Monitoring Made Easy October 2015 APRIL 2015
About Packet Power Founded in 2008 Based in Minneapolis, MN Global partner network Customers on 6 continents Over 30,000 monitoring units deployed 2
Our goal Make it easy and affordable to capture energy information everywhere it is of value 3
Create a monitoring platform that is: Cost-effective Flexible Complete Secure Robust Simple 4
We Built It Secure, purpose-built wireless mesh network 860-900MHz and 2.4GHz Power monitoring from 10 to 3000+ amps plug and play smart power cables plus busway, panel, PDU and whip Flexible environmental monitoring temperature, RH and pressure Simple software cloud or local open full SNMP and Modbus support Simple Robust Secure Complete Flexible Cost-effective 11
Simple network connectivity Gateways access data from up to 150 monitors each add gateways to grow standard, SNMP and Modbus models Use Hubs to connect SNMP or Modbus monitors to EMX DCIM BMS EMX 12
Facility-wide power monitoring Device, branch circuit and mains metering AC and DC Wide range of form factors New build and retrofit Primary uses cost allocation operations management energy efficiency 13
Power monitoring products Smart power cables 10 to 100A Single- and three-phase Panel monitoring panel infeed circuits or selective branch circuits switchgear, MDPs, RPPs, floor PDUs Current-only monitoring 48V and 380V DC monitoring Integrated power strips, busways and whips 14
Wireless DC Monitoring Offerings Three related offerings 200-380V HVDC for data centers 48V for telecom / cable / wireless 5-24V for low voltage monitoring Report V, A, W, Wh at ± 1% accuracy Net metering capable Use Packet Power s wireless mesh network 17
48V DC Monitoring Wireless power monitors Integrated 35 and 65 amp CTs External 20 3000A solid- or split-core CTs Small size 35 x 35 mm base Powered directly from 35 to 60V source ± 1% accuracy at 10-100% of range DIN rail, adhesive pad, cable tie or screw mount 18
High Voltage Direct Current Monitoring Full power monitoring for DC systems 100 to 380 Volts 20 to 3000 Amps Wireless data transmission using secure Packet Power mesh network Suitable for use in busways and other enclosed environments 19
HVDC Components Voltage and current sensors Wireless communication to display unit Integrated or external CTs Compact 35 x 35 mm base DIN rail mount option Display Mounts easily in 1 NPT knockout Forms wireless connection to other displays and Ethernet Gateway Display and CTs powered by 5V DC power supply 20
Initial DC Product Models 48 VDC Current / Power Monitors (20-65 V) Product Number CT Type Amperage CT Inside Diameter (mm) DC03-T00S Solid Core Integrated 35 8.5 DC06-T00S Solid Core Integrated 65 8.5 DC0E-T100 Split Core External 100 21 DC0E-T200 Split Core External 200 21 DC0E-T300 Split Core External 300 35 DC0E-T400 Split Core External 400 35 DC0E-T500 Split Core External 500 35 DC0E-T800 Split Core External 800 50 DC0E-T1X0 Split Core External 1000 84x22 DC0E-T2X0 Split Core External 2000 100x42 24 VDC Current / Power Monitors (5-36 V) Product Number CT Type Amperage CT Inside Diameter (mm) DC03-000S Solid Core Integrated 35 8.5 DC06-000S Solid Core Integrated 65 8.5 DC0E-0100 Split Core External 100 21 DC0E-0200 Split Core External 200 21 DC0E-0300 Split Core External 300 35 DC0E-0400 Split Core External 400 35 DC0E-0500 Split Core External 500 35 DC0E-0800 Split Core External 800 50 DC0E-01X0 Split Core External 1000 84x22 DC0E-02X0 Split Core External 2000 100x42 Example HVDC Models Product Number Current Voltage DG30-V01S 1 x 300A Solid Core External Yes DG06-002S 2 x 65A Solid Core Shared DG03-001S 1 35A Solid Core Shared DG06-002S includes: 1 x Display 2 x Integrated 65A CT Current Monitors 1 x 380 to 5V DC Power Supply 1 x Harness Kit 22
Flexible environmental monitoring E306-1 to 6 temperature points per unit AC power or PoE with splitter E312-1 to 12 temperature points per unit 2 x AA battery or optional AC power Temperature probe choices individual probes - 1 to 15 meters probe assemblies - 1, 2, 3, 4 or 6 probes / cabinet Option for relative humidity and differential pressure 25
Instant information from EMX Get immediate value data automatically flows on install no external consultants needed customize when and as you see fit Real-time alerts Flexible reporting Cloud service or local software Works with non-packet Power monitors 26
Proven worldwide 33
Sophisticated monitoring made easy Simple Easy to install Easy to get the data Easy to manage configures itself adapts to changes grows easily optimizes performance Designed for tough conditions Contends with a lot of metal and noise long wavelengths ~ 900 MHz multiple paths small transmissions dynamic routing Works for big and small installs Robust Secure Complete Flexible Hardware low price per unit no need to run cables or remove existing devices use your existing software Software low total cost Instant access to information no need for expensive consultants works with existing monitoring units Shortest time to value Cost-effective Separate from primary networks Limited, purpose-built protocol Wireless / wired separation Data is pulled on wired network Sub-divide wireless networks Encryption Monitor where you want servers, branch circuits, PDUs, panels, switchgear low, medium and high-density tracking Mix and match as you see fit Grow easily over time Fully open and vendor neutral works on any vendors hardware send data from our monitors to other software use data from other monitors in our software Power monitoring Environmental monitoring Software 34
Monitoring Made Easy Thank you Distribué en France par Daxten France Distributeur Européen exclusif