ICS Regent. Guarded Analog Output Modules. 4 to 20 ma (T3480) PD-6026

Similar documents
ICS Regent. Relay Output Modules. Low Power and High Power (T3446L and T3446H) PD-6017

ICS Regent. Monitored Digital Input Modules 24 VDC (T3411) PD-6031

ICS Regent. AC Guarded Digital Output Module 110 VAC (T3464) PD-6021

ICS Regent. Multiplexed I/O Modules PD-6035 (T3491)

ICS Regent. Thermocouple Input Assembly. Input Module, Mux, Termination Panel and Cable (T3431-IM, T3431-Mux, T3431-TP and T3431-CA) PD-6024

ICS Regent. Communications Package for W INTERPRET. Guarded Peer-Link Communications (T3831) PD-6041

32-Channel Analogue Input Module Differential Input

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

RT4F-110V/25A RECTIFIER

16-Channel Digital Output Module 120Vac/dc

Trusted High Integrity Power Supply System ( Vac and 24 Vdc)

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

RT4F-120V/20A-WAC RECTIFIER

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

RT4B-110V/12A RECTIFIER

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

XPSMCMDO Digital output pairs expansion modules with screw term

RT12-240V/2.4kW Rectifier Specification

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output

This Datasheet for the IC660BBA104. Block 115Vac/125Vdc Analog Current Source 4 Inputs / 2 Outputs

XPSMCMCO0000EM Modbus TCPIP diagnostic expansion module with screw term

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

GFK-2415A March Type of sensor connection

RT4F-48V/50A-WAC RECTIFIER

H-series (Rectifier Module)

P3-SCM. General Specifications

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

OPERATING INSTRUCTION

XPSMCMDI Input expansion module with screw term

Power supply CP-C 24/5.0

Chassis Power Supplies

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

XPSMCMMX inputs 2 output pairs expansion module with screw term

BC-9000 Field Calibration Procedure CF1_FIELDCAL_BC9000 Revised 03/16/2013

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

MINI-PS AC/10-15DC/8

Model 500 Series Laser Diode Driver User's Manual

P2-04DA Analog Output. Removable Terminal Block Specifications

This Datasheet for the IC660BBA026. Block 24/48Vdc Analog Current Source 6 Inputs.

RE9RA21MW7 off-delay timing relay s V AC -

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS:

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

P2-04AD Analog Input. Removable Terminal Block Specifications

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

RE7RM11BU off-delay timing relay with control contact s - 24 V AC DC - 1OC

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

TM3TI4 module TM3-4 inputs temperature

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

Allen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon

FL MC 2000E (SM40) LC

Autoranging True RMS Multimeter User Manual

DM-918 OPERATIONS MANUAL AUTORANGING MULTIMETER

RMCN22BD Analog Converter ma - for Zelio Analog

P2-16AD-2 Analog Input. Connector Specifications

KEPCO SINGLE OUTPUT, 1U SIZE, 100 WATT HOT SWAP PLUG-IN POWER SUPPLIES TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS, HSF-1UR 100W SERIES

TM3TI8T module TM3-8 inputs temperature

Model INSTRUCTION MANUAL DIGITAL MULTIMETER

This Datasheet for the IC660BBD025. Block 5/12/24Vdc Sink I/O 32 Circuits.

Model HM-535 Power Supply Installation and Service Instructions

Installation Instructions

Industrial Power Supplies

RE7YA12BU time delay relay for star-delta starter s - 24 V AC DC - 2OC

Digital ac/dc (24V) Input Module

Model Number Structure

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

ATV930U30M3 variable speed drive - ATV930-3kW - 200/240Vwith braking unit - IP21

Analog Current Input - 16 Channel IC693ALG223. Current Ranges. Power Requirements and LEDs. Location in System. Analog Input Modules

TSP-BCM48, TSP-BCM48A. Operating Instruction Manual. Page 1 of 13

TM3TI4 module TM3-4 inputs temperature

User's Guide. MiniTec TM Series Model MN25 MultiMeter

SCC-AO10 Isolated Analog Output Module

BRC SERIES 20kW High Voltage Power Supply

Shown with terminal block Supports diagnostic point fault contacts in the logic program

NEUROLOGIC RESEARCH CORPORATION MODEL 2500

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

General Specifications. P2-8AD4DA-2 Analog Input/Output

SFP450-12BG AC-DC Front-End Data Sheet 12V Output, 450 Watts

Measurement Systems Datascan Installation and User Guide

AutoRanging Digital MultiMeter

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

TM3AI4 module TM3-4 analog inputs

1492-SP Supplementary Protectors

INSTRUCTION MANUAL. SIL 3 Switch/Proximity Detector Repeater Relay Output, Termination Board Models D6032S, D6032D

Analog Voltage Combination Module

CompactBlock Guard I/O EtherNet/IP Safety Modules

P2-04DAL-2 Analog Output. Removable Terminal Block Specifications

2562 QUICK START GUIDE

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN

TOXALERT MODEL AIR 2000

The PM1000 series is a universal 4 digit LED plug-on display for transmitters with 4-20mA 2 wire output and fitted with DIN43650 connector.

Monitoring technique. VARIMETER Voltage relay MK 9064N, MH 9064

Momentum 171 CCC Processor with Ethernet Communication Port

VersaMax IP I/O Module

ACTIONI/Q Q498. DC Powered DC Input Field Configurable Isolator with Math Functions

ASTAT XB/XBm Remote Operator

Analog Monitor Installation Manual

Transcription:

ICS Regent PD-6026 Guarded Analog Output Modules 4 to 20 ma (T3480) Issue 1, March, 06 Guarded analog output modules provide 4 to 20 ma current outputs for a maximum of six user loads per module. These modules are called Guarded because the module's dualredundant design ensures that no single fault within a module will inadvertently change an output's signal. The module's triplicated Safetybus interface ensures that no Regent system failure will inadvertently affect the output signal. Extensive fault detection and annunciation of critical redundant circuits ensures the modules will continue to operate in a fail-safe manner. Features Six 4 to 20 ma output circuits. Dual, high resolution, 12-bit D/A converters per output. Fault tolerant operation when connected in parallel with another module of the same type. Hot-replaceable. Comprehensive self-testing of all critical circuits. Front panel indicators on each module show active/fault, shutdown, and on status. 2500 volt minimum electrical isolation between field and logic circuits. TÜV certified, Risk Class 5, non-interfering. Two Guarded output modules can be connected in parallel to obtain fault tolerant control of current to the loads. In this parallel module configuration, either module can be removed and replaced while the other Guarded module continues to control the loads without interruption. Industrial Control Services 1

Module Operation A block diagram of the Guarded analog output module is shown in Figure 1. The processor modules send triplicated write data commands over the I/O Safetybus to the Guarded output module. Onboard the Guarded output module the triplicated data are routed to two independent voter and I/O Safetybus logic sections. Each section independently votes the triplicated data and drives one digital-to-analog (D/A) converter for each of the six output channels. Figure 1. Block Diagram of Guarded Analog Output Module. For each output channel, one of the D/A converter output signals is used for the actual analog output drive signal. The other D/A converter output signal generates a redundant reference output signal. When all circuits are operating correctly each channel s drive output and reference output should be the same. These two signals are compared on the module and must be the same in order for the module to control the field outputs. 2 Industrial Control Services

The combination of redundant interface circuits, D/A converters, and comparison of drive and reference signals produces a fail-safe signal to the load. For fault tolerant operation, two Guarded analog output modules can be used in parallel. In this configuration, the STATUS OUT and STATUS IN signals are cross-strapped between the two redundant modules. This connection causes only one of the analog output modules to control the field devices, while the redundant module is in a standby mode. In the standby mode the module has its D/A converter output signals shunted to AGND. This allows the module to completely test and validate its analog drive circuits while the other module controls the load devices. If the controlling module fails, it turns off and the standby module becomes the controlling module. This switch over occurs in less than 5 msec and is effectively bumpless for most field devices. Testing and Diagnostics The voter and I/O bus interface logic of the Guarded analog output module are automatically tested by the processor modules. Discrepant data are sent through one of three legs of the I/O Safetybus to determine whether the module s voters are able to outvote the incorrect data. A failure to return the correct majority-voted result to the processors produces an I/O module error indication at the processor modules and a module fault indication at the I/O module. Each type of module has a unique identification code that is read by the controller. This code lets the controller know which type of module is installed in each I/O chassis slot and how to address that module and its points specifically. If a module is removed, or is replaced with a module of a different type, the processor modules will indicate an I/O module error. Loopback logic tests periodically write data to the module and then read it back to determine whether the module s I/O bus interface logic is functioning correctly. To detect a failure in the redundant analog drive circuits, each channel s redundant D/A converter output signals are compared. If they are not the same, a fault signal is sent to the fault summary circuits to disable the module s outputs PD-6026 Mar-06 3

shunting all six output channel signal outputs to AGND via the diode matrix. Important! An open circuit wiring fault to a load will cause the output signal comparison for that channel to fail. In single module configurations this may produce undesirable effects. Refer to page 11, Effects of Open Circuit Field Wiring, for further details and recommendations. Front Panel Indicators Figure 2 shows the physical features of a Guarded analog output module. The front panel of each module contains active and fault status indicators, an on status indicator, and a shutdown indicator. Active and Fault Status Indicators These green and red LEDs indicate the overall health of the module and its field circuits. During normal operation the green ACTIVE indicator flashes at the controller's scan rate. If a module fault occurs the red FAULT indicator turns on and the green ACTIVE indicator turns off. Note: The module will indicate a FAULT if field power is not applied. On Status Indicator In a single module, fail-safe configuration this green LED is on when the module is operating correctly. If any output channel s dual D to A converters fail to compare, the module shuts off and this LED turns off. In a dual module, fault tolerant configuration only one of the two parallel modules is controlling the load current while the other is in a standby mode. Only the ON status indicator on the controlling module is turned on (the standby module's ON indicator will remain off). If the controlling module fails, its ON status indicator will turn off and the standby module's ON status indicator will turn on (as it becomes the controlling module). Shutdown Indicator Upon loss of communications with the controller, output modules enter either a shutdown or hold fault mode. If the I/O 4 Industrial Control Services

unit is set to shutdown, the red SHUTDOWN indicator will turn on when the communications with the controller are lost. If the I/O unit is set to hold, the SHUTDOWN indicator will always be off (see page 11, Fault Mode Jumper). Note: When the module is installed in the I/O chassis or when logic power (from the I/O power supply modules) is first applied to the module, it will be in the shutdown mode until the first output scan, regardless of the fault mode jumper settings. Also, removing two I/O transceiver modules, two I/O power supply modules, or two power legs will cause the module to be in the shutdown mode. PD-6026 Mar-06 5

Figure 2. Guarded Analog Output Module. 6 Industrial Control Services

Application Guarded analog output modules are suited for high integrity control of analog output devices. Guarded output modules can be used for fail-safe or fault tolerant operation. Fail-Safe Configuration As shown in Figure 3, fail-safe configuration uses a single Guarded module. In this configuration, the worst case failure will cause the output to fail to the off state. In a fail-safe configuration, a module failure and subsequent removal of the module disables all of its outputs. Figure 3. Fail-Safe Configuration. Fault Tolerant Configuration For fault tolerant operation, two Guarded modules are connected in parallel as shown in Figure 4. In this configuration, operation continues even if one module fails. In the fault tolerant configuration, a failed module can be removed and replaced without interrupting operation of the loads. PD-6026 Mar-06 7

Figure 4. Fault Tolerant Configuration. Field Wiring Field wiring terminal blocks on the I/O chassis are used to connect power sources and loads to the module. The terminal blocks are located directly above and below the slot where the module is installed. Each terminal block consists of ten #6 wire clamp screw terminals capable of holding two 12 AWG wires. Figure 5 shows the proper field wiring for a single module and Figure 6 shows the field wiring for fault tolerant modules connected in parallel. Two terminals are provided for connecting to each output load device. All six analog output channels must be connected to a load device or else the output circuit testing will fail. For each unused spare output channel, short its two output terminals together by installing a wire across the appropriate terminals on the I/O chassis. Each module has one-pair of terminals for connecting an external 24 VDC field power supply to power the field-side D/A circuits and output current signals. Output circuit testing requires the presence of this field power. If the field power is disconnected, output testing fails and a module fault is indicated. Important! When two guarded analog output modules are used in a fault tolerant configuration, the A and B terminals must be cross strapped between the two modules as shown in Figure 6. 8 Industrial Control Services

Figure 5. Fail Safe Field Wiring. PD-6026 Mar-06 9

Figure 6. Fault Tolerant Module Wiring. 10 Industrial Control Services

Effects of Open Circuit Field Wiring When a Guarded analog output module is controlling the outputs (as opposed to the standby mode) an open circuit in the field wiring connected to a load device will be detected as a failure. This causes the controlling module to switch off, annunciate a fault and enter the standby mode. Once in the standby mode, all of its outputs are shunted to AGND internal to the module, thus eliminating the open circuit and the module s comparators become healthy. This will have one of two effects based upon single or dual module configuration: Single Guarded Module Configuration In a single guarded output configuration the module will toggle back and forth between the controlling and standby modes about every one or two seconds. The ON status LED on the face of the module will turn on and off repeatedly until the open circuit field wiring is corrected. During this time the module FAULT status LED will also be on and the system will report a fault for this module. Important! Each time the single module enters the standby mode all six of the output channels are taken off line and the field signals become 0 ma. When the module switches back to the control mode the field signals return to their controlled values. This causes the output loads that have healthy wiring connections to experience an output signal that toggles between 0 ma and their controlled values which often produces undesirable effects. To avoid this, you should monitor the fault status system control relay for the output module in your application program and use it to set all of the analog output channels to zero. Turning all of the outputs off will often be safer than letting them toggle between 0 ma and a controlled value. Dual Guarded Module Configuration In a dual module configuration the two modules will switch back and forth between control and standby modes. The ON status LED will appear to ping-pong back and forth between the two modules about every one or two seconds. This will continue until the open circuit field wiring is corrected. During this time the module FAULT status LED will also be on for each of the modules and the system will report a fault for both modules. PD-6026 Mar-06 11

While in this mode the remaining output loads that have healthy field wiring connections should continue to be controlled correctly because one of the two modules is always in the control mode. Fault Mode Jumper The fault mode jumper is located behind the ID switch cover in the lower left-hand corner of each I/O chassis. The position of the fault mode jumper determines the module's response to system level faults. The fault mode jumper s position will cause all output modules in the I/O chassis to either shutdown (set all outputs to zero) or to hold (hold the last state) after a system level failure occurs. An example of a system level failure is the failure of two processor modules. Keying The I/O chassis can be physically keyed to prevent accidental damage caused by inserting a module into a slot wired for a different module type. Figure 7 illustrates how the slot keys are installed on the I/O chassis slot field wiring connectors. The slot key positions for the Guarded analog output module are listed in Table 1. Table 1. Slot Key Positions. 12 Module Upper Connector Lower Connector T3480 9 10 Industrial Control Services

Figure 7. Installing Slot Keys. Configuration Each output module is configured using the WINTERPRET I/O Configuration Editor. In the editor you will perform the three steps described below to configure the output module. PD-6026 Mar-06 13

1) Set the Module Type: Position the cursor on the module slot you wish to define. Choose Set Module Type from the Edit Menu and select the Guarded analog output module from the list. 2) Edit the Module Definition: Choose Edit Module Definition from the Edit Menu. A dialog box will open where you can define the analog output point definitions. Figure 8. Guarded Analog Output Module Definition. 3) Edit each point: Choose Edit from the Module Definition dialog box to define a name and description for each output point. In the Analog Output Point dialog, enter names and values for the configuration fields as described below. 14 Industrial Control Services

Figure 9. Defining an Analog Output Point. Name Also called the tag name, this is the name used in the application program to reference the output point. The name can be up to 12 characters long. Description This 40-character field provides a place to describe the output point definition. The description is used to help document your system (it does not affect application program operation). Comm Protect Marking the Comm Protect check box protects the point from changes by communications functions such as data write, forcing, and load initial value when Comm Protect is enabled. Initial Value The initial value for the output is loaded to the Regent when you load the I/O configuration and also when you load the application program that controls the output. Final Value The final value for the output is loaded to the Regent when the application program that controls the output is deleted. Unless special circumstances exist, you should always enter zero, so that the output is turned off when you delete the application program that controls it. PD-6026 Mar-06 15

Programming Outputs are controlled by writing application programs that solve for output values. For example, placing an output tag name in the result field of a math element in ladder logic will set the analog output to the value calculated by the math element. Note that the data range for analog outputs is 0 to 4095 corresponding to the output current rage of 4 to 20 ma. Often you may choose to write analog control logic using an engineering unit number range other than 0 to 4095 to simplify the creation and interpretation of the control logic. If you do so you should use the analog scaling function block to unscale your calculated value to the 0 to 4095 range required for the analog output. An example of an analog scaling entry for analog outputs is shown in Figure 10. Figure 10. Unscaling an Analog Output. This example implies that some other control logic solves a value for the shared register AO1_ENG_VAL which ranges from 0 to 10,000 (the low and high values). The analog scaling entry shown in the example then converts the engineering unit value to the analog output range of 0 to 4095, storing the converted value in the analog output AO1. By using an engineering unit range of 0 to 10,000 for your 16 Industrial Control Services

control logic, you maintain the full resolution of the analog output (1 part in 4096) and have a convenient engineering range that represents 0.00 to 100.00% (the two decimal places are implied). Programming Fault Tolerant Guarded Analog Outputs To program guarded analog outputs in a fault tolerant configuration, you should create control logic to calculate the value for one of the guarded analog outputs and copy this calculated value to the redundant guarded analog output. If you use the unscale entry in the analog scaling function block you should place this copy logic after the analog scaling function block in your application program. Figure 11 illustrates how the Assign instruction in ladder logic can be used. Figure 11. Programming Fault Tolerant Outputs. In this example GAO1A is the name of the analog output that has been set by your control logic, and GAO1B is the redundant analog output. When power flows to the Assign element, it reads the value of GAO1A and stores that value to GAO1B, so that both of the redundant analog outputs have the same value. Maintenance There are no user replaceable parts inside the Guarded analog output module. Re-calibration is recommended once per year, in order to maintain the rated accuracy of the analog output signals over an extended period of time. The following procedure describes the equipment and steps necessary to calibrate the Guarded analog output module. Calibration Procedure Equipment Required A 5½-digit voltmeter. PD-6026 Mar-06 Six 250 ohm, 0.005%, 5 ppm/ C resistors to convert the six output signals from a current to a voltage. 17

Potentiometer adjustment tool. Phillips screwdriver I/O module extender, catalog number T3322. PC running the WINTERPRET software, used to force the analog output channels to the specific values for calibration. Calibration Preparation The module must be calibrated while connected to an I/O chassis of an operational Regent system. Important! During calibration, the Guarded analog output module will be disconnected from the actual controlled field devices. Appropriate precautions should be taken to ensure that the disconnection of the control signals does not pose a safety risk to plant personnel or process equipment. There are Offset and Gain potentiometers for each analog output channel. In addition there are three reference voltage potentiometers and four test points to measure the reference voltages. These potentiometers are located on a circuit board inside the module's protective clamshell housing (see Figure 12). During the calibration steps you will remove the printed circuit board from the housing in order to access these potentiometers for adjustment. The potentiometers for each analog output channel are identified in Table 2. The potentiometers labeled R19, R17 and R22 are used to adjust the reference voltages. Table 2. Potentiometer Identification. 18 Channel Offset Potentiometer Gain Potentiometer 1 R101 R100 2 R201 R200 3 R301 R300 4 R401 R400 5 R501 R500 6 R601 R600 Industrial Control Services

Figure 12. Guarded Analog Output Module Calibration Potentiometer Locations. The I/O extender module has jumper posts that allow you to connect or disconnect the I/O slot field wiring on the I/O chassis to the printed circuit board plugged into the I/O extender. During the calibration steps you will remove any jumpers installed on these posts in order to connect the precision load resistors to the analog outputs. Figure 13 shows the jumper posts to which you should connect the precision resistors for each analog output channel. PD-6026 Mar-06 19

Figure 13. I/O Extender Connections for Guarded Analog Output Calibration. Important! Within each pair of jumper posts, make sure that you connect the resistors to the jumper posts nearest the front of the I/O extender. Do not make any connections to the jumper posts nearest the I/O chassis backplane these connect to the actual field wiring attached to the I/O slot terminals on the I.O chassis. Calibration Steps 1. Remove the module to be calibrated from the I/O chassis. 2. Install the I/O extender module into the slot from which the module was removed. 3. Remove the jumpers (if installed) labeled CH1 through CH16 from the I/O extender module. 20 Industrial Control Services

4. Connect the six precision resistors to the I/O extender jumper posts as shown in Figure 13. Use test clips as required to make the connections. 5. Remove the four screws on one side of the module and remove the printed circuit board from the module clamshell housing. 6. Install the printed circuit board into the I/O extender module. Allow the board to warm up for approximately one minute. 7. Connect the voltmeter's negative probe to test point TP4. Measure the voltage at TP1. The voltage should be 10.0000 VDC (±0.0003 VDC). Use R22 to adjust the voltage. 8. Connect the voltmeter s negative probe to TP4. Measure the voltage at TP2. The voltage should be 8.0000 VDC (±0.0002 VDC). Use R17 to adjust the voltage. 9. Connect the voltmeter negative probe to TP4. Measure the voltage at TP3. The voltage should be 2.0000 VDC (±0.0001 VDC). Use R19 to adjust the voltage. 10. Using the forcing functions of WINTERPRET, force all of the six analog outputs to zero. Refer to the Regent User s Guide for more details about the forcing functions. Wait approximately one minute after forcing the outputs to allow them to stabilize. 11. Adjust each of the six Offset potentiometers until the voltage measured across the corresponding precision resistor is +1.0000 V (± 0.0002 V). Connect the voltmeter across the resistor leads to measure the voltage. 12. Force all six of the outputs to 4095. Wait approximately one minute after forcing the outputs to allow them to stabilize. 13. Adjust each of the six Gain potentiometers until the voltage measured across the corresponding precision resistor is +4.9990 V (± 0.0002 V). After completing one iteration of the calibration, repeat the offset and gain adjustments (steps 10 through 13) until the readings are within specifications. It is necessary to repeat PD-6026 Mar-06 21

these steps as there may be some interaction between the gain and offset adjustments. 14. As a final check, use WINTERPRET to force all six outputs to 2048. Wait one minute and verify that the voltage measured across each of the precision resistors is +3.0000 VDC (±0.0002 VDC). If the Offset and Gain adjustments are within the limits stated in steps 11 and 13 above, but this midvalue point is not, return the Guarded analog output module to the factory for repair or replacement. 15. Calibration is complete. Unplug the printed circuit board from the I/O extender module and replace it in its clamshell housing. Remove all forcing of the analog outputs from the force table using WINTERPRET. Remove the I/O extender module from the I/O chassis and reinstall the calibrated module in the I/O chassis. The module s red Fault indicator will be on until you perform a voted reset by pressing the Reset buttons on two of the Regent processor modules. After the voted reset is complete, the module s green Active indicator should turn on. Latent Fault Testing Procedure Equipment Required A digital multimeter with diode test mode (2 ma current source). Six 250 ohm, 0.005%, 5 ppm/ C resistors to terminate the analog output channels. One 47K ohm, 5%, ¼ Watt resistor for fault injection tests. Phillips screwdriver I/O module extender, catalog number T3322. PC running the WINTERPRET software, used to force the analog output channels to the specific values for calibration. Testing Preparation A portion of the tests are performed on the module while it is disconnected from the rest of the system and removed from its protective clamshell housing. For the remainder of the tests 22 Industrial Control Services

the module must be connected (using the I/O extender) to an I/O chassis of an operational Regent system. It is recommended that these tests are performed each time that you calibrate the Guarded analog output module. There are two diodes for each analog output channel that must be tested for latent faults. In addition the fault summary logic is exercised by injecting a fault. The locations of the diodes and other necessary test and measurement points for this procedure are shown in Figure 14. The I/O extender module has jumper posts that allow you to connect the six 250 Ohm termination resistors to the printed circuit board plugged into the I/O extender. During the calibration steps you will remove any jumpers installed on these posts in order to connect the termination resistors to the analog outputs. Figure 13 shows the jumper posts to which you should connect the resistors for each analog output channel. PD-6026 Mar-06 23

Figure 14. Location of Test Points for Latent Fault Testing. Testing Steps 1. Remove the module to be tested from the I/O chassis. 2. Install the I/O extender module into the slot from which the module was removed. 3. Remove the jumpers (if installed) labeled CH1 through CH16 from the I/O extender module. 24 Industrial Control Services

4. Connect the six termination resistors to the I/O extender jumper posts as shown in Figure 13. Use test clips as required to make the connections. 5. Remove the four screws on one side of the module and remove the printed circuit board from the module clamshell housing. 6. With the printed circuit board removed from the system, check the forward voltage drop (in-circuit) on all 12 output diodes with a digital multimeter in the diode test mode (2 ma current source). Verify that the forward voltage drop is within the following tolerances: 0.6 to 0.8 volts for CR100, CR200, CR300, CR400, CR500, and CR600. 0.2 to 0.45 volts for CR101, CR201, CR301, CR401. CR501 and CR601. 7. Check the resistance (in-circuit) of the 12 output diodes reversely polarized with a digital multimeter set to 20 MOhm resistance range, by connecting the (+) lead of the meter to the cathode and the (-) lead of the meter to the anode of the diode. Verify that the resistance is within the following tolerances: > 20 MOhm for CR100, CR200, CR300, CR400, CR500, and CR600. > 1 MOhm for CR101, CR201, CR301, CR401. CR501 and CR601. 8. If any of the tests in steps 6 or 7 fails, the board should be returned to the factory for repair or replacement. If the tests passed continue to step 9. 9. Install the printed circuit board into the I/O extender module. Perform a voted reset (press two of the processor module Reset buttons) and verify that the module is Active (green Active LED is on and red Fault LED is off). Allow the board to warm up for approximately one minute. 10. Connect a 47K Ohm, 5% resistor between TP4 (AGND) and the top lead of the first resistor (10K Ohm) on the SIP resistor network RN101 (Figure 14 shows the exact location of this resistor). Verify that the module signals a PD-6026 Mar-06 25

fault (green Activity LED turns off and the red Fault LED turns on). 11. Disconnect the one end of the 47K Ohm resistor from TP4. The other end should still be connected to the top lead of the 10K Ohm resistor on RN101. Restore the module to the Active state by performing a voted reset. Now take the end of the 47K Ohm resistor that you removed from TP4 and reconnect it to TP3 (+2VREF). Verify that the module indicates a fault. 12. Restore the module to the Active state by performing a voted reset. 13. Repeat steps 10 through 12 for output channels 2 through 6 connecting the 47K Ohm resister to the appropriate resistor network (RN201 through RN601). Use the same test points TP4 and TP3 as used for output channel 1. In each case, verify that the fault injection procedure causes a fault indication on the module. 14. If any of the fault injection tests does not produce a fault indication, the module should be returned to the factory for repair or replacement. 15. Calibration is complete. Unplug the printed circuit board from the I/O extender module and replace it in its clamshell housing. Remove the I/O extender module from the I/O chassis and reinstall the module in the I/O chassis. The module s red Fault indicator will be on until you perform a voted reset. After the voted reset is complete, the module s green Active indicator should turn on. Safety Considerations The Guarded analog output module is TÜV certified as noninterfering, and can be used in a safety system for non-safety critical outputs. Analog outputs are rarely used to perform safety critical interlock functions, but processes may have control applications that demand a high integrity for analog control functions. The guarded analog output module is ideally suited for these types of applications. In all applications the 26 Industrial Control Services

safety of the process should not be dependent on the operations of the guarded analog output module. To maintain the highest level of integrity, users are advised to periodically perform the calibration and latent fault testing described in the Maintenance section of this document. Refer to page 17 for specific details on performing these procedures. Specifications Safetybus Power 0.8 load units Number of Outputs Six External Power Voltage: Current: 24 VDC ±10% 0.5 amps Output Range 4 to 20 ma Data Range 0 to 4095 Resolution 12-bit (1 in 4096) Accuracy 0.05% of full scale @ 25 C Drift ±50 ppm/ C Load Resistance 0 to 400 ohms Settling Time 0.1 ms (to 0.1% of full scale) Heat Dissipation 14 Watts, 47 BTUs/hour Isolation 2500 volts minimum (field wiring to control logic) Operating Temperature 0 to 60 C (32 to 140 F) Storage Temperature -40 to 85 C (-40 to 185 F) Operating Humidity 0 to 95% relative humidity, non-condensing Vibration 10 to 55 Hz: ±0.15mm Shock Operating: PD-6026 Mar-06 15 g, ½ sine wave, 11 msec 27

Electromagnetic Interference IEC 801 Part 2 - Electrostatic Discharges IEC 801 Part 3 - Radiated Electromagnetic Fields Safety Level 3: Contact discharge of 6 kv Level 3: 10 V/M, 27 MHz 500 MHz Certified to DIN V VDE 0801 (non-interfering) and designed to meet UL 508 and CSA 22.2, No. 142-M1981 Dimensions Height: Width: Depth: Weight 28 12.6" (320 mm) 1.27" (32 mm) 10.12" (257 mm) 3.5 lbs (1.6 kg) Industrial Control Services