ACOS 300. Reliable protection for network and constructions in medium- and high voltage

Similar documents
TWO-WINDING TRANSFORMER DIFFERENTIAL

Feeder protection relay SPAA 121 C. Product Guide

Protection relays.

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Earth-fault Relay SPAJ 110 C. Product Guide

INTRODUCTION. The PL-50 MO and PM-250 families represent the. PM-250-H: Horizontal box. PM-250-V: Vertical box

PROTECTION RELAYS THE ULTRA LINE NUMERICAL MULTIFUNCTION INTELLIGENT DEVICE FOR PROTECTION, SUPERVISION, METERING AND CONTROL

For Transmission, Distribution and Machinery protection.

Perfect protection smallest space

IDS SAS. Station Automation System for Complex Applications

Residual overvoltage relay

Bus Bar Protection Relay B-PRO 4000

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

InteliPro. Protection Relay for Parallel Applications. Technical Specification

High impedance protection relay

Protection Relays PHASE & RESIDUAL OVERCURRENT

SYMAP R Plug in Variants FI, MI, 87M, TI Technical data

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators

Siprotec 7ST61 / 7ST63

Substation Automation Products. Line differential protection RED670 Relion 670 series

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

TU531, TU532 Terminal Unit

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Feeder/ Motor Protection Relay VAMP 40

STEP-PS/1AC/24DC/1.75

Voltage regulator. SPAU 341 C 1MRS MBG Issued: July 1998 Status: Revised Version: C/ Data subject to change without notice

MINER-S Station Controller

MiCOM P122C Time-Overcurrent Protection

UMG 20CM. UMG 20CM 20 Channel Branch Circuit Monitoring Device with RCM. Harmonics via analysis channel RCM. Alarm management.

Telecontrol and Automation Systems

Transformer Protection Relay

Substation Automation Products. Bay control REC670/650 Relion 670 and 650 series

Numerical motor protection in medium voltage networks Motor Protection and Control REM620

Contact protection relay

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

extending the boundaries of technology evolution of proven technology FEATURES

Perfect protection smallest space

UMG 20CM. 20 Channel Branch Circuit Monitoring Device with RCM

This annex is valid from: to Replaces annex dated: Location(s) where activities are performed under accreditation

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

GPM500 Generator Protection Module

TF501, TF521 Terminal Bases

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers

Relion 615 series Line Differential Protection and Control RED615 Ver. 2.0 Technical Presentation

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

MINER-S Station Controller. Substation Automation

Station Automation based on IEC 61850

e 2 TANGO -400 Overcurrent Relay K Catalogue EN

Safety Standards. Model Number: Unit Weight:

MC 11 EB-2 Power supply cabinet with external bus, AC version

Type VRLTC tap changer

Safety Standards. Model Number:

Substation Automation Products. Generator protection REG670/650 Relion 670 and 650 series

MULTI 9 System Catalog UL Recognized C60N Supplementary Protectors

SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

Feeder protection relay SPAA 341 C. Product Guide

DIN Rail RTU 540CMD01 Data sheet

AO523 Analog Input Module

Sturdy and Powerful ACOS 750

Safety Standards. Model Number:

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

MINI-PS AC/10-15DC/8

ATV310HU30N4E variable speed drive ATV310-3 kw - 4 hp V - 3 phase

CM597 Ethernet Communication Module

Products Portfolio. Pole mounted Vacuum Recloser

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

Feeder Protection Relay REF 610. Product Guide

100BPS15 B. MDS Medical AC-DC Open Frame 15Volt, 100Watt / MDS-100BPS15 B ``` Highlights & Features. Safety Standards.

FL MC 2000E (SM40) LC

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Feeder protection relay

Solid-State Contactors

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D

Safety Standards. Model Number:

REL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485

Safety Standards. Model Number:

www. ElectricalPartManuals. com l Basler Electric MPS100 MOTOR PROTECTION SYSTEM ADVANTAGES WINDOWS SOFTWARE ADDITIONAL INFORMATION

Control Panel CP600 CP635, CP635-B, CP635-WEB

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

TAPCON NEXT-GENERATION VOLTAGE REGULATORS. transformer control

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

Scout-S Station Controller

040APS12 B MDS. MDS Medical AC-DC Open Frame 12Volt, 40Watt / MDS-040APS12 B ``` Highlights & Features. Safety Standards.

Synchro-check relay. Application

Safety Standards. Model Number:

CM592 PROFIBUS Communication Module

Arc protection relay. Features Three-phase overcurrent function. Application

Product Details. Contents. Features and Mounting Options for SUNNY STRING-MONITOR SSM24-11

ATV12H075M3 variable speed drive ATV kW - 1hp V - 3ph - with heat sink

AI561 Analog Input Module

PROTECTION, AUTOMATION & CONTROL

RT12-240V/2.4kW Rectifier Specification

ATV12H018M2 variable speed drive ATV kW hp V - 1ph

Overcurrent and Arc Protection by Reyrolle Alexander Erokhin. 21, 2017 I Berlin

SACE Emax 2 Specification guide

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Transcription:

ACOS 300 Reliable protection for network and constructions in medium- and high voltage

IDS GmbH: Your competent partner for protection technology Network protection for medium- and high voltage Already minor incidents, such as branches dropping on overhead lines or underground cables damaged by construction works, may lead to short circuits or earth faults and, consequently, cause hazard to valuable equipment through dangerous currents and voltages. In the worst of cases, even human life may be put at risk. Power failures resulting from such incidents can lead to incalculable risks. Moreover, power in feeds from renewable energy sources and their volatility put additional strains on power grids. Therefore, efficient solutions for energy distribution networks and decentralized power generation plants are in ever-increasing demand, to help ensure a secure energy supply and protect persons and valuable equipment against damage. The increasing degree of network automation through safe network protection technology reduces the staff s workload, thereby also leading to a further reduction of costs. Products and service by one With the protection equipment family ACOS 300, IDS GmbH offers innovative grid protection technology. ACOS 300 is designed for the reliable protection of medium-voltage grids and transformers on the high-voltage level, and for their monitoring and control. The ACOS 300 series features the following highlights: Complete portfolio of overcurrent, distance and differential protection functions for medium- and high-voltage systems Comprehensive control and monitoring functions (local control in ACOS 35x) Further functions as reserve protection 3,5 /5,7 color touch display (ACOS 35x) B/W display (ACOS 33x) Integrated web server to provide support for operation, tests and configuration Configuration via function plan according to IEC 61131-3 Full communication capability according to IEC 61850 and IEC 60870-5-103/-104. Uniform, flat and compact design for all types Possibility of a deposed display Integration in door, swing gate, rack or on mounting plate Comprehensive logging system Furthermore, a wide range of additional functions is available as protection reserve. For the implementation of individual protection concepts in medium-voltage grids, the following protection devices with integrated control function (combined protection) are available: Protection devices: ACOS 331 for non-directional overcurrent-time/motor protection ACOS 333 for directional overcurrent-time protection ACOS 334 for distance protection ACOS 335 for line differential protection Combined protection devices: ACOS 351 for non-directional overcurrent-time protection ACOS 353 for directional overcurrent-time protection ACOS 354 for distance protection ACOS 355 for line differential protection ACOS 357 for motor protection The following devices (combined protection) have been specially designed for the protection of high-performance two-winding and three-winding transformers: ACOS 392 for transformer differential protection for two-winding transformers ACOS 395 for transformer differential protection for three-winding transformers IDS protection devices are suitable for seamless integration into the digital station automation system IDS SAS and into third-party systems.

Earth fault protection: Double earth fault Tripping characteristic overcurrent protection Tripping characteristic earth fault protection Overcurrent Protection All ACOS 300 devices include an overcurrent protection function as a standard. The simplest variant, ACOS 351, is designed for non-directional overcurrent protection. Tripping takes place either independently of the current, or current-dependent, with inverse characteristics according to IEC 60255-151, Edition 1.0, 2009-08 and IEEE. In addition to overcurrent protection, ACOS 353 includes several voltage protection functions. Based on a voltage evaluation, a direction decision is made, thereby ensuring selectivity even in bidirectional power lines. The desired tripping range can be set using different parameters. Earth-Fault Protection Earth faults or ground faults are frequently occurring faults in grid operation. In grids with effective neutral earthing, dangerous currents may occur at the point of fault, which have to be eliminated as quickly as possible. The standard configuration scope of each ACOS 300 device also includes earth fault protection functions, which are similar to the overcurrent-time protection function; the total current measured at the neutral point and the calculated zero current, respectively, serve as characteristic quantity. Overcurrent protection: Single-sided feed Overcurrent protection: Double-sided feed

Tripping characteristic distance protection Tripping characteristic line differential protection Distance Protection An algorithm that is specially adapted to insulated and deleted networks ensures reliable, safe and selective operation. Up to five zones can be parameterized using an individually configurable polygon. A protection function against inadvertent energizing ensures quick reactions to an existing fault (e.g. after an automatic reclosing) upon connection. If a double earth fault is detected, the distance protection function switches one of the two affected phases off, depending on which phase has been prioritized. The now single-phase earth fault is finally eliminated through an earth overcurrent protection function. Line Differential Protection This protection function is based on a comparison of the synchronized scanned currents at both line ends. If the detected differential current is too high, a tripping signal is generated. Error currents caused by transmission faults of the transformers are taken into account in a tripping characteristic and do not induce tripping. The benefits of the line differential protection function also include selectivity and quick tripping across the entire protection range. Distance protection: meshed topology Line differential protection

Tripping characteristic neutral point differential Tripping characteristic transformer differential Transformer Differential Protection A comparison of measured currents (primary, secondary and tertiary) takes place after numerical adaptation of switching groups and amplitudes and after an evaluation of the second and fifth harmonic for transformer inrush stabilization. If the detected differential current is too high, a tripping command is generated. Additionally, the zero-current differential protection function compares the summation current measured at the neutral point with the calculated zero-current component of the three phases. If the parameterized deviation is exceeded, tripping is induced. Other important features of the transformer differential protection function for two- and three-winding transformers are selectivity and instantaneous tripping across the entire protection range. Motor Protection Electrical motors are the heart of driving systems in industrial installations. Apart from the standard configuration of the non-directional overcurrent-time protection device ACOS 351, the following additional functions that are specially designed for the protection of motors against thermal and mechanic overload up to the megawatt range are available: under voltage protection start-up monitoring anti-jam protection undercurrent monitoring prevention of thermal overload caused by an excessive number of start-ups per hour Three-winding transformer Motor protection

Local Control, Parameterization and Diagnostics ACOS protection devices can be easily operated via the 3.5 color touch display and four capacitative touch keys. Control, Parameterization and Diagnostics via Web Server A web server that is accessible via ordinary web browsers provides several additional servicing functions. The web server shows an identical image of the local display. ACOS 35x with color-touch-display Parameterization for web server The following functions are available: Indications on the display are, to a large extent, freely configurable and can be adapted to the user s requirements. Plant image with circuit state display Indication of - Measured values, also as maximum value display - Event display - Protection and system settings Operation and switchgear control - Command output with multi-level operational concept - Set position display on demand and during a command cycle - Further control functions Display of different levels Online parameterization Firmware update Online visualization of measured values, logical statuses, event lists and system characteristics Upload of fault logs in COMTRADE format Administration of passwords Archiving of documentation (user manuals, configuration descriptions etc.) Devices are password-protected for safer access. Fault log Voltage Online data Parameter changes, as well as the display of measured values and logical statuses, can be easily done online. Furthermore, it is possible to carry out system settings with regard to the station bus, FO-cables, Ethernet and serial communication. Any and all event signals can be visualized in an event list.

Communication The following standard protocols can be used for system communication: IEC 61850 IEC 60870-5-103 IEC 60870-5-104 Communication can be done via one of the following interfaces: 1 x 10/100Base-TX Ethernet 1 x 10/100Base-FX Ethernet 1 x serial RS 485/422 1 x serial optical interface A 10/100Base-TX Ethernet interface serves as service interface. Communication between devices (e.g. differential protection devices) takes place via FO cables. Engineering Tool The engineering tool included in the ACOS protection equipment is designed for intuitive operation and enables the user to make the following settings: off-line parameterization of protection and control functions hardware and software configuration system settings communication settings creation of static and dynamic displays, e.g. single-line diagrams, switches, measured values User-defined interlocks can be implemented quickly and easily via the graphic function chart. The four display levels (Normal, Master, Designer, Administrator) enable a comprehensive overview, thus facilitating work with the engineering tool even more. Time synchronization is done either serially (DCF77) or via NTP.

The protection devices of the ACOS 300 series are certified according to the following standards: Criteria Insulation resistance Surge voltage AC withstand voltage Interference immunity (EMC) Electrostatic discharge Radiated radio-frequency electromagnetic fields Burst Surge Conducted radio-frequency common mode Power frequency magnetic fields Voltage dips and short interruptions Damped oscillatory waves Emitted interference Radiated disturbances Conducted disturbance at main ports Communication protocol Norm EN 60255-5, Class III EN 60255-5, Class III EN 61000-4-2, IEC 60255-22-2 EN 61000-4-3, IEC 60255-22-3 EN 61000-4-4, IEC 60255-22-4 EN 61000-4-5, IEC 60255-22-5 EN 61000-4-6, IEC 60255-22-6 EN 61000-4-8 EN 61000-4-11 IEC 60255-22-1, EN 61000-4-18 EN 55011, IEC 60255-25 EN 55011, IEC 60255-255 IEC 61850 Certificate Level A IEC 61850-6, 7-1, 7-2, 7-3, 7-4 and 8-1 Do you want to know more about our products and solutions? Please get in touch! We are happy to help you. IDS GmbH Nobelstraße 18 76275 Ettlingen Phone: 07243 218-0 info@ids.de www.ids.de 01/2016

ACOS 300 Technical Data Supply voltage Feature Power supply backup time CPU Display and control elements Value 18-72 VDC, 35-50 VAC 80-150 VDC, 85-130 VAC 150-300 VDC, 160-265 VAC 200 ms 2 x 500 MHz 4 capacitive touch keys (ON, OFF, scrolling, LED acknowledgement); 16 LED (configurable, 3 colors); individuell gestaltbarer LED-Beschriftungs-Einschub Visualisation 3,5 /5,7 TFT color touch display; 320*240 pixel (ACOS 35x) B/W Display; 128* 64 pixel (ACOS 33x) Service interface 1x Ethernet 10/100 Base-TX Combined Ethernet/COM interface (Ethernet Over Board) Communication interfaces 1 x Ethernet 10/100Base-TX 1 x Ethernet 10/100Base-FX or 2 x 10/100Base-FX Rail Switch (HSR) 1 x RS 485/RS 422 oder 1 x serial optical Communication protocols IEC 61850; IEC 60870-5-103; IEC 60870-5-104; Modbus TCP; SPA-Bus Digital inout No. of inputs Signaling-circuit voltage Plug-in connector Digital output No. of outputs Switching voltage Switching capacity Breaking capacity (L/R = 40 ms) Constant load Plug-in connector Digital output (Trigger module) No. of outputs Switching voltage Switching capacity Breaking capacity (L/R = 40 ms) Making capacity Constant load Plug-in connector Voltage measurement (adjustable) No. of inputs Nominal voltage Accuracy Plug-in collector Current measurement (adjustable) No. of inputs Nominal current Accuracy Plug-in connector Housing ACOS 35x Building type Slots Material Dimensions (WxHxD in mm) Housing ACOS 33x Building type Material Dimensions (WxHxD in mm) Ambient conditions Storage temperature Operation temparature Relative air humidity 6/12 (optionally extendable) 24/48 V DC / 60 V DC / 110 V DC / 220 V DC 16-ways 5/8 (optionally extendable) 250 V AC/DC at 220 V DC: 0,2 A 8 A 16-ways 2/4 (independent trigger circuits) 110 V DC/220 V DC at 220 V DC: 4 A 30 A 8 A 12-ways (at 4 outputs) 4 100V/ 3, 100V, 200V/ 3, 200V +/- 0,5 % 8-ways 4 1A/5A (optional: Channel 4: 0,2A/1A) +/- 1 % 8-ways 19/2 Rack, Panel & wall mount (optional remote display) 7 Aluminium chromed 235 x 132,5 x 242 Housing for panel mounting Aluminium black anodized 144 x 144 x 212-40 C +70 C -25 C +55 C max. 90% (without condensation) Stand 01/2016, Technical modifications reserved IDS GmbH Nobelstraße 18 D-76275 Ettlingen Phone +49 7243 218-0 Fax +49 7243 218-1 00 E-Mail info@ids.de Internet www.ids.de

ACOS 300 Protection Functions Protection function IEC ANSI ACOS 351 ACOS 353 ACOS 354 ACOS 355 ACOS 357 ACOS 392 ACOS 395 ACOS 331 ACOS 333 ACOS 334 ACOS 335 Definite time overcurrent protection I>>> 50 Overcurrent-time protection I>, I>> 51 Overcurrent protection, voltage-dep. 51V Directional overcurrent protection I Dir>, I Dir>> 67 Instantaneous earth-fault overcurrent Io>>> 50N Overcurrent-time delay, earth Io>, Io>> 51N Directional earth-fault overcurrent Io Dir>, Io Dir>> 67N Line differential protection 3IdL> 87L Distance protection Z< 21 Power swing detection and blocking I2h> 68 Unbalanced load protection I2> 46 Thermal overload T> 49 Tranformer differential earth-fault 3IdT 87T 2W 3W Differential earth-fault protection REF 87N Overvoltage protection U>, U>> 59 Undervoltage protection U<, U<< 27 Residual voltage earth-fault protection Uo>, Uo>> 59N Phase-sequence monitoring U2> 47 Frequency protection f<, f<<, f>, f>> 81 Rate-of-frequency-change protection df/dt 81R Overfluxing V/Hz 24 Synchro-check SYNC 25 Automatic reclosing 0 -> 1 79 Voltage transformer monitoring 60 Breaker failure protection CBFP 50BF Motor starting protection 48 Undercurrent protection 37 Restart interlock 66 Directional power monitoring P>, P< 32 Reactive power undervoltage protection QU 92 Wattmetric earth-fault protection I0-W 67W Intermittent earth-fault protection I0-IEF 67N-IEF Protection against current unbalance 60 Minimum current level I> Automatic frequency relief AFE