GUIDE TO VERIFYING SURGE PROTECTIVE DEVICES INSTALLED IN LIGHTNING PROTECTION SYSTEM INSTALLATIONS ARE COMPLIANT WITH UL 96A.

Similar documents
DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

BSPD Surge Protective Devices

File E Project 05NK Issued: Revised: REPORT CLASSIFIED FOR USE WITH SPECIFIED EQUIPMENT (XUPD)

The following standards are the basis of design, manufacture, and test of SPD equipment: Guide for Surge Voltages in Low-Voltage AC Power Circuits

1. Section Lightning Protection for lightning protection system. D. The installation shall be in conformance with NEC Article 285.

Liebert AccuVar (ACV Series) Surge Protective Device (SPD) (With Noise Filtering) GUIDE SPECIFICATIONS for a Parallel Surge Suppression System

White Paper October 2009

SECTION SURGE PROTECTION DEVICES. A. Section includes Surge Protection Devices for low-voltage power, control, and communication equipment.

Eaton s SPD Series for integration into electrical distribution equipment

Specifications, Installation, and Operating Instructions

US Catalog March Surge protective devices (SPDs) UL range

Eaton s Innovative Technology Surge Suppression Guideform Specification High Exposure DIVISION 16 SECTION 16289

Eaton s Innovative Technology Surge Suppression Guideform Specification Low Exposure DIVISION 16 SECTION 16289

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

GE TR7000 Series Wall Mounted Surge Protective Device (SPD)

Remote contact signaling available. visual status indication

White Paper Surge Protective Devices in Automatic Transfer Switches

File E Project 08NK November 24,2009 REPORT TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7)

Surgelogic Surge Protective Device I-Line Plug-On Unit Series

SECTION SURGE PROTECTIVE DEVICES

In the simplest terms, surge protective devices (SPDs) prevent damaging transient voltage surge levels from reaching the devices they protect.

File E Project 08NK October 2, 2009 REPORT SURGE PROTECTIVE DEVICES (VZCA) GE Zenith Controls Bonham, TX

Surgelogic. Surge Protective Devices (SPDs) Residential. Catalog 6671CT9701R08/

glossary GE Digital Energy Power Quality Surge Protective Devices (SPDs)

Secondary Surge Arrester Instruction Manual Page 1 of 5

GENERAL UL th EDITION BID SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

Internal Modular SPDs

Presenter Information

GENERAL UL th EDITION DESIGN-BUILD SPEC: SURGE PROTECTIVE DEVICES Prepared by THOR SYSTEMS, INC.

TECH NOTE #: CPS-1 SUMMARY OF APPLICABLE UL AND IEEE STANDARDS

2.1. SPD, Power Conditioning, PF Capacitors and Harmonic Filters. Contents Description. Introduction. Surge Protection and Power Conditioning

Datasheet SPD II 1 Surge Protectors for AC Power Distribution SPD II PV Surge Protectors for Photovoltaic Installations

AC Surge Protection Devices

B. System Design and Performance Requirements

SECTION TRANSIENT VOLTAGE SURGE SUPPRESSION

DTK-WH8PLUS. Premium Whole House Surge Protection General Product Specifications

Surge & Filter Protection Addressing your industrial power quality needs.

Reliability in Surge Protection. Photovoltaic Systems.

THE SURGE PROTECTION SOLUTION

Lightning and Surge Protection for PV Systems

BUSSMANN. North American UL Type 1, 2 and 4, and data signal surge protective devices SERIES. Application note 3193

Datasheet Stock No: RS Pro

CPS block & CPS nano UL rd Ed. Surge protective devices (SPD)

Surge Protection V1-T2-2 V1-T2-2 V1-T2-3 V1-T2-4. Learn Online

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

The protection you rely on

Surge Protective Devices. STV100K Series. Instruction Manual

Surge Protective Devices. STV100K Series. Instruction Manual

Surg Sur e P ot r ection

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

1. This section describes the materials and installation requirements for surge protective devices (SPD) for the protection of all AC electrical

Liebert TVSS: The First Line of Defense - Product Overview. Jim Tiesi

Reliability in Surge Protection. Surge Protection. AC & DC Power Photovoltaic Coaxial Telecom Gas Discharge Tubes.

Overvoltage Protection

NEMA 1 / IP40 metal housing. Compact design

SOUTH CAROLINA ELECTRIC COOPERATIVES SECONDARY TYPE 1 SURGE PROTECTIVE DEVICE SPECIFICATIONS Updated/Revised: October 6, 2014

Surge Protection Devices for. Facility Engineers And Electricians. Today s Information. History of SPD Protection. Why Specify an SPD?

Section 9 TVSS. Contents

M ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS

TDX Series. Transient Discriminating TM TVSS

Surge Protective Devices (SPD)

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

Surge Protective Devices. STV25K Series. Instruction Manual

I-Line SPDs Square D TM Internally Mounted Surge Protective Devices

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing

INTRODUCTION TO SPECIFYING SURGE PROTECTION SURGE PROTECTION NOTE 1 INTRODUCTION TERMS PROBABILITY OF SURGES APPEARING:

SECTION TRANSIENT VOLTAGE SUPPRESSION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

Equipment level protection for AC/DC network cable, data and low voltage applications. Available in din-rail and direct inline installation.

Advancements in Surge Protection

SPGS America Surge Protective Device (SPD) Advice For The Bussiness Owner and The Homeowner

SURGE PROTECTION OPTION

Gas Discharge Tube. Indicator Light(2) UL Parallel 1600 V N N / PU-20KS10KTTN. UL Series 1600 V N N 15 A PU-20KD10KTTN

C E R T I F I C A T E O F C O M P L I A N C E

Clipper Power System Visor Series

Surge Protection Devices (SPD)

Innovative Technology line filters and surge protectors

Surge Protection V1-T2-2 V1-T2-2 V1-T2-3 V1-T2-4. Learn Online

Current Regulatory and Industry Updates for Surge Protective Devices (SPD)

Point-of-Use Surge Protection

Surge Protection Systems Performance and Evaluation

SPM Series Plug-in Surge Protector Type 2/3 (Test Class II/III) Single & Three Phase Surge Arresters

Surge Protection for Surveillance Systems

User Manual - Canada. TPS3 03 DC For DC Photovoltaic Applications. Surge Protective Device

ETITEC - Lightning and Surge Arresters

R-LB R-LX Series Installation, Operation & Maintenance Manual

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment

Installation Instructions for Eaton Surge Protective Device XXCFXXX10-DIN and XXCFXXX10-DIN2

Model KEP. Transfer Switch Standard Features. Automatic Transfer Switches Service Entrance Rated. Enclosed Contact Power Switching Units.

Each VariSTAR Type AZU arrester must pass the following production tests: 100% Physical Inspection 100% Leakage Current Test 100% RIV Test

GE Digital Energy. Power Quality

C E R T I F I C A T E O F C O M P L I A N C E

AC and DC Protector Applications

White Paper. UL Standards for Power Control System Equipment

Reliability in Surge Protection. LED Lighting Systems.

Surge Protective Device

C E R T I F I C A T E O F C O M P L I A N C E

Surge Protection Devices Ex9UE2

SPM Series. Plug-in Surge Protection

Outdoor Risk and Equipment Protection

C E R T I F I C A T E O F C O M P L I A N C E

Transcription:

JULY 29, 2014 GUIDE TO VERIFYING SURGE PROTECTIVE DEVICES INSTALLED IN LIGHTNING PROTECTION SYSTEM INSTALLATIONS ARE COMPLIANT WITH UL 96A. HOW TO VERIFY SURGE PROTECTIVE DEVICES SUITABLE FOR USE ON ELECTRIC SERVICE ENTRANCES IN COMPLIANCE WITH UL 96A UL LISTED SURGE PROTECTIVE DEVICES, INCLUDING PHOTOVOLTAIC APPLICATIONS (PV SPDS) - (CCN VZCA) - TYPE 1 & 2 ONLY ARE SUITABLE FOR LPS Rating: 1000 Volts AC or less or 1500 Volts DC or less UL Standard: UL 1449, 3 rd Edition UL 96A Paragraph Reference: 13.1 Product Identity consisting of one of the following: Surge Protective Device, or SPD, and marked as Type 1 or Type 2 SPD. The UL Listing Mark requires the use of a holographic label, regardless of the country of manufacture. (Note This also applies to the New Enhanced UL Certification Mark) Electrical Ratings, Operating Volts, Frequency & Number of Phases or DC, Voltage Protection Rating (VPR), Nominal Discharge Current (In) Rating (minimum 20kA), Maximum Continuous Operating Voltage Rating (MCOV), and Short-Circuit Current Rating (SCCR). PV SPDs are marked, "For Use in Photovoltaic Systems Only," or the equivalent. SPDs investigated for general dc applications may also be marked, "Suitable for Use in Photovoltaic Systems." Page 1 of 12

Type 1 devices are suitable to be installed on the line or load side of the service disconnect overcurrent protective device and where the circuit voltage does not exceed 1000V. Type 2 devices are suitable to be installed only on the load side of the service disconnect overcurrent protective device and where the circuit voltage does not exceed 1000V. Need to verify the following electrical ratings based on the device markings: The operating voltage rating is suitable for the circuit voltage. Nominal Discharge Current (In) Rating is 20 ka or greater. UL RECOGNIZED COMPONENT SURGE PROTECTIVE DEVICES, INCLUDING PHOTOVOLTAIC APPLICATIONS (PV SPD) - (CCN VZCA2) - TYPE 4, MARKED SUITABLE FOR USE AS TYPE 1 OR 2 ONLY Rating: 1000 Volts AC or less or 1500 Volts DC or less UL Standard: UL 1449, 3 rd Edition UL 96A Paragraph Reference: 13.1 Recognized Company s Identification Catalog, Model, or other product designation as shown in the Certification Directory. The Recognized Component Symbol. Nominal Discharge Current (In) rating (minimum 20 ka) Marked suitable for use as a Type 1 or 2 SPD. PV SPDs are marked, "For Use in Photovoltaic Systems Only," or the equivalent. SPDs investigated for general dc applications may also be marked, "Suitable for Use in Photovoltaic Systems." Must be factory installed by utilization equipment manufacturer only, as part of UL Listed equipment, i.e., switchboard, panelboard, etc. Only devices recognized as suitable for use as Type 1 or Type 2 applications are acceptable for LPS applications. Devices marked as suitable for Type 1 applications are suitable to be installed on the line or load side of the service disconnect overcurrent protective device and where the circuit voltage does not exceed 1000V. Devices marked as suitable for Type 2 applications are suitable to be installed only on the load side of the service disconnect overcurrent protective device and where the circuit voltage does not exceed 1000V. Page 2 of 12

Need to verify the following electrical ratings based on the device markings: The operating voltage rating is suitable for the circuit voltage. Nominal Discharge Current (In) Rating is 20 ka or greater. Recognition information is available to installers on the On-Line Certification Directory for this UL LISTED COMBINATION CIRCUIT BREAKER AND SURGE-PROTECTIVE DEVICES (CCN DIMV) TYPE 1 OR 2 ONLY ARE SUITBLE FOR LPS Rating: 600 Volts AC or less UL Standard: UL 1449, 3 rd Edition UL 96A Paragraph Reference: 13.1 Product Identity consisting of one of the following: Circuit Breaker and SPD or Circuit Breaker and Surge-protective Device, and marked as Type 1 or Type 2 SPD. Electrical Ratings, Operating Volts, Frequency & Number of Phases, Voltage Protection Rating (VPR), Nominal Discharge Current (In) Rating (minimum 20kA), Maximum Continuous Operating Voltage Rating (MCOV), and Short-Circuit Current Rating (SCCR). Must be factory installed by utilization equipment manufacturer only, as part of UL Listed equipment, i.e., switchboard, panelboard, circuit breaker enclosures, etc. Type 1 devices are suitable to be installed on the line or load side of the service disconnect overcurrent protective device and where the circuit voltage does not exceed 600V. Type 2 devices are suitable to be installed only on the load side of the service disconnect overcurrent protective device and where the circuit voltage does not exceed 600V. Need to verify the following electrical ratings based on the device markings: The operating voltage rating is suitable for the circuit voltage. Nominal Discharge Current (In) Rating is 20 ka or greater. Page 3 of 12

UL LISTED TRANSIENT VOLTAGE SURGE SUPPRESSORS OR TVSS (CCN XUHT) Note - This category has been discontinued and information is no longer available on UL s On-Line Certification Directory for devices previously covered in this It is recommended that devices under the category (VZCA), (VZCA2), or (DIMV) surge protective devices be used, since information is readily available on the On-Line Certification Directory. Rating: 600 Volts AC or less UL Standard: UL 1449, 2 nd Edition UL 96A Paragraph Reference: 13.1 For the purpose of verifying compliant devices manufactured prior to this category being discontinued, the following guidelines should be used: The Word Listed Control Number (4 digit alpha numeric number) Product Identity consisting of the following: Transient Voltage Surge Suppressor or TVSS and reference to LPS, i.e. TVSS for LPS. Special Note - The device is not suitable for LPS applications unless device is marked with the LPS reference. The UL Listing Mark requires the use of a holographic label for devices manufactured in China effective as of 11/01/1996. Only suitable to be installed on the load side of the service disconnect overcurrent protective device and where the circuit voltage does not exceed 1000V. Do not need to verify Nominal Discharge Current (In) rating. Only need to verify device is marked as indicated above. UL LISTED LIGHTNING PROTECTION SURGE ARRESTERS (COMPLIMENTARY LISTED FOR CCNs OWHX AND XUHT) Note - This category has been discontinued and information is no longer available on UL s On-Line Certification Directory for devices previously covered in this It is recommended that devices under the category (VZCA), (VZCA2), or (DIMV) Surge Protective Devices be used, since information is readily available on the On-Line Certification Directory. Rating: 600 Volts AC or less UL Standard: UL 1449, 2 nd Edition ANSI/IEEE C62.11 UL 96A Paragraph Reference: 13.1 Page 4 of 12

For the purpose of verifying compliant devices manufactured prior to this category being discontinued, the following guidelines should be used: The Word Listed Control Number (4 digit alpha numeric number) Product Identity consisting of one of the following: Surge Arrester, Secondary Surge Arrester, Secondary MOV Surge Arrester, Secondary Metal-Oxide Surge Arrester, Secondary Valve Type Surge Arrester, or Distribution Duty Surge Arrester. In addition, since this device is required to be complementary listed under the category of (XUHT), the following product identity would also need to be marked on the device: Transient Voltage Surge Suppressor or TVSS Device must be Complementary UL Listed under the categories (OWHX) and (XUHT). Device is suitable to be installed on the line or load side of the service disconnect overcurrent protective device and where the circuit voltage does not exceed 600V. Do not need to verify Nominal Discharge Current (In) rating. Only need to verify device is marked as indicated above. UL LISTED SURGE ARRESTERS (CCN VZQK) RATED GREATER THAN 1000 VOLTS AC NOTE Currently, there are no listings established under this The Guide Card information is available to installers on the On-Line Certification Directory. Ratings: Greater than 1000 Volts AC Device Standard & UL 96A: ANSI/IEEE C62.11 or ANSI/IEEE C62.1 UL 96A Paragraph Reference: 13.3 Product Identity consisting of the following: "Surge Arrester," "Distribution Normal Duty Surge Arrester" or "Station Class Surge Arrester," or other appropriate product name as shown in the individual Listing. Page 5 of 12

Device is suitable to be installed on the line or load side of the service disconnect overcurrent device. Verify device is marked as indicated above and suitable for use in a circuit voltage greater than 1kV. HOW TO VERIFY SURGE PROTECTIVE DEVICES SUITABLE FOR USE ON COMMUNICATION, RADIO, AND TELEVISION SYSTEMS IN COMPIANCE WITH UL 96A UL LISTED PRIMARY PROTECTORS FOR COMMUNICATION CIRCUITS (CCN QVGV) Rating: 300 Volts or less UL 497 Primary Protectors for Paired-Conductor Communication Circuits UL 96A Paragraph Reference: 13.2 The following is required to be marked on the device or on the smallest unit container in which the product is packaged: Product Identity consisting of the following: Signal Circuit Protector, Telephone Protector, or Network Interface Device. Typical use applications include circuits for voice, audio, data, interactive services, telegraph, fire alarm & burglar alarm wiring, network interface devices, etc. At this time, it is not required that the device be marked or verified for a Nominal Discharge Current (In), although it is recommended to use devices marked with a 10kA. Device should be mounted near the point of service entrance. Page 6 of 12

HOW TO VERIFY SURGE PROTECTIVE DEVICES SUITABLE FOR USE ON COAXIAL SIGNAL CABLE SERVICE ENTRANCES IN COMPLIANCE WITH UL 96A UL LISTED PRIMARY PROTECTORS FOR COAXIAL COMMUNICATION CIRCUITS AND NETWORK-POWERED BROADBAND COMMUNICATION SYSTEMS (CCN QVKC) Rating: 300 Volts or less UL 497C Primary Protectors for Coaxial Communication Circuits UL 96A Paragraph Reference: 13.2 The following is required to be marked on the device or on the smallest unit container in which the product is packaged: Product Identity consisting of the following: Primary Coaxial Protector. Typical use applications include circuits for coaxial communication circuits, network powered broadband communication systems, coaxial cable (CATV) systems, etc. At this time, it is not required that the device be marked or verified for a Nominal Discharge Current (In), although it is recommended to use devices marked with a 10kA. Device should be mounted near the point of service entrance. Page 7 of 12

HOW TO VERIFY SURGE PROTECTIVE DEVICES SUITABLE FOR USE ON OUTDOOR ANTENNA LEAD-IN CONNECTIONS FOR RADIO AND TELEVISION RECEIVING EQUIPMENT AND AMATEUR RADIO-TRANSMITTING AND RECEIVING EQUIPMENT IN COMPLIANCE WITH UL 96A UL LISTED ANTENNA DISCHARGE UNITS (CCN ASWA) Rating: None Required UL 452 Antenna Discharge Units UL 96A Paragraph Reference: 13.2 Product Identity consisting of the following: "Antenna Discharge Unit," or other appropriate product name as shown in the individual listing. Typical use applications include antenna systems for radio & television, i.e., multi-element, vertical rod, and dish. Do not need to verify Nominal Discharge Current (In). Only need to verify device is marked as noted above. Device should be mounted on the antenna lead-in conductor. UL LISTED PROTECTORS FOR ANTENNA LEAD-IN CONDUCTORS (CCN QVLA) Rating: None required UL 497E Outline of Investigation for Protectors for Antenna Lead-In Conductors UL 96A Paragraph Reference: 13.2 Page 8 of 12

The following is required to be marked on the device or on the smallest unit container in which the product is packaged: Product Identity consisting of the following: "Antenna Lead-in Protector" or "Antenna Lightning Protector," or other appropriate product name as shown in the individual Listing. Typical use applications include antenna installations for radio and television receiving equipment, amateur radio transmitting and receiving equipment, cellular telephone towers and WiMax or WiFi wireless networks. Do not need to verify Nominal Discharge Current (In). Only need to verify device is marked as noted above. Device should be mounted on the antenna lead-in conductor. HOW TO VERIFY SURGE PROTECTIVE DEVICES SUITABLE FOR USE ON CLASS 2 OR 3 REMOTE CONTROL, SIGNALING AND POWER-LIMITED CIRCUITS OR FIRE PROTECTION SIGNALING CIRCUITS IN COMPLIANCE WITH UL 96A UL LISTED ISOLATED LOOP CIRCUIT PROTECTORS (CCN QVGQ) Rating: 300 Volts or less UL 497B Protectors for Data Communication and Fire Alarm Circuits UL 96A Paragraph Reference: 13.2 The following is required to be marked on the device when size permits, or on the smallest unit container in which the product is packaged: Product Identity consisting of the following: "Isolated Loop Circuit Protector Page 9 of 12

Typical use applications include Class 2 or Class 3 remote control, signaling and power limited circuits, or fire protection signaling circuits. Do not need to verify Nominal Discharge Current (In). Only need to verify device is marked as noted above. Device should be mounted near the point of service entrance. Page 10 of 12

How to search for Surge Protective Devices for Lightning Protection System Installations in compliance with UL 96A Step 1 - Go to www.ul.com Scroll down to the very bottom of the web page and select Online Certification Directory as shown below. This will take you to the search page. Page 11 of 12

Surge Protective Devices (SPD) Search Page Step 2 - The search page as shown below is where you will enter the UL Category Code (CCN). For example VZCA, DIMV, QVGV, etc. To help with finding DC rated SPDs, type in DC in the keyword field. This field can also be used to narrow your searches. Page 12 of 12