InBin-P Pressure switches from 5 Pa Pa

Similar documents
ExBin-D Transducers for ExPro-B... sensors (probes) ExPro-B... Thermostats / humidistats ( C, % rh)

InCos-P Pressure sensor 20 Pa Pa

InReg Volume flow controller Pa

ExCos-P Pressure sensor 20 Pa Pa

Transmitter for Temperature / humidity sensors. Compact. Easy installation. Universal. Cost effective. Safe.

Connectable sensors (compulsory for ExCos-D.. transducer) have a look on separate data sheet

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

ExReg-V Volume flow controller Pa

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

RТTH DUAL ROOM SWITCH

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

VAV compact controller KNX / PL-Link

HMT330 Series Humidity and Temperature Transmitters for Industrial Applications

DP DP2500 DP0250

Insertion Flowmeter for compressed air and gases DN50 - DN700 (2-28 )

CDD4 Duct Carbon Dioxide Transmitter

Millenium II +: general characteristics

DP2500 DP0250. Differential Pressure Transmitter. Product Bulletin

VAV compact controller GDB181.1E/3 GLB181.1E/3

RXTP ROOM TEMPERATURE

Output Signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power Supply DC V, ±10%, 0.3 W

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Screw terminal panels, Relay output boards, connection cables

RXTH DUAL ROOM SENSOR / SWITCH

Installation and User Guide

14 Pressure Measurement. Measuring Devices Description Pressure range Connection Device Page

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

PTU300 Combined Pressure, Humidity and Temperature Transmitter

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

Inductive sensor with analog output BI15-M30-LI-EXI

Output signal active note. Output signal. temperature DC V, DC V DC V, DC V DC V

Product data sheet accessories control and regulation Accessories AIRWIN

THERMASGARD TM 65. Immersion screw-in duct temperature measuring transducer, calibratable, with multi-range switching and active output TECHNICAL DATA

Inductive sensor NI3-EG08K-Y1-H1341

Inductive proximity switches with long operating distance, series 500

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

Technical data. Dimensions: see page 116. ): 4 kv Rated insulation voltage (U i Over-voltage category: Power supply. Rated operating voltage (Un):

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Operating Instructions Differential Pressure Transducer PS27

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Precision humidity/temperature control/sensing

Temperature and humidity regulator H3020 H3021 H3023 H3027. Instruction Manual

Datasheet DE DB_EN_DE44_LCD Rev. ST4-C 07/17. Digital 2-channel differential pressure switch/transmitter with colour-change LCD * *

Output signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power supply DC V, ±10%, 0.3 W

Inductive sensor BI1.5-EG08-Y1-H1341

Motor protection relays

CAEL-DP Series Dew Point Transmitter for Industrial Control

Inductive sensor BI1.5-EG08-Y1-H1341

Immersion Temperature Sensors

Technical Data. General specifications. Rated operating distance s n 3 mm

Temperature Switches

Magnetic field sensor Magnetic-inductive Proximity Sensor BIM-M12E-Y1X

TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O

Output Signal. Temperature 22DTH-56M BACnet DC V, DC V. Electrical Data Power Supply DC V, ±10%, 0.7 W

Operating Instruction

Flow measurement FlexFlow PF20S Flow sensor for industrial applications

Humidity transmitter for critical climate applications

Compact Coded Magnetic Safety Interlock Switch and Control Units

TFR5. Room or outdoor temperature sensor. Operating instructions for temperature sensor. English page 1...5

Digital electropneumatic positioner

VAV modular controller

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Digital electropneumatic positioner

PCD DIGITAL Differential pressure probe

asense m III in industrial wall mounted housing / CO sensor with built-in general purpose controller

Operating Instructions for Digital Thermometers. Model: DTM

TRANSMITTERS. HygroFlex & HygroClip-EX. Applications. Highlights

MODEL: M5DY SEN TRONIC AG CURRENT LOOP SUPPLY. [2] POWER INPUT AC Power M: V AC (Operational voltage range V, Hz)

EE360. High-End Moisture in Oil Transmitter. Typical applications. Features EE360 EE360. (+34)

LMP 308. Separable Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO / 0.

CDD Carbon Dioxide Transmitter

Rotary Measuring Technology

Distance and Position Sensors

Digital input modules

VAV compact controller

Modular pressure transmitters for harsh environments DST P500, DST P507 and DST P550

Rated operational Control Voltage Uc Supply Voltage Connection Rated operational current 40 C voltage Ue Us 25A AC-53a 32A AC-53a

EC centrifugal module - RadiPac

Power supply module, bus connection module

The industrial humidity transmitter

CombiTemp TFRN/TFRH. Operating instructions. Temperature sensor. Operating Instructions: EN.

EC axial fan - HyBlade

Inductive angle sensor with analog output Ri360P1-DSU35TC-ELi-Exi

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

Thread length (overall length) material

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

Differential Pressure Controller DPC 200

E2A. Ordering Information. Cylindrical Proximity Sensor. Safe Mounting with Greater Sensing Distance. E2A Cylindrical Proximity Sensor 1

EC centrifugal module - RadiPac

5 Fieldbus Technology

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

LED unit. Selection diagram LED COLOUR white LED red LED green LED blue LED orange LED INDICATION MODE CONNECTIONS MOUNTING TYPE

Ordering Key. Type Rated Operational Rated operational Control Voltage Uc Options

HMT360 Series Intrinsically Safe Humidity and Temperature Transmitters

Ferrous metal (The sensing distance decreases with non-ferrous metal.) Power supply voltage (operating voltage range)

VM series. features. web contents. code description. available models. inductive sensors. Cylindrical M12 in AC B H

Transcription:

InBin-P Pressure switches from 5 Pa...100 Pa Electrical, binary pressure or differential pressure switches with adjustable switch activation delay 24 VAC/DC supply voltage, potential free switching contact InBin - P-100 InBin - P-100 - CT InBin - P-100 - OCT Subject to change! Compact. Easy installation. Universal. Cost effective. Safe. Type Sensor Supply Range Min. setting Max. pressure Output switch Max. ratings Wiring diagram InBin - P-100 Pressure 24 VAC/DC 0...100 Pa 5 Pa 5.000 Pa pot. free contact 250 VAC, 0,1 A / 30 V, 0,5 A SB 1.0 InBin - P-100 - CT as above with aluminium housing and Amercoat painting (sensor connection and cable glands nickel-plated, screws in stainless steel) InBin - P-100 - OCT as above offshore version seawater-resistant, with aluminium housing and Amercoat painting (stainless steel tubes for clamping ring connection, cable glands M20 1,5 mm nickel-plated, screws in stainless steel) Application Pressure or pressure switch Amercoat version...-ct Offshore version...-oct Description The InBin-P-100 pressure switch generation from 5...100 Pa is a revolution for differential pressure switches in HVAC systems, in chemical, pharmaceutical, industrial and Offshore-/Onshore plants. IP66 protection, small dimension, universal functions and technical data guarantee safe operation even under difficult environmental conditions. The switching point is scalable within the maximum ranges. The integrated display is for actual value indication which can be switched off. All sensors are programmable on site without any additional tools. InBin-P-100-OCT is equipped with stainless steel 316L tubing Ø 6 mm. Highlights For industrial use Integrated junction box Power supply 24 VAC/DC Output potential free switching contact Display with backlight, can be switched off Adjustable switching characteristics Adjustable hysteresis Adjustable starting bypass time Adjustable switch activation delay Compact design and small dimension ( L B H = 180 107 66 mm ) Robust aluminium housing in protection class IP66 Down to 20 C ambient temperature applicable Password locking CT versions have an excellent resistance to chemicals and seawater OCT as CT version plus pressure tube connection for clamping ring Ø 6 mm 1 / 6

Technical data Power supply 24 VAC/DC ± 20% (19,2 28,8 VAC/DC) 50 60 Hz Current, power consumption 150 ma, ~ 4 W, internal fuse 500 mat, without bracket, not removable Galvanic isolation Supply 1,5 kv Electrical connection Terminals 0,14 2,5 mm² at integrated junction box, stripping length 9 mm, torque 0,4 0,5 Nm Cable entry 2 M16 1,5 mm, cable diameter ~ Ø 5 10 mm (...-CT in nickel-plated) Cable entry...-oct 2 M20 1,5 mm, cable diameter ~ Ø 6 13 mm (...-OCT in nickel-plated) Display LCD with backlight, display for configuration, user guidance, parameter and actual value indication via LEDs Control elements 3 buttons for configuration Housing protection IP66 in acc. to IEC 60529 Housing material Aluminium casting, coated (...-CT/...-OCT = version in Amercoat marine painting, seawater-resistant...-oct = Offshore version) Dimension / weight L W H = 180 107 66 mm / ~ 950 g Ambient temperature/-humidity 20 +50 C / 0 95 % rh, non condensed Storage temperature 40 +70 C Measuring range 0 100 Pa Range scalable on site Minimum measuring range is 5 % of full range = 5 Pa Maintenance Maintenance free, nevertheless maintenance must be complied with regional standards, rules and regulations Sensor circuit Internal circuit Sensor Piezo-pressure-transmitter Pressure connection P+ / P sleeves Ø 4 6 mm, OCT-version has a Ø 6 mm stainless steel tube connection for clamp ring fittings Response time of sensor T90 / 5 sec. Accuracy of pressure < ± 1 % typically, max. ± 5 % of end value ± 1 Pa Setting range hysteresis 0,1 Pa 10 Pa (factory setting 2 Pa) Start delay 5 sec. Starting bypass time 3 240 sec. (via menu adjustable; preset 120 sec.) Switch activation delay 0...240 sec. (via menu adjustable; preset 0 sec./off) Setting zero point Via menu, mechanical short circuit of P+ / P for the moment of zero point setting Output switch Potentail free switching contact Ratings load max. 0,5 A at 30 VAC/DC / 0,1 A at 250 VAC / 0,1 A at 220 VDC Ratings load min. 10 mw / 0,1 V / 1 ma Mechanical life 10 10 6 Electrical life (rated load) 100 10 3 Wiring diagram (SB) SB 1.0 Installation sensor / tubing Safe area Approbations Accessories CE-Mark CE No. 0158 EMC directive 2004/108/EC Low voltage directive 2006/95/EC Protection type IP66 in acc. to EN 60529 Potential compensation external PA-terminal, 4 mm² Protection Class Class I (grounded), overload voltage category II acc. EN 61010-1 MKR Kit 2 Kit PTC Mounting bracket for round ducts up to Ø 600 mm Consists of 2 m flexible pressure tube Ø 6 mm, 2 connection nipples consisting of 2 connecting tubes Ø 6 mm for tube fittings 2 / 6

Electrical connection InBin-P-100 switches are equipped with a 24 VAC/DC power supply. The supply has to be connected at terminal 1 ( /~) and 2 (+/~). The electrical wiring must be realized via integrated junction box. If supply voltage 24 VAC/DC differs from the relay voltage different or double isolated cables must be used.the starting bypass delay can be activated by a short circuit of terminal 2 and teminal 3 (AUB). An active bypass delay is indicated with blinking LEDs. Attention: Do not open covers when circuits are alive! Wiring diagram InBin-P-100 InBin-P-100 SB 1.0 24 VAC/DC + ~ ~ PE AUB 1 2 3 4 Relay 250 VAC 0,1 A / 220 VDC 0,1 A 30 VAC/DC / 0,5 A SW-IN (GND) SW-Ch1 5 6 PA If supply voltage 24 VAC/DC differs from the relay voltage different or double isolated cables must be used. function close (nc) or open (no) can be selected via menu Password input The default / delivery setup is 0000. In this configuration the password input is not activated. To activate a password change the 4 digits into your chosen numbers (e.g. 1234) and press Enter. Please keep your password in mind for next parameter change! Due to a new parameter setup the password is requested. Important information for installation and operation A. Installation, commissioning, maintenance The cable has to be drawn through the cable gland. After electrical connection the cable gland must be fixed tighten. IP66 must be fulfilled. In acc. with operation InBin switches are maintenance free. The sensors must not be opened by the customer. For electrical connection use the internal junction box. Attention: Before opening the internal junction box cut off the power supply. B. Supply and Contact Wires from safety extra low voltage must be separated from others. Only at 24 VAC/DC supply and signal wires in one cable is permitted. All others use separate or double isolated cables. Install overload protection fuse < 10 A. C. Pressure sensors After mounting and installation, a zero point compensation must be done, because the offset value depends on the installation position. Have a look at parametrisation. D. Long cabling For using long signal wires, shielded cables are recommended. The shield must be connected to the InBin-P switch inside the terminal box. E. Separate ground wires Use for supply and signal wires a separate ground. Display and buttons Installation Safe area Dimensions in mm 157,5 67 80 107 117 Display for programming and indication Push button ENTER Push button for level select Change operation- / parametrisation mode To change from operation to parametrisation mode push the enter button minimum 3 seconds. Back over the menu save. Indication of data logging A blinking unit in the display shows that data is received and the device is working. Dimensions / drillings 132 166 66 55 ~ 180 213 170 for P+ P Supply 24 VAC/DC Relay 250 VAC/0,1 A 30 V/0,5 A Maintenance must comply with regional standards, rules and regulations Do not open covers when circuits are alive For electrical connection use the integrated junction box The cable must be installed in a fixed position and protected against mechanical and thermical damage Connect protection earth Avoid thermal transfer from sensor probe to transducer (ensure max. ambient temperature). Ambient temperature 20 +50 C Close all covers, entries with min. IP66 All transducers are maintenance free For outdoor installation a protective housing against rain, snow and sun should be applied Only wet cleaning Zero point compensation for pressure transmitter For a InBin-P-100 pressure switch installation a zero point compensation should be performed to adjust value deviations of the module s installation position. Therefore the pressure nipples P+ / P must be connected with a short circuit tube and the zero point compensation accomplished by following the menu. Before starting the compensation the device should be connected to the power supply for minimum of 15 minutes to reach the working temperature! 3 / 6

Parametrisation and commissioning of InBin-P-100 transducers Preparation of parametrisation / operation Operation Parametrisation, push for 3 sec. If password (PW) protection is active: put PW in, push Change operation- / parametrisation mode To change from operation to parametrisation mode push Enter button for minimum 3 seconds. Back over the menu save. Menu Function Enter Indication Select Enter Next indication Next selection Enter Next menu Menu 1 Preset select application Menu 2 unit sensor 1 select physical unit Pa, mbar, InH2O Menu 3 set 1 select switching point 1 Menu 4 adjust set 1 Menu 5 hysteresis* select physical unit adjust hysteresis Menu 6 mode* select switching charateristic norm. open (no), norm. closed (nc) select sensor interval Menu 7 Menu 8 Menu 9 Menu 10 Menu 11 Menu 12 time select time for starting bypass (AUB) and switch activation delay Menü 13 lamp select backlight Menu 14 zero point compensation adjust bypass time** on, off adjust switching off delay*** Menu 15 Menu 16 security select password save select save data enter password no, yes, return, default setting * Useable in professional mode only (see Menu 1 professional mode) ** Bypass delay *** Switch activation delay: With this function the condition operation can be hold for the selected time. Setting the switching off delay to 0 will deactive the function. 4 / 6

Using the menu 1 Preset To beware complexity during the parametrisation process, the InBin-P has several pefined setups which distinguish between its intended application. You'll find a detailed desciption of all possible presets in the following section. Fan speed monitoring The preset FAN is designed for use in fan speed monitoring applications. Menu1: Select "FAN" and press the enter button. If the FAN -preset has been selected in menu 1, all settings were made as the following ones: The user has not to set the menu 5 hysteresis and menu 6 mode, this will be done via software. These menus will be skipped during the further parametrisation process. Filter monitoring air flow The preset FILT is designed for use in filter monitoring applications. ventilator Professional mode For all other applications the professional mode is designed for. Using the menu 6 mode Menu1: Select PRO and press the enter button. If the PRO -preset has been selected in menu 1, the parametrisation procedure will be added by two further menus: menu 5 hysteresis and menu 6 mode. For this preset the user has to select the values for the hysteresis and for the mode. First of all the user has to define the device range. For example: - The device should indicate ( LED) if the pressure is under the setpoints, mode down-range has to be selected. With other words: the measure value is ly under the setpoints. - The device should indicate ( LED) if the pressure is over the setpoints, mode up-range has to be selected. (The measure value is ly over the setpoints.) - The device should indicate ( LED) if the pressure is between the setpoints, mode mid-range has to be selected. (The measure value is ly between the setpoints). This mode is only for 2-stage devices available (InBin-P...-2). In the second step the switching characteristic of the relay has to be selected: - ly closed (nc): if the measure value is in the range (see above), the corresponding relays were closed. - ly open (no): if the measure value is in the range (see above), the corresponding relays were open. You'll find a detailed desciption of all possible settings in the following section. Switching characteristic up-range ly closed Up-range : the range is above and Filter Air flow Menu1: Select FILT and press the enter button. If the FILT -preset has been selected in menu 1, all settings were made as the following ones: The user has not to set the menu 5 hysteresis and menu 6 mode, this will be done via software. These menus will be skipped during the further parametrisation process. 5 / 6

Switching characteristic up-range ly open Up-range : the range is above and Switching characteristic down-range ly closed Mid-range : the range is under and Switching characteristic mid-range ly closed Mid-range : the range is between and (for 2-stage devices only) Switching characteristic down-range ly closed Mid-range : the range is under and Switching characteristic mid-range ly open Mid-range : the range is between and (for 2-stage devices only) 6 / 6