AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

Similar documents
AcquiSuite Ally 48 Advanced Branch Circuit Monitor

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS

BCM2 Series Branch Circuit Monitors Quick Setup Guide

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

PM Series Power Meter

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!

Models beginning with 2M, 2L or 2X. Product Description. Technical Specifications. Installation Instructions. Series 2000 Multiple Meter Units (MMUs)

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter

PowerLogic High Density Metering System 1-Meter Enclosure

DTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A

Technical Specifications. Multi Function Meter

Power Squad 12 Power Battalion 48

SEM3 - Embedded Micro Metering Module

USER MANUAL 2012 V1.1

GE Industrial Solutions. DET-756 Installation Instructions ASPMETER Panelboard Monitoring System

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

SECTION SWITCHBOARDS

ACCESS 9340/9360 Meter Input/Output Module

H704-42(H)(E), H704-42/1(H)(E)

PDI Modular Compact Remote Power Panel

MID PRELIMINARY DATA SHEET. RI-D Series. Single Phase Multifunction Energy Meter (MID Certified) MID

DKM-407 DIN RAIL TYPE NETWORK ANALYZER

Technical Specifications. Dual Source Energy Meter (EB / DG)

SECTION ( ) LIGHTING CONTROL PANELBOARD

MIC-2 MKII, Multi-instrument DATA SHEET

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

Power Meter PowerMonitor 500

PanelView Plus/VersaView CE Terminals and Display Modules

DKM-405 NETWORK ANALYSER WITH TOTAL HARMONIC DISTORTION DISPLAY

Technical Specificaions. kwh Energy Meter

INSTALLATION INSTRUCTIONS

EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters

E3xA, E3xB, E3xC, E3xE

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

Quick Start Guide TS A

B+G E-Tech User Manual for SDM630 SDM630. Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 2013 V1.

UMG 20CM. 20 Channel Branch Circuit Monitoring Device with RCM

NEW ERA METER. Installation & Operation Guide NE METER

Satellite INSTALLATION GUIDE

3-Phase, Dual-Input 6-Slot Power Supply System STARTUP GUIDE

INSTALLATION INSTRUCTIONS

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

Multifunction Transducer MT440

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

*Approved by CSA for non-hazardous locations (Group Safety Publication IEC Third Edition).

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

Technical data sheet. PowerLogic power-monitoring units EM3500 series DIN Rail meter

PV Rapid Shutdown device

INTEGRA DIGITAL METERING SYSTEMS

MODULAR CIRCUIT MONITORING SYSTEM

Technical Specifications. Dual Source kwh Energy Meter

Wa r n i n g-wa r n i n g-wa r n i n g

MCS-POWERMETER. Getting Started Manual. MCS Total Solution for all your Control Needs

EM-15 / EM-20 Energy Management Switch

PowerLogic EM4000 series

Nature Power Inverters. Modified Sinewave 1000w/1500w True Sinewave 1000w/2000w. Owner s Manual

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

PRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

BCPM Series Panelboard Monitoring Systems

PRO-1250D CT MID DIN rail three phase four wire energy meter.

MultiCube Single Phase Multi-Function Electricity Meter. Installation and Operation

Electronic Submeter with Advanced WiFi Ethernet Capability

Modified Sinewave Series. Power Inverter 1000/1500 MW 1210, MW1215. True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220.

Installation Job Aid for VSP 4850GTS

DEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S

SLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001

Autoranging True RMS Multimeter User Manual

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

HT2000 Transverter Installation & Operation Manual

INSTALLATION INSTRUCTIONS Protocol Energy Meter EM-RS485 and Current/Voltage Transducers DANGER WARNING

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

User Guide True RMS Multimeter Extech EX205T

U niversal Measuring Device UMG 96 S. Little Fieldbus Giant. Modbus / Profibus. Harmonics. Memory. Analogue outputs. Digital I/O

APM Power Meter User Guide. CAUTION: Risk of Danger Read complete instructions prior to installation and operation of the unit

MU110-6U. Analog output module 6 channel. User guide

Principal LED Street Stik Fluorescent Bulb Replacements

CVM-B100 CVM-B150 INSTRUCTION MANUAL (M010B B)

INSTALLATION INSTRUCTIONS STZ-R SERIES (ENGLISH)

Digital Multifunction Meters. Digital Multifunction Meters

Principal LED Qwik Stik Fluorescent Bulb Replacements

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D

Mini Digital Multimeter

Installation Job Aid for VSP 4450GTX-HT- PWR+

IPD163C. Single-Phase Multifunction Meter User Manual Version: V1. August 20, 2017

CU port USB 2.0 hub. Version: 1.1 Date:

Surge Protective Devices. STV100K Series. Instruction Manual

ACUREV Three-Phased DIN-Rail Multifunction Meter FEATURES

Surge Protective Devices. STV100K Series. Instruction Manual

BFM-II BFM-II BRANCH FEEDER MONITOR. Highlights

Installation and Operation Manual

INSTALLATION INSTRUCTIONS Protocol Energy Meter EM-RS485 and Current/Voltage Transducers DANGER WARNING WARRANTY DISCLAIMER

EnerSure Installation Guide

Sync Control. Installation/Operation Manual Rev. E

Transcription:

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter Install Guide Revision C (12/18)

DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Revision C (12/18) Turn off all power supplying equipment before working on or inside the equipment. Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes. This equipment must only be installed and serviced by qualified electrical personnel. Read, understand and follow the instructions before installing this product. Product may use multiple voltage/power sources. Be sure all sources of power have been disconnected before servicing. Use a properly rated voltage sensing device to confirm power is off. DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors. Failure to follow these instructions will result in death or serious injury. CAUTION This product is not intended for life or safety applications. Do not install this product in hazardous or classified locations. The installer is responsible for conformance to all applicable codes. Mount this product inside a suitable fire and electrical enclosure. A qualified person is one who has skills and knowledge related to the construction and operation of this electrical equipment, and the installation, and has received safety training to recognize and avoid the hazards involved. NEC2011 Article 100 No responsibility is assumed by Leviton for any consequences arising out of the use of this material. DO NOT EXCEED 346V Line to Neutral or 600 volts Line to Line. This meter is equipped to monitor loads up to 346V L-N. Exceeding this voltage will cause damage to the meter and danger to the user. Always use a Potential Transformer (PT) for voltages in excess of 346V L-N or 600 volts line to line. The VerifEye is a 600 Volt Over Voltage Category III device. For use in a Pollution Degree 2 or better environment only. A Pollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity. Consider the enclosure, the correct use of ventilation, thermal properties of the equipment, and the relationship with the environment. Installation category: CAT II or CAT III Provide a disconnect device to disconnect the meter from the supply source. Place this device in close proximity to the equipment, and within easy reach of the operator, and mark it as the disconnecting device. The disconnecting device shall meet the relevant requirements of IEC 60947-1 and IEC 60947-3 and shall be suitable for the application. In the US and Canada, disconnecting fuse holders can be used. Provide overcurrent protection and disconnecting device for supply conductors with approved current limiting devices suitable for protecting the wiring. If the equipment is used in a manner not specified by the manufacturer, the protection provided by the device may be impaired. For the complete safety information for this product, see the full user guide. 2

Technical Specifications Revision C (12/18) Specification Service Types Voltage Channels Current Channels Maximum Current Input Measurement Type Line Frequency Power AC Protection Power Out Waveform Sampling Parameter Update Rate Measurements Description Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) 90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. Two independent voltage reference inputs 48 channels, 0.525 VAC max, 333 mv CTs, 0-4,000+Amps depending on current transducer 150% of current transducer rating (mv CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs. True RMS using high-speed digital signal processing (DSP) with continuous sampling 50-60 Hz From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max Use of 12 volt auxiliary output requires 100 VAC minimum input voltage. 0.5A Fuse 200kA interrupt capacity Unregulated 12VDC output, 200 ma, self-resetting fuse 1.8 khz 1 second Volts, Amps, kw, kvar, kva, apf, dpf, kw demand, kva demand, Import (Received) kwh, Export (Delivered) kwh, Net kwh, Import (Received) kvah, Export (Delivered) kvah, Net kvah, Import (Received) kvarh, Export (Delivered) kvarh, Net kvarh, THD, Theta, Frequency. All parameters for each phase and system total. Accuracy 0.2% ANSI C12.20-2010 Class 0.2 Resolution Indicators Pulse Input Alarm Output Values reported in IEEE-754 single precision floating point format (32 bit). 4-line display, tri-color backlight (PhaseChek ) AMC12 4 inputs, AMC48 2 inputs Voltage Phase Loss Alarm (SPDT Relay - 30 VDC) ( only) Communication Hardware Supported Protocols Max Communication Length (RS485) RS-485 Loading RS-485, Ethernet, & USB (for configuration only) Modbus RTU or BACnet Master Slave Token Passing protocol (MS/TP) Modbus (using SunSpec IEEE-754 single precision floating point model) BACnet MS/TP Modbus TCP BACnet IP 1200 meters total cable length, with Data Range of 100K bits/second or less 1/8 unit 3

Communication Rate (baud) Data Bits 8 Parity Stop Bit 2, 1 Termination Mechanical Wire Connections Mounting High Voltage Cover Modbus: 9600 (Default), 19200, 38400, 57600, 76800, 115200 BACnet: 9600 (Default), 19200, 38400, 76800 None, Even, Odd None provided 12-22 AWG 600 VAC, Voltage connection must be #14 AWG or larger & 600 VAC rated Enclosure or Panel Mount IP40 (embedded version) Operating Temperature -20 to + 60⁰ C (-4 to 140⁰ F) Humidity Enclosure 5% to 95% non-condensing ABS Plastic, 94-V0 flammability rating, connections sized for 1 inch EMT conduit Dimensions (L) 33.7cm x (W) 25.2cm x (H) 8.0 cm (13.3 x 10 x 3.1 ) (no enclosure version) (L) 24.7cm x (W) 25.2cm x (H) 8.0 cm (9.8 x 10 x 3.1 ) (no enclosure version) PCBA Dimensions (L) 21.6cm x (W) 21.6.0cm x (H) 6.4 cm (8.5 x 8.5 x 2.5 ) Obvius Ally Configuration Console Minimum System Requirements Operating System Windows 7. Windows 8, Windows 10 Communications Port USB or Ethernet connectivity Safety FCC Compliance Serial/Ethernet Meters This device has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at user s own expense. The following are UL Recognized: AMC12-B-y-z, -P-y-z, AMC48-B-y-z, -P-y-z The following are UL Listed: AMC12-C-y-z, AMC48-C-y-z Conforms to UL Std 61010-1, 3rd Edition, UL 61010-2-30:2010 Certified to CSA Std C22.2 No. 61010-1, 3rd Edition 4

Mechanical Specifications & Mounting Series AMC48 - Enclosure Series AMC12 - Enclosure 5

Series AMC48 Enclosure Drill Pattern Series AMC12 Enclosure Drill Pattern 6

Series AMC48 Mounting Plate Template 7

The following section illustrates the 12 channel model. The mounting components are slightly different, but follow the same procedure. STEP 1) Remove top cover screws (4x) and high voltage cover screws (2x) provided STEP 2) Locate, mark, and drill wall mounting points (2x 6x customer supplied) The plastic enclosure itself can be used as a template for marking the drill locations on the wall. #8 Fastener If the meter is not available for use as a drill template, a drawing indicating the spacing between mounting holes can be found in the appendix. The centerline holes are intended for fastening to wall studs. If hollow wall fasteners are used, the outer 4 mounting points are recommended. 8

STEP 3) Mount conduit fittings, conduits, and blanking plugs STEP 4) Connect voltage leads 9

STEP 5) Attach high voltage cover IP30 TOUCH SAFE (with internal cover installed) STEP 6) Connect CT and Communications Wiring Connecting Voltage Connect the voltage leads (L1, L2, L3, and N, as necessary) to the meter through a dedicated disconnect or circuit breaker. A voltage lead of 14 AWG THHN Minimum 600VAC rating (or equivalent) is required. IMPORTANT: Verify the circuit breaker is marked as the disconnect breaker for the meter. 10

Wiring the AcquiSuite Ally Meter in a 3-wire, Split ɸ Service Panel High voltage MAY BE PRESENT. Risk of electric shock. Life threatening voltages may be present. Qualified personnel only. 3-Wire, 1 Phase used On MAINS L1-N, L2-N (RōCoils Shown) Connect the Neutral wire to V INPUT 1 (N) on the meter Meter is powered from L1 to L2 on the V Input 1 terminal (Label as Disconnect)) Single Phase 110 VAC Plug Loads L1-N or L2-N Single Phase 220 VAC Plug Load L1-L2 3-Wire, 1 Phase Split Load L1-N, L2-N Illustrating the intended wiring configuration for each of the Service Types available in the Service drop-down list under Meter Setup EXAMPLE LOADS: Single Phase L1-N or L2-N 110 VAC: Lighting, Appliance, Living Zone Single Phase L1 L2 220 VAC: Water Heater, Clothes Dryer, Equipment with no neutral wire. Split Phase L1 L2 220 VAC: Service Entrance, Equipment with neutral wire. 11

Wiring the AcquiSuite Ally Meter in a 4-wire, 3 ɸ Service Panel 3 Wire, 3 ɸ used On MAINS L1-N, L2-N, L3-N (Rogowski Coils Shown) Connect the Neutral wire or Ground wire to V INPUT 1 (N) on the meter Single Phase Branch Loads L1-N Meter Power Connect all phases to the V INPUT 1 terminal (Label as Disconnect) 4 Wire, 3 ɸ WYE load (Neutral Current) L1-N, L2-N, L3-N 3-Wire, 3 ɸ DELTA load (No possibility of Neutral Current) L1-N, L2-N(est), L3-N Illustrating the intended wiring configuration for each of the Service Types available in the Service drop-down list under Meter Setup Note: The AcquiSuite Ally Meter Series uses the Neutral Terminal as a voltage reference. For systems without a neutral conductor, Leviton suggests connecting a ground wire to this terminal. If the neutral terminal is left open, L-L measurements will be accurate, but L-N measurements may not be symmetric. If a ground wire is connected to the Neutral terminal, <2mA will flow into the ground wire. 12

Wiring the CTs to the AcquiSuite Ally Meter The image below is the counterpart to the service panel illustration and indicates how to connect CTs to the input terminals on the AcquiSuite Ally, for each service type. For service types that are not specifically listed, it is recommended to choose single phase service and configure each channel individually. Three phase loads are illustrated on the left and split phase loads on the right as an example only. Elements are fully interchangeable on the meter. Current and voltage inputs must be installed in phase for accurate readings (e.g. CT1 on Line 1, CT2 on Line 2) Orientation is critical: Ensure that all CTs are properly oriented with the line and load, as marked. Failure to install CTs in the correct orientation and on the correct phase will lead to inaccurate meter readings. 13

14 Revision C (12/18)

Communication Verification Revision C (12/18) Verification includes confirmation of BOTH the physical interface settings (Serial or Ethernet) and the protocol (Modbus or BACnet) settings. The LCD User interface can be used to quickly confirm the settings required for each combination of interface and protocol. The interface is intuitive and groups together commonly associated registers. The complete interface is presented in Appendix A as a navigational map. Arrows indicate how to move from one menu display to the next. A Reverse Contrast entry in the documentation indicates the active menu item in a list which corresponds to a blinking character in the physical LCD. The ENTER button is used to select a property and up / down buttons are used to select among the values supported by the meter. Note that changes to the meter configuration are limited to the communication interface using the LCD. If additional changes (such as CT type) are required they must be made using a software interface. Example LCD Navigation AcquiSuite Ally Configuration Console / Web Application If your AcquiSuite Ally model does not include the LCD user interface or if you prefer to verify the installation using software, then verification is facilitated through the AcquiSuite Ally 15

Configuration Console PC application or the Web App which shares a common design. Refer to the section on Configuration Details in the full user manual, or the AcquiSuite Ally Web App. Pulse Inputs Ally ACM12 meters are equipped with 4 pulse inputs and Ally ACM48 meters (hardware version I) are equipped with 2 pulse inputs. Pulse counting supports accumulation of consumption data from any external meter using a dry contact (Form A Relay) or open collector outputs. The AcquiSuite Ally pulse inputs are compatible with low speed meters. The pulse duration must exceed 50mS in both the logic low and high state allowing for a maximum input frequency of 10 Hz. Pulse scaling, resetting and accumulated values are accessed through registers and are system in scope. Refer to the register list, Obvius Ally Configuration Console, or videos for more information. >50 mec Typical Pulse Sequence >50 mec 16