient for most applications. Press 8 to accept. the dis 2 (Display 2) menu. This is the display value at which the high range of the output will be transmitted. selected and to increment the selected digit. Press when done to accept the new display value. 9 10 the Out 2 (Output 2) menu. Press to accept the default value. when done to Return Meter to Factory Defaults If a mistake has been made while programming the meter and it is unclear where the error occurred, the best option may be to perform a factory reset of the meter and begin again. ======== MeterView Pro Software ======== On the Advanced Features In the confirmation window that appears, click tab, in the bottom left-hand corner, click the Reset Meter Factory Defaults button. OK. The meter will reset to factory defaults. ======== Meter Configuration Menus ======== Press and hold for five seconds to enter the Advanced Features menu. to reset. diag (Diagnostics) menu is displayed. The meter will flash all of the LED segments and then display ProcES (Process). LIM6200QS_D - 06/16