Legal Information The Schneider Electric brand and any registered trademarks of Schneider Electric Industries SAS referred to in this guide are the sole property of Schneider Electric SA and its subsidiaries. They may not be used for any purpose without the owner's permission, given in writing. This guide and its content are protected, within the meaning of the French intellectual property code (Code de la propriété intellectuelle français, referred to hereafter as "the Code"), under the laws of copyright covering texts, drawings and models, as well as by trademark law. You agree not to reproduce, other than for your own personal, noncommercial use as defined in the Code, all or part of this guide on any medium whatsoever without Schneider Electric's permission, given in writing. You also agree not to establish any hypertext links to this guide or its content. Schneider Electric does not grant any right or license for the personal and noncommercial use of the guide or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this publication.
Shore Connection 500 kva Table of Contents Important Safety Instructions SAVE THESE INSTRUCTIONS...5 Safety Precautions...6 Overview...7 User Interface...7 Menu Tree...8 Display Symbols...9 Configuration...10 Configure the Display Language...10 Configure the Date and Time... 11 Set the Dry Contacts...12 Access the Parameters...12 Available Commands and Status Conditions...12 Set Up a Contact...14 Other Available Settings...14 Personalise the GFC...15 Access the Personalisation Parameters...15 Available Personalisation Commands...15 Operation...16 Operating Modes...16 Normal Mode...16 Standby Mode...16 Operation Procedures...16 Start Up the GFC...16 Isolate an Installation...17 Transfer the GFC Back to Normal AC Power...18 GFC Monitoring...19 Overview...19 PLC Setting...20 Building Management System Setting...20 Remote Monitoring System Setting (Option)...20 Maintenance...21 Life Cycle Monitoring (LCM)...21 Disable the Life Cycle Monitoring (LCM) Function...21 Troubleshooting...22 General Status LEDs...22 Buzzer...22 Mimic Panel...22 990-5695 001 3
Important Safety Instructions SAVE THESE INSTRUCTIONS Important Safety Instructions SAVE THESE INSTRUCTIONS Shore Connection 500 kva Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of this symbol to a Danger or Warning safety message indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death. DANGER DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. Failure to follow these instructions will result in death or serious injury. WARNING WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. Failure to follow these instructions can result in death, serious injury, or equipment damage. CAUTION CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Failure to follow these instructions can result in injury or equipment damage. NOTICE NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this type of safety message. Failure to follow these instructions can result in equipment damage. Please Note Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 990-5695 001 5
Shore Connection 500 kva Important Safety Instructions SAVE THESE INSTRUCTIONS A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved. Safety Precautions DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH All safety instructions in this document must be read, understood and followed. Failure to follow these instructions will result in death or serious injury. DANGER HAZARD OF ELECTRICAL SHOCK, EXPLOSION OR ARC FLASH After the UPS system has been electrically wired, do not start up the system. Start-up must only be performed by Schneider Electric. Failure to follow these instructions will result in death or serious injury. 6 990-5695 001
Overview Overview Shore Connection 500 kva User Interface A. Graphical display B. Output ON C. Minor or environmental alarm LED D. Major alarm E. Help/buzzer off button F. Function keys G. Main menu button H. OFF button. I. ON button. J. Voltage on GFC load K. Inverter LED L. PFC LED 990-5695 001 7
Shore Connection 500 kva Overview Menu Tree Main Menu Measurements Alarms History Settings Controls Measurements Alarms History Settings Controls Load Inverter Normal AC Time-stamping Statistics since last maintenance Statistics since the commissioning Language Date and time Contrast Buzzer volume Temperature units Screensaver Personalisation 1 Output voltage Dry contacts Password Reset alarm Enable PLC control mode Connect the load LED test Reset statistics Disable LCM signalization Disable OOL signalization Confirm number of available GFC Personalisation Automatic start Rated Output voltage Frequency Rated Output 1. Only available if no PLC is installed. 8 990-5695 001
Overview Shore Connection 500 kva Display Symbols Vertical selection Delete Other selection Measurements Enter/confirm Increase Next page Decrease Previous page Save Details Alarm History Details on each module Return to previous screen/menu 990-5695 001 9
Shore Connection 500 kva Configuration Configuration Configure the Display Language 1. Press the button. 2. Press the button until Settings is highlighted, and press the button. 3. Press the button until Languages is highlighted, and press the button. 4. Press the button until the desired language is highlighted, and press the button. 5. Press the button. 10 990-5695 001
Configuration Shore Connection 500 kva Configure the Date and Time NOTE: For event time-stamping, the correct date and time must be set. 1. Press the button. 2. Press the button until Settings is highlighted and press the button. 3. Press the button until Date and time is highlighted and press the button. 4. Press the and buttons until the desired date is displayed and press the button. 5. Repeat step 3 to set the month, year, hour, minutes, and seconds. 6. Press the button. 7. Press the button. 990-5695 001 11
Shore Connection 500 kva Configuration Set the Dry Contacts Access the Parameters NOTE: The default password (factory set) is 000. 1. Press the button. 2. Press the button until Settings is highlighted, and press the button. 3. Press the button until Dry contacts is highlighted, and press the button. 4. Press the and buttons until the first digit of the password is displayed, and press the button. 5. Repeat step 4 to select the second and third digits of the password. NOTE: The default password (factory set) is 000. 6. Press the button. Available Commands and Status Conditions Available Status Conditions Outputs O1 to O6 NOTE: If PLC is used, outputs O1 and O2 are reserved for GFC state. A GFC state is encoded in 2 bits: GFC state Bit value for output O1 Bit value for output O2 Standby (GFC power converter off; electronic only powered) OFF (GFC started, output static switch opened) 0 1 2 1 2 1 2 ON (GFC connected to the load) 1 2 0 Major alarm or powered off (maintenance mode) 0 0 2. Closed contact. Output relay contact is normally open. 12 990-5695 001
Configuration Shore Connection 500 kva Charger inoperable Check the GFC Environment alarm EPO activated Fuse blown General alarm Inverter inoperable Load protected Overload PFC inoperable Phase rotation inoperable Maintenance position GFC fan inoperable Available commands Inputs I1 to I4 If PLC is used, inputs I1, I2, and I3 are forced for following commands: Inputs Commands Activation I1 PLC start On rising edge when relay contact closes I2 PLC standby On rising edge when relay contact closes I3 Dry contact output forced in 50 Hz On level when relay contact is closed Input state change is validated when the input state is stable for 200 ms. Customer alarm 1 Customer alarm 2 Customer alarm 3 Customer alarm 4 Limit input power during operation on genset power. 990-5695 001 13
Shore Connection 500 kva Configuration Set Up a Contact The example shows a setup of an output contact. The procedure is identical for an input contact. It is necessary to first access the parameters (See Access the Parameters, page 12.) 1. Press the button until Output is highlighted and press the button. 2. Press the button until the contact to be set is highlighted and press the button. 3. Press the button until the desired status condition is highlighted and press the button. 4. Press the and buttons until the desired delay is displayed and press the button. 5. Press the button. 6. Press the button until Yes is highlighted and press press the button. 7. Press the button. Other Available Settings Settings Contrast Buzzer volume Possible choices 0 to 100% in 10% steps 0 to 100% in 10% steps Temperature units C or F Screensaver Output voltage Default welcome screen, alarms, normal AC measurements +/-3% in 0.5 V steps Password New password (the default value is 000) 14 990-5695 001
Configuration Shore Connection 500 kva Personalise the GFC Access the Personalisation Parameters Only available if PLC is not used. Before starting, the GFC must be in maintenance bypass mode. 1. Press the button. 2. Press the button until Settings is highlighted and press the button. 3. Press the button until Personalisation is highlighted and press the button. 4. Press the and buttons until the first digit of the password is displayed and press the button. 5. Repeat step 4 to set the second and third digits of the password. 6. Press the button. Available Personalisation Commands Before starting the personalisation sequence, the GFC must be stopped. Standard personalisation functions 3 Factory set-up Other possible choices Automatic start Disabled Enabled Rated output voltage 400 V 380 V, 415 V, 440 V Rated output frequency 60 Hz 50 Hz Load level warning 4 100% 40 to 100% in 10% steps 3. Some personalisation functions may not be available depending on your installation. 4. These personalisation settings do not require the GFC to be stopped. 990-5695 001 15
Shore Connection 500 kva Operation Operation NOTE: Only trained and certified personnel must carry out the following operation procedures. Operating Modes Normal Mode Normal AC source is available, GFC coupled: Load powered LED (A) is ON. The load is powered by the GFC. Standby Mode Normal AC source is available, GFC is stopped: Minor or environmental alarm LED (B) is orange and load LED (C) is orange. The buzzer sounds intermittently. The load is not powered by the GFC. Operation Procedures Start Up the GFC CAUTION HAZARD OF INJURY OR EQUIPMENT DAMAGE Connection of power and control cables must be carried out and checked by qualified personnel. Failure to follow these instructions can result in injury or equipment damage. The doors of the cabinets must be open. Before starting the sequence, the switches must be in off position, as indicated below: 16 990-5695 001
Operation Shore Connection 500 kva GFC Cabinets The circuit breakers upstream of the normal AC line must be open. The GFC must be shut down; the load is not powered. 1. Close the upstream circuit breakers on the normal AC lines and external power source ventilation. 2. Perform the following steps on all GFC cabinets: a. Turn the Q1 switch to ON. b. Check that the PFC LED is green 3. Turn the Q5N switches on all GFC cabinets to ON. 4. Check the presence of all GFC units on the display of one of the GFC units. 5. Press the button. 6. Close the doors. 7. Press the ON button on all the GFC units. The load is powered by the GFC system when enough units are ready and all LEDs are green. Isolate an Installation NOTE: The GFC must be ON. At the end of this procedure, the load is no longer powered with AC power. 990-5695 001 17
Shore Connection 500 kva Operation 1. Perform the following steps on the first GFC cabinet: a. Press the OFF button for 3 seconds. The load is powered by the other GFC unit. If there is no other GFC unit, the load is no longer powered. b. Open the door. 2. Perform the following steps on the first GFC cabinet: a. Turn the Q5N switch to OFF. b. Turn the Q1 switch to OFF. 3. Press the OFF button of the last GFC cabinet for 3 seconds. The load is no longer powered. 4. Perform the following steps on the last GFC cabinet: a. Turn the Q1 switch to OFF. b. Turn the Q5N switch to OFF. 5. Open the upstream circuit breaker for external power source for ventilation. Transfer the GFC Back to Normal AC Power The doors of the cabinets must be open. Before starting the sequence, the switches must be in off position, as indicated below: GFC Cabinets 1. Close the upstream circuit breakers on the normal AC lines and external power source ventilation. 18 990-5695 001
Operation Shore Connection 500 kva 2. Perform the following steps on all GFC cabinets: a. Turn the Q1 switch to ON. b. Check that the PFC LED is green. 3. Turn the Q5N switches on all GFC cabinets to ON. 4. Check the presence of all GFC units on the display of one of the GFC units. 5. Press the button. 6. Close the doors. 7. Press the ON button on all the GFC units. The load is powered by the GFC system when enough units are ready and all LEDs are green. GFC Monitoring Overview A. Remote Monitoring System (RMS) network via ethernet 5 B. Remote Monitoring System (RMS) network via modem C. PLC network or Building Management System (BMS) network via Modbus D. PLC I/O network E. PLC F. Hub G. RMS center 5. For monitoring via web, please consult the after-sales support or the local office. 990-5695 001 19
Shore Connection 500 kva Operation PLC Setting PLC setting is done by a Schneider Electric field service engineer during installation. Building Management System Setting For building management system setting, refer to: AP9635 network management card user s guide Modbus register map Remote Monitoring System Setting (Option) Remote monitoring system setting is done by a Schneider Electric field service engineer during installation. 20 990-5695 001
Maintenance Maintenance Shore Connection 500 kva Life Cycle Monitoring (LCM) The life cycle monitoring function provides GFC maintenance advice. A. Environment alarm LED B. Enter button Press the Enter button to display the LCM ALERT information Alarm details LCM alarm details End of warranty. Check recommended. End of wearing parts service life. Technical check recommended. Description Contact Schneider Electric to extend the optimum operating period of your installation. The parts of the product that are subject to wear should be checked. Contact Schneider Electric. Disable the Life Cycle Monitoring (LCM) Function 1. Follow one of the procedures when LCM messages are displayed: For temporary disabling: Press the ESC button. The message will be repeated twice every 30 days 6. For complete disabling of LCM messages: Select Disable LCM indications in the Controls menu. NOTE: You will no longer be informed of LCM events related to your GFC. 6. Default setting. 990-5695 001 21
Shore Connection 500 kva Troubleshooting Troubleshooting An alarm is present when: at least one LED is red at least one LED is orange the buzzer beeps If an anomaly occurs, the display instructs the operator on the required action. General Status LEDs The load powered LED (A) is ON and green: The load is powered. The major alarm LED (B) goes ON red: The load is not powered. Follow the displayed instructions. The environment alarm LED (C) is ON and orange: Minor or environment alarm. The load is still powered. Follow the displayed instructions. Buzzer Stop the buzzer by pressing the Stop buzzer button (A). Mimic Panel One of the following LEDs goes ON red: A. PFC is inoperable. 22 990-5695 001
Troubleshooting Shore Connection 500 kva B. Inverter is inoperable. C. Load is not powered. One of the main GFC functions is unoperable. Follow the displayed instructions. 990-5695 001 23
Printed in. Schneider Electric Schneider Electric 35 rue Joseph Monier 92500 Rueil Malmaison France + 33 (0) 1 41 29 70 00 www.schneider-electric.com As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication. 2012 2016 Schneider Electric. All rights reserved. 990-5695 001