RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Similar documents
RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

Heating Controllers. Siemens Building Technologies HVAC Products. Synco 700

Central control unit

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

Heating Circuit Controller

Immersion Temperature Sensors

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Power supply module, bus connection module

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

Resistance measuring module

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

Switching and Monitoring Device

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

RMZ792. Bus Operator Unit. Building Technologies HVAC Products. Synco 700

Universal Controller

Heating Circuit Controller

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

s Climatix AHU ext. module 14 I/O POL955.XX/XXX Climatix

Extension module for lighting control

Room Temperature Controller

Temperature controller for multi-zone ducted systems

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

ERF910. RF Repeater. Synco living

Room unit with PPS2 interface

TXM1.8U TXM1.8U-ML. Universal modules TX-I/O

Super universal modules

Digital input modules

Room Temperature Controller

TXM1.8RB. TX-I/O Blinds module

Central Communication Unit OZW775

Temperature Controller (Heat Pumps)

Non-communicating room controllers

Air damper actuators

Web interface BACnet/IP

RF adapter plugs, dimming

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Island bus expansion module

Room Temperature Controllers

Temperature Controller

RMZ790. Operator Unit. Building Technologies. Synco 700

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Electromotoric actuators

BACnet/IP Web Interface

Semi flush-mounted room temperature controllers with LCD

Temperature controller Ducted systems

Electrical Actuators

Room Temperature Controller with 7-Day Time Switch, LCD and opt. Remote Temperature Sensor

Fast running actuators for air dampers

Extension module Integration of existing PTM I/O modules in Desigo Used with PXC50...D, PXC100...D or PXC200...D

SAX.. ACVATIX Electromotive actuators for valves. with a 20 mm stroke

Universal Controllers

SEH62.1. Digital Time Switch

Electromotive actuators for combi valves

Electrical Actuators

CLIMATIX STEQ, STCM DATASHEET FOR CONTROLLING, SWITCHING AND MONITORING FUNCTIONS. POWER SUPPLY RELAY OUTPUTS. Power supply. 4.

Non-communicating room controllers

Rotary actuators for ball valves

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

PHOENIX CONTACT Features

Semi flush-mounted room temperature controllers with LCD

Rotary version, three-position control

Room unit with PPS2 interface

Communication module to connect M-bus devices to POL6xx.xxx controllers.

Compact Universal Controllers

RXL21.1 RXL22.1. Room controllers RXL. Communicating controllers for fan-coil applications FC-10, FC-11, FC12

Product and functional description

MCX08M2 Programmable controller

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

M-Bus Central Unit. Use

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Switching and monitoring device

AEW Pulse Adapter. Building Technologies

7-day room temperature controller

Electrical Actuators

Room automation station

Product and functional description

M-bus web server. Meters and Energy Cost Allocation WTV676-HB6035

Status display unit with P-bus connection

Electrical actuators

MINI MCR-SL-UI-REL(-SP)

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

Room unit with PPS2 interface

Data Sheet T 6493 EN. TROVIS 6400 Automation System TROVIS 6493 Compact Controller. For panel mounting (front frame 48 x 96 mm/1.89 x 3.

Voltage monitoring relays CM-ESS.1 For single-phase AC/DC voltages

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

Electromotoric actuators

Semi Flush-mount Room Temperature Controllers with LCD

OEM. Room unit QAA822 with2- wire interface. Building Technologies CLIMATIX TM. For use with Climatix controllers

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

Product and functional description

Interface converter for VAV compact controllers

MINI MCR-SL-PT100-UI(-SP)(-NC)

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

MINI MCR-SL-PT100-UI-200

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

Room unit with PPS2 interface

Switching module for AC V and up to three load stages, with manual switching

Transcription:

3 136 Synco 700 Extension odules for heating controller RH760B RZ782B RZ783B Extension modules for use with the RH760B heating controller to provide additional auxiliary functions Use Heating plants controlled by the RH760B heating controller. For the heating controller s field of use, refer to Data Sheet N3133. Functions The universal modules are designed to increase the number of inputs and outputs of Synco 700 controls, thus providing additional control and monitoring functions. The following inputs and outputs are provided: Type reference Number of universal inputs Number of Number of relay outputs analog outputs NO Changeover RZ782B 3 1 2 1 RZ783B 4 1 3 2 Type summary Type of module Heating circuit module DHW module Type reference RZ782B RZ783B CE1N3136en 30 ay 2008 Building Technologies HVAC Products

Ordering When ordering, please give name and type reference, for example: Heating circuit module RZ782B The module connector listed under "Accessories" must be ordered as a separate item, if required. Equipment combinations The extension modules must be used in connection with the RH760B heating controller. They cannot be used in connection with other controls of the Synco 700 family. For information about the heating controller RH760B, refer to Data Sheet N3133. Product documentation Type of documentation ounting Instructions Product Range Description CE Declaration of Conformity Environmental Declaration Classification number 3110 S3110 T3110 E3110 02 Technical design ode of operation The RZ78 extension modules complement the RH760B heating controller and can not operate autonomously. Use of the extension modules is determined by the selection of the basic type (basic configuration). All settings required in connection with the extension modules are made on the heating controller. The signals from sensors, signal sources, etc., are delivered to the heating controller and then handled; the control signals and commands generated by the controller are fed to the respective extension module from where they are passed on to the connected actuating devices. The extension module is powered by the RH760B heating controller, which also identifies and monitors the module. echanical design Basic design In terms of mechanical design, the extension modules are identical to the Synco 700 controls. No wiring between the modules or to the heating controller is required; the electrical connections are made by attaching the modules to the controller. Synco 700 control with attached extension module RZ78 Operation The extension modules have no setting and operating elements; operation takes place with the operator unit RZ790 or RZ791. There is one exception, the module has an LED for indicating the operating state. 2/8

Indicating and connecting elements 2 2 6 3145Z01 1 2 3 4 1 Connecting elements for the Synco 700 control or for one extension module 2 ounting facility for fitting the module to a top hat rail 3 Fixing facility for the cable tie 4 LED (green) for indication of operation 5 Connecting elements for one extension module 6 Rest for the terminal cover 6 5 Accessories Accessories Type reference Data Sheet odule connector RZ780 N3138 Engineering notes ounting and installation notes Fuses, switches, wiring and grounding must be in compliance with local safety regulations Sensor cables should not be run parallel to mains-carrying cables powering loads such as actuators and pumps The module are designed for: ounting in a standard cabinet as per DIN 43 880 Wall mounting on an existing top hat rail (EN 50 022-35 7.5) Wall mounting using two fixing screws Flush panel mounting Not permitted are wet or damp spaces; the permissible ambient temperatures must be observed Disconnected the system from the power supply prior to mounting and installation the module The module insert may not be removed from the terminal base! The module must be fitted to the right of the controller in the correct order The extension modules need not be wired between themselves or to the controller. The electrical connections are made automatically when plugging the modules. If it is not possible to arrange all extension modules side bye side, the first of the detached modules must be connected to the previous module or the controller by using the RZ780 module connector. In that case, the cumulated cable length may not exceed 10 meters 3/8

Low-voltage side ains voltage side The connection terminals for protective extra low-voltage are located in the upper half of the module, those for mains voltage (actuators and pumps) at the bottom Only one solid or stranded wire may be connected to each terminal (spring cage terminals). For fixing the wires, the cables must be stripped by 7 to 8 mm. To introduce the wires into the spring cage terminals, or to remove them, a screw driver size 0 or 1 is required. Cable strain relief can be ensured with the help of the lugs for cable ties The module mounted on the top hat rail together with other modules can only be removed from the rail after the 3 catches have been brought into their release-andhold position (audible "click"). After removal, the catches must be pushed back into their snap-on position The module is supplied complete with ounting Instructions Commissioning notes During the commissioning process, the outputs are in a defined off state. Disposal notes Larger plastic parts carry material identifications conforming to ISO/DIS 11 469 to facilitate environment-compatible disposal. Technical data Power supply Rated voltage (via the controller) AC 24 V ±20 % Power consumption 3 VA Analog inputs (X ) Sensors Passive 1 or 2 (averaging) LG-Ni 1000, T1, Pt 1000, NTC 575 Active DC 0 10 V Signal source Passive 0 2500 Ω Active DC 0 10 V Digital Inputs (X ) Contact sensing (status / counting values) Voltage DC 15 V Current 5 ma Requirements for the status and impulse contacts Signal coupling potential-free Type of contact maintained or impulse contacts Insulating strength against mains potential AC 3750 V to EN 60 730 Perm. resistance Contacts closed max. 200 Ω Contacts open min. 50 kω Positioning outputs Output voltage DC 0 10 V (Y1, Y2) Output current ±1 ma ax. load continuous short-circuit Switching outputs External supply line fusing (Q ) Non renewable fuse (slow) max. 10 A Automatic line cutout max. 13 A Release characteristic B, C, D to EN 60 898 Cable length max. 300 m 4/8

Relay contact data Switching voltage max. AC 265 V / min. AC 19 V AC current (cos φ = 0.6) max. 4 A ohm., 3 A ind. at 250 V min. 5 ma at 19 V min. 20 ma Switch-on current max. 10 A (1 s) Contact life at AC250 V guide values: at 0.1 A res. 2 10 7 cycles at 0.5 A res. 4 10 6 cycles (N.O.) 2 10 6 cycles (changeover) at 4 A res. 3 10 5 cycles (N.O.) 1 10 5 cycles (changeover) Reduction factor at ind. (cos φ = 0.6) 0.85 Insulating strength Between relay contacts and system electronics (reinforced insulation) AC 3750 V, to EN 60 730-1 Between neighboring relay contacts (operational insulation) Q1 Q2; Q3 Q4 AC 1250 V, to EN 60 730-1 Between relay groups (reinforced insulation) [Q1, Q2] [Q3, Q4/Q5] AC 3750 V, to EN 60 730-1 Power supply external Voltage AC 24 V devices (G1) Current max. 4 A Electrical connections Connections terminals spring cage terminals For solid wires 0.6 mm dia 2.5 mm 2 For stranded wires without ferules 0.25 2.5 mm 2 For stranded wires with ferules 0.25 1.5 mm 2 Degrees of protection Degree of protection of housing to IEC 60 529 IP 20 (when mounted) Safety class to EN 60 730 device suited for use with equipment of safety class II Environmental conditions Operation to IEC 60 721-3- Climatic conditions class 3K5 Temperature (housing with electronics) 0 50 C Humidity 5 95 % r. F. (non-condensing) echanical conditions class 32 Transport to IEC 60 721-3-2 Climatic conditions class 2K3 Temperature 25 +70 C Humidity <95 % r. F. echanical conditions class 22 Classifications to ode of operation, automatic controls type 1B EN 60 730 Degree of contamination, controls environment 2 Software class A Rated surge voltage 4000 V Temperature for ball-test of housing 125 C aterials and colors Terminal base polycarbonate, RAL 7035 (lightgray) odule insert polycarbonate, RAL 7035 (lightgray) Packaging corrugated cardboard 5/8

Norms and standards Product safety Automatic electrical controls for household and similar use EN 60 730-1 Special requirements for energy controllers EN 60 730-2-11 Electromagnetic compatibility For use in industrial and domestic environments Immunity Emissions conformity to EC directive Low-voltage directive EN 60 730-1 EN 60 730-1 2004/108/EC 2006/95 EC conformity to Australian EC Framework Radio communication act 1992 Radio Interference Emission Standard AS/NZS 3548 Environmental compatibility The environmental product declaration ISO 14001 (Environment) CE1E3110en02 contains data on environmentally ISO 9001 (Quality) compatible product design and assessments (RoHS SN 36350 (Environmentally compliance, materials composition, packaging, environmental benefit, disposal) RL 2002/95/EG compatible products) (RoHS) Weight RZ782B excl. packaging 0.28 kg RZ783B excl. packaging 0.28 kg Connecting terminals RZ782B X1 X2 G1 X3 Q11 Q23 Q33 RZ782B G1 G0 Y1 Q12 Q14 N1 Q24 N2 Q34 3136G01 RZ783B X1 X2 G1 X3 X4 Q11 Q23 Q33 Q43 Q51 RZ783B G1 G0 Y1 Q12 Q14 N1 Q24 N2 Q34 Q44 Q52 Q54 3136G02 G0 System neutral for signal output G1 Output voltage AC 24 V for powering external active devices easuring neutral for signal input N Spark suppression device for 3-position actuators Q Potential-free relay inputs and outputs for AC 24 230 V X Universal signal inputs for LG-Ni 1000, 2 LG-Ni 1000 (averaging), T1, Pt 1000, DC 0 10 V, NTC 575, 0 2500 Ω, contact sensing (potential-free) Y Control or status outputs DC 0 10 V Notes Each terminal (spring cage terminals) can accommodate only 1 solid wire or 1 stranded wire Double terminals are internally interconnected With 3-position control of actuators operating on AC 230 V, the radio interference suppression element must be activated. For that purpose, terminal N1 is to be connected to the neutral conductor and a wire link is to be fitted between terminals N1 and N2 6/8

Connection examples Heating circuit module RZ782B L B B1 3136A01 AC 24...230 V X1 X2 G1 G0 Y1 G1 X3 Q11 Q23 Q12 Q14 N1 Q24 N2 Q33 Q34 A2 N G G0 Y Y1 Y1 N Y2 Y2 1 A2 B1 1 Y1 Y2 Heating circuit module RZ782B Flow temperature sensor Heating circuit pump Actuator with DC 0 10 V input 3-position actuator DHW module RZ783B L 3136A02 B B1 B B2 AC 24...230 V X1 X2 G1 G1 G0 Y1 X3 X4 Q11 Q23 Q12 Q14 N1 Q24 N2 Q33 Q34 Q43 Q44 Q52 Q51 Q54 A3 N G G0 Y Y1 Y1 N Y2 Y2 1 A3 B1 B2 1 Y1 Y2 DHW module RZ783B DHW flow temperature sensor Storage tank temperature sensor Charging pump Actuator with DC 0 10 V input 3-position actuator 7/8

Dimensions 10,5 75 5 3 2,8 117 3 3 = 90 45 35 66,4 3 ø 5,2 ø = 44 EN 60 715-TH 35-7.5 = = 97 314501 Dimensions in mm 8/8 2006-2008 Siemens Switzerland Ltd Subject to alteration