CONTROLLER INSTALLATION OPERATION & QUICK START

Similar documents
Application Engineering

USER'S GUIDE BARD-LINK TM LC /LC SOLID STATE DUAL UNIT LEAD/LAG CONTROLLER & TEC-EYE HAND-HELD DIAGNOSTIC TOOL

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

INSTALLATION INSTRUCTIONS

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

WALL MOUNTED PACKAGE AIR CONDITIONER REPLACEMENT PARTS MANUAL. Models: WA181, WA241. Contents. General Notes. Important

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller

Submittal Data Sheet intelligent Touch Manager DCM601A71

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units

Models: WA182, WA242. Contents. Cabinet Components. Control Panel. Blower Assembly. BARD MANUFACTURING COMPANY Bryan, Ohio 43506

Product Manual SZ2141

SEZ7656E1045B. Installation Guide for BACnet MS/TP RTU Terminal with IAQ Control CONTENTS

CDD Carbon Dioxide Transmitter

Millennium Simplicity Elite Parameter Points and Quirks

INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST

Prodigy Control System Premium Rooftop Unit Control

INSTALLATION INSTRUCTIONS MBPEFY Series Mixing Box for Mitsubishi PEFY Series Units. Before Starting Installation Warning. Installation Instructions

Installation Guide (3/6 Outputs)

FX 2 Instruction Manual

Installation Instructions

ADVANCED PROGRAMMING & FEATURES

4-step Chiller and Heat Pump Controller

Specification and Design Catalog. Waterside Economizer

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet

Custom Controller Installation Instructions

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

L Connection Network Control System For Energence Rooftop Units

Daikin HVAC Controls Guide Specification

RDF Series Room Temperature Controllers

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

RS-485 Modbus RTU Networking Room Thermostats with LCD for Fan Coil Units

SEZ7656R1045B / SEZ7656H1045B

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

SE7600E Series Application Guide

SEZ7260X5x45B Installation Guide for BACnet MS/TP Zone Controller

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

Operation Guide CT32 ENGLISH

Home Manager System Model TS40B Wall Display Operating Instructions

C7110C1001A / C7110D1009A WALL MODULES

BA/BS4S Temperature Sensor Installation & Operating Instructions

VTR8300 User Interface Guide VTR8300 Room Controller Series

M1000 INTELLIGENT ZONE CONTROL SYSTEM

Wiring Diagrams INDEX. UNIT DESCRIPTION DRAWING NUMBER FIG. NO. 09DK Field Wiring 09DK DK054,064

System 450 Series Reset Control Modules with Real-Time Clock and Relay Output

Economizer Controller Installation Guide

INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST

BACVIEW MANUAL Software Version 3.06 INSTALLATION AND OPERATION MANUAL

RS-485 Modbus RTU Networking FCU Thermostats with 0(2)-10 VDC Fan Output

ECONOMIZERS. Z1ECON30B-1 ECONOMIZER (Cat No. 10Z29) INSTALLATION INSTRUCTIONS FOR ECONOMIZERS USED WITH ZC,ZG,ZH UNITS CAUTION WARNING

DataNab it8: Intelligent Communicating Thermostat

CDD4 Duct Carbon Dioxide Transmitter

Installation, Start-up and Operating Instructions

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide

Product Manual SZ2144

GPC Plus Controller. General Information & Application Guide

BACnet Flow Controller for Fan Filter Units

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

MANUAL INSTALLATION + SERVICE. Price Intelligent Controller. PIC Series. v400 Issue Date: 12/18/ Price Industries Limited. All rights reserved.

BACnet MS/TP Interface User s Guide

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins

V0STAT51P-2 Programmable Wired Controller

MicroTech Unit Ventilator Controller

Application Engineering B U L L E T I N. AE R1 November Intelligent Store Discus V1.0 Operators Manual

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

SUPPLEMENTAL MANUAL FACTORY-INSTALLED LENZE AC TECH VARIABLE FREQUENCY DRIVES (VFD) IN RENEWAIRE (ERV) VENTILATORS TABLE OF CONTENTS

INSTALLATION INSTRUCTIONS ECONOMIZERS WITH EXHAUST. For Use with Bard 3-1/2 through 6 Ton Wall Mount Air Conditioners and Heat Pumps

T7560A1036 Digital Wall Module

Installation & Operation Guide. Setra Systems, Inc. 159 Swanson Road, Boxborough, MA

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet

ESC 201. Installation and Operating Instructions Manual. SG Jan 2015

AE R6 July 2018 Electronic Unit Controller

PROLON INSTALLATION AND START UP GUIDE

SE7600F Series. Installation Guide for RTU with Modulating Heat CONTENTS

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

HE-6800 Series Humidity Transmitters with Temperature Sensor

SE7600E Series. Installation Guide for Commerical HVAC Applications CONTENTS

SER8300 Series Line Voltage Room Controller with Optional PIR Sensor Installation Guide

FCU-4 FAN COIL CONTROLLER

MicroTech 2000 Water Source Heat Pump Unit Controller

Field Installation Manual External Bolt-On Economizer for ComPac I Air Conditioners

Multi-Point Gas Detection and Control System

Carbon Monoxide (CO) Gas Detection and Control System

SK Installation Instructions

FACTORY CONTROLS SYSTEM. VAV/CAV Controller Technical Guide

INSTALLATION INSTRUCTIONS

RTD-W Installation Instructions

Wiring Diagrams UNITS WITH STARTING SERIAL NUMBER 3507Q

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit

SER8300 Series Line Voltage Room Controller with Optional PIR Sensor Installation Guide

BB5-Lite TECHNICAL MANUAL

PumpDrive. Self -cooling, motor-independent frequency inverter. Brief Instructions

FACTORY CONTROLS SYSTEM. MUA II Controller Technical Guide

CDD4 Series Room CO2 Transmitter Installation Instructions

Fast Route to Reliable Energy Savings ZIP Economizer

Operation Guide CT101

Transcription:

CONTROLLER INSTALLATION OPERATION & QUICK START Controller: 8403-066 ECU Series Controller Manual: 2100-559 Supersedes: NEW File: Tab 19 Date: 05-02-11 Page 1 of 6

TABLE OF CONTENTS Installation Note... Page 3 Controller Installation... Page 3 Controller Connections... Page 3 Start-Up Note... Page 4 Basic Operation... Page 4 Quick-Start Programming... Page 4 Model Selection & System Enabling... Pages 4 & 5 Temperature Setpoints & Notes... Pages 5 & 6 Page 2 of 6

*INSTALL NOTE: For optimum temperature sensor performance, the Bard ECU-Series Controller must be mounted on an interior wall and away from any heat sources, sunlight, windows, air vents, air circulation obstructions, and/or any other cause of erratic or false temperature sensing. Controller Installation: Mounting controller 1. Complete rough-in wiring using a minimum 18 AWG control wiring, see Controller Connections: Control Wiring for exact number of conductors. 2. Turn the hex screws in the bottom and top of Controller clockwise (inward) until they clear the cover. Remove Base Plate from controller. 3. Route completed wiring through Base Plate. 4. With the embossed UP arrows of the Base Plate pointing to the ceiling, fasten the Base Plate to the desired wall location or vertical 2x4 wall handybox. 5. Make appropriate control wire connections (see Controller Connections: Control Wiring) to the terminal blocks. 6. Replace Controller over Base Plate, being careful not to pinch/dislodge connections. 7. Turn hex screws in bottom/top of Controller counter-clockwise (outward) to secure cover. Controller Connections: Control Wiring Attach control wiring per control wiring diagram/terminal legend below. 8403-066 DIGITAL CONTROLLER +B -A IN4 IN3 GND IN2 24 COM 24V OUT 9 GND 7-9 OUT 8 OUT 7 RLY 6 SC 4-6 RLY 5 RLY 4 RLY 3 SC 1-3 RLY 2 RLY 1 UNIT LOW VOLTAGE TERMINAL BLOCK F E Y1 G W1 W2 Y R C 1 Terminal Function + B MSTP + (not used) - A MSTP - (not used) IN4 IN3 GND IN2 Outdoor Temperature Sensor Pressure Transduce r Sensor Ground s Lockout Alarm Type Communication s Communication s Form Inpu t 10K OHM Type 3 Inpu t Inpu t Inpu t 24 COM 24VAC Com 24V 24VAC OUT 9 GND7-9 OUT 8 OUT 7 Fan Motor Control Control Ground Unloader Solenoid Control Blower Motor Control Analog Output Analog Output Analog Output Analog Output 0-5 VDC, 0-700 PSIG Relay Closure 0-10VDC 0 or 5VDC PWM 0-10VDC 2 RLY 4 Heater Contactor # 1 Relay Output Relay 3 4 5 6 7 SC 4-6 24VAC to Relay Outputs 4-6 RLY 5 Heater Contactor # 2 R LY 6 (not used) R LY 3 (not used) Relay Output SC1-3 24VAC to Relay Outputs 1-3 RLY 2 Compressor Contactor Relay Output Relay Relay MIS-2852 C R LY 1 (not used) Page 3 of 6

START-UP NOTE: Upon initial power-up, indoor fan will cycle on for approx. 30 seconds, and then shut off. System will be in the OFF position. Default time and date will be 12:00 a.m., Jan. 1, 2000. - In order for the system to operate in either heating or cooling mode(s), the controller must be initially programmed with specific HVAC model number, specific System Enabling, and appropriate temperature Setpoints. Basic Operation: Home, Main Menu, and Override Screens Navigate the menus and change settings by pressing a combination of various arrow buttons and the Enter button. Push the: Enter button to select and/or exit value editing Up or Down button to move among entries Right or Left button to move among value fields Left button to return to the home screen Quick-Start Programming: Model Selection, System Enabling, and Temperature Setpoints Model Selection to select specific HVAC unit model from the Home Screen, press: 1. Right button to access the Main Menu Screen 2. Down button through entries to highlight Advanced 3. Enter button to select Advanced and enter Advanced Screen 4. Enter button again to select/enter Applications Screen 5. Controller will ask for Admin Level Password Factory Default Admin Level Password: BARD 6. Down button to highlight Additional Setup 7. Enter button to select/enter Additional Setup Screen 8. Enter button again to select/enter Unit Model Screen 9. Enter button again to highlight current model 10. Up/Down buttons to choose from available models: - W3*V Model Wall Mount 3-Ton Variable Capacity System (Factory Default) - W5/6*V Models Wall Mount 4/5-Ton Variable Capacity Systems - P60/72*V Models Packaged 5/6-Ton Variable Capacity Systems 11. Enter button to select/save appropriate model 12. Left button (5x) to navigate back to Home Page System Enabling to access system types from the Home Screen, press: 1. Right button to access the Main Menu Screen 2. Down button through entries to highlight System 3. Enter button to select System and enter System Screen 4. Enter button again to select System Enable 5. Up/Down buttons to choose between six (6) options. Page 4 of 6

System Enabling (Cont d.) Auto: Conventional System in Auto-Changeover mode. HVAC system will cycle heating and cooling automatically to stay within preset heating and cooling Setpoints. Heating: Conventional System in Heating-Only mode. HVAC system will cycle heating in reference to Heating Setpoint only. Unit will not activate cooling sequence. Cooling: Conventional System in Cooling-Only mode. Setpoint only. Unit will not activate heating sequence. HVAC system will cycle cooling in reference to Cooling Off: HVAC system is inactive. CCVC: Continuous Compressor, Variable Capacity application in auto-changeover mode. HVAC system will cycle heating and cooling automatically to stay within preset heating and cooling setpoints. Compressor will modulate from 100% to 20%, but will not shut off. Typically used for applications where cycling of compressor is not allowable due to use of on-site generators an MRI Mobile Trailer, for instance. CCFC: Continuous Compressor, Full Capacity Application in auto-changeover mode. HVAC system will cycle heating and cooling automatically to stay within preset heating and cooling setpoints. Compressor will not modulate, but will stay at 100% capacity and will not shut off. Typically, this mode is selected for testing purposes only. *NOTE: Upon initial start-up of any system-enable utilizing compressor, the unit may undergo a series of self-diagnostics, wherein a series of audible clicks are heard. This may delay compressor function for up to 5-minutes. 6. Enter button to select chosen operational mode 7. Left button to navigate back to Main Menu Screen 8. Left button to navigate back to Home Page Temperature Setpoints to access Setpoints from Home Screen, press: 1. Right button to access Main Menu Screen 2. Down button through entries to highlight Setpoints 3. Enter button to select Setpoints and enter Setpoints Screen - Use the Up/Down buttons to scroll through setpoints Cool Setpt / Heat Setpt are for occupied periods Cool Setback / Heat Setback are for unoccupied periods, and will only be used if scheduling is enabled (see the Advanced Programming section) Min Setpt Diff is the closest the Heating and Cooling setpoints can come to one another. (3 F is recommended minimum) Deadband is the space in degrees from setpoint in which the Cooling and/or Heating sequence will modulate to 100% capacity (2 F is recommended minimum). 4. Enter button to select specific Setpoint option 5. Up/Down button to enter specific degree amount for setpoint 6. Enter button to save new setpoint. 7. Left button to navigate back to Main Menu Screen 8. Left button to navigate back to Home Page *NOTE: Although the cooling/heating setpoints can be accessed by simply pressing the arrow keys during normal operation, any changes made in this fashion will be for a specific length-of-time as an override feature only. This temperature change will not be permanent. See the Advanced Programming section for further information. Page 5 of 6

**NOTE: Any system start-up conducted with indoor ambient temperatures lower than 56 F or above 86 F will experience an internal Low-Temperature or High-Temperature alarm. This will not affect normal operation, and can be cleared easily. See the Advanced Programming section for further information. Start-up procedures conducted with extreme temperatures indoors/outdoors may cause a SERVICE warning flashing on the face of the controller. This also will not affect normal operation, and should clear itself once interior temperatures and refrigerant pressures normalize. ***NOTE: ECU-Series Controller will become sluggish/inoperable at extremely low temperatures (< 20 F). Care should be taken to warm controller before initial start-up. ECU-Series Controller should be fully operational at this point. For further controller enhancement or operation detail, please consult the Advanced Programming section. Page 6 of 6