DIN-rail mountable relay unit for commercial control, power switching and home automation applications

Similar documents
BARIX IO12. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL. Version: 2.

BARIX X8. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications. Version: 2.01.

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

G303 RIO (REMOTE I/O) AND LOW END RTU

HANDS-ON TRAINING GUIDE

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

P3-SCM. General Specifications

ADAM-4510 RS-422/RS-485 Repeater ADAM-4510S Isolated RS-422/485 Repeater ADAM-4520 Isolated RS-422/485 Converter Startup Manual

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

ISOLATED RS-232 TO RS-422/485 CONVERTER

CDN503 HIGH DENSITY I/O ADAPTER USER GUIDE

PK2200 Series. Features. C-Programmable Controller. Specifications Board Size Enclosure Size Operating Temp.

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

ICD105A 1008 page 1/ r001 ICD105A. Industrial RS-232 to RS-422/485 Converter

PCI 2 Axis Servo Card

DM STREAMER. Application User Manuale. Configuring and Using Digital Message Streamer Application. Doc. Release Date and Version: 27. Apr / 1.

Features: Analog to Digital: 12 bit resolution TTL outputs, RS-232 tolerant inputs 4.096V reference (1mV/count) 115K max speed

CONTROL MICROSYSTEMS Analog Output Module. Hardware Manual

PCI 2 Axis Servo Card

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

CDN502 HIGH DENSITY I/O ADAPTER USER GUIDE

Expansion Module HZS 541-1S

Serial Data DIN Fiber Link System

CONTROL MICROSYSTEMS and 5407 Relay Output Module. Hardware Manual

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

PACSystems* RX3i IC695CMM002 and IC695CMM004

6222 Two Door Module Technical Operations Manual

POWERWISE INDAC SETUP MANUAL

Operation and Maintenance Manual

Getting started with your DGH module:

PCD DIGITAL Differential pressure probe

DCC-8 DIGITAL TO EIGHT CURRENT LOOP CONVERTER OPERATING MANUAL

Moxa TCC-100 Series User s Guide

The PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector.

Ethernet to Digital I/O +RS232 +Switch

Specification For 90 Watts Adapter Power Supply Model No: ADB002 Customer ID: 000G Revision: 4.0

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

PRELIMINARY. Preliminary Technical Datasheet #TDAX Discrete I/O P/N: AX inputs, 8 relay outputs, SAE J1939 with Electronic Assistant

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

DI-917MB/DI-918MB. Heavy-duty 1A solid-state relays provide dependable on/off control of industrial devices. Analog Output Module. Four Analog Outputs

Flomatic Smart Card TM Model FDHC-100 (Digital High-Resolution Controller) Configuration and Operation Manual

Measurement Systems Datascan Installation and User Guide

Getting Started with your D3000M Series Module

Discrete I/O 12 Discrete Inputs 8 Relay Outputs CANopen P/N: AXDIO128CO

hipecs-cio52 CANopen I/O module with 4 analog outputs

GS202 Encoder Switch

PACSystems* RX3i IC695CMM002 and IC695CMM004

PACSystems* RX3i IC695CMM002-EG and IC695CMM002CA-EG IC695CMM004-EG, IC695CMM004CA-EG, and IC695CMM004LT-EG

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Network audio encoder / decoder with I/O for professional and broadcast applications

The SilverNugget is a servo controller/driver for NEMA 17 & 23 frame microstep motors.

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL

High Voltage DC Meter

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

iologik R1200 Series User s Manual

Moxa TCC-100 Series Hardware Installation Guide

SCM5B. SLX200 Data Acquisition System. isolynx. Data Acquisition Systems. Visit our website Features

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic

icex-cmtm General specs and Installation guide

Copyright: December 2017 Nidec Issue: E

VCL-TP, Teleprotection Equipment With Trip Counter Display Panel

PLC Racks IC697CHS782/783

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

General Operating, Maintenance and Installation Manual

Hardware Reference IO/5640. Analog/Digital I/O-Extension

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

Quick Start Installation Guide

D/E Remote Relay Panel User Guide

i-7550 PROFIBUS to RS-232/422/485 Converter User's Manual High Quality, Industrial Data Acquisition, and Control Products

VCL-TP, Teleprotection Equipment

Advant OCS. The Compact and Cost Effective Advant Controller. Advant Controller 210. Open Control System

Features and Benefits. Certifications

PEAKTRONICS DHC-100 FEATURES. Digital High-Resolution Controller

Industrial Power Supplies

MED102A. Industrial Serial to Single-mode Fiber Converter

Intelligent 4 Port RS-422/485 to 2 Port Ethernet Serial Device Server with PoE

LT900SERIES. 1xN Multi-Channel Switch Operation Manual

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT

Absolute Encoder Multiturn

Copyright Extract from Conditions of Sale Safety Warning

PCAN-Router FD Universal, programmable Converter for CAN FD and CAN. User Manual. Document version ( )

OTB1S0DM9LP I/O distributed module OTB - Modbus non isolated serial link m

MD3. Microstepping Motor Driver Page 1 of 7. Description. Software. Mechanical Drawing. Features

A general-purpose industrial input/output

General Specifications. P2-SCM Serial Communications

Instructions. Modbus RTU Card (WSIQ-COM-MB)

3690 N.W. 53rd Street Fort Lauderdale, FL SC-2124 SC-2124M. 24 Channel Universal Scanner. Installation and Operation Manual P/N 145F-11902

I/O EXPANSION MODULES

CONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

120 WATT FLEX ATX TYPE WITH ACTIVE PFC

VL BPC MINI. A configurable industrial computer platform. Data sheet 2930_en_F. 1 Description. 2 Features

Discrete I/O P/N: AXDIO inputs, 8 relay outputs, SAE J1939 with Electronic Assistant

HIGH-VOLTAGE DC METER

CONTROL MICROSYSTEMS and 5404 Digital Input Module. Hardware Manual

8051 Intermidiate Development Board. Product Manual. Contents. 1) Overview 2) Features 3) Using the board 4) Troubleshooting and getting help

DI-904MB/DI-905MB/DI-906MB

VL BPC MINI. A configurable industrial computer platform Intel Atom Z510PT CMAT IPC Module Option [I28] AUTOMATION Data Sheet 2930_en_A.

Transcription:

BARIX R6 DIN-rail mountable relay unit for commercial control, power switching and home automation applications PRODUCT MANUAL Version: 01.03 Date: 07/20/2005 For Firmware Version 2

Table of Contents Introduction...1 Hardware...2 Case...2 Connectors...2 Power supply requirements...2 RS-485...3 LED Indicators...3 Configuration Memory...3 Connectors...4 Connector Pin out overview...4 J5,J6,J7 Pin out (Relays)...4 J2, J4 Pin out Extension Connectors...5 J1 Pin out (RS-485 and Power)...5 Protocol support...6 General...6 Supported Standard Commands...6 Special Commands...6 Exceptions...7 Command 68...7 Command 69...7 Command 70...8 Confi guration...9 Default Parameters...9

Connecting external loads...10 Connecting a Barix Barionet controller..11 RS-485 wiring...11 RS-485 troubleshooting...11 Reference wire...11 RS-485 termination...11 Modbus Register Map...12 Live I/O...12 Configuration Data...12 Complete Register Map...14 Complete Coils Map...14 Technical specifi cations...15 CPU...15 Relays...15 Load Connectors...15 RS-485 / Power Connector...15 Host Interface...15 Extension Connectors...15 Power Supply Requirements...15 LED Indicators...15 Case...15 Misc...15 Conformity...15

Introduction The BARIX R6 is a relay extension unit for the Barionet adding 6 relays capable of switching 10 Amps at up to 250 VAC. Since the standard Modbus/RTU protocol is used, the BARIX R6 can also be employed in other applications as a Modbus controllable relay unit. The device is configured via the serial interface using standard Modbus read/writes. If the device ID is unknown, a special command is available, which can be sent via broadcast and uses the serial number of the device to send it new configuration info. A default settings jumper allows to set the device temporarily to a default configuration. The protocol supported is Modbus/RTU at 19200 (default) and 9600 Baud, with even (default) or no parity. For applications needing fast setting of relays on multiple devices, special commands have been added to the standard Modbus functionality. BARIX AG 1/20

Hardware Case The BARIX R6 relay extension uses a DIN-Rail mountable plastic case which directly snaps onto a standard DIN-Rail. A mounting bracket is also available as an option. The snap-on cover can easily be removed using a screwdriver. All screw terminal blocks are conveniently positioned outside of the cover, so the only reason to remove the cover is to access the default jumper in case the device configuration is not known. The RS-485 bus and power connection is available on multiple connectors to facilitate easy daisy-chaining. 8 LED indicators show the status of the outputs as well as power and RS-485 traffic generated by the unit. Connectors The load connectors are screw terminal connections which allow the insertion of wires up to AWG14 (2.5mm 2 ). For every relay, the NO (normally open) and NC (normally closed) contacts are brought out to a terminal. For safety reasons, these terminal blocks are not removable. All load connectors are positioned on the top side of the device. The RS-485 bus and operating power of the unit can be connected via a 6-pin removable screw terminal block, positioned on the bottom side of the device. Two extension connectors carrying the RS-485 and power connections, one on the left and one on the right side, facilitate easy daisy chaining of multiple devices. Power supply requirements The BARIX R6 is equipped with a universal power input and accepts both AC and DC voltage. The AC supply range is12 to 24 Volts and 9 to 30 Volts when powered by a DC power supply. A switching power regulator generates the internally needed operating voltage of 5VDC with high efficiency and consumes with all relays activated maximal 3.5 Watts only. The R6 is reverse polarity protected. RS-485 The host interface of the BARIX R6 is an RS-485 interface, which is connectible via extension connectors as well as via screw terminals. Besides A and B signals for the differential, BARIX AG 2/20

bidirectional bus signal, a third connection is available, commonly referred to as reference ground. This signal is internally tied to signal ground via a 100 Ohm series resistor. Termination resistors are NOT provided on-board. A termination resistor may be added at each far end of the RS-485 bus, if required. The BARIX R6, as well as other Barix I/O extension units, feature soft pull-up (B) and pull down (A) of 10kOhm resistors, which force the inactive bus to a relatively high impedance, idle condition. Both A and B line signals are heavily protected against ESD (Electrostatic Discharge). Supported interface configurations are 19200 baud, 8bit, even parity, 1 stop bit (**default**) 19200 baud, 8bit, no parity, 1 stop bit 9600 baud, 8bit, even parity, 1 stop bit 9600 baud, 8bit, no parity, 1 stop bit LED Indicators Eight LED indicators on the unit show the following conditions: LED 1: operating power LED 2: R6 answers to Modbus messages LED 3..8: state of the 6 output relays Configuration Memory The Barionet R6 contains 256 bytes of configuration memory which can be read and (most of it) written via standard Modbus commands. The EEPROM based memory is persistent over power outages, no batteries are used. BARIX AG 3/20

Connectors 1 2 3 4 Connector Pin out overview J5,J6,J7 Pin out (Relays) All relays provide separate NO/NC capability, and can switch up to 10 Amps at max. 250VAC. An indicator LED per relay is activated together with the relay. The COM terminal is connected to NC if the relay is inactive, and NO when the relay is activated. Pin J5 J6 J7 1 NC 1 NC 3 NC 5 2 NO 1 NO 3 NO 5 3 COM 1 COM 3 COM 5 4 NC 2 NC 4 NC 5 5 NO 2 NO 4 NO 5 6 COM 2 COM 4 COM 6 J2 and J4 (Molex, p/n 22-27-2041, 4A max) are provided for easy connection of multiple devices, and are located at the left and BARIX AG 4/20

J2, J4 Pin out Extension Connectors right sides. They carry the unregulated supply voltage and RS-485 bus signals. Pin Function 1 VCC (+) 2 VSS (-) 3 RS-485 A 4 RS-485 B J1 Pin out (RS-485 and Power) J1 can be used to connect the supply voltage and the RS-485 bus to the relay unit. These screw terminals are electrically identical to the expansion connectors J2 and J4. In addition, a reference ground and Signal GND pin is provided. Reference ground is connected to the Signal ground of the Barionet R6 via a 100 Ohm resistor and can be used for grounding applications. Signal GND is the system ground of the R6 which is NOT identical to the supply VSS pin and is used for measuring purposes only. Pin Function 1 Reference GND 2 RS-485 A 3 RS-485 B 4 VCC (+ or ~) 5 VSS (- or ~) 6 Signal GND BARIX AG 5/20

Protocol support General The BARIX R6 communicates via the well known Modbus/RTU protocol over its RS-485 interface. The unit is also configured via writes to Modbus registers. In addition to the actual I/O register(s), a 256 byte information area is accessible which contains device type, software version, serial number, the configuration as well as user changeable storage. Attention: Writing to registers can take up to 10 milliseconds per address before being confirmed (Modbus acknowledge). Supported Standard Commands The following standard Modbus commands are supported by the BARIX R6. All other commands will be answered with an exception code. Due to the limited memory resources of the BARIX R6, the unit cannot receive messages larger than 95bytes and will ignore these (for example, write multiple registers commands). CMD (hex) Function 03 (0x03)read (holding) register 05 (0x05)write single coil 06 (0x06)write single register 16 (0x10)write multiple registers Special Commands The BARIX R6 also supports some special, Barix proprietary commands which have been implemented to ease configuration and facilitate the use of the R6 in conjunction with non-modbus systems. These commands are further described in this manual and are: CMD (hex) Function 68 (0x44)set all outputs on multiple units 69 (0x45)set configuration using serial number 70 (0x66)set coil without acknowledge Exceptions The BARIX R6 responds to malformed commands or access violations with the defined Modbus exceptions. BARIX AG 6/20

Command 68 The command code 68 (hex 44) can be used to set the outputs of a whole group of R6 devices very fast and efficiently. The command is sent via broadcast and can address multiple units, with one byte per device carrying the information for all 6 outputs. All devices addressed by this command will synchronously set their outputs after the command is completely received. No acknowledge is returned. Command format: Byte 1-0xff (broadcast address) Byte 2-0x44 (command code) Byte 3 - ah (first address, hi, always 0) Byte 4 - al (first address, Modbus address of first device) Byte 5 - ch (count, # bytes, hi, always 0) Byte 6 - cl (count, #bytes, lo 8 bit) Byte 7 - nb (number of bytes following (redundant) Byte 8...8+nb: data bytes for multiple devices Byte 8+nb+1: crc1 (crc1 according to Modbus spec) Byte 8+nb+2: crc1 (crc1 according to Modbus spec) Example: a command with al=5, cl=nb=4, data 01,02,04,08 will set the outputs on the R6 with Modbus address 5 to 01 which means relay one on, all others off, outputs on the R6 with the Modbus address 6 to 02 which means relay two on, all others off, devices with address 7 and 8 accordingly. All other devices with Modbus addresses 1..4 and 9..255 are not affected by the command. Command 69 The command code 69 (hex 45) is used to set an R6 device which is connected to the bus and which address is unknown (but serial parameters are correct) or which is forced to default settings with the default jumper. The command can also be sent multiple times with different serial parameters to find the device. The serial number of the device, which can be found on a label on the unit (format xxx-yyy), needs to be inserted into this block to address the specific unit. The block is sent out as a Modbus broadcast. BARIX AG 7/20

Bytes 272, 273, 274, 275 of the Modbus register map (configuration memory positions 16..19) will be written with the provided information if the serial number matches. Command format: Byte 1-0xff (broadcast address) Byte 2-0x45 (command code) Byte 3 - s1 (serial number, first part) Byte 4 - s2 (serial number, second part) Byte 5 - s1 (serial number, first part, repeated) Byte 6 - s2 (serial number, second part, repeated) Byte 7 - c1 (configuration data for register 272) Byte 8 - c2 (configuration data for register 273) Byte 9 - c3 (configuration data for register 274) Byte 10 - c4 (configuration data for register 275) Byte 11 - crc1 (crc1 according to Modbus spec) Byte 12 - crc2 (crc2 according to Modbus spec) Despite the broadcast addressing, the unit will respond with a command acknowledgment (containing bytes 1..6 plus crc)! Command 70 The command code 70 (hex 46) is used to set an R6 output without a return acknowledgment. The command uses the exact syntax of the 05 (set coil) command, but the R6 does not send an answer and is immediately ready to receive the next message. The command should be send addressed to the device address and NOT as a broadcast, otherwise all R6 units on the bus will react to it. This command has been added to the Barionet R6 to allow slow systems, which are not Modbus native and cannot react fast to serial input (like common home automation systems) to set a series of relays of one or multiple R6 units without the need to observe Modbus message timeouts, answers etc. BARIX AG 8/20

Configuration Default Parameters The BARIX R6 is configured via the RS-485 interface using standard Modbus commands. If the address of the device is not known, it can be temporarily set to default parameters by setting a jumper in the device. No reset is necessary. Within 5 seconds after applying the jumper, the default parameters are assumed. It is NOT necessary to reset or to power cycle the device after removing the jumper! If no valid Modbus blocks are received by the relay unit for a 5 second time interval, the serial interface is reset and reconfigured with stored parameters. Use a screw driver to remove the snap-on case top. On one side of the case lift one latch first and gently pull the top then lift the second latch and remove the top completely. J3 is a 4 pin connector and is located between LED7 and LED8. To set default parameters connect the lower two pins using a standard jumper (not included). When the jumper is set, the default parameters are: Serial interface 19200 Baud, even parity, 1 stop bit Modbus Address 255 BARIX AG 9/20

Connecting external loads The BARIX R6 features 6 relays capable of switching resistive loads (lamps, heater) 10 Amps at up to 250 VAC. ~ P ~ N Cautious calculations should be performed when switching inductive loads like motors or transformers as used in low voltage halogen light systems: A transformer produces a high voltage when switched off causing an arc which is reducing the life span of the relay contacts. ~ P 12VAC ~ N Motors have a high start up current (typical factor of 2 to 5 times the nominal current! ) so even a motor with a nominal current draw of 5 Amps could reduce the life time of relay contacts significantly. We advise to check the technical specs of the used motor and to also take in account the added initial current draw caused by the attached mechanics. ~ P ~ N M BARIX AG 10/20

Connecting a Barix Barionet controller The actual Barix Barionet controller features two 3pin expansion connectors which are NOT compatible with the 4pin expansion connectors of the BARIX R6. This will be changed in a future hardware revision of the Barix Barionet controller to allow for daisy chaining. This is already supported between BARIX R6 devices and other Barionet extension devices. RS-485 wiring However, connecting a Barix Barionet controller is simple as it features the RS-485 signals on J7 which is a detachable screw terminal block: Pin 485 1 Reference GND 2 Not used 3 Not used 4 RS-485 A 5 RS-485 B 6 Reference GND connect Pin 4 (J7) to Pin 2 (J1) of the BARIX R6 (RS-485 A) connect Pin 5 (J7) to Pin 3 (J1) of the BARIX R6 (RS-485 B) RS-485 troubleshooting Reference wire RS-485 termination When communication problems occur two measures can be taken to improve the RS-485 signal quality. When using two separate power supplies a third wire should be used to ensure a common voltage level : Connect Pin 1 or Pin 6 (J7) to Pin 1 (J1) of the BARIX R6 When the two devices need to be connected over a long distance both sides of the cable should be terminated using a 100 Ohm resistor to suppress signal reflections: Connect a 100 Ohm resistor between Pin 4 and Pin 5 (J7) directly at the terminals of the Barionet controller Connect a 100 Ohm resistor between Pin 2 and Pin 3 (J1) directly at the terminals of the BARIX R6 BARIX AG 11/20

Modbus Register Map The BARIX R6 supports all 64k address locations in the Modbus address maps, however, unimplemented locations generate an exception when read or written. The Modbus address range is divided in multiple address maps, all 65535 registers in size. The Barionet R6 implements the coils (64k, 1bit) and the registers (64k, 16 bit). There are no functions provided to read back discrete (1bit values) in the shipping software version. Attention: all Modbus addresses count from 1, while the protocol addresses start at 0. Example: Modbus register 1 is addressed in Modbus/RTU as 0. This documentation uses the Modbus register number in the protocol the address must be one less!! Live I/O The state of the relays can be set/reset using set coil and write register commands. In addition, the state of the relays can be read back using the read register command. In the coil/discrete address map, only positions 1..6 (Modbus/RTU addresses 0..5) are populated in the BARIX R6, which are mapped to relays 1..6. Write access to any other address is prohibited. In the register address map, the relays can be written simultaneously by accessing register 1. Bit 0 is relay 1, bit 1 is relay 2,... bit 5 is relay 6. Configuration Data All configurable parameters are accessible using standard Modbus read/write commands to registers. The configuration information area is 256 bytes, which are accessible as 256 byte registers (lower 8 bits only), registers 257..512 in the Modbus memory map. The first 16 bytes of the configuration registers are one-time writable only after setting these registers to a value not equal to 255 (hex 0xff) they cannot be changed any more. All other registers can be read and written. Within these first 16 bytes, Device type, software version, and serial number are stored. In addition, the installer of the unit can use 8 bytes to write BARIX AG 12/20

permanent information (like shipping date, system ID where the unit is installed etc). Of the remaining 240 bytes, the first 16 bytes have a special meaning (configuration registers) all other registers (290..512) can be used by the installer/customer to store information. ID registers Device information such as device ID, software version etc can be accessed using standard register read commands. This information is read-only and cannot be overwritten. The information is accessible using standard reads from addresses 257..264. Register 257: set fixed to 0xB1 (stands for Barionet R6) Register 258: software version, 2 at the time of printing. Register 259: first part of the serial number (byte) Register 260: second part of the serial number (byte) Register 261..264 are reserved for future use by Barix Register 265..272 are usable as one-time writable storage by the installer or controlling software. Configuration registers Device configuration can be set and read using standard Modbus commands. The R6 will reset its actual communications parameters to these values anytime it does not receive valid host communication for more than 5 seconds and the default jumper is NOT set. Register 273: Default relay settings in this Register are 00 by default, if Bit 0 is set, Relay 1 will be activated at startup etc.. Register 274: Serial interface mode: only bit 7 and bit 0 are used. Bit 0 selects between 9600 (set) and 19200 (reset) baud. Bit 7 selects between no (set) and even (reset) parity. Register 275: This register holds the Modbus address of the unit. Register 276..289: Reserved for future enhancements. BARIX AG 13/20

Complete Register Map Detailed register map again please note that the protocol address in Modbus/RTU is the register number -1!! Registe Function r 1 Live I/O (Byte, Relay state in bit 0..5) 2..256 Reserved, not accessible 257 Device type (hex 0xB1) 258 Firmware version 259 Serial number 1 st part 260 Serial number 2 nd part 261..264 reserved 265..272 One-time writable for installer 273 Default relay setting for startup 274 Serial interface mode 275 Modbus address 276..289 reserved 290..512 Memory for installer/software use 513... not accessible 65536 Complete Coils Map Detailed coils map please note that in the protocol, address in Mobus/RTU is the coil number -1!! Coil Function 1..6 Relay 1..6 7..65536 Reserved, do not access BARIX AG 14/20

Technical specifications CPU Relays Load Connectors RS-485 / Power Connector Host Interface Extension Connectors Power Supply Requirements LED Indicators Case Misc. Environmental conditions Conformit y PIC 16F688, 20MHz clock frequency 6 independent relays (250VAC 10A, 16Amax <1sec) Operate time: 7ms nominal, release time: 3ms nominal. Contact resistance: 50mOhm (measured at 1A 6V) Operating cycles: 10mio typical at no load. Relay type: Massuse ME-11 or equivalent 3 screw terminal blocks non-removable, with common, NO (normally open) and NC (normally closed) contacts for wires AWG26 - AWG14 / 0.15 2.5mm 2 Detachable screw terminal block for wires AWG28 - AWG16 / 0.08-1.3 mm 2 RS-485: 9600 and 19200 Baud, 8 bit, even or no parity. 2 extension connectors (4 pin) with RS-485 and power terminals, Molex 22-27-2041, 4A max., extension cable (3 /75mm) included (consisting of 2 Crimp Terminal Housings Molex 22-01-2045 and 8 female Crimp Terminals Molex 08-50-0114 of Molex 2759 series) 12 to 24 VAC / 9 to 30 VDC 3.5 Watt max. (all relays active) 1 LED for power indication 1 LED for active traffic indication 6 LEDs for relay status indication High quality plastic, 220 grams, DIN-rail mountable 4.13" x 3.34" x 2.83"/105mm x 85mm x 32mm Internal connector for default settings jumper Temperature:32 to 104 F / 0 to 40 C Humidity: < 70% relative humidity non-condensing FCC A and B, CE A and B Emission EN60730-1:2000 (Class B) Immunity EN60730-1.2000 BARIX AG 15/20

2005 Barix AG, Zürich, Switzerland. All rights reserved. The newest information about our devices and the latest version of this manual is available via download from our website, www.barix.com. We explicitly reserve the right to change and improve the product without notice. All trademarks mentioned or used are belonging to their respective owners. Barix, BARIX R6 and Barionet are trademarks of Barix AG, Switzerland and are registered in certain countries. Barix AG Barix Technology Inc. Seefeldstrasse 303 2182 Helena Rd. 8008 Zürich St. Paul, MN 55128 SWITZERLAND USA Phone: +41 43 433 2211 Phone: (866) 815-0866 Fax: +41 44 274 2849 Fax: (209) 755-8435 Internet web: email: www.barix.com sales@barix.com