Automationdirect.com. D i r e c t L o g i c S D S N e t w o r k M a s t e r. S m a r t D i s t r i b u t e d. S y s t e m M o d u l e

Similar documents
Automationdirect.com. D i r e c t L o g i c M a g n e t i c P u l s e I n p u t C o p r o c e s s o r F 4-8 M P I

Automationdirect.com. D i r e c t L o g i c M O D B U S S L A V E F 4 S L V - M B

45SD Series Bus Expansion Cards For use with Q45X Series Photoelectric Sensors on SDS Bus Networks

Automationdirect.com. D i r e c t L o g i c H i g h S p e e d P a r a l l e l. B r i d g e C P U F 3 - P M U X - 1

BusBlock Digital I/O Module for the Smart Distributed System

Ethernet Modbus X80 Gateway Device Type Manager

Making the decision to switch from PLC to PC-based Control has gotten even easier with the introduction of MachineLogic Control Software.

P3-SCM. General Specifications

LAB 10 INTRODUCTION TO LADDER LOGIC PROGRAMMING. 2 Lab Equipment 2.1. CLICK Series Micro Programmable Logic Controller (PLC)

1.4. Electronic Products. Contents Description E33 esm Keypad Multiplexed Switch Module Product Selection...

D0 DCM Module Setup Direct

ReeR MOSAIC SUPPLEMENTAL MANUAL. Please refer to the Safety Components Disclaimer which1 follows these examples

BIET EtherNet Interface

T1K MODBUS Base Controller Specifications

Quad Digital I/O Board for the Smart Distributed System

BusBlock Analog Input Module for the Smart Distributed System

OPERATING INSTRUCTIONS

ALS c en Alspa CE80 20 N80 Bus Interface Unit User s Manual

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

CsCAN Data Concentrator Module

IRB-MON O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY PHOTOEYE U L M O N I T O R E D DEVICE

Installation Instructions

BusBlock Digital I/O Module for the Smart Distributed System

1 1 Getting Started $ "% # + %#! & %! + % $!% +!% $% # * %&# $ +!% ' *!# * %&# $ + $$ %!% "&% &%"&% # $$ $ +!( % " % $!%! %$ + $) % "$!# %% "!

Motion Control Video Rundown and References

BusBlock Analog Input Module for the Smart Distributed System

Installation Guide. Direct

Chapter. Maintenance and. Troubleshooting. In This Chapter...

CTI 2541 REDUNDANT PROCESSOR MANAGER INSTALLATION AND OPERATION GUIDE Version 1.4

indus technologies IDEX 300 Hard Drive Switch Installation & Operation For SATA Drives

Table of Contents 1. Safety Precautions and Warnings General Information Hardware Overview Tool Description Specif

Combinational and sequential systems. Prof. Cesar de Prada Dpt. of Systems Engineering and Automatic Control UVA

Eaton Corporation Cutler-Hammer Business Unit 811 Green Crest Drive Columbus, OH PanelMate PLC Direct Communication Driver Manual

DeviceNet PCI Card Instructions Manual

Wireless Expansion Module V2.0 OMN-RCV3. Reference & Installation Manual. Stand-Alone System

Mitsubishi FX Net Driver PTC Inc. All Rights Reserved.

D4--DCM. Data Communications Module. Manual Number D4-DCM-M

Chapter. Modbus. In This Chapter...

PRM Integration Guide with Pepperl+Fuchs HiDMUX2700 HART Multiplexer

General Specifications. P2-SCM Serial Communications

MODEL USBP-DIO16RO8. DIGITAL INPUT/OUTPUT BOARD w/8 ELECTROMECHANICAL RELAYS USER MANUAL

Copyright: December 2017 Nidec Issue: E

ControlLogix 7252 LDT Interface Manual Revision 1.1

BusBlock Digital I/O Module for the Smart Distributed System

Read this chapter to familiarize yourself with this manual. It tells you how to use the manual properly and efficiently.

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

Appendix A Fast!UTIL

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

PROFIBUS DP/CAN Gateway PCA-100. User Manual

Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160

EM-F-7G Safety Extension Module

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module

HART USER GUIDE FOR GASSONIC OBSERVER-H ULTRASONIC GAS LEAK DETECTOR

Operating Instructions Extended Cascade Controller MCO 101

QuickStart Manual QS -DSOFT32 -M

BusBlock Digital I/O Module for the Smart Distributed System

II II SQUARE D COMPANY

Do-more H2 Series PLC System Specifications

User Manual for IC300ETN100. SmartStack Ethernet Module

The I-7530A RS-232/485/422 to CAN Converter

DirectNET Host. Communications Programs. In This Chapter...

Maximum Value for OEMs SM. NX70 Serial Communications Unit (SCU) User Manual

User Guide IM/C250 MOD_3. Modbus (RTU) Communications Option C250 and V250

L01 - Effective Design Methods for Integrating Safety Using Logix Controllers. For Classroom Use Only!

Setting the DCM Switches

GRAPHIC DIGITAL INDICATOR with PROFIBUS Interface CSD-912B-70. Instruction Manual EN

BrewTroller Phoenix. Owners Manual. Updated - March 14, 2016 BREWTROLLER PHOENIX 1

PLC Programming D R. T A R E K A. T U T U N J I

Programmable Logic Controllers

Using the D2 DCM with MODBUS

S7-200 Tip Information on Timers Tip No. 33. S7-200 Tips

IRB-MON UNIVERSAL SAFETY PHOTOEYE OPERATING UL MONITORED DEVICE

V E2B Snap-in I/O Module

CONTACTOR DRIVER BOARD. DS200CDBAG1A and DS200CDBAG1B

User Manual for IC300ETN100. SmartStack Ethernet Module. August 01, 2000 GFK FANUC Spares

X-12s Users Manual. X-12s User Manual Revisions Revision Description Initial release. Xytronix Research & Design, Inc.

ControlLogix SIL2 System Configuration

Introduction. Getting Started. Getting Started. D2 HPP Handheld Programmer

User Guide Supplement Modbus TM Serial Data Communications Option IM/C100 MOD_6. /8 DIN Process Indicators and Controllers C100, C150, C160 and V100

User Manual for XL-J1939

IRB-RET O P E R A T I N G I N S T R U C T I O N S UNIVERSAL SAFETY RETROREFLECTIVE PHOTOEYE U L MONITORED DEVICE

FORD KM Tool (CAN BUS) User Manual

Powered Roller Controller for DeviceNet

DMP SATA DOM SDM-4G-V SDM-8G-V SDM-16G-V

GE Fanuc Automation. Computer Numerical Control Products. DeviceNet Board. Operator's Manual. GFZ-63404EN/03 March FANUC CNC Controls

ICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031

CA-A480-A Elevator Controller. Reference & Installation Manual

in Berlin (Germany) Sponsored by Motorola Semiconductor NEC Electronics (Europe) Siemens Semiconductors Organized by

SmartStack SAE J1939 Communication Module

INSTALLATION INSTRUCTIONS. Revision C1 Rapid City, SD, USA, 02/2010 MODEL ALT-XXX-3-SW

User Manual FRN 1.xx 2.xx

Motors Automation Energy Transmission & Distribution Coatings. Profibus DP SRW 01. User s Manual

Important Product Information

HomePlug Mediaxtream Ethernet Adapter

Oracle. Field Service Cloud Using the Parts Catalog

(Catalog Number 1747-SN) Product Data

System Monitoring and Troubleshooting

Flex Series User Guide

Connecting SLC Systems as Remote I/O to PLC-5 Processors

User Guide. Beckhoff CTNet I/O. Remote I/O for CTNet. Part Number: Issue: 3.

Transcription:

Automationdirect.com D i r e c t L o g i c 4 0 5 S D S N e t w o r k M a s t e r S m a r t D i s t r i b u t e d S y s t e m M o d u l e F 4 - S D S Order Number: F4-SDS-M

TRADEMARKS Automationdirect.com is a Trademark of Automationdirect.com incorporated. CoProcessor is a Trademark of FACTS Engineering, Inc. COPYRIGHT Copyright 1994, FACTS Engineering Inc., 8049 Photonics Dr., New Port Richey, Florida, 34655.. World rights reserved. No part of this publication may be stored in a retrieval system, transmitted, or reproduced in any way, including but not limited to photocopy photograph, magnetic or other recording media, without the prior agreement and written permission of FACTS Engineering, Inc. Last Issued Date: October 1994 Current Issued Date: December 1999

WARNING Thank you for purchasing automation equipment from FACTS Engineering. We want your new FACTS Engineering automation equipment to operate safely. Anyone who installs or uses this equipment should read this publication (and any other relevant publications) before installing or operating the equipment. To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and usually change with time. It is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation is in compliance with the latest revision of these codes. At a minimum, you should follow all applicable sections of the National Fire Code, National Electrical Code, and the codes of the National Electrical Manufacturers Association (NEMA). There may be local regulatory or government offices that can help determine which codes and standards are necessary for safe installation and operation. Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation. If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call us at 1-800-783-3225. This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware and software, nor to provide for every possible contingency in connection with installation, operation, and maintenance. Features may be described herein which are not present in all hardware and software systems. FACTS Engineering assumes no obligation of notice to holders of this document with respect to changes subsequently made. FACTS Engineering retains the right to make changes to hardware and software at any time, without notice. FACTS Engineering makes no representation or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability of fitness for purpose shall apply.

TABLE OF CONTENTS CHAPTER 1: INTRODUCTION...1.1 SDS NETWORK FEATURES...1.1 APPLICATIONS...1.1 SDS PROTOCOL FEATURES...1.2 Identification Data...1.2 Diagnostic Data...1.2 Operational Parameters...1.2 Extended Operations...1.3 High Performance...1.3 SDS Network Master Module Specifications, F4-SDS...1.4 CHAPTER 2: CONFIGURATION... 2.1 SLOT DEPENDENT CONFIGURATION...2.1 Slot Dependent V-Memory Locations...2.1 Extended Operations Pointer...2.2 Communication Rate Code...2.2 Communication Rate Code Table...2.2 Error Code...2.3 Error Code Table...2.3 OnLine/OffLine Status Table Pointer...2.4 Extended SDS Bus Diagnostics...2.5 SDS NETWORK MASTER OPERATION RUNG...2.6 Slot Dependent BUSY Relay...2.6 Special Purpose (SP) Data Communications Relays...2.6 SDS Network Master Slot and Number of SDS Inputs...2.7 SDS Addressing Table...2.7 Number of SDS Outputs...2.8 SDS Addressing Table...2.8 Start Address of SDS Outputs...2.9 Start Address of SDS Inputs...2.9 Location of SDS Network Master Operation Rung...2.10 Example SDS Network Master V-Memory Map...2.12 CHAPTER 3: PORT CONNECTIONS AND NETWORK WIRING...3.1 SDS NETWORK MASTER CONNECTIONS...3.1 SDS BUS CONNECTION...3.2 APPENDIX A: TROUBLE SHOOTING... 4.1 DESCRIPTION OF NORMAL OPERATION...4.1 COMMON SDS MASTER PROBLEMS AND SOLUTIONS...4.1

CHAPTER 1: INTRODUCTION The SDS Network Master Module, F4-SDS, is the interface between a single Smart Distributed System of up to 64 intelligent SDS field devices and the DirectLogic DL405 PLC. The SDS Network Master Module maps input devices directly into the DL405 X, C, GX or V-Memory locations. Output devices are directly mapped into DL405 Ys, Cs, or V-Memory locations. SDS NETWORK FEATURES The features of the SDS Network make it an ideal intelligent device network for the factory floor and other rugged applications. T T T T T T T Low cost four wire installation is easy to install and maintain. Brad Harrison quick-disconnects eliminate installation errors when adding a device. Power is integrated into device wiring. Low cost network hardware originally developed for automobile systems such as anti-lock brakes (CAN bus). High-Information network provides advanced diagnostics and features. Response times to.10 msec per device. Industrially rugged and highly noise immune differential data transmission. Advanced error management and nondestructive arbitration with undetected bit error rates near zero. APPLICATIONS A SDS Network is typically used in distributed I/O installations such as conveyors and other applications where field devices are not concentrated. It is also used when an application requires one of the unique features or the advanced diagnostics provided by of the SDS Network. Other PLC Direct networking options for reducing wiring costs include Slice I/O (16 points per drop) and Remote I/O (128 points per drop). 1.1

SDS PROTOCOL FEATURES Each SDS device contains a data base which consists of identification data and diagnostic information. Each device data base also contains parameters which control the operation of the device. These features are summarized in the following table. The "Type" column indicates items which the SDS Network Master Module can Read Only (R), or can Read and Write (R/W). Item Description Type Identification Data Device Address Unique SDS address for this device, 1-126 R Vendor Identification Number assigned to the manufacture of the device R Tag Name Nick name assigned to the device by the user R/W Catalog Listing Manufacture's order number R Device Name Manufacture's device description or name R Vendor Name Manufacture's name R Software Version SDS device's software version number R Date Code Manufacture's date code for the device R Serial Number Manufacture's device serial number R Diagnostic Data Number of Operations Counter used for maintenance purposes R/W Elapsed Time Number of minutes the device has been operating R/W Power Cycles Number of power cycles the device has experienced R/W Diagnostic Errors Diagnostic Errors Counted during last self test R Sensor Diagnostics 32 Bus, Device, and Environmental error flags R/W Device Type SDS General Class of device codes R Operational Parameters NO/NC NO=0, NC=1 operation R/W On Delay Timer De-bounce time in msec of ON change of state R/W Off Delay Timer De-bounce time in msec of OFF change of state R/W Motion Detect Timer ON-OFF and OFF-ON transitions reset the timer R/W Batch Counter Number of operations before a change of state R/W Cyclical Timer Maximum rate of change of state indications R/W 1.2 INTRODUCTION

Extended Operations The FACTS Engineering SDS Network Master Module provides additional advanced capabilities. T Eight devices can be configured as high speed counters. Input transitions are accumulated by the SDS Network Master Module independently of the PLC scan. Current count values are reported to the PLC each scan. Control bits are provided to run and reset each counter individually. T The entire data base of a single device can be read into a user specified block of V-Memory with a single command. Using DirectSoft, this data can be hot linked (using DDE) to other Windows applications such as WonderWare or Paradox. T Read/Write parameters such as a device's Tag Name and timers can be changed in V-Memory then loaded into the device using a single command. Using the DDE capabilities built into DirectSoft, this data can originate from another Windows applications such as WonderWare or Paradox. High Performance The SDS Network Master is an intelligent Communication CoProcessor module which interfaces with the DL405 CPU using high speed parallel dual port memory. The dual port memory bus of the DirectLogic 405 has a bandwidth which rivals much larger PLCs. This bus can read 256 and write 128 bytes of CoProcessor dual port memory every scan. The use of dual port memory frees the SDS Network Master from the overhead often associated with communicating with a ladder logic CPU. The SDS Network Master's 26 MHz processor executes instructions at up to 6.5 MIPS. This insures the SDS Network Master is not a limiting factor in most applications. INTRODUCTION 1.3

SDS Network Master Module Specifications, F4-SDS Communication Rate 125K, 250K, 500K, 1M bps Maximum Distance Rate Devices Trunk Drop 125K 64 1600' 24' 250K 64 800' 12' 500K 64 400' 6' 1M 32 100' 3' Protocol Error Detection SDS, Honeywell Micro Switch CRC error checking and other techniques provide for an undetected bit error rate near zero. Status Indication LEDs POWER (green) ON-LINE (green) NODE ERR (red) (These multi-function LEDs are described on page??) Port Maximum Number of F4-SDSs per DL405 CPU I/O Configuration Range Impact on PLC Scan Time 9 Pin 8 Installed in CPU Base 16 to 64 Inputs 8 to 48 Outputs Minimal to 3 msec maximum each F4-SDS module 1.4 INTRODUCTION

CHAPTER 2: CONFIGURATION SLOT DEPENDENT CONFIGURATION The SDS Network Master is configured using a block of slot dependent configuration V-Memory locations in the DL405 CPU. These locations should be initialized before the SDS Network Master is used. The following table shows the V-Memory locations associated with each slot. These memory locations must be made retentive if the module should operate when the PLC powers up in program mode. Slot Extended Operations Pointer Slot Dependent V-Memory Locations Communication Rate Code Error Code OnLine/OffLine Status Table Pointer 0 V7660 V7670 V7710 V7730 1 V7661 V7671 V7711 V7731 2 V7662 V7672 V7712 V7732 3 V7663 V7673 V7713 V7733 4 V7664 V7674 V7714 V7734 5 V7665 V7675 V7715 V7735 6 V7666 V7676 V7716 V7736 7 V7667 V7677 V7717 V7737 2.1

Extended Operations Pointer The Extended Operations Pointer is a constant that specifies where the parameters which control the extended functions of the SDS Network Master are located (See Appendix B: Extended Operations). This location should be initialized on the first PLC scan. The value loaded is a constant that corresponds to a V-Memory location. The following example sets the Extended Operations Pointer to V7000 for a SDS Network Master installed in slot 4. Constant that corresponds to V7000 Slot 4 Extended Operations Pointer location Communication Rate Code The Communication Rate Code specifies the communication bit rate the SDS Network Master will use. This location should be initialized on the first PLC scan. The value loaded is a constant from the following Communication rate code table. The following example sets the communication rate to 1M bps for a SDS Network Master installed in slot 4. Constant that corresponds to 1M bps Slot 4 Communication Rate Code location Communication Rate Code Table Code Bit Rate 1 125K bps 2 250K bps 3 500k bps 4 1M bps The communication rate only needs to be programmed in the SDS Network Master. Then on power-up, the Master will automatically set all the SDS devices on the network to the programmed communication rate. 2.2 CONFIGURATION

Error Code The high byte of the Error Code location contains the SDS Network Master Module firmware version number. If an error is detected by the module's self diagnostics then an error code is placed in the low byte of the Error Code V-Memory location. The low byte is normally zero (no errors). The Error Code location is not written to until the module receives the first WX instruction from the PLC. It will also not write to this location if the slot dependent configuration data is incorrect or if the PLC is in program mode. Please refer to Trouble Shooting beginning on page 20 for additional information. Possible error codes are listed in the Error Code Table. Error Code Table Error Code Description 0 WX Executed Without Errors 1 Invalid Number of Inputs 2 Invalid Number of Outputs 3 Invalid Input Address 4 ROM CheckSum Error 5 Power-Up WDT Time-Out has Occurred 6 Severe Communication Problem in SDS Bus 7 Number of SDS Inputs Greater than PLC Block Size 8 Invalid Extended Operation Configured 9 Power-up WX instruction is Extended Operations, Output address and number of I/O expected 10 Invalid OnLine/OffLine Status Table Address in slot dependent location (V7730-V7737) 11 SDS Address change failed, duplicate address 12 SDS Address change failed, node does not exist. A firmware version 1.0 module installed in slot 3 would place 1002 in V7713 if the programmed number of outputs was invalid. CONFIGURATION 2.3

OnLine/OffLine Status Table Pointer The SDS Network Master reports the status of all configured nodes starting at the location specified by the OnLine/OffLine Status Table Pointer. At power-up, the SDS Network Master trains all the devices on the network with the programmed communication rate, self tests the network, then determines which devices are online. An ON bit in the OnLine/OffLine Status Table indicates that a device is online, an OFF bit indicates that a device is offline. If any device goes offline, the red NODE ERR led will turn on solid. Devices may not be added to the network with power applied. The first V-Memory location of the OnLine/OffLine Status Table Pointer is the OnLine/OffLine status for the first 16 SDS inputs. There is one V-Memory location for every 16 SDS inputs. The next V-Memory location in the status table contains the OnLine/OffLine status for the first 16 SDS outputs. There is one V-Memory location for every 16 SDS output devices. The following example sets the OnLine/OffLine Status Pointer to V2000 for a SDS Network Master installed in slot 4. Constant that corresponds to V2000 Slot 4 location to place OnLine/OffLine Table Pointer The online status bits can be used in conjunction with a devices ON/OFF status bits to interlock the operation of the device. 2.4 CONFIGURATION

Extended SDS Bus Diagnostics The SDS Network Master Module writes extended diagnostic information to the three V-Memory locations after the last output OnLine/OffLine status V-Memory location. Bus at Limit This counter is normally 0. A non-zero value indicates there is too much message traffic for the current communication rate. Should this happen, increase the communication rate or reduce the amount of message traffic. Message traffic can be reduced in several ways. The Cyclical Timer can be used to control the repeat rate of discrete input devices. The Batch Counter can be used to pre-scale (divide up) discrete inputs used for counting. Also, the de-bounce timers can be used to prevent input chatter. Over-runs This counter is normally 0. A non-zero value indicates that messages are arriving faster than the SDS Network Master can process them. Should this happen, reduce the communication rate or reduce the amount of message traffic (see Bus at Limit) Bus Errors This counter is normally 0. A non-zero value indicates that there is a high percentage of communication errors on the bus. CONFIGURATION 2.5

SDS NETWORK MASTER OPERATION RUNG The SDS Network Master is operated using a single rung of ladder logic. This rung specifies the slot where the F4-SDS is installed, the number of SDS input bytes, the number of SDS output bytes, the DL405 V-Memory location of the first SDS output, and the V-Memory location of the first SDS input. Slot Dependent BUSY Relay hh ii oo ssss dddd Slot Number of F4-SDS Number of SDS Input Bytes Number of SDS Output Bytes Starting V-Memory address of SDS Outputs. Starting V-Memory address of SDS Inputs. The slot dependent BUSY relay should be included in the WX rung. The following table shows the relay to use for each of the eight possible slots where the F4-SDS can be installed. Special Purpose (SP) Data Communications Relays Slot 0 1 2 3 4 5 6 7 BUSY 120 122 124 126 130 132 134 136 ERROR 121 123 125 127 131 133 135 137 If the F4-SDS module has not processed the last WX instruction executed, the Special Purpose (SP) BUSY relay associated with the slot where the F4-SDS module is installed is turned on. Normally the SDS Network Master communicates with the PLC every scan. It is possible that under conditions of severe network loading, the BUSY relay may be energized. This coil is normally off. If the F4-SDS module is not communicating with the PLC then the ERROR relay associated with the SDS's slot is energized. If the ERROR relay is energized please refer to the trouble shooting section. 2.6 CONFIGURATION

SDS Network Master Slot and Number of SDS Inputs The first LD (LOAD) instruction of the configuration rung uses a high byte and a low byte to specify the module's slot number and the SDS number of input bytes. The high byte (hh) is the slot where the F4-SDS is installed. The range of valid slot numbers is 0 to 7. The low byte (ii) is the number of input bytes. This is an even number ranging from 2 to 8. hh ii oo ssss dddd Slot Number of F4-SDS Number of SDS Input Bytes Number of SDS Output Bytes Starting V-Memory address of SDS Outputs. Starting V-Memory address of SDS Inputs. NOTE: All SDS input device addresses must be less than or equal to the highest possible input address based on the number of input bytes specified. If 2 input bytes (16 devices) are specified then the highest input address is 2x8 = 16. The number of input bytes plus the number of outputs bytes must be # 8. SDS Addressing Table Input Address Range Number of Input Bytes Output Address Range Number of Output Bytes C 1-16 1-32 1-48 1-64 2 4 6 8 17-64 33-64 49-64 0 If the number of input or output bytes is zero, the WX rung is ignored by the PLC. When the number of input bytes is 8, the SDS Network Master ignores the number of output bytes. 1-6 1-4 1-2 1* CONFIGURATION 2.7

Number of SDS Outputs The second LD (LOAD) instruction of the configuration rung specifies the number of output bytes. The valid range for the number of output bytes is 1 to 6. hh ii oo ssss dddd Slot Number of F4-SDS Number of SDS Input Bytes Number of SDS Output Bytes Starting V-Memory address of SDS Outputs. Starting V-Memory address of SDS Inputs. NOTE: All SDS output device addresses must be greater than the highest possible input address and less than or equal to the maximum configured output address. If 2 input and 2 outputs bytes are specified then the highest output address is 2x8 + 2x8 = 32. The number of input bytes plus the number of outputs bytes must be # 8. SDS Addressing Table Input Address Range Number of Input Bytes Output Address Range Number of Output Bytes C 1-16 1-32 1-48 1-64 2 4 6 8 17-64 33-64 49-64 0 If the number of input or output bytes is zero, the WX rung is ignored by the PLC. When the number of input bytes is 8, the SDS Network Master ignores the number of output bytes. 1-6 1-4 1-2 1* 2.8 CONFIGURATION

Start Address of SDS Outputs The LDA (LOAD ADDRESS) instruction of the configuration rung specifies the starting V-Memory address where SDS outputs come from. Any valid V-Memory reference may be placed here. The O in the LDA instruction stands for Octal. To specify V1400 as the starting data address use O1400. To specify V40500 as the starting address use O40500. hh ii oo ssss dddd Slot Number of F4-SDS Number of SDS Input Bytes Number of SDS Output Bytes Starting V-Memory address of SDS Outputs. Starting V-Memory address of SDS Inputs. Start Address of SDS Inputs The WX instruction of the configuration rung specifies the V-Memory location where SDS inputs will be placed. Any valid V-Memory reference may be placed here. To specify V1400 as the starting data address use V1400. To specify V40400 as the starting address use V40400. hh ii oo ssss dddd Slot Number of F4-SDS Number of SDS Input Bytes Number of SDS Output Bytes Starting V-Memory address of SDS Outputs. Starting V-Memory address of SDS Inputs. CONFIGURATION 2.9

NOTE: If enabled, the asynchronous high speed counters use the 8 V-Memory locations following the last SDS input V-Memory location. See Appendix B for more information on Extended Operations. Location of SDS Network Master Operation Rung For normal operation, the SDS Network Master Operation WX rung should be executed every scan. When the WX rung is executed, the status of the specified outputs are saved for later output to the SDS Network Master. For this reason the WX rung is normally placed at the end of the program. If the WX rung is placed before the ladder logic which changes the state of one of the SDS outputs, then the SDS output change of state will be delayed by one additional PLC scan time. The following diagram shows how the SDS inputs and outputs fit into the DL405 CPU run mode operation. DL405 CPU Scan Read Inputs Reads SDS Input status from SDS Master Writes SDS Output status to SDS Master Solve the Application Program Write Outputs 2.10 CONFIGURATION

Example: The SDS Network Master Module is installed in slot 4. Extended Operations begin at V7000 (optional). The communication rate is 1M bps. The OnLine/OffLine Status table begins at V2000. There are 16 SDS inputs and 16 SDS outputs on this network. SDS inputs 1-16 are written to X260-X277 (V40413). SDS outputs 17-32 are read from Y460-Y477 (V40523). Constant that corresponds to V7000 Slot 4 Extended Operations Pointer location Constant that corresponds to 1M bps Slot 4 Communication Rate Code location Constant that corresponds to V2000 Slot 4 OnLine/OffLine Status Table Pointer 04 = Slot Number of F4-SDS 02 = 2 Bytes of SDS inputs 02 = 2 bytes of SDS outputs V40523 = Starting address to copy SDS outputs from V40413 = Starting address to copy SDS inputs to CONFIGURATION 2.11

Example SDS Network Master V-Memory Map OnLine/OffLine Status Table SDS Inputs SDS Outputs Extended Operations V2000 Inputs 1-16 V40413 X260-X277 V40523 Y460-Y477 V7000 Control Codes V2001 Outputs 17-32 V40414 Input 1 Count V7001 Counter Control V2002 Bus at Limit V40415 Input 2 Count V7002 Database Pointer V2003 Over-runs V40416 Input 3 Count V2004 Bus Errors V40517 Input 4 Count V40420 Input 5 Count V40421 Input 6 Count V40422 Input 7 Count V40423 Input 8 Count SDS input devices with addresses of 1 to 16 correspond to DL405 input contacts X260 to X277 respectively. SDS output devices with addresses of 17 to 32 are activated by DL405 output coils Y460 to Y477. V2000 contains the OnLine/OffLine status of the SDS input devices. The least significant bit of V2000 corresponds to the OnLine/OffLine status of SDS input 1. The most significant bit of V2000 corresponds to the OnLine/OffLine status of SDS input 16. If the bit is ON then the associated device is online, if the bit is OFF the associated device is offline. Since 2 bytes were configured for inputs, only 1 V-Memory location is required for OnLine/OffLine status of inputs (V2000). The next V-Memory location (V2001) is the start of the OnLine/OffLine status of SDS output devices. If an odd number of bytes are configured for inputs, the OnLine/OffLine status of outputs will start at the next V-Memory location. 2.12 CONFIGURATION

CHAPTER 3: PORT CONNECTIONS AND NETWORK WIRING The F4-SDS Network Master interfaces to the SDS Network using a 9-pin D type connector. This connector provides bus data connections to the network. Typically the communications cable is connected to a terminal block in the control panel. The bus power supply and the cable to the F4-SDS are connected to this terminal block. Please refer to the diagram on the following page. SDS NETWORK MASTER CONNECTIONS The bus power is not supplied by the SDS Network Master. No connection to pins 5 or 6 is required. These pins may be used to simplify daisy chain connections. Pin Number Description Symbol 1 BUS COMMUNICATIONS (+) BUS + 2 BUS COMMUNICATIONS (+) BUS + 3 BUS COMMUNICATIONS (-) BUS - 4 BUS COMMUNICATIONS (-) BUS - 5 BUS POWER (+) PWR + 6 BUS POWER (+) PWR + 7 COM BUS POWER (-) PWR - 8 COM BUS POWER (-) PWR - 9 SHIELD SHLD NOTE: Pins 1-2, 3-4, 5-6, and 7-8 are internally connected to simplify daisy chain connections. 3.1

SDS BUS CONNECTION 3.2 PORT CONNECTIONS AND NETWORK WIRING

APPENDIX A: TROUBLE SHOOTING DESCRIPTION OF NORMAL OPERATION At power up, the POWER LED is ON. The ON-LINE LED flashes ON very briefly. This indicates that a valid slot dependent configuration has been read. The NODE ERR LED comes ON for about one second then goes OFF. This indicates that the module is setting the communication rate of all devices on the network. The ON-LINE LED comes ON for about one second then goes OFF for about one second and repeats this pattern as long as no errors are detected. The slot dependent module BUSY and ERROR special relays are OFF. The module writes the firmware version to the slot dependent V-Memory location with no error codes. The module signs on in the I/O configuration table as "D4-DCM". COMMON SDS MASTER PROBLEMS AND SOLUTIONS Problem: Symptom: Cause 1: Solution: "No Heartbeat" At power-up, The ON-LINE LED flashes ON briefly then goes OFF. The NODE ERR LED never comes ON. The SDS Network Master Operation rung (WX) is not executing. Add the WX rung if it does not exist. Verify that the special relay (SP) used is for the slot that the module is installed in. Verify that the PLC is in RUN mode. The WX instruction is not executed while the PLC is in program mode. Verify that the WX rung values are valid. The WX rung will not execute if the number of inputs or the number of outputs specified is zero. Cause 2: Solution: The SDS cable is defective or disconnected before the first device. Repair the SDS Network cable then power cycle the network. At least one SDS device must be connected to the SDS Network Master. 4.1

Problem: Symptom: Cause: Solution: "Railroad Lights" At power-up, the ON-LINE and NODE ERR LEDs flash back and forth. Slot dependent configuration V-Memory locations are invalid. Check the slot dependent V-Memory locations for valid values. Slot Dependent V-Memory Locations V7660-V7667 Extended Operations Pointer V7670-V7677 Communication Rate Code V7730-V7737 OnLine/OffLine Status Table Pointer Valid values K1400 to K7377 K1 to K4 K1400 to K7377 Problem: Symptom: "Power LED Goes OFF" The POWER LED flashes about every ten seconds followed by a brief flash of the ON-LINE LED. The ERROR relay associated with the SDS module's slot is energized. Cause: Solution: SDS Network cable is defective or disconnected before the first device connection. Repair or reconnect the SDS Network cable then power cycle the network. Problem: Symptom: Cause: Solution: "Red NODE ERR LED Stays ON" The red NODE ERR LED comes ON solid. The ON-LINE LED continues to flash normally at one second intervals. A device that was previously online is now offline. Reconnect or replace device. 4.2 TROUBLE SHOOTING

Problem: Symptom: Cause: Solution: "Red NODE ERR LED Flashes" The ON-LINE LED is ON solid and the red NODE ERR LED is flashing very fast. There is an error in the WX rung. Look at the slot dependent error code location to determine the exact error and take the appropriate action. Error Code Table Error Code Description 0 WX Executed Without Errors 1 Invalid Number of Inputs 2 Invalid Number of Outputs 3 Invalid Input Address 4 ROM CheckSum Error 5 Power-Up WDT Time-Out has Occurred 6 Severe Communication Problem in SDS Bus 7 Number of SDS Inputs Greater than PLC Block Size 8 Invalid Extended Operation Configured 9 Power-up WX instruction is Extended Operations, Output address and number of I/O expected 10 Invalid OnLine/OffLine Status Table Address in slot dependent location (V7730-V7737) 11 SDS Address change failed, duplicate address 12 SDS Address change failed, node does not exist. TROUBLE SHOOTING 4.3