A66N2 Installation and Programming Manual

Similar documents
A66SM Installation and Programming Manual

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

Optidrive Applications Support Library

Optidrive Applications Support Library

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09

GE Consumer & Industrial Electrical Distribution. AF-600 FP TM Metasys. Operating Instructions

Contents. Index 35. VLT HVAC Drive Metasys N2

Optidrive VTC Modbus RTU Register Map

E2 Modbus RTU Register Map

Firmware Manual - EC Series Drives

Unidrive M200, M201 (Frame 1 to 4) Quick Start Guide

1. Safety Danger Warnings Earthing and earth fault protection... 4

1.1.1 Software Version Introduction About this Manual References 2

Copyright: December 2017 Nidec Issue: E

MC3000 Series Drives Metasys N2 Communications Guide

3GV M Modbus RTU Register Map

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Quick Start Guide For GVX9000 AF Drives

Unidrive M400 (Frame 1 to 4) Quick Start Guide

MCH Series Drives Metasys N2 Communications Guide

Quick Start Guide Cutler-Hammer SVX9000 Drives from Eaton Corporation CONTENT STEP 1 Keypad Operation Overview STEP 2 Standard Wiring Diagrams and

GE Consumer & Industrial Electrical Distribution. AF-600 FP TM Metasys. Operating Instructions

GV3000/SE AC Drive Quick Reference Version 6.06

Tongta Inverter TDS-F8

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 1.10

VLT 2800 DRIVE SPECIFICATIONS

INDEX 1. GENERAL RS-485 OPTION BOARD TECHNICAL DATA General... 5 t n RS-485 FIELDBUS BOARD LAYOUT AND CONNECTIONS... 6 RS-485 NXOP

Copyright: December 2017 Nidec Issue: E

Display / Adjustment Options VW3-A16101, VW3-A16102, VW3-A16103

Step 1: Choose the Appropriate CPU Step 2: Make the Connections

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 2.00

Altivar 21 Programming and Operation Guide

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION

Table of Contents 1. Overview Installation...6

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

User Guide Regenerative & Non-Regenerative Digital DC Drives 5 to 1000 HP

Tracer Summit. Interface to Square D Drives BAS-PRC004-EN. June 2000

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

Instructions. Modbus RTU Card (WSIQ-COM-MB)

Metasys N2 Communications Protocol Operating Instructions

SAFETY PRECAUTIONS. Throughout this manual we use the following two illustrations to make you aware of safety considerations:

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

Metasys Integrator Powerware Application (previously the Exide Application)

Zenith DS9000 Dispensing System

QUICK REFERENCE GUIDE

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA

EQ5 SERIES Quick Start Guide for Constant Torque Applications

mbc082 Bus Converter

TR200 DRIVE STANDARD FEATURES

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

ETM MD100 Drive System 1/2HP (370W) User Manual. Table of Contents. Drive Features

1. Introduction. 2. Installation MODBUS INTERFACE

ATV12HU22M3 variable speed drive ATV12-2.2kW - 3hp V - 3ph - with heat sink

ATV12P075M3 variable speed drive ATV kW - 1hp V - 3ph - on base plate

ATV12H075M3 variable speed drive ATV kW - 1hp V - 3ph - with heat sink

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Issue 06

ATV12H018M2 variable speed drive ATV kW hp V - 1ph

TR150 DRIVE STANDARD FEATURES

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04

MCD 200 MCD 500. Remove the Profibus Module using the following procedure: 1. Remove power from the module.

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

CNInformation SCHNEIDER ELECTRIC

Technical Instructions Document No February 25, Modbus RTU Interface Module for SED2. Description. Product Part Number

ATV32HU11M2437 variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink

Installation and Programming Manual

Unico 2400 Drive Faults Descriptions and Causes Dec. 2016

LOW VOLTAGE BLDC MOTOR CONTROLLER

- 15G0078B110 - PROFIBUS MODULE INSTRUCTIONS FOR ASAC-0/ASAC-1/ASAB

Johnson Controls Metasys N2 Communications Interface

QUCM Limitorque Controller

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Diagnostics and troubleshooting

SMD SERIES INVERTER MODBUS CONTROL OPERATION MANUAL. Document: SLmod-e2

Instruction Bulletin. ALTIVAR 58 Adjustable Speed Drive Controllers

Reliance GV3000 Drive Registers

Safety Instruction. This symbol indicates the possibility of injury or damage to property.

Motors I Automation I Energy I Transmission & Distribution I Coatings. SymbiNet CFW-11. User s Manual

FlexPak 3000 Drive Operator Interface Module (OIM) User s Guide

Flomatic Smart Card TM Model FDHC-100 (Digital High-Resolution Controller) Configuration and Operation Manual

vacon nx ac drives brake chopper unit (bcu) application user s manual

MODERNIZE YOUR DC CRANES. Convert Your DC Controls to State-of-the-Art Energy Efficient OmniPulse DDC Series 2 Drives

VS mini J7 to J1000 Replacement Instructions

LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4

GEMCO. Installation & Programming Manual. Series 1746R. PLC Resolver Interface Module. For Allen-Bradley SLC 500 I/O Chassis

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION

Installation and Programming Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS For Chemline A- & Q-Series Actuator with Digital (AC) Positioner

ATV61HC31Y variable speed drive ATV61-310kW - 690V - without EMC filter

MCH Series Drives BACnet Communications Guide

ATV310HU30N4E variable speed drive ATV310-3 kw - 4 hp V - 3 phase

1550-N2 Revision 1.7 A-B Drives Protocol Interface September 1999

Metasys Integrator Caterpillar Application

GPD 506/P5 Apogee - FLN Technical Manual

IM-pAC. Getting Started Guide. AC variable speed drive for 3 phase induction motors from 0.25kW to 4kW, 0.33hp to 5hp. Model sizes A, B and C

ATV32HU75N4 variable speed drive ATV kw V - 3 phase - with heat sink

PROGRAMMING MANUAL IM262R00. AQUAVAR Intelligent Pump Controller START-UP GENIE PROGRAMMING MANUAL

Operation manual. HDOM-Profibus-V0. More options please visit;

LS M100 Frequency Inverter Easy Start Guide

Transcription:

A66N2 Manual A66N2 Installation and Programming Manual This Manual describes the A66N2 Communications Adapter for the Altivar 66 Variable Frequency Drive, its uses and set up. Effective: 14 February 2001 Niobrara Research and Development Corporation P. O. Box 3418 Joplin, MO 64803 Telephone: (800) 235-6723 or (417) 624-8918 Facsimile: (417) 624-8920 Internet: http://www.niobrara.com

Altivar is a trademark of Square D. N2 and Metasys are trademarks of Johnson Controls, Inc. Modbus Plus is a trademark of Schneider Automation. Subject to change without notice. Niobrara Research and Development Corporation 2001. All Rights Reserved. 2 A66N2 Manual

Contents CONTENTS...3 1 INTRODUCTION...5 2 INSTALLATION...7 Serial Link Control... 8 Frequency Scaling... 8 Fault Management... 9 3 OPERATION...11 4 TROUBLESHOOTING...19 A66 card not responding... 19 Inconsistent communication... 19 A66N2 Manual 3

1 Introduction The A66N2 communications adapter card connects an Altivar 66 variable frequency drive controller (see Figure 1 below) to an N2 multidrop network. It will allow the N2 bus master to adjust drive operational parameters; command, control, and monitor drive operation; and diagnose drive fault conditions. The A66N2 is a Type 3 PCMCIA card with an attached 3 meter cable terminated with a 15- pin D-Sub connector. The A66N2 is designed to operate in the PCMCIA slot of an I/O extension module (VW3A66201T or VW3A66202T) or communication carrier module VW3A66205(not the drive s main PCMCIA slot), and requires drive firmware revision 3.2 or later. NOTE: This manual is not intended to be used as a guide for drive operations. It is written to explain connection of the A66N2 to the N2 network, and to describe the mapping of the drive parameters into the N2 points list. For information on drive operation, refer to Instruction Bulletin VD0C06S304B (Altivar 66 User s Manual). Figure 1: Altivar 66 variable frequency drive. A66N2 Manual 5

2 Installation Refer to Section 1 of Instruction Bulletin VD0C06S308 for installation instructions for the A66N2 communication card in the Altivar 66 drive controller. Please note the following additions/modifications to the Square D installation instructions: For the A66N2 communications card to operate correctly, the drive into which it is installed must have revision 3.2 or later firmware. This may be viewed on the Drive Identification menu page, for example ATV66U41N4, CT, V3.2 In the drive s communications setup (menu 11), set Protocol to Modbus+ and Address to the desired N2 LAN address. Set the Timeout to a value appropriate for the system s scan rate. When the drive is under Serial Link Control, this timeout value will determine how long the drive will run without receiving communications from the N2 bus master before shutting down. The Peer Cop and Global Data parameters are not used and should be set to NO and zero respectively (see Serial Link Control, below, for exceptions). When the card is recognized by the drive, the drive s Comm State menu (menu 12) will reflect the selected address and show a constantly changing token counter. The adapter supports the N2 serial protocol at 9600 bits per second, 8 data bits,1 start bit, 1 stop bit, and no parity. These settings cannot be changed in the field. NR&D recommends limiting network size to a maximum of 32 devices, including the network master device. The A66N2 PCMCIA card has an attached cable which terminates in a 15-pin D- Subminiature male plug. LAN Connection to this plug is as shown in Figure 2 on page 8. Connection to this plug may be made using Phoenix Contact part number FLKM-D 15 SUB/B, or by building a cable to make the following connections: A66N2 Manual 7

8 15 7 14 6 13 5 12 4 11 3 10 2 9 1 Ref N2- N2+ Figure 2: Connection of N2 LAN to A66N2 DB-15 connector. Because the motor leads from a variable frequency drive transmit a lot of electrical noise, it is important to keep the network wiring as isolated as possible from the motor leads and any other high current wiring. If the VFD is mounted in a shielding enclosure, a minimum of network wiring should be inside the enclosure, with the remainder of the wiring done in a separately grounded enclosure. Serial Link Control The default configuration for the A66N2 communication card as described above will cause the drive to enter SLC or Serial Link Control when the PCMCIA card is initialized by the N2 host device. This means that the drive expects to get its operational parameters (run speed, direction, etc.) from the communications link. In situations where it is not desirable to have the drive commanded over the serial network, the card can be configured to not automatically put the drive into SLC mode upon initialization. In order to disable the drive s automatically entering SLC mode on initialization, the configuration parameter PEERCOP in the drive s Communications Setup menu (Menu 11) should be set to YES. When this is done, the drive will prompt for further information: Num. Registers should always be set to 1 for use with this communications card. Command Node may be set to one of several values, to select different SLC startup behaviors and different scaling factors for points AI-1 and AO-1, other than the default scaling provided by the drive. SeeTable 1 below for configurations available via the Command Node parameter. Frequency Scaling In some situations, the default scaling for frequency (Reference Frequency = AO-1 and Output Frequency = AI-1) is unwieldy or even unusable. Different output scales may be accessed by setting the PEERCOP parameter in the drive s Menu 11 to YES (as described above), and setting the Num. Registers field in the subsequent menu to 1. Then set the Command Node to one of the values described in Table 1 below to select a different scaling to be applied to the frequency parameters AO-1 and AI-1. 8 A66N2 Manual

Table 1: Configurations available through Command Node parameter COMMAND NODE Scaling Disable Comm Timeouts NO 1 Altivar 66 Drive native scaling: Units = 0.0151 * Hz, thus: Set AO-1 to 662 for 10Hz output. NO 2 Frequency scaled to Hz: Units = Hz, thus: NO NO Set AO-1 to 10.0 for 10Hz output. 3 Frequency scaled to % of High Speed Units = 100 / High NO NO Speed, thus: With High Speed set to 60.0 Hz, Set AO-1 to 16.7 for 10Hz output. 4 16 Reserved. Do not use these values for Command Node. --- 17 Native scaling (Same as Command Node = 1) YES NO 18 Hz scaling (Same as Command Node = 2) YES NO 19 Percent scaling(same as Command Node = 3) YES NO 20 32 Reserved. Do not use these values for Command Node. --- 33 Native scaling (Same as Command Node = 1) NO YES 34 Hz scaling (Same as Command Node = 2) NO YES 35 Percent scaling(same as Command Node = 3) NO YES 36 48 Reserved. Do not use these values for Command Node. --- 49 Native scaling (Same as Command Node = 1) YES YES 50 Hz scaling (Same as Command Node = 2) YES YES 51 Percent scaling(same as Command Node = 3) YES YES 52 64 Reserved. Do not use these values for Command Node. --- SLC on Initialization Fault Management When the Altivar 66 drive is operating in Serial Link Control (SLC) mode, the timeout value set in Menu 11 controls how long the drive will continue to run after losing communications from the N2 master. When the timeout expires without receiving a message from the master, the drive will go into fault mode and stop the motor. NOTE: In systems where loss of motor control is not a safety issue, the drive s Serial Timeout feature may be disabled on drive power-up by setting an appropriate value for Command Node as described in Table 1, above. If Comm Timeout is disabled, the drive will continue running at its last commanded speed after loss of communication. In order to enable fault recovery over the N2 network, set Auto-Restart in Menu 7.4 (Fault Management) to YES. In the Auto-Restart submenu, set Restarts and Delay time as appropriate for the system. If Auto-Restart is set to NO, the fault must be recovered at the drive control panel. With Auto-Restart set to YES, the drive will exit fault mode, and resume normal operations after the drive is re-initialized via the N2 network, and after Delay time has expired. A66N2 Manual 9

3 Operation The essential command and monitoring parameters of the Altivar 66 drive controller are mapped into Analog Inputs and Outputs, and into Binary Inputs and Outputs according to the N2 protocol. These parameters may be configured for high alarm, low alarms, high warning, low warning, and COS differential, and the inputs may be monitored for COSs, as provided by the N2 protocol. Note the following exceptions: The A66N2 does not support overriding analog inputs. The A66N2 does not support auto-restore on override release. When an overridden binary point is released, it reverts to the current value reported by the drive. When an overridden analog point is released, its value does not change. The A66N2 does not support JCI-use-only attributes and status flags of any point region. The A66N2 does not support the minimum on-time, minimum off-time, nor maximum cycles/hour attributes of any binary output points. The A66N2 card has two LED indicators. The green indicator will flash as N2 communications packets are received. The red indicator will flash if a packet or command is in error or otherwise not recognized by the card. If the last message sent to the card has an error, the red light may stay on until a new, good, packet is received. Errors which will light the red LED include: CRC error, inter-character timeout error, attempt to read or write an unsupported or illegal point, an inappropriate command for the data type, an illegal N2 opcode, and the device has reset and is waiting for the Identify Device Type command. All of the configuration and monitoring registers in the Altivar 66 which are not mapped into AI, AO, BI, or BO points are accessible as ADI points. Table 6, on page 14 shows the function assignment of each ADI point. Complete information on these points use may be obtained from Instruction Bulletin VD0C06S309 (Modbus+ PCMCIA manual) or Instruction Bulletin VW3A66301U (Uni-Telway, Modbus/JBUS Protocols PCMCIA Comm. Card Kit manual). The following tables describe the point mapping of the A66N2 communication card: A66N2 Manual 11

NPT 1 NPA 2 UNITS AI 1 0.0151 * Hz AI 2 % Terminal Strip Analog Input 1 AI 3 % Terminal Strip Analog Input 2 AI 4 % Terminal Strip Analog Input 3 AI 5 % Terminal Strip Analog Input 4 1 Network Point Type 2 Network Point Address Table 2: A66N2 Analog Input Point List POINT RANGE / DESCRIPTION VALUE Output Frequency (-26478-26478) corresponding to (-400 to 400Hz) NOTES Reflects actual drive output frequency 42 (0-100) 45 (0-100) 64 (0-100) 65 (0-100) 66 Table 3: A66N2 Binary Input Point List NPT 1 NPA 2 UNITS POINT RANGE / DESCRIPTION VALUE BI 1 Drive Faulted 0-Ok 1-Fault BI 2 Terminal Strip 0-Off Logical Input 1 1-On BI 3 Terminal Strip 0-Off Logical Input 2 1-On BI 4 Terminal Strip 0-Off Logical Input 3 1-On BI 5 Terminal Strip 0-Off Logical Input 4 1-On BI 6 Terminal Strip 0-Off Logical Input 5 1-On BI 7 Terminal Strip 0-Off Logical Input 6 1-On BI 8 Terminal Strip 0-Off Logical Input 7 1-On BI 9 Terminal Strip 0-Off Logical Input 8 1-On BI 10 Fault (FLT) 0-OK 1-Fault condition BI 11 Motor Running 0-Stopped 1-Running BI 12 Actual Rotation 0-Forward Direction 1-Reverse 1 Network Point Type 2 Network Point Address NOTES 50, bit 0 44, bit 1 44, bit 2 44, bit 3 44, bit 4 44, bit 5 44, bit 6 44, bit 7 44, bit 8 41, bit 2 41, bit 8 41, bit 9 12 A66N2 Manual

NPT 1 NPA 2 UNITS AO 1 0.0151 * Hz AO 2 % Terminal Strip Analog Output 1 AO 3 % Terminal Strip Analog Output 2 AO 4 % Terminal Strip Analog Output 3 1 Network Point Type 2 Network Point Address Table 4: A66N2 Analog Output Point List POINT RANGE / DESCRIPTION VALUE Reference Frequency (-26478-26478) corresponding to (-400 to 400Hz) NOTES A negative reference frequency will cause the motor to turn in the opposite direction from the Reverse Command point. 22 (0-4095) 24 (0-4095) 30 (0-4095) 31 Table 5: A66N2 Binary Output Point List NPT 1 NPA 2 UNITS POINT RANGE / DESCRIPTION VALUE BO 1 Run/Stop Command 0-Stop 1-Run BO 2 Reverse Command 0-Fwd 1-Reverse BO 3 Terminal Strip 0-Off Logical Output 1 1-On BO 4 Terminal Strip 0-Off Logical Output 2 1-On BO 5 Terminal Strip 0-Off Relay Output 2 1-On BO 6 Terminal Strip 0-Off Relay Output 3 1-On BO 7 Terminal Strip 0-Off Relay Output 4 1-On BO 8 DC Brake 0-Disabled 1-Enabled BO 9 No Orient Stop 0-Orient 1-No Orient BO 10 Freewheel Stop 0-Disabled 1-Enabled BO 11 Fast Stop 0-Disabled 1-Enabled BO 12 Voltage Reduce 0-Default 1-Reg 2029 BO 13 Serial Link Control 0-Non-SLC 1-SLC 1 Network Point Type 2 Network Point Address NOTES 21, bit 5 32, bit 1 23, bit 1 23, bit 2 23, bit 6 23, bit 7 23, bit 8 21, bit 6 21, bit 7 Overrides Fast Stop 21, bit 8 21, bit 9 21, bit 10 21, bits 1 and 2. A66N2 Manual 13

Table 6: A66N2 Internal Integer (ADI) Point List ADI Address 1 Bit Description 1 --- High Speed 2 --- Low Speed 3 --- Accel 1 4 --- Decel 1 5 --- Accel 2 6 --- Decel 2 7 --- Slip Compensation 8 --- IR Compensation 9 --- Profile 10 --- Voltage Boost 11 --- Damping 12 --- Bandwidth 15 --- Motor Overload 21 0 Drive Reset 1 Assignment of logic commands over link (DLI) 2 Assignment of references over link (FLI) 3 Alternate ramps (Ramp 2) 4 Suppression of communication control (NTO) 5 Run/Stop Command 6 Braking by DC injection (DCB) 7 Orient Stop 8 Freewheel Stop 9 Fast Stop 10 Command of voltage reduction 11 Multi-Motors 12 Multi-Parameters 14 External fault command (EFL) 15 Peer Cop Adjustment storage 22 --- Reference Frequency 23 1-3, 6-8 Command of Lox / ROx state 24 --- Command of AO1 Level 25 --- Current Limit level 26 --- Motoring torque limit level 27 --- Regenerating torque limit level 29 --- Voltage reduction level 30 --- Command of AO2 level 31 --- Command of AO3 level 14 A66N2 Manual

Table 6: A66N2 Internal Integer (ADI) Point List (cont d) ADI Address 1 Bit Description 32 0 Command of current limit 1 Run direction 3 Command of torque limit 8 Elapsed timer reset 41 0 Mode in which all commands are assigned 1 Drive controller ready (RDY or SLC) 2 Fault (FLT) 3 Reset authorized 4 Brake engage relay state 5 Forced local 6 NTO 7 Resettable fault 8 Motor running 9 Actual rotation direction 10 DC injection braking 11 Steady state 12 Motor thermal overload alarm 14 Current limit 15 No line power (NLP) 42 --- Output frequency 43 --- Output current 44 1-8 Display of logic input activation (LI1 - LI8) 9-10 Display of logic output activation (LO1 - LO2) 11-14 Display of relay activation (R1 - R4) 45 --- Value of analog input (AI1) 46 --- Motor torque 47 --- Speed reference 48 0 Local command mode T/K 1 Logic commands over link (DLI) 2 Reference commands over link (FLI) 3 Dynamic braking 4 Fast stop 5 Power loss, ramp stop 6 Gating state 7 Orient complete 8 Deceleration (DEC) 9 Acceleration (ACC) 10 Multi-motor or 11 Multi-parameter selected 13 Drive controller thermal fault 14 Torque limit 15 Stopping by the keypad A66N2 Manual 15

Table 6: A66N2 Internal Integer (ADI) Point List (cont d) ADI Address 1 Bit Description 49 0 Jog 1 Shutdown complete 2 Cycle complete 3 Alternate ramp 4 Auto/Manual 5 Frequency level 1 attained 6 Frequency level 2 attained 7 Current level 1 attained 8 Current level 2 attained 9 Thermal level 1 attained 10 Thermal level 2 attained 11 No ramp follow 12 Run output command 13 Rotation direction 50 0 Drive faulted, stopped 4 State of adjustment semaphore 5 State of command semaphore 51 --- Display of fault causing trip 52 --- Display of present faults 53 --- Output power 54 --- Output voltage 55 --- Line voltage 56 --- Bus voltage 57 --- Motor thermal state value 58 --- Drive controller thermal state value 59 --- Elapsed time (hours) 60 --- Elapsed time (minutes) 61 --- Output speed (rpm) 62 --- Machine frequency reference number (customer units) 63 --- Machine frequency (customer units) 64 --- Value of analog input AI2 65 --- Value of analog input AI3 66 --- Value of analog input AI4 67 --- Value of AO1 68 --- Value of AO2 69 --- Value of AO3 70 --- Speed ramp output 72 --- Nominal motor voltage range 75 --- Number of motor or parameter set selected 76 --- Cycles step number in progress 77 --- Preset speed number in progress 16 A66N2 Manual

Table 6: A66N2 Internal Integer (ADI) Point List (cont d) ADI Address 1 Bit Description 101 --- Assignment of AI1 102 --- Assignment of AI2 103 --- Assignment of AI3 104 --- Assignment of AI4 105 --- Assignment of AO1 106 --- Assignment of AO2 107 --- Assignment of AO3 108 --- Assignment of LO1 109 --- Assignment of LO2 112 --- Assignment of R1 113 --- Assignment of R2 114 --- Assignment of R3 115 --- Assignment of R4 116 --- Assignment of LI1 117 --- Assignment of LI2 118 --- Assignment of LI3 119 --- Assignment of LI4 120 --- Assignment of LI5 121 --- Assignment of LI6 122 --- Assignment of LI7 123 --- Assignment of LI8 141 --- Indicates the position of marker on 1 of 8 past faults 142 --- Past fault 1: Drive controller state 143 --- Past fault 1: Name of fault 144 --- Past fault 2: Drive controller state 145 --- Past fault 2: Name of fault 146 --- Past fault 3: Drive controller state 147 --- Past fault 3: Name of fault 148 --- Past fault 4: Drive controller state 149 --- Past fault 4: Name of fault 150 --- Past fault 5: Drive controller state 151 --- Past fault 5: Name of fault 152 --- Past fault 6: Drive controller state 153 --- Past fault 6: Name of fault 154 --- Past fault 7: Drive controller state 155 --- Past fault 7: Name of fault 156 --- Past fault 8: Drive controller state 157 --- Past fault 8: Name of fault A66N2 Manual 17

Table 6: A66N2 Internal Integer (ADI) Point List (cont d) ADI Address 1 Bit Description 201 --- Drive controller horsepower (hardware rating) 202 --- Drive controller horsepower (configured rating) 203 --- Drive controller voltage range 204 --- Line frequency recognized 205 --- Drive controller maximum rated frequency 206 --- Drive controller nominal current 207 --- Drive controller maximum current 212 --- Memory card option 213 --- Communication carrier option 214 --- Presence of keypad 215 --- I/O Extension option card 217 --- PCMCIA communication card 222 --- State of command node 223 --- Token rotation time 224 --- Token count 225 --- Messages received 236 --- Command semaphore 1 N2 ADI addresses are offset from the Altivar 66 internal registers (as listed in the Modbus/JBUS communication card manual) by 2000. Thus, ADI 1 is the same as the Altivar 66 register 2001, etc. 18 A66N2 Manual

4 Troubleshooting A66 card not responding In most cases, this indicates faulty network wiring. With the drive powered and the A66 card connected to an active network, the LED indicators on the top of the card provide some information. If the GREEN LED flashes, it indicates that the card is seeing network traffic. If the RED LED flashes, it indicates the previously received message is in error. If the RED LED flashes on every message, it could mean the network wires could be switched (A for B, or + for -). If the card is wired correctly but fails to communicate, double-check the Communication Setup in Menu 11. The A66P1 should have a unique network address. See the installation and configuration information on page 7. Inconsistent communication If communications can be established with the A66 card but the communication is inconsistent, network noise could be causing messages to be lost on the network. In this case, the RED LED on the top of the A66 card will be flashing occasionally indicating an incomplete message or one with a failed checksum. The card does keep a running count of messages received with checksum errors. This statistic is reported on Menu 12 of the Altivar Drive, under Token Good: X ms. X will be an integer counter of the number of messages the card has received with checksum errors. This counter counts up to 65535 and stops. The counter may be reset by cycling power on the drive. When checksum errors on the network are interfering with communications, the network wiring must be evaluated for noise immunity. The network wiring should be as isolated as possible from the inherently noisy motor leads from the VFD. Where Faraday (grounded metal) shielding cannot be between the motor leads and the network wiring, keep the wires as physically separate as possible. In as short a run as possible, get the network wiring into its own grounded metal enclosure, or out of the metal A66N2 Manual 19

enclosure containing the motor leads. All network wiring should be run through shielded conduit to avoid electromagnetic interference. 20 A66N2 Manual