Protocol interface AK-PI 200 REFRIGERATION AND AIR CONDITIONING. Manual

Similar documents
Protocol interface AK-PI 300

Refrigeration and Air Conditioning Controls. Technical Leaflet. Monitoring, Control and Alarm System m2 REFRIGERATION AND AIR CONDITIONING

AK-SC255 Fact Sheet & Recommended Accessories List

ELECTRONIC CONTROLS & SENSORS. AK-SC255 Fact Sheet Version R Software Software version 02_085

MCX08M2 Programmable controller

MAKING MODERN LIVING POSSIBLE AK-255 CO 2. Controller On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

Modulating controlled actuator AME 11

CI-tronic Reversing contactor Type RCI

Data sheet. MCX15B electronic controller MAKING MODERN LIVING POSSIBLE. REFRIGERATION & air CONDITIONING DIVISION. Danfoss Electronics spa

Danfoss Enterprise Manager AK-EM 800

Programmable controller MCX152V

Capacity controller AK-PC 710. Manual

AK-SM 720 Boolean logic REFRIGERATION AND AIR CONDITIONING. User guide

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035

FGC LON System. Technical Specification

VLT Line Filter MCC 107 EMC Filter Series VLT Midi Drive FC 280 (K1 K3)

Industrial Switches Industrial Switches

ENGINEERING TOMORROW. User Guide. BACnet MS/TP Communication with MBS UBR-01 Router. VLT HVAC Drive FC 102 VACON 100 HVAC. vlt-drives.danfoss.

Danfoss commercial compressors Secop compressors produced for Danfoss Bluetooth Gateway

ECL Comfort V a.c. and 24 V a.c.

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway

MODEL: GR8-EM. Communication Adaptor GR8 Series

USER MANUAL. Longo programmable controller LPC-2.MC8 Main module. Version 10

Gas Controller System DGC-06

Installation and User Guide

Installation guide. Data communication link to m2 - LON with EKC - LonWorks

DMT PERFORMING UNDER PRESSURE DMT. Applications. Special features. Description 1/9

Designed for commercial, residential and industrial applications, guarantee rapid installation with few and easy connections.

SonoSelect and SonoSafe energy meters

RXTP ROOM TEMPERATURE

The ECL Apex 20 is operated by means of either a PC or the ECL Apex Web Panel. Temperature input signals are based on Pt 1000 or 0-10 V.

M-Bus Central Unit. Use

Molded Case Circuit Breakers and Disconnect Switches Auxiliary Contacts for Type NZMH4-...

CNVT-USB-RS485 MODBUS TO USB CONVERTER. Operating instructions

MODEL: R2K-1 SEN TRONIC AG. R2K Series

Energy Management BUS Adapter Type VMU-B

6 Port Unmanaged Industrial Gigabit Ethernet Switch w/ 4 PoE+ Ports and Voltage Regulation - DIN Rail / Wall-Mountable

ModEva numerical control units can control up to 18 axes of which 2 are synchronized hydraulic axes especially intended for press-brakes.

PowerFlex 400 AC Drive Guide Specification

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

MindConnect IoT 2040 Product Sheet

General information. Display. Supply voltage

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes. Input current

SonoMeter 30 Ultrasonic energy meter for heating and cooling applications

living connect and Danfoss Link CC wireless thermostat system. Total temperature control from one central point.

General information. Display. Supply voltage. Input current

3G/4G LTE Cellular to Ethernet and Serial Secure Industrial Gateway. SE5901B Series FEATURE HIGHLIGHTS PRODUCT DESCRIPTION

Installation Guide DEVIlink CC Central Controller

vacon 100 hvac for indoor climate control

living connect and Danfoss Link CC wireless thermostat system. Total temperature control from one central point.

General information Engineering with Programming package. Display with display. Supply voltage 24 V DC Yes

Portable low-pressure controller Model CPC2000

General information. Display. Supply voltage. Input current

Technical Information Fieldgate SFG500

ZBRN1 access point- 2 RJ V AC/DC-4 displays-5 LEDs-Eth-Modbus-wireless radio

3G/4G LTE Cellular to Ethernet and Serial Secure Modbus Gateway/Router. MB5901B Series FEATURE HIGHLIGHTS PRODUCT DESCRIPTION

Installation and configuration. WebAccess and its modules for ECL Comfort 200 / 300

General information. Display. Supply voltage. Input current

General information. Display. Supply voltage. Input current

PRELIMINARY. USB1 / USB2 USB host interface to read data via memory stick. Bus Out (system bus) For connection to a router

Appearance Size (mm) Power supply voltage Model (W H D) 100 to 240 VAC K3SC to 240 VAC

ProData DATA LOGGER. Chapter 03 ProData data logger. Ethernet. Pulse inputs and Pulse outputs. Modbus-Ethernet gateway. Thermistor input.

General information. Display. Supply voltage

Programmable controller MCX06C

BD Controller 101N07xx Series 24 V DC with Tool4Cool LabEdition software Operating Instructions

Programmable controller Type MCX06C

ProData data logger. Ethernet. Pulse inputs and Pulse outputs. Thermistor input. Modbus-Ethernet gateway. Memory 32 MB. Threshold value monitoring

PHS Series. PowerHUBB Node - Satellite

General information. Display. Supply voltage. Input current

Solid-state Timer. Ordering Information. Ultra-slim Timer for G2R Relay Socket. H3RN-jj. Accessories (Order Separately) Connecting Socket

IMC-P111FX / IMC-P111P Series

General information. Display. Supply voltage

General information. Display. Supply voltage. Input current

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

Energy Management BUS Adapter Type VMU-B 01

SCS (System Core Server) Model BCY44100M

EMC-1 TM. Ethernet Meterbus Converter. DIMENSIONS [inches (millimeters)] Installation and Operation Manual

Wall-/Pipe Mounted Universal Process Indicator

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Sigma Solar Server. Our systems and solutions for photovoltaic power plants

Access Terminal IF-800

General information. Display. Supply voltage. Input current

Intelligent Operator Panel for SINAMICS G converters siemens.com/sinamics-accessories

Display. Supply voltage. Input current. Encoder supply. Output current. Power losses. Memory

Output Voltage* (nom.)(adjustable)

Service Tool AK-ST 500

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

AC 800M for Compact Product Suite Outline of all modules

General information. Display. Supply voltage. Input current. Encoder supply. Output current

C160 Wall-/Pipe Mounted Universal Process Indicator

MW5501C Series MW5502C Series. 1 or 2-Port Industrial Wireless Modbus TCP/RTU/ASCII Gateway FEATURE HIGHLIGHTS PRODUCT DESCRIPTION

Ascom d43 DECT Handset

IMC-P111FX Series IMC-P111P Series

Air data test indicator Model CPA2501

PSC-AC. PSC AC-series W 1 to 3 Outputs. AC-DC Power supply. Input Voltage ranges. Single output ratings. 2-3 outputs ratings

Inkjet Printer UX Series PREMIUM CLASS. Coding Solutions by Hitachi

DMT340 Series Dewpoint and Temperature Transmitters for Very Dry Conditions

TEMPERATURE CONTROLLER 2 HEAT/ 2 COOL with Digital Room Temperature Display. Made in Australia 100% Australian Owned Company

Transcription:

Protocol interface AK-PI 200 REFRIGERATION AND AIR CONDITIONING Manual

Introduction Function The AK-PI 200 is an intermediary link allowing AKC and AKL type controllers to be operated via a system manager, e.g. AK-SM 720. The actual operation of the controllers is carried out with an AK-ST 500. (AKC and AKL controllers use the DANBUSS data communication system. The communication is controlled by a gateway, e.g. AKA 245. In a solution with an AK-PI 200 and a system manager, the gateway should not be used.) Application The AK-PI 200 is used on systems where the system unit is an AK-SM 720 and where there are one or more controllers with DANBUSS data communication. The unit links the communication to DANBUSS so that the system manager can present all the controllers on the system. DANBUSS controllers are presented on an equal footing together with LON RS 485 controllers and MODBUS controllers. All controllers can be viewed and operated from the system manager s network overview. The solution can be used on existing systems where the majority are DANBUSS controllers and where it would be desirable to change the system operation to a browser-based interface instead of an AKM software interface. Or it can be used on new systems where the majority might be controllers with LON communication and other individual controls can be AKC controllers. Principle The link between the system manager and the AK-PI 200 is via a TCP/IP. In this very simple connection the two units can be connected to each other via a crossed cable. This is where the IP addresses are set to static addresses. On larger systems or where there is also outgoing IP communication from the system, the connection must be made via a router. Here the IP addresses can be dynamic, but if there is communication to the system from outside, they must be static. If you are not sure whether you should select static or dynamic, abide by the following recommendation: Dynamic is the easiest. Here the router itself allocates an address for the system manager and another for the PI unit. But you should only select this solution if the system is closed without a connection for an external operation interface. With static you must obtain a couple of addresses yourself at the local IT department and you must also set the addresses yourself in the two units. This solution must always be used when the system is operated by an external service company, e.g. for log collection, alarm management or service. Contents Introduction... 2 Installation... 4 Requirements and terms... 6 Ordering... 8 Data... 8 2 Manual RS8EX202 Danfoss 02-2009 AK-PI 200

Number of controllers Up to 60 controllers can be connected to a single AK-PI 200. If there are more than 60 controllers, two AK-PI 200 units should be used. Up to two AK-PI 200 units can be connected to a single system manager, in other words up to 120 controllers on the DANBUSS communication. If there are two AK-PI 200 units, the connection to the system manager is led via a router or a switch. Addresses In principle there are three types of addresses: IP addresses Both the system manager and the AK-PI 200 must have an IP address set. The address can be either dynamic or static the desired value is selected with a setting. If static is chosen, an address must also be set. If the system can be accessed externally, the setting in the system manager AK-SM 720 must always be set to static so that the external connection always recognises the address and can communicate with the unit. (The IP address is set in a menu). Network addresses There must always be one and only one master system manager on a network. This is defined with the address setting = 1. This system manager controls the communication to all the other controllers on the network. The PI unit is perceived as a controller on the network and its address can be viewed in the IP list. (Up to two PI units can be connected to the system manager, which is master - i.e. has address =1) (You set the network address on the front of the system units and on the front of the PI units.) Set the system manager to address 1. If there are several system managers (slave network), set these to addresses 2 to 10. Each PI unit is set with a separate address. Select 12 or higher, e.g. 21. Interconnection When setting the system manager, a menu must also be set in which the relevant AK-PI 200 chooses the network. The system manager then knows the way to the different DANBUSS controllers. The system manager must be version 1.20 or later. Controller addresses All controllers on the same network must have different addresses. In other words, all controllers that are connected to a system manager on either: the LON communication the MODBUS communication or the DANBUSS communication. Start with the addresses on DANBUSS. They must be set with a DIP switch and cannot be set to higher than 120. The addresses on the LON and MOD buses can be set higher. No more than 200 controllers can be connected to a system manager. DANBUSS communication: Address options 1 to 120 LON communication: Address options 1 to 999 MODBUS communication: Address options 1 to 247 Max. number of controllers: 200 AK-PI 200 Manual RS8EX202 Danfoss 02-2009 3

Installation Preparing controllers on DANBUSS In an existing system If it is an existing system in which the controllers have previously been connected to a gateway, the pairing (network number) with the gateway is registered so it can be set in AK-PI 200. 1. Register the network number for the later setting. In a new system 1. Set the address of the controller 2. Switch it on if it is not already on 3. Set the desired language in the controller (connect the AKA 21 and set the language selection menu. Disconnect the AKA 21 after entering settings). Network number Preparing TCP/IP connection The AK-PI 200 must have a connection to the system manager both physically and with a software setting. This can take place in one of the following ways: 1. Connection a) Direct connection (only used if there is not an external connection via a router). The cable between the two units must be a crossed cable. (A static IP address is always used here.) b) Cables from the units are connected to a router or to a switch. (A dynamic or static IP address is used here.) 2. Setting a) Router - Dynamic: There are no settings in the router - Static: A static address range must be set in the router b) AK-SM 720 - Select static if the connection between the system unit and the AK-PI 200 is with a crossed cable or there is an external connection to the system. Then set the IP address (an IP address must be obtained from the local IT manager). - Select dynamic if it is a closed system and the two units are connected to a router or a switch. c) In the AK-PI 200 the IP address is set either to static or to dynamic. - Select static if the connection between the system unit and the AK-PI 200 is with a crossed cable. Then set the IP address (an IP address must be obtained from the local IT manager). - Select dynamic if it is a closed system and the two units are connected to a router or a switch. 3. If a router or switch is connected, it must be turned on. 1a) 1b) Crossed cable 4 Manual RS8EX202 Danfoss 02-2009 AK-PI 200

Preparing the system manager 1. Set its address on the front to 1 (there must always be a system manager with address 1 on a network (1=master)). If there are several networks and thus several system managers, they must have addresses 2 to 10. 2. Connect the controllers to the two data communications, LON and MODBUS. Switch on the controllers and set an address in each controller. Addresses may not be duplicated not even with addresses on the DANBUSS network. 3. Apply power to the system manager 4. If a static IP address is used, this must be set 5. Enter the system manager's service PIN Preparing the AK-PI 200 1. Set its address on the front (e.g. to 12) 2. Apply the power 3. If a static IP address is used, this must be set 4. Set network number for the DANBUSS group. (In previously version (1.0x) of AK-PI 200 the number is not visible but is fixed programmed to 1. If it is a updating of AK-PI 200 to version 1.1x it must be set to 1.) 5. (You can activate the Service PIN function at this point. If you do, this means you do not have to start the scan function in the next point.) Perform the first scan 1. Start the scan function in the system manager wait for the results (the controllers on the LON and MODBUS communication will now be located and visible in the network overview). 2. Go to the next page of the network overview, which details the IP registrations. Check that the AK-PI unit is registered. Interconnection Define which AK-PI 200 unit the system manager should recognise (several units can be registered but the system manager with address 1 can only control two units. 1. There is a menu in the system manager in which settings must be entered. Go to the Setup menu/protocol interface (the system manager must be version 1.20 or later). 2. Select the address of the AK-PI 200, which is to be connected to the system unit. Perform scan number 2 and locate the DANBUSS controllers 1. Perform a new scan of the system manager. Wait for the results. (All controllers will now be located.) See the system manager manual for further installation. AKC device AK-PI 200 Manual RS8EX202 Danfoss 02-2009 5

Requirements and terms Principle The installation of the data communication must be carried out as specified in the guide to the RC8AC. The terminations must be in order. Language options in an AKC controller When data is retrieved and sent to the AK-PI 200 and then on to the system manager and operation software, it will appear in the language selected in the controller. If the wrong language is displayed, the AK-PI 200 must be restored to factory settings and an associated file on the PC must be deleted. (C:Program files\adap-kool\service tool\data\cashe\code no). The whole process must then be repeated, but this time with a different language selected. Up to 60 AKC controllers can be connected to a single AK-PI 200. Up to two AK-PI 200 units can be connected to a single system manager. Up to 20 different types of AKC controller can be connected. There must not be a gateway or an AKA 21 connected to the DANBUSS communication it is the AK-PI 200 that controls the communication to the controllers. Network addresses Here is a small summary of the networks and addresses that can occur: 11:001 is the master system manager 11:002 to 11:010 are slave networks controlled by 11:001 (the figure 11 keeps track of the networks and cannot be changed). 11:012 to 11:999 are addresses for units on the network. The units can be AK-PI 200 units or wireless units, or they can be controllers in which the data communication takes place via TCP/IP. 1: xxx will be controllers that are registered under the master system manager. 2: xxx will be controllers that are registered under slave network number 2. 6 Manual RS8EX202 Danfoss 02-2009 AK-PI 200

The overview display will show the following: The address of the system manager that AK-PI 200 is connected to The status of the alarm transmission Date and time The quality of the DANBUSS communication signal The configuration display gives access to the following: The configuration lock is only used if a static IP address is to be set. Under "System setup" you can give the unit a name IP settings can be entered Examples of IP addresses AK-PI 200 Manual RS8EX202 Danfoss 02-2009 7

Ordering Type Function Application Language Code no. AK-PI 200 Protocol interface Intermediary link between system manager and controllers with DANBUSS data communication English, German, French, Italian, Dutch, Spanish, Portuguese, Danish, Swedish and Finnish 080Z8521 Accessories Transformer module 230 V / 115 V to 24 V AK-PS 075 18 VA Supply 080Z0053 Data Supply voltage 24 V a.c. +/- 20% Power consumption AK-PI 200 12 VA Ambient temperature During transport -40 to 70 C During operation -20 to 55 C, 0 to 95% RH (non condensing) No shock influences / vibrations Enclosure Material PC / ABS Density IP10, VBG 4 Approvals Mounting Weight EU low voltage directive and EMC requirements are complied with UL 873, For mounting on wall or DIN rail Approx. 600 g LVD tested according to EN 60730 EMC tested Immunity according to EN 61000-6-2 Emission according to EN 50081-1 UL file number: E166834 Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. DE-DB 8 Manual RS8EX202 Danfoss 02-2009 AK-PI 200