Citect for Windows Driver Specification Extract Hitachi Driver

Similar documents
Citect for Windows Driver Specification Klöckner Moeller PS316/PS416 and PS4200 Drivers

Citect for Windows Driver Specification Extract

Citect for Windows Driver Specification Extract FIPNT Driver

Citect for Windows, Version 5.xx MICRXNET Driver, User Information

Citect for Windows Driver Specification

Station 2. Inverter. PU connector (Note1)

Modbus TCP Client Ethernet Modbus TCP Client Modbus TCP Server Ethernet Modbus TCP Server 5

Hitachi H/EH/EHV Series

Device/PLC Connection Manuals

Device/PLC Connection Manuals

Device/PLC Connection Manuals

Power Mate Series Driver

Citect for Windows Driver Specification Modnet Driver

Citect for Windows, Version 5.xx MXCOMP driver, User information and design

Citect for Windows Driver Specification Extract

SIMATIC S5 CPU Direct Driver

Device/PLC Connection Manuals

Device/PLC Connection Manuals

XGK Series CPU Direct Driver

Melsec-Q Link(SIO) Driver

GP-PRO/PBIII for Windows Device/PLC CONNECTION MANUAL. Keyence Corporation PLC

Device/PLC Connection Manuals

OMRON Corporation PLC SYSMAC CJ1M Series Connection

Flexi Soft Driver SICK AG

Mitsubishi QSeries QnA Serial Communication

1.1 Siemens S5/S7 Series

Table of Contents... 1 Operation Mode... 2 Connecting System Menu... 14

SIMATIC S5 CPU Direct Driver

DF1 Driver. Rockwell Automation, Inc.

Device/PLC Connection Manuals

Citect for Windows Driver Specification GETCP Driver

Pro-face Memory Link(SIO) Driver

FP7 Connection Manual

OMRON Corporation PLC SYSMAC C Series Connection

Setting the DCM Switches

SAPHIR SIO Driver. Siemens Building Technologies

OMRON Corporation PLC SYSMAC C Series Connection

User Manual Connection to Mitsubishi MelsecA

v12 (applies to HitOPC version and later)

INDEX. Document Name : User Manual for SC10EJ Serial to Ethernet Converter

SIMATIC S5 3964(R) Driver

Connection Cable Communication 232C Port Method GP 1762-L24BWA. the CPU Unit RS-232C

Device/PLC Connection Manuals

PC CONNECTION Programmable Terminal Operation Manual

Model XS1000 TCP/IP to RS232/422/485 Device Server User s Manual

Device/PLC Connection Manuals

Wonderware Operations Integration Supervisory Mitsubishi Electric MELSEC Server (G-1.2 Series)

Pass-Through Function

D0 DCM Module Setup Direct

MDNET-5W. Wi-Fi/Ethernet/RS485 Converter Operation Manual. Version /03/24

PC CONNECTION Programmable Terminal OPERATION MANUAL

Mitsubishi Serial Driver Help Kepware Technologies

A GUIDE TO RS-232 COMMUNICATION WITH FX PLCS

Connection Guide (RS-232C)

VIGOR PROGRAMMABLE LOGICAL CONTROLLERS VIGOR ELECTRIC CORP.

NordField Electronics

APPLICATION MANUAL for NETWORK

Mitsubishi FX3 Driver Configuration Manual

TABLE OF CONTENTS. Communication Functions

Fuji Flex Driver Help Kepware Technologies

J1939/Modbus Slave Gateway FAQ

CJ Series General-purpose Serial Connection Guide (RS-232C) OMRON Corporation Displacement Sensor (ZW-7000 series)

Chapter 5: Communications 5 1 SR55 Communications Overview 5 2

Yaskawa Electric MP900 Series Driver

Device/PLC Connection Manuals

SIEMENS S7-200 PPI Direct

Connection Guide (RS-232C) OMRON Corporation

Industrial Serial Device Server

MCF. User's Manual. Air Flowmeter NPT Model. for Communication Functions. No. CP-SP-1301E

A Series CPU Direct Driver

Analog Devices Driver Kepware, Inc.

SAFETY PRECAUTIONS. Throughout this manual we use the following two illustrations to make you aware of safety considerations:

Serial Connection of HC900 Hybrid Controller to 900CS Control Station

PLC Driver Manual 2800 & 2900

Eaton Corporation Cutler-Hammer Business Unit 811 Green Crest Drive Columbus, OH PanelMate Mitsubishi Communication Driver Manual

COMMUNICATION INTERFACE (RS-232C/RS-485)

CJ Series General-purpose Serial Connection Guide OMRON Corporation V500-R2 Series Fixed Laser-Type Barcode Reader

Fuji Electric Corporation. MICREX-F Series SIO

Melsec-Q CPU (SIO) Driver

Lufkin Modbus Serial Driver Help Kepware Technologies

Webinar Organizers. Ryan Shea. Bruce McDuffee. Joe Ryan. Webinar Moderator. Applications Specialist. Product Manager. Precision Digital Corporation

Connection Guide (RS-232C) OMRON Corporation

Cutler-Hammer D50/300 Driver PTC Inc. All Rights Reserved.

XGT/XGB Series Cnet V1.5

Industrial-Automation System HIMatrix. MODBUS Master/Slave. Manual

Communication Setting Sample

Omron Toolbus Driver Help Kepware Technologies

Hi5 Robot Driver. Hyundai Heavy Industries

Device/PLC Connection Manuals

ROC Plus Ethernet Driver

RS232/RS485/RS422 to TCP/IP Converter ITEM NO.: RS007

ALLEN-BRADLEY MICROLOGIX / SLC500 & EASON 2000 FAMILY

ECOV-110 User s Manual

Chaper 1: E10+ PLCs Host-Link Command Format

Schneider Electric TSX07/37/57 Series Unitelway Driver

Fuji Flex Driver PTC Inc. All Rights Reserved.

F 2 MC FAMILY MICROCONTROLLER EMULATOR

Mitsubishi FX Net Driver PTC Inc. All Rights Reserved.

Ladder Communication Modules

Communication. Outline of Communication. Merits

Transcription:

Citect for Windows Driver Specification Extract Hitachi Driver Author: Date Action Rupert Reeve 13/11/95 Wrote it Bill Rayer 13/12/95 Modifications Masoud Varjavandi 16/1/96 Modified Huang Weiguang 15/12/2000 Modified and Add TCP/IP connection

Contents 1. TARGET DEVICE(S) AND PROTOCOL 4 1.1 Introduction 4 1.2 Device Manufacturer 4 1.3 Device Definition 4 1.4 Communications Method 4 1.5 Communications/Hardware Configuration 4 1.5.1 Serial connection 4 1.5.2 TcpIp connection 7 1.6 Special Requirements 8 1.7 Contacts 8 2. USER INTERFACE 9 2.1 Introduction 9 2.2 Driver Name 9 2.3 Communication forms 9 2.3.1 Serial Connection Forms 9 2.3.2 TcpIp Connection Forms 10 2.4 Pulldown lists Help 12 2.5 IO Device Variable Types 12 2.6 PROTDIR.DBF 13 2.7 Parameters and INI options 13 2.7.1 Standard Parameters 13 2.7.2 Driver Specific Parameters 13 2.8 Driver Specific Errors 14 2.9 Driver Error Help 14 2.10 Debug Messages 14 2.11 Stats Special Counters 14 2.12 Hints and Tips 14 hitachi_extract.doc 2

3. REFERENCES 15 3.1 References 15 hitachi_extract.doc 3

1. Target Device(s) and Protocol 1.1 Introduction This section defines the types of I/O Devices that are targeted by this driver. 1.2 Device Manufacturer HITACHI 1.3 Device Definition Hitachi programmable controllers: H200 series, H700 series 1.4 Communications Method Serial connection. Either direct to the programming port or via a COMM-2H module. Tcp/Ip connection. Via a LAN-ETH module. 1.5 Communications/Hardware Configuration 1.5.1 Serial connection The programming port uses RS232 into a 15 pin connection. The COMM -2H module allows for RS232 or RS422 connection. Using RS422 connection allows up to 32 multidropped HITACHI controllers. 1.5.1.1 Wiring Diagrams Refer to H - Series, Intelligent serial port module manual. hitachi_extract.doc 4

1.5.1.1.1 RS232 pinouts When COMM module is directly connected to a personal computer (B16-EX). COMM-2H RS-232C signal name SD 2 RD 3 RS 4 CS 5 RV1 (ER) (Note 2) 6 RV2 (DR) 7 PHL 8 SG 9 Pin No. Note 1 The direction of each signal is indicated by arrows. Notes: 1) It can be left unconnected, however, it is used when connection between the CPU and host is established, to make connection cable the same. Pin No. 1 FG 2 SD 3 RD 4 RS 5 CS 6 DR 7 SG 8 CD 14 PV12 16 NV12 20 ER B16-EX Signal name 2) This signal may be connected to the DR signal at host. 1.5.1.1.2 RS422 pinouts When COMM-2Hs are connected through RS-422 after connecting the first COMM module to host through RS-232C. Host RS-232C COMM module (1st unit) COMM module (2nd unit) COMM module (3rd unit) TXDP TXDN TYDG RXDP RXDN RXDG TXDP TXDN TYDG RXDP RXDN RXDG TXDP TXDN TYDG RXDP RXDN RXDG To the next stage hitachi_extract.doc 5

The directions of each signal are indicated by arrows. When COMM module is connected to host through RS-422. COMM module (1st unit) COMM module (2nd unit) Host SD(A) SD(B) FG RD(A) RD(B) FG TXDP TXDN TYDG RXDP RXDN RXDG TXDP TXDN TYDG RXDP RXDN RXDG To the next stage The directions of each signal are indicated by arrows. 1.5.1.2 I/O Device Settings 1.5.1.2.1 Station Numbers Set any of the station numbers from 0 to 31. NOTE: The station numbers 0 to 31 are used. If any number greater than 31 is set, the staton with that number is not set, but station 31 is set. 1.5.1.2.2 Communication Settings Swith No. Items Switch Settings 1 Bit Length ON: 8 OFF: 7 300 600 1200 2400 4800 9600 19.2K 19.2K 2 Transmission speed (BPS) OFF ON OFF ON OFF ON OFF ON 3 OFF OFF ON ON OFF OFF ON ON 4 OFF OFF OFF OFF ON ON ON ON hitachi_extract.doc 6

5 Parity present/ none 6 Parity even/odd 7 Stop bit length 8 Sum check present/none ON: Present OFF: None ON: Even OFF: Odd ON: 2 OFF: 1 ON: Present OFF: None 1.5.1.3 Software Setup No special software is required in the programmable controller. 1.5.2 TcpIp connection 1.5.2.1 Wiring Diagrams Use commom Ethernet wiring. 1.5.2.2 I/O Device Settings IP address setting You can not set IP address in normal mode, Please change operation mode by MODE switch. The functions related with IP address setting is shown in the following: N0 Functions Mode setting switch Description 1 IP Address information setting IP address is set newly.set the information of IP address etc. in IP address setting area. Then write plc program an run to finish the setting. 2 Reference of IP address setting IP address setting is read. IP address informationis read to IP address eading area. 3 IP address default setting IP address returns to default value. IP address 192.0.0.1 IP address of other stationto test 192.0.0.255 Task port 1 Task port 2 3004.1(TCP/IP) 3005.1(TCP/IP) Task port timeout observation 0(no observation) Note: When change a setting of MODE setting switch, press RESET switch or apply power again. hitachi_extract.doc 7

1.5.2.3 SoftWare Setup No special software is required. 1.6 Special Requirements NONE. 1.7 Contacts Douglas Waterford, Manager PLC Engineering services, NHP Ph 748 3444, Fax 648 4353 Brendan O Driscoll and Paul Stride from NHP. hitachi_extract.doc 8

2. User Interface 2.1 Introduction This section defines how the user will see the driver. This relates directly to how the Citect forms need to be filled out and any special INI options. For the kernel, the debug trace messages and the Stats.Special counters are documented. 2.2 Driver Name HITACHI 2.3 Communication forms 2.3.1 Serial Connection Forms 2.3.1.1 Boards Form Board Type If using a serial board or COM port, you should enter COMx. Address If using a serial board or COM port, you should enter 0. I/O Port Leave this field blank. Interrupt Leave this field blank. Special Options Leave this field blank. 2.3.1.2 Ports Form Baud Rate This value should match the setting of the PLC - 9600 is recommended. Data Bits 7 top Bits hitachi_extract.doc 9

1 Parity EVEN_P Special Opt When using the H-200 a special option of -H should be used in this field to enable hardware hand shaking. 2.3.1.2 IO Devices Form protocol HITCAHI Address The address format is as follows LLUUMMPP[ :n][ /tm Where LL UU MM PP n m is the Lump address Loop No in two hexadecimal digits is the Unit No in two hexadecimal digits is the Module No in two hexadecimal digits is the Port No in two hexadecimal digits is optional office number (ie station address) in decimal. is a single optional hex digit to set the TM Response byte in the protocol. If the optional office number is included then the driver will include this information in the protocol request and thus support multi-dropped connection to multiple devices via RS422. The /Tm is 0 to F and the time is 0 to 160 ms, the response TM value is 10ms, the default value is 0 for a maximum communication speed. 2.3.2 TcpIp Connection Forms 2.3.2.1 Boards Form Board type TCPIP. Address This should be 0. I/O Port hitachi_extract.doc 10

Leave this field blank. Interrupt Leave this field blank. Special Options Leave this field blank 2.3.2.2 Ports Form Baud Rate Leave this field blank Data Bits Leave this field blank top Bits Leave this field blank Parity Leave this field blank Special Opt User must enter the destination IP address of Ethernet module. Use the following format: -Ia -Pn -T where: a Is the destination IP address in standard Internet dot format. (For example 192.9.2.60) n 3005. The destination Port number. For using task code protocol, this can only be 3004 or -T Forces the driver to use TCP (the default), rather than UDP (-U). 2.3.2.3 IO Devices Form protocol HITCAHI Address The address format is as follows LLUUMMPP hitachi_extract.doc 11

Where LL UU MM PP is the Lump address Loop No in two hexadecimal digits is the Unit No in two hexadecimal digits is the Module No in two hexadecimal digits is the Port No in two hexadecimal digits 2.4 Pulldown lists Help The following entries should be included in the Citect Help.DBF spec file. TYPE DATA FILTER PROTOCOL HITACHI 2.5 IO Device Variable Types IO Device Type Citect data type Citect data type External Input X a,b DIGITAL External Output Y a,b DIGITAL CPU Link L h DIGITAL Internal Input M h DIGITAL Internal Output R h DIGITAL External Input External Output CPU Link Internal Input Internal Output WX a,c WY a,c WL h WM h WR h Description/Special Usage/Limitations/ Valid Ranges Where: A B C H First three digits of the I/O Bit location or I/O Word location in hex. The last two digits of the I/O Bit location in decimal (0-99). The last digit of the I/O Word location in decimal. Internal locations in hexadecimal.hex values must be hitachi_extract.doc 12

preceded by a 0 (zero). 2.6 PROTDIR.DBF TAG FILE BIT_BLOCK MAX_LENGTH OPTIONS HITACHI HITACHI 240 240 0x214f 2.7 Parameters and INI options 2.7.1 Standard Parameters Block 40 Delay 0 MaxPending 2 Polltime 0 Timeout 1000 Retry 1 WatchTime 30 2.7.2 Driver Specific Parameters 2.7.2.1 Serial connection parameters Parameter name Default value Allawable value Description StartUpDelay 1000 When init channel, After send NAK FF, make a delay, in ms. IgnoreWarning 1 0,1 When 1, response with warning will be considered as normal, driver will accept the response, When 0, response with warning will be considered as error, driver will not accept the response. neots 20 2-50 After receive neots EOT, the unit will be break NewTaskCode 0 0,1 When 1, use task code A0- A5 instead of 40-45 hitachi_extract.doc 13

ReconnectTime 120 30-200 Unit break time(second) 2.7.2.2 TcpIp connection parameters Parameter name Default value Allawable value Description ChecksPerTimeOut 4 It decides how many times to check if a request is timeout IgnoreWarning 1 0,1 When 1, response with warning will be considered as normal, driver will accept the response, When 0, response with warning will be considered as error, driver will not accept the response. NewTaskCode 0 0,1 When 1, use task code A0- A5 instead of 40-45 MaxOutStanding 1 1-255 How many requsts can take place in the same time 2.8 Driver Specific Errors 2.9 Driver Error Help 2.10 Debug Messages 2.11 Stats Special Counters 2.12 Hints and Tips hitachi_extract.doc 14

3. References 3.1 References HITCAHI PROGRAMMABLE CONTROLLER H - SERIES, Intelligent Serial Port Module, I n- struction Manual. hitachi_extract.doc 15