This data sheet is only valid in association with the IL SYS INST UM E user manual.

Similar documents
IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

IB IL AO 2/SF... Inline terminal with two analog outputs. AUTOMATION Data sheet 6655_en_06. 1 Description

PHOENIX CONTACT - 11/2008

PHOENIX CONTACT - 10/2006

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

IB IL 24 DI 16 IB IL 24 DI 16-PAC

AXL E IOL AO1 U M12 R

IBS IL 24 BK RB-T-2MBD

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

FLM DI 8 M12. Function. Fieldline Modular Device With Eight Digital Inputs. Data Sheet

GFK-2415A March Type of sensor connection

NI REM Remote I/O Overview DATASHEET. Analog Output Module for Remote I/O

IB IL 24/48 DOR 2/W-XC-PAC

IB IL 120 DI 1. Function. INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area. Data Sheet 5764B

Rexroth Inline terminal with one analog output

IBS IL 24 RB-LK-2MBD:

8 24 V DC, 8 24 V DC,

IB IL IB IL PAC

This data sheet is only valid in association with the IL SYS INST UM E user manual.

ILC 200 IB ILC 200 IB-PAC

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

MINI MCR-SL-UI-2I(-SP)(-NC)

TRIO-DIODE/12-24DC/2X10/1X20

AXL BK PN (-ME) Axioline bus coupler for PROFINET IO. Data sheet. 1 Description

MINI MCR-SL-PT100-UI-200

ILB BT ADIO 2/2/16/16

MINI-PS AC/10-15DC/8

ILB DN 24 DI16 DO16. Inline Block IO Module for DeviceNet With 16 Digital Inputs and 16 Digital Outputs. AUTOMATIONWORX Data Sheet 6885_en_05

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

FL MC 2000E (SM40) LC

PHOENIX CONTACT - 07/2006

AXL F AO4 1H. Axioline F analog output module, 4 outputs. Data sheet. 1 Description

IBS PCI SC/I-T. Controller Board for PC Systems With PCI Bus. Data Sheet 6039B

MINI MCR-SL-PT100-UI(-SP)(-NC)

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

AI561 Analog Input Module

Temperature modules. 8 inputs for connection of thermocouple sensors S20-AI-8-UTH

AXL E PB DIO16 M12 6P

PSI-MODEM-SHDSL/SERIAL

PHOENIX CONTACT Features

NI REM Remote I/O Overview DATASHEET. Digital Output Module for Remote I/O

IBS ST (ZF) 24 BK LB-T

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

TM3AI4 module TM3-4 analog inputs

NI REM Remote I/O Overview DATASHEET. Digital Input Module for Remote I/O

FL SWITCH SFNB. Five- and Eight-Port Standard Function Ethernet Switch with Narrow Housing. AUTOMATION Data Sheet 2642_en_H.

RAD-DAIO6-IFS. I/O extension module, 1 analog input/output, 2 digital wide-range inputs/outputs. INTERFACE Data sheet.

MINI MCR-SL-UI-2I-NC. Extract from the online catalog. Order No.:

DI572 Digital Input Module

AO561 Analog Output Module

PHOENIX CONTACT - 10/2009

AI531 Analog Input Module

DI561 Digital Input Module

MINI MCR-SL-UI-REL(-SP)

NI REM Remote I/O Overview DATASHEET. Bus Coupler for Remote I/O

IB IL EX-IS TEMP 4 RTD/TC-PAC

QUINT-BUFFER/24DC/24DC/40

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

PB IL 24 BK DIO 16/16

AXL E EC DI16 M12 6P. Axioline E EtherCAT device, plastic housing, 16 inputs, 24 V DC, M12 fast connection technology. Data sheet.

PHOENIX CONTACT - 05/2007

QUINT-PS-3x AC/24DC/10

Installation Instructions Temperature transmitter TAA /00 06/2011

DC562, digital input/output module,

DC561, digital input/output module,

STEP-PS/1AC/24DC/1.75

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description

IB IL RS 232 IB IL RS 232-PAC

FL SWITCH SFN(T) 16-Port Standard Function Ethernet Switches for Normal and Extreme Environments. AUTOMATION Data Sheet 2806_en_C

TM3TI4 module TM3-4 inputs temperature

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

AO523 Analog Input Module

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

TU531, TU532 Terminal Unit

TM3TI4 module TM3-4 inputs temperature

VL BPC MINI. A configurable industrial computer platform Intel Atom Z510PT CMAT IPC Module Option [I28] AUTOMATION Data Sheet 2930_en_A.

PI-EX-ME-2NAM/COC-24VDC

IL CAN BK-TC-PAC. Extract from the online catalog. Order No.:

VersaPoint I/O Module

DX561 Digital Input/Output Module

AXL E PN DI8 DO8 M12 6P

MINI MCR-SL-CVS NC

Valueline Industrial PC

PHOENIX CONTACT - 12/2007

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage. Input current. Encoder supply. Output current

General information. Display. Supply voltage. Input current

TM3TM3 module TM3-2 temperature inputs and 1 analog output

Extract from the online catalog

VL BPC MINI. A configurable industrial computer platform. Data sheet 2930_en_F. 1 Description. 2 Features

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

TF501, TF521 Terminal Bases

General information. Display. Supply voltage. Input current

IBS ST 24 BK-T INTERBUS-S. Data Sheet. Bus Terminal Module. Product Description

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

General information. Display. Supply voltage. Input current. Encoder supply. Output current

VersaMax IP Input Module

Transcription:

Inline analog input terminal, 4 inputs for connecting voltage signals Data sheet 8081_en_01_C01 PHOENIX CONTACT 2015-04-14 1 Description The terminal is designed for use within an Inline station. It is used to acquire analog voltage signals. Features 4 analog, bipolar, differential input channels for connecting voltage signals Connection of sensors in 2-wire technology Voltage ranges: 0 V... 10 V, -10 V... +10 V Mean-value generation of the inputs Process data update of all channels in 250 µs Diagnostic and status indicators This data sheet is only valid in association with the IL SYS INST UM E user manual. Make sure you always use the latest documentation. It can be downloaded from the product at www.phoenixcontact.net/catalog.

2 Table of contents 1 Description... 1 2 Table of contents... 2 3 Ordering data... 3 4 Technical data... 4 5 Tolerance data... 6 6 Internal circuit diagram... 7 7 Terminal point assignment... 8 8 Connection notes... 8 9 Installation instructions... 8 10 Connection examples... 8 11 Electrical isolation... 9 12 Local status and diagnostic indicators... 9 13 Process data... 9 13.1 OUT process data... 9 13.2 IN process data... 10 13.3 Read firmware version... 10 14 Measured value representation in the different formats... 11 14.1 IB IL format... 11 14.2 S7-compatible format... 11 8081_en_01_C01 PHOENIX CONTACT 2

3 Ordering data Description Type Order No. Pcs. / Pkt. Inline analog input terminal, complete with accessories (connector and labeling field), inputs: 0-10 V, ±10 V, 2-wire connection method IB IL AI 4/U-PAC 2700459 1 Accessories Type Order No. Pcs. / Pkt. Shield connection clamp, for shield on busbars, contact resistance < 1 mohm (Assembly) Shield connection clamp, for shield on busbars, contact resistance < 1 mohm (Assembly) Shield connection clamp, for shield on busbars, contact resistance < 1 mohm (Assembly) Shield connection clamp, for shield on busbars, contact resistance < 1 mohm (Assembly) SK 8 3025163 10 SK 14 3025176 10 SK 20 3025189 10 SK 35 3026463 10 Support for busbars (Assembly) AB-SK 3025341 10 Support, Length: 95.5 mm, Width: 6.2 mm, Color: gray (Assembly) AB-SK 65 3026489 10 Support, Length: 10 mm, Width: 56 mm, Height: 20 mm, Color: silver AB-SK/E 3026476 10 (Assembly) PEN conductor busbar, 3mm x 10 mm, length: 1000 mm (Assembly) NLS-CU 3/10 SN 1000MM 0402174 10 Power terminal block, Connection method Screw connection, Load current AK 4 0404017 50 : 41 A, Cross section: 0.5 mm² - 6 mm², Width: 7 mm, Color: silver Power terminal block, Connection method Screw connection, Load current : 41 A, Cross section: 0.5 mm² - 6 mm², Width: 7 mm, Color: green-yellow Power terminal block, Connection method Screw connection, Load current : 41 A, Cross section: 0.5 mm² - 6 mm², Width: 7 mm, Color: black AKG 4 GNYE 0421029 50 AKG 4 BK 0421032 50 Documentation Type Order No. Pcs. / Pkt. User manual, English, Automation terminals of the Inline product range IL SYS INST UM E - - Data sheet, English, INTERBUS addressing DB GB IBS SYS ADDRESS - - 8081_en_01_C01 PHOENIX CONTACT 3

4 Technical data Dimensions (nominal sizes in mm) 140,5 119,8 71,5 Width Height Depth Note on dimensions 12.2 mm 119.8 mm 71.5 mm Housing dimensions General data Color Green Weight 66 g (With connector) Ambient temperature (operation) -25 C... 55 C Ambient temperature (storage/transport) -25 C... 85 C Permissible humidity (operation) 10 %... 95 % (according to DIN EN 61131-2) Permissible humidity (storage/transport) 10 %... 95 % (according to DIN EN 61131-2) Air pressure (operation) 70 kpa... 106 kpa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kpa... 106 kpa (up to 3000 m above sea level) Degree of protection IP20 Protection class III, IEC 61140, EN 61140, VDE 0140-1 Connection data Inline connectors Connection method Spring-cage connection Conductor cross section, solid 0.08 mm²... 1.5 mm² Conductor cross section, stranded 0.08 mm²... 1.5 mm² Conductor cross section [AWG] 28... 16 Interface Inline local bus Connection method Transmission speed Transmission physics Inline data jumper 500 kbit/s Copper Inline potential routing / Power consumption Communications power U L Current consumption from U L I/O supply voltage U ANA Current consumption from U ANA Power consumption 7.5 V DC (via voltage jumper) Typ. 55 ma 24 V DC Typ. 30 ma Typ. 0.94 W (total) 8081_en_01_C01 PHOENIX CONTACT 4

Analog inputs Number of inputs 4 (differential inputs, voltage) Connection method 2-wire Resolution A/D 12 bit A/D conversion time max. 6.5 µs Measured value representation 12 bits (11 bits + sign bit) Data formats IB IL, S7-compatible Process data update Typ. 250 µs (all channels) Filtering None or mean-value generation over 4, 16, or 32 measured values Overload protection ±30 V DC, maximum Voltage input signal 0 V... 10 V (Default), -10 V... 10 V Input resistance of voltage input Typ. 324 kω Limit frequency (3 db) 300 Hz Open circuit response Goes to 0 V Common mode voltage range signal - ground max. 50 V Programming Data ID code (hex) 7F ID code (dec.) 127 Length code (hex) 04 Length code (dec.) 04 Process data channel 64 Bit Input address area 8 Byte Output address area 8 Byte Parameter channel (PCP) 0 Byte Register length (bus) 64 Bit PROFIBUS telegram data Required parameter data Need for configuration data 10 Byte 5 Byte Error messages to the higher level control or computer system Failure of the internal I/O supply I/O error message sent to the bus coupler I/O supply failure Message in the diagnostic code (in the IB IL format) Overrrange or underrange Message in the diagnostic code (in the IB IL format) Configuration invalid Message in the diagnostic code (in the IB IL format) Electrical isolation/isolation of the voltage areas 5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC, 50 Hz, 1 min 5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC, 50 Hz, 1 min 7.5 V supply (bus logic), 24 V supply U ANA / I/O 500 V AC, 50 Hz, 1 min 7.5 V supply (bus logic), 24 V supply U ANA /functional earth ground 500 V AC, 50 Hz, 1 min I/O / functional earth ground 500 V, 50 Hz, 1 s Conformance with EMC Directive 2004/108/EC Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Electromagnetic fields EN 61000-4-3/IEC 61000-4-3 Fast transients (burst) EN 61000-4-4/IEC 61000-4-4 Transient surge voltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B; 6 kv contact discharge, 8 kv air discharge Criterion A; Field intensity: 10 V/m Criterion B, 2 kv Criterion B; supply lines DC: ±1 kv/±1 kv (symmetrical/asymmetrical); shielded I/O cables: ±1 kv 8081_en_01_C01 PHOENIX CONTACT 5

Conformance with EMC Directive 2004/108/EC Conducted interference EN 61000-4-6/IEC 61000-4-6 Noise emission test according to EN 61000-6-3 Radio interference properties EN 55022 Criterion A; Test voltage 10 V Class A Approvals For the latest approvals, please visit www.phoenixcontact.net/catalog. 5 Tolerance data The following applies for tolerance values: The data is valid for nominal operation (U A = 24 V in the default configuration (unless documented otherwise). Default configuration: 16-sample mean-value, IB IL format Tolerances at T A = 25 C; 500 kbps, without meanvalue Absolute Relative Typ. Max. Typ. Max. 0 V...10 V, ±10 V ±20 mv ±50 mv ±0.2% ±0.5% Typical data contains offset error, gain error, and linearity error in the respective default setting. All tolerances indicated as a percentage are related to the positive measuring range final value. Please also observe the values for temperature drift and the tolerances under influences of electromagnetic interferences. Tolerance and temperature response at T A = -25 C... +55 C Drift Typical Maximum 0 V...10 V, ±10 V ±75 ppm/k ±100 ppm/k The drift values refer to the relevant measuring range final value. Tolerances influenced by electromagnetic interference Electromagnetic fields EN 61000-4-3/ IEC 61000-4-3 Fast transients (burst) EN 61000-4-4/ IEC 61000-4-4 Conducted interference EN 61000-4-6/ IEC 61000-4-6 < ±1.0% < ±1.0% < ±1.0% Additional tolerances may occur due to the influence of highfrequency electromagnetic interference caused by wireless transmission systems in the near vicinity. The values specified refer to nominal operation in the event of direct interference to components without additional shielding such as a steel cabinet, etc. The above mentioned tolerances can be reduced by providing further shielding measures for the I/O module (e.g., use of a shielded control box/control cabinet, etc.). 8081_en_01_C01 PHOENIX CONTACT 6

6 Internal circuit diagram Key: Local bus UL+ UANA SUPI 4 SUPI 4 Protocol chip UL- Supervisor µc µc Microprocessor 24VANA 5VANA +/-15VANA Supervisor Hardware monitoring # U MUX 4 Optocoupler 4 REF Power supply unit with electrical isolation +24 V (U S ) +24 V (U M) U1+ U2+ U3+ U1- U2- U3- MUX Analog-digital converter with integrated multiplexer U4+ U4- Input amplifier Figure 1 Internal wiring of the terminal points Low pass filter Electrically isolated area REF Reference voltage source Explanation for other used symbols has been provided in the IL SYS INST UM E user manual. 8081_en_01_C01 PHOENIX CONTACT 7

7 Terminal point assignment 9 Installation instructions 1.1 1.2 1.1 2.1 1.2 2.2 2.1 2.2 High current flowing through potential jumpers U M and U S leads to a temperature rise in the potential jumpers and inside the terminal. To keep the current flowing through the potential jumpers of the analog terminals as low as possible, always place the analog terminals after all the other terminals at the end of the main circuit (for the sequence of the Inline terminals: see also IL SYS INST UM E user manual). 1.3 1.3 2.3 2.3 10 Connection examples 1.4 1.4 2.4 2.4 1.1 2.1 Figure 2 Terminal point assignment 1.2 2.2 U U 1.3 2.3 Terminal Signal Meaning point 1.1 +U1 Positive voltage connection for channel 1 1.2 +U2 Positive voltage connection for channel 2 1.3 +U3 Positive voltage connection for channel 3 1.4 +U4 Positive voltage connection for channel 4 2.1 -U1 Negative voltage connection for channel 1 2.2 -U2 Negative voltage connection for channel 2 2.3 -U3 Negative voltage connection for channel 3 2.4 -U4 Negative voltage connection for channel 4 8 Connection notes Always connect the analog sensors using shielded, twisted pair cables. Connect the shielding with the shielding accessories given in the ordering data. Insulate the shielding at the sensor or connect it with a high resistance and a capacitor to the PE potential. Figure 3 Figure 4 1.4 2.4 Connector for voltage measurement 1.1 2.1 1.2 2.2 1.3 2.3 1.4 2.4 +24 V U P GND Differential voltage input with active 3-wire transmitter 8081_en_01_C01 PHOENIX CONTACT 8

11 Electrical isolation 13 Process data The terminal uses four input process data words and four output process data words. Each channel is mapped to a word. U Local bus (IN) U L (7,5 VDC) ANA (24 VDC) 24V +/-15V +5V Periphery Interface bus interface Microprocessor A B Local bus (OUT) U L (7,5 VDC) U ANA (24 VDC) The analog values are transmitted via the input process data. The configuration is specified via the output process data. 13.1 OUT process data The terminal can be configured channel-by-channel with the output process data. FE potential Analog Inputs Electrical isolation between area A and B Order of the process data words: OUT1 OUT2 OUT3 OUT4 Channel 1 Channel 2 Channel 3 Channel 4 Assignment of the configuration words (OUT1... OUT4): Figure 5 Electrical isolation of the individual function areas 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Configuration 0 0 0 0 0 Filter 0 0 Format Measuring range 12 Local status and diagnostic indicators D Bit 15 Code (bin) Configuration 0 Do not accept 1 Accept Figure 6 D Local status and diagnostic indicators The configuration specified in the word is accepted if bit 15 is set. If bit 15 is not set, the last accepted configuration is used. The configuration is not saved retentively in the terminal. It is therefore not necessary to transmit the configuration constantly. That means, bit 15 must not be set constantly. If bit 15 remains set, the transmitted configuration is compared with the configuration of the terminal in every bus cycle. The terminal is reconfigured if the configurations are different. Designation Color Meaning D green Diagnostics (bus and logic voltage) For detailed information on diagnostics, please refer to the IL SYS INST UM E user manual. Function identification Yellow 8081_en_01_C01 PHOENIX CONTACT 9

Bits 9... 8 Code (bin) Filter 00 16-sample mean-value (default) 01 No filter 10 4-sample mean-value 11 32-sample mean-value Bits 5... 4 Code Format 00 IB IL (default setting) 10 S7-compatible Other Reserved See also Section "Measured value representation in the different formats". Bits 3... 0 Code Measuring range 0000 0 V... 10 V (default) 0001 ±10 V Other Reserved 13.2 IN process data The measured values and diagnostic messages (in the IB IL format) are transmitted channel-by-channel to the PLC via the process data input words IN1 to IN4. Order of the process data words: 13.3 Read firmware version OUT1 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Assignment (hex) 3 C 0 0 Meaning Read firmware version To read the firmware version transmit the value 3C00 hex in the output data word OUT1. The words OUT2... OUT4 still contain the configuration words for channels 2 to 4. In response you get the firmware version in input data word IN1. The input data of the associated channels are transmitted in the other input data words. IN1 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Assignment (hex) 1 2 3 6 Meaning Firmware version 1.23 Device ID The device ID allows you to distinguish between two devices with the same programming data (ID code, length code). Inline terminal ID code Length Device ID code IB IL AI 4/U-PAC 7F hex 04 hex 6 IB IL AI 4/I-PAC 7F hex 04 hex 3 IN1 IN2 IN3 IN4 Channel 1 Channel 2 Channel 3 Channel 4 The measured values are transmitted in the IB IL format or in the S7-compatible format (see Section "Measured value representation in the different formats"). 8081_en_01_C01 PHOENIX CONTACT 10

14 Measured value representation in the different formats 14.1 IB IL format The measured value is represented in bits 14 to 4. An additional bit (bit 15) is available as a sign bit. 14.2 S7-compatible format The measured value is represented in bits 14 to 4. An additional bit (bit 15) is available as a sign bit. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB Analog value 0 0 0 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 SB Analog value X X X X SB Sign bit SB X Sign bit This bit can have the value 0 or 1. The bit is always 0 when a measured value is transmitted. The bit can have the value 1 only when a diagnostic code is transmitted. Significant measured values Input data 0 V... 10 V ± 10 V hex dec SB SB 8001 Overrange > 10.837 > 10.837 7F00 32512 10.837 10.837 7530 30000 10.0 10.0 0010 16 0.00533 0.00533 0000 0 0 0 FFF0-16 - -0.00533 8AD0-30000 - -10.0 8100-32512 - -10.837 8080 Underrange - < -10.837 Significant measured values Input data 0 V... 10 V ±10 V hex dec SB SB 7FFF Overrange > 11.754 > 11.754 7EF0 32496 11.754 11.754 6C00 27648 10.0 10.0 0010 16 0.00579 0.00579 0000 0 0 0 FFF0-16 - -0.00579 9400-27648 - -10.0 8100-32512 - -11.754 8000 Underrange - < -11.754 The value 8000 hex is specified in S7-compatible format for all errors for which diagnostic codes 8001 hex to 8040 hex are output in IB IL format. In the IB IL format a diagnostic code is mapped to the input data in the event of an error. 8001 Measuring range exceeded (overrange) 8004 Measured value invalid/no valid measured value available 8010 Configuration invalid 8020 Faulty supply voltage 8040 Device faulty 8080 Below measuring range (underrange) 8081_en_01_C01 PHOENIX CONTACT GmbH & Co. KG 32823 Blomberg Germany 11 www.phoenixcontact.com