LINETRAXX RCMS150. Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems)

Similar documents
ISOMETER isoev425 with coupling device AGH420

ISOMETER isoev425/isoev425hc with coupling device AGH420

ISOMETER isopv with coupling device AGH-PV

COMTRAXX COM465IP. Condition Monitor with integrated gateway for the connection of Bender devices to Ethernet TCP/IP networks

COMTRAXX COM465IP. Condition Monitor with integrated gateway for the connection of Bender devices to Ethernet TCP/IP networks

COMTRAXX COM465DP. Condition Monitor with integrated gateway for the connection of Bender devices to PROFIBUS DP and Ethernet TCP/IP networks

COMTRAXX COM460IP. BMS-Ethernet-Gateway

ISOMETER iso685-d-b. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Preliminary data sheet

COMTRAXX COM465IP. Condition Monitor with integrated gateway for the connection of Bender devices to Ethernet TCP/IP networks

BMS-Ethernet-Gateway COM460IP

VMD420-DM Voltage and frequency monitor

T M. IRDH375 Series. Digital Ground Fault Monitor / Ground Detector For Ungrounded (Floating) AC/DC Systems. Technical Bulletin NAE / 09.

preliminary ISOMETER isoev425 with coupling device AGH420 Preliminary datasheet

RCMB20/RCMB Series

VEO. V2UF230V10 Art.Nr.: TECHNICAL DATA

RCM420-DM. Residual current monitor for AC current monitoring in TN and TT systems with an analogue interface Software version: D240 v1.2x.

02/11/2015

VEO. V2ZR V AC/DC Art.Nr.: V2ZR10P V AC/DC Art.Nr.: TECHNICAL DATA

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Control elements. Fine adjustment. Status indication. 24 V DC typ. 0,25 W / 0,25 VA. 24 V DC typ. 0,03 W / 0,09 VA. 0,15 3 s. 0,5 10 h.

CC612 EV charge controller

RCMA420-DM Residual current monitor

VEO. V2ZS V AC/DC Art.Nr.: V2ZS20P V AC/DC Art.Nr.: TECHNICAL DATA

RM35UB3. Product data sheet Characteristics. voltage control relay RM35-U - range V AC. Main. Complementary

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

RM17UB3. Product data sheet Characteristics. voltage control relay RM17-U - range V AC. Main. Complementary

Contact protection relay

Zelio Control-modular measurement and control relays 1

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

RM17UAS. Product datasheet Characteristics. voltage control relay RM17-U - range V DC. Main. Complementary. Price* : 70.

RM35TF V AC

Electronic timer CT-ERS.21

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

RM35JA32MR Current control relay 0.15A 15A, 2 C/O

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E

Electronic timer CT-ERD.12

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Electronic timer CT-AHD.22

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA

TU531, TU532 Terminal Unit

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

Electronic timer CT-AWS Impulse-OFF with 2 c/o contacts Data sheet

Power supply CP-C 24/5.0

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

RM17TG. Main. Product or component type. Product specific application. Relay monitored parameters. Switching capacity in VA 250 V AC

RM35LM33MW liquid level control relay RM35-L V AC/DC

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

PHOENIX CONTACT - 07/2006

MIC-2 MKII, Multi-instrument DATA SHEET

RM22TG. Product data sheet Characteristics. three-phase control relay Vac, 2 C/O. Main. Complementary. Network number of phases

Electronic timer CT-ARS.11

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description

RTU500 series Data Sheet Power Supply CP-E 24/2.5

RM17UB3. Price* : USD

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Messaging module CP-C MM

AO523 Analog Input Module

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

RM22LA32MR Level control relay RM22-L V AC/DC - 2 C/O

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

Switching relay CT-IRS with 1, 2 or 3 c/o contacts Data sheet

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

PHOENIX CONTACT Features

AI531 Analog Input Module

Nemo SX - Multifunction control module

QUINT-PS/ 1AC/24DC/ 5

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

QUINT-DC-UPS/24DC/10. Extract from the online catalog. Order No.:

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

RE22R2CMR Off-delay Timing Relay s 300h V AC/DC - 2C/O

Electronic timer CT-VWD Impulse-ON with 1 c/o contact Data sheet

Digital input modules

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

QUINT-DC-UPS/24DC/10. Extract from the online catalog. Order No.:

Three-phase monitoring relay

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

RE22R2QGMR Star-Delta Timing Relay s 300h V AC/DC - 2C/O

RE22R2KMR Off-delay Timing Relay s 10min V AC/DC - 2C/O

JUMO Quantum PID100/PID200/PID300

TF501, TF521 Terminal Bases

Switching relay CT-IRE with 1 c/o (SPDT) contact

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

FL MC 2000E (SM40) LC

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

AX522 Analog Input/Output Module

Faults on the system Proximity switch connection technology:

Zelio Control - modular measurement and control relays 1 Speed control relays RM35 S

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

ETD-BL-1T-OFF-CC- 10S

Transcription:

LINETRAXX RCMS150 Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems) RCMS150_D00259_00_D_XXEN/09.2016

LINETRAXX RCMS150 Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems) Product description The 6-channel residual current monitor RCMS150 is intended for measurement of AC and DC fault currents in earthed systems, which can emerge from insulation faults on loads with six-pulse rectifiers or one-way rectifiers with smoothing. The device can measure residual currents up to I Δ = 500 ma in a frequency range of DC 0 2 khz. Two separately adjustable response values allow a distinction to be made between prewarning and alarm. The device features an RS-485 interface which can be used to transfer measured values and alarm values. Setting parameters is also possible via this interface. LINETRAXX RCMS150 Device features Continuous residual current monitoring in compliance with DGUV Vorschrift 3 (German Social Accident Insurance Regulation 3) AC/DC sensitive residual current monitor type B with 6 channels K1 6 (each channel features 2 measuring channels: 1 x RMS, 1 x DC) Compatible with RCMS460/490 in a system setup Ideal for applications with space limitations Easy DIN rail or screw mounting to standard distribution panels 2 separately adjustable response values (DC or r.m.s.) per channel Continuous self monitoring Fully shielded measuring current transformers to avoid external influences due to magnetic fields that may cause disturbances Compatible with Bender gateways of type COM465IP, CP700 Up to 534 measuring channels in the monitored system that can be combined via BMS bus RS-485 interface with BMS bus (Modbus RTU on request) BMS address range 2 90 Intended use The device RCMS150 is suitable for measuring residual currents up to I Δ = 500 ma in a frequency range of DC 0 2 khz. The monitored circuit is rated for a voltage of 300 V and a load current of 32 A. The device can be operated at an altitude of up to 2000 m above mean sea level. Function description The residual currents are recorded and evaluated as r.m.s. values in the frequency range DC 0 2 khz. The response values can be set via the connected gateways. The user can set four response values per channel 1 6: I Δn1 RMS, I Δn2 RMS, I Δn1 DC, I Δn2 DC. If one of the four set response values I ΔN is exceeded, the assigned response delay t on starts. If the response value continues to be exceeded, the corresponding message (prewarning or alarm) is displayed on the gateway after the response delay t on has elapsed. In the event of an alarm, the alarm LED of the respective channel K1 6 lights up yellow. If the recorded residual current falls below the release value (response value minus hysteresis) the delay on release t off begins. If the value remains below the release value after t off has elapsed, the message on the gateway is reset. If the alarm LED of the respective channel has been lit, now it goes out. A pending response value violation is emitted via the BMS interface with address and measuring channel indication and can be evaluated by means of a gateway. All devices can be accessed via the network from any PC using a standard web browser (Firefox, Internet Explorer). Like this, all relevant measurement data of the monitored system are available. All device-related parameters of the RCMS150 can be set via the gateway technology. To ensure the device function, a continuous automatic self test is run, which monitors the function of all measuring current transformers. In the event of a device error, all alarm LEDs flash. Approvals and certifications UL508 in preparation CSA in preparation 2 RCMS150_D00259_00_D_XXEN/09.2016

Residual current monitor LINETRAXX RCMS150 Display and operating controls 1 2 3 4 5 ON/COM x1 x10 6 8 7 1 - Slot for screw mounting 2 - Alarm LEDs for the measuring channels K1 6 3 - Line feed-through of the measuring current transformers for the measuring channels K1 6 4 - ON LED: Power On LED 5 - Determination of ones' position of the BMS address 6 - Determination of tens' position of the BMS address 7 - Connection to the supply voltage 8 - Connection RS-485, BMS bus Wiring diagram L1 L2 L3 N PE PE ON/COM x1 x10 1 circuit 1 circuit 2 circuit 3 circuit 4 circuit 5 circuit 6 1 - Residual current monitor RCMS150 2 - Supply voltage U S DC 24 V 3 - RS-485 interface with BMS bus (Modbus RTU on request) 4 - Terminating resistor (required at the beginning and at the end of the bus) 3 Note: Only insulated primary conductors suited for the indicated rated voltages are to be used! 2 A B +24V GND 4 RCMS150_D00259_00_D_XXEN/09.2016 3

Residual current monitor LINETRAXX RCMS150 Technical data Insulation coordination according to IEC 60664-1 The data are valid for the monitored primary circuit to the output circuit Output circuit (+, -, A, B) Rated insulation voltage 300 V Overvoltage category III Rated impulse withstand voltage monitored circuit/output circuit 4 kv Range of use 2000 m AMSL Rated insulation voltage 250 V Pollution degree 3 Insulation BI: Overvoltage category III DI: Overvoltage category II To achieve double insulation (DI) for overvoltage category III, insulated primary conductors with sufficient rated voltage must be used on the application side. Voltage test acc. to IEC 61010-1 AC 2.2 kv Power supply Nominal supply voltage U S with galvanic separation Power consumption Residual current measuring range Frequency range Measuring range Resolution measured value DC 24 V < 4 W 0 2000 Hz ±500 ma 1 % of the set response value Response values Residual current I ΔN2 RMS 0 300 ma (30 ma)* Residual current I ΔN2 DC 3 300 ma (6 ma)* Ratio I ΔN2 RMS/I ΔN2 DC 0.2 5 Prewarning I ΔN1 RMS/DC 50 100 % (50 %)* Response tolerance I ΔN2 DC 10 500 Hz -20 0 % 500 Hz 2 khz -20 +100 % Hysteresis 10 25 % (15 %) Time response Start-up delay t start-up Response delay t on1 RMS/DC t on2 RMS/DC Delay on release t off1 DC t off2 RMS normal operation indication internal device fault or BMS bus address set incorrectly indication BMS bus address (after device start/address modifica- Indication (LEDs) ON green green (flashing quickly) green (flashing slowly) tion) ALARM K1 6 yellow yellow (flashing) 0.5 600 s (0.5 s)* 0 600 s (0 s)* 0 600 s (0 s)* 0 600 s (1 s)* 0 600 s (1 s)* I Δ > I Δn measured value range exceeded Interface Interface/protocol RS-485/BMS Connection terminals A/B Shielded cable (one end of shield connected to PE) twisted pair, e.g.: J-Y(St)Y 2x0.8 Cable length 1200 m Bus terminating resistor external 120 Ω (0.25 W) Device address, BMS bus 2 90 (2)* Environment/EMC EMC immunity IEC 61000-6-2 emission IEC 61000-6-3 Operating temperature -25 +70 C Classification of climatic conditions acc. to IEC 60721: Stationary use (IEC 60721-3-3) 3K5 Transport (IEC 60721-3-2) 2K3 Long-term storage (IEC 60721-3-1) 1K4 Classification of mechanical conditions acc. to IEC 60721: Stationary use (IEC 60721-3-3) 3M4 Transport (IEC 60721-3-2) 2M2 Long-term storage (IEC 60721-3-1) 1M3 Connection Connection type pluggable push-wire terminal Connection properties: rigid, flexible/conductor sizes AWG 0.2 1.5 mm²/awg 24 16 Multi-conductor connection (2 conductors with the same cross section): rigid 0.2 1.5 mm² flexible 0.2 1.5 mm² flexible with ferrule without plastic sleeve 0.25 1.5 mm² flexible with ferrule with plastic sleeve 0.25 0.75 mm² Stripping length 10 mm Other Operating mode continuous operation Position of normal use any Enclosure material polycarbonate Flammability class UL94 V-0 Screw mounting to standard distribution panels with 12 TE 2 x M6 DIN rail mounting mounting clip (accessories) Tightening torque 1.5 Nm Documentation number D00259 Weight 170 g Measuring current transformer Diameter cable gland Load current Bus parameter Alarm Measured value Times ( )* = factory settings 10 mm 32 A threshold value exceeded, system fault measured value, DC component, r.m.s. (resolution 0.1 ma) response delay, delay on release, start-up delay 4 RCMS150_D00259_00_D_XXEN/09.2016

Residual current monitor LINETRAXX RCMS150 Example for a system design ON/COM x1 x10 RCMS150 COM465IP * 120 Ω 120 Ω (DIP switch COM465IP) * Optionally CP700 Ordering information Nominal supply voltage U S DC Type Art. No. 24 V RCMS150 B 9405 3025 Dimension diagram Dimensions in mm 10 245 Accessories 38 Description Art. No. Mounting clip for DIN rail mounting B 9108 0110 205 Suitable system components 3 26 Description Type Art. No. 230 6 Condition Monitor with integrated gateway COM465IP 1) B 9506 1065 Condition Monitor CP700 1) B 9506 1030 RS-485 repeater DI-1DL B 9501 2047 Power supply AN410 B 924 209 RCMS460-D-1 B 9405 3001 Residual current monitor 2) RCMS460-D-2 B 9405 3002 RCMS490-D-1 B 9405 3005 RCMS490-D-2 B 9405 3006 1) from function module C 2) suitable for measured value and alarm indication only, not suitable for parameter setting 4 RCMS150_D00259_00_D_XXEN/09.2016 5

Bender GmbH & Co. KG P.O. Box 1161 35301 Grünberg Germany Londorfer Straße 65 35305 Grünberg Germany Tel.: +49 6401 807-0 Fax: +49 6401 807-259 E-mail: info@bender.de www.bender.de BENDER Group RCMS150_D00259_00_D_XXEN / 09.2016 / pdf / Bender GmbH & Co. KG, Germany Subject to change! The specified standards take into account the version that was valid at the time of printing.