Design of Substation and Distribution Station Monitoring System Based on DELPHI and Intelligent Modules

Similar documents
Design of Communication Function Test System for Intelligent Low Voltage Electrical Apparatus Based on LabVIEW and Modbus RTU Protocol

SPM33. MODBUS Protocol and register List V1.5

Design of SCADA power Distribution Monitoring System based on PLC and Configuration Software

Design of Coal Mine Power Supply Monitoring System

A Design of Remote Monitoring System based on 3G and Internet Technology

The Application of CAN Bus in Intelligent Substation Automation System Yuehua HUANG 1, a, Ruiyong LIU 2, b, Peipei YANG 3, C, Dongxu XIANG 4,D

Hierarchical protection control system of smart substations

Battery Energy Storage System Information Modeling Based on IEC 61850

SPM90 MODBUS PROTOCOL AND REGISTER LIST V1.0

Data Cleaning for Power Quality Monitoring

Improvement of the Communication Protocol Conversion Equipment Based on Embedded Multi-MCU and μc/os-ii

The Design and Development of the Precision Planter Sowing Depth Control System

WSK INTELLIGENT TEMPERATURE AND HUMIDITY CONTROLLER USER MANUAL

INTELLIGENT SCADA FOR LOAD CONTROL

Intelligent Three-dimensional Layout Design of Video Cameras in Substations

A New Virtual Vibration and Temperature Test and Analysis Instrument of Wheel-Set Based on LabVIEW2011

Condition Monitoring System of Mine Air Compressors Based on Wireless Sensor Network

Serial Communication Based on LabVIEW for the Development of an ECG Monitor

A Field Monitor System of Rodpumped Wells Based on GPRS

WebAccess Driver Configuration Manual

Revision 1.2. July 24, COM Protocol Manual. for MDC and ADC N 11th St - San Jose CA

Research on Technologies in Smart Substation

Design of Soybean Milk Machine Control System based on STC89C52. Ya-gang SUN, Yue ZHANG, Zhi-gang YANG, Rui-cheng ZHANG and Xiao-wei SHEN

Design of Smart Home System Based on ZigBee Technology and R&D for Application

AN WIRELESS COLLECTION AND MONITORING SYSTEM DESIGN BASED ON ARDUINO. Lu Shaokun 1,e*

PRICOM Power Communication and Control Systems

Design and Implementation of High-Speed Real-Time Data Acquisition and Processing System based on FPGA

3rd International Conference on Mechanical Engineering and Intelligent Systems (ICMEIS 2015)

The Introduction and Future Development of EMS System. Luohe Electric Power Bureau. Li Quanhai

Design of Coal Mine Comprehensive Parameters Monitoring System Based on DSP

A Training Simulator for PD Detection Personnel

Chapter 2 State Estimation and Visualization

Input Channels: 4 differential or four single-ended. Address / Baud rate / range configurable by the user

Analysis of Computer Hardware Maintenance Methods

Fault Analysis of Distribution Network with Flexible Ring Network Control Device

Smart Power Flow Monitoring and Controlling using Raspberry Pi

Preliminary Research on Distributed Cluster Monitoring of G/S Model

Realization of IEC Protocol in DTU

IDCE-840CT Battery Discharger & Capacity Tester

Research and Application of Mobile Geographic Information Service Technology Based on JSP Chengtong GUO1, a, Yan YAO1,b

8 Channel Analog Input Module Datasheet. Address / Baud rate / range configurable by the user

Automated Analysis of Digital Relay Data Based on Expert System

Design of Greenhouse Temperature and Humidity Monitoring System Based on ZIGBEE Technique Ming Xin 1,a, Wei Zhongshan 1,b,*

A liquid level control system based on LabVIEW and MATLAB hybrid programming

REALISATION OF AN INTELLIGENT AND CONTINUOUS PROCESS CONNECTION IN SUBSTATIONS

SCADA SYSTEM FOR PEDEEE SYRIA PROJECT

PLC Simulation Control of Assembly Line

Design of Underground Current Detection Nodes Based on ZigBee

Research of digital temperature measurement system in vacuum thermal test based on DS18B20

A solution for applying IEC function blocks in the development of substation automation systems

Applied Research on AC/DC Integrated Power Supply of Substation Lu Zhigang1, a, Lei Bo1, b, Zheng Yongqiang2, c

Agriculture Wireless Temperature and Humidity Sensor Network Based on ZigBee Technology

Smart Power Flow Monitoring and Control

A CEP based ETL method of active distribution network operation monitoring and controlling signal data

Analog signal to RS485 or RS232 Converter, A/D Converter

Modicon Modbus ASCII Serial. Modbus ASCII Serial / Modicon Serial Device Driver Guide. Version 4.5 rev 0 Advantech Corp., Ltd.

WebAccess Driver Configuration Manual

////// SUBSTATIONS. Control command and local Scada

October 05, ECE 421 Session 12. Utility SCADA and Automation. Presented by: Chris Dyer

Website: Technical Support: Skype: fcwkkj or Jason.chen842 Phone: QQ Group:

Dupline. Data Logger. Types G , G Product Description. Ordering Key G Type Selection. Input/Output Specifications

Application of Co-simulation Technology Based on LabVIEW and Multisim in Electronic Design

Phone: Fax: Web:

Application and Research of Integrated Information Exchange System Between Substation and Dispatch Center

Getting Started with your D3000M Series Module

The Design of Intelligentized Switch Cabinet Based on the Internet of Things

Power infrastructure monitoring system on Embedded Web

Modern Equipment for Recording and Analyzing the Events in Electric Stations

Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India

DDL DEVELOPMENT FOR APPLICATIONS BASED ON HART PROTOCOL. Alexandre Baratella Lugli and Ana Carolina de Oliveira Patrício

REGIONAL COUNTRY INFORMATION SERVICE PLATFORM BASED ON HYBRID NETWORK

, ,China. Keywords: CAN BUS,Environmental Factors,Data Collection,Roll Call.

Case Study: Implementation of 132kv Malegaon Sub-Station Using SCADA

November 29, ECE 421 Session 28. Utility SCADA and Automation. Presented by: Chris Dyer

String monitoring with CMS - Circuit monitoring system Increased productivity and improved maintenance of PV systems

PMAC3624 User Manual V2.0. Embedded power monitoring system server

DataVU 5 - Interface Manual Modbus

Supervisory System Design and Implementation of Automatic Illumination Control for Dimmable Flat LED Lighting Devices in Buildings

The principle of a fulltext searching instrument and its application research Wen Ju Gao 1, a, Yue Ou Ren 2, b and Qiu Yan Li 3,c

SEL Real-Time Automation Controller (RTAC)

DataVU 5 - Interface Manual Modbus

AUTOMATION OF POWER DISTRIBUTION USING SCADA

Research on technical scheme of outdoor-layout relay protection in smart substation

INTELLIS. Modbus Direct Network Monitor

1 Introduction to the software

Hitachi s Latest Supervisory, Operation and Control System for Thermal Power Station

Signal Isolators & Conditioners

Research on Heterogeneous Network Integration in Distribution Communication Network

How OPC UA Software Enhances Big Data Integrity for IIoT SCADA Systems. Charles Chen Product Manager

Wireless Remote Water Meter Design of Automatic Meter Reading System

Modbus on S8. Modbus is a simple, open protocol for both PLC and sensors. Details on Modbus can be found on

PROFIBUS DP/CAN Gateway PCA-100. User Manual

Modbus RTU Serial / Modicon Serial Device Driver Guide

SMART E-BILL GENERATION USING PLC

Multi-Split VVVF System for Electric Submersible Pump on Extraction Flat Roof on the Sea

RTD Temperature acquisition converter WJ25

Embedded Smart Home System Based on ZigBee Song Chi

IQ Home Modbus-RTU Master

User s Manual For CMC-MX Soft Starter. Version: 1.0. Date:

Protection and Control System Using Open Network Architecture for Power Systems

Transcription:

Journal of Information Hiding and Multimedia Signal Processing c 2016 ISSN 2073-4212 Ubiquitous International Volume 7, Number 4, July 2016 Design of Substation and Distribution Station Monitoring System Based on DELPHI and Intelligent Modules Rongjin Zheng, Xiaosheng Huang and Huiqiong Deng College of Information Science and Engineering Fujian Provincial Key Laboratory of Big Data Mining and Applications Fujian University of Technology No3 Xueyuan Road, University Town, Minhou, Fuzhou City, Fujian Province, China, 350118 zrj@fjut.edu.cn Received October, 2015; revised April, 2016 Abstract. It builds a kind of hierarchical distributed computer monitoring and control system through adding communication modules and intelligent acquisition modules without changing the primary equipment of 10 kv substation and distribution station. DELPHI is brought in the communication software which based on MODBUS-RTU protocol. And the problems of monitoring and control from distribution modules are solved. It also develops human-machine interface and realizes the monitoring of substation and distribution station. Therefore, the automation level of substation and distribution station is improved greatly. Keywords: Substation and distribution station; Monitoring system, Serial communications. 1. Introduction. As the terminal substation, impacts caused by the faults of 10 kv substation are relatively small. Because of lacking attention for a long time, the automaticity of 10 kv substation is very low, and makes its operation and maintenance difficult [4]. In recent years, with the development of society and economy, this situation has been changing because of the appearance and the implementation of the smart grid. In the new built substations, intelligent primary equipment, which contains communication interface, is increasingly used. Moreover, some reform solution for the old substations has been proposed [2] [5]. Ref.[2] focuses on the description of monitor and control software for each function module, but it lacks the specific design of monitor solution for the whole substation, and the method and protocol of communication are not considered. Ref. [5] focuses on the multithreading communication technology, but lacks the user interface for monitoring. The monitoring system design of substation proposed in this paper can realize a layered and distributed computer monitoring system without changing the primary equipment of 10 kv substation. The problem of monitor and control for scattered module parameters is solved by the communications protocol software of MODBUS-RTU and the DELPHIbased monitoring interface. The approach proposed is proved to be effective for achieving the monitor of substation and improving the automaticity. Its low cost and high reliability overcome the drawbacks of the present communication configuration system, which is expensive and complex. For the substation with intelligent primary equipment, acquisition module is not needed by using the technology solution proposed. The system built has 818

Design of Substation and Distribution Station Monitoring System 819 been used in a 10 kv substation, and works well. It is proved to have good extensibility, flexible, strong real-time performance and a high cost-effectiveness. 2. System composition. As the scale of 10 kv substation and distribution station is not large and the monitoring distance is not long, RS485 is chosen for serial bus. Subordinate construction is used in the whole system. PC is the main control unit (upper-computer), the intelligent modules which have been added in the switch cabinet (lower computer) is the passivity performing unit and the switch cabinet is the monitoring object. The centralized management and optimization of monitored results can be realized through the computers powerful data process perform. RS232 serial port is changed to RS485 through HEXIN-III converter and then connects to intelligent collection modules. And then the control of several intelligence data acquisition models (lower computer) is realized. Each switching value and analog quantity is collected by corresponding intelligent modules. And then, it realizes the decentralized control of multiple parameters and remote communication. Figure 1 shows the overall structure of monitoring system. 2.1. Chosen of intelligent acquisition module. Considering the product maturity and develop speed, ADAM4050 of ADVANTECH is chosen as I/O collection module. The remote signaling and telecontrol can be realized based on RS-485 through the simple commands with the format of ASCII. As the install of ADAM400 serial modules is flexible and it fits for the hanging and guide way in industry field. It also supplies software package for the users and the develop period of the application system is decreased greatly. EDA9033D of Shangdong Lichuang Science and Technology Corporation is chosen as analog quantity collection module. It is a kind of intelligent three phase parameters comprehensive collection module. And the update period of real-time data is 40mS- 1000mS which can be set. Figure 1. The overall structure of monitoring system 2.2. Design of MODBUS communication. MODBUS is a kind of common language which applied in electronic controller. It can realize the information change and data communication between EDA serial modules and PLC, RTU, DCS or the monitoring system which possess MODBUS compatibility. It has become a general industrial standard. Therefore, control equipment from different manufacturers can constitute industry network for centralized monitoring.

820 R. J. Zheng, X. S. Huang, and H. Q. Deng 2.2.1. Setting of MODBUS communication format. MODBUS means that the most significant byte is stored at the lowest memory address which expresses address and data items. It means the most significant byte should be sent first when sending several bytes. New information always begins with quiescent times which less than 3.5 bytes in RTU pattern. And then, the first domain (device address) is sent next. The whole information of frame should be transferred in the form of continuous data flow. It will make an error. If the interval time is over 1.5 bytes before the end of information. Standard structure of MODBUS-RTU frame information as seen in Tab 1. Table 1. Standard structure of MODBUS frame information Address Function Begin Data domain CRC check-ing End domain domain T1-T2-T3-T4 8 bit 8 bit n*8 bit 16 bit T1-T2-T3-T4 2.2.2. MODBUS function code. Function code 01 (0x01): reading the output state of one or multiplex switch signal. Function code 02 (0x02): reading the input state of one or multiplex switch signal (DI). Function code 03 (0x03): reading multiplex registers. Function code 05 (0x05): writing the output state of one switch signal (remote control). Function code 06 (0x06): writing one register. Function code 0F (0x0F): writing the output multiplex switch signal (remote control). Function code 10 (0x10): writing multiplex registers. 2.2.3. CRC code. The host or slave can judge the information through CRC code. It will make an error in the transfer process for electronic noise or the other disturbance. CRC can check in the data communication process from the host or slave. The wrong data can be abandoned. And the system reliability and communication efficient will be improved. CRC domain contains two bytes which includes binary value with 16 bits. It will be added into the information after being calculated by transmission equipment. The receiving equipment calculates the received CRC again and then checks the value. If the CRC values are different, it means something is wrong. It only uses 8 data bits when calculating CRC. It means the begin, the end and the parity bit will not be calculated in CRC calculation. Calculation of CRC code: 1) CRC register with 16 bits are preset all 1 (0xFFFF); 2) XOR calculation between the first binary data with 8 bits ( the first byte of the information frame) and the lower 8 bits in the CRC register. And the result is stored in the lower 8 bits CRC register; 3) The content of the CRC register should be right shifted (to the lower bit) and the higher bit is filled with 0. And then check the shifted bit; 4) If the shifted bit is 1, and then XOR should be calculated between CRC register and A001 (1010 0000 0000 0001) which is preset. If the shifted bit is 0, then do nothing; 5) Repeat the step 3 and 4 about 8 times and then the 8 bit data will be handled; 6) Repeat the step 2 to 5 and then handle the next byte of the information frame; 7) The 16 bits CRC can be gotten through the steps above; 8) The CRC will be added into the information begins with lower byte and then higher byte.

Design of Substation and Distribution Station Monitoring System 821 3. Monitoring software design of the upper computer. Delphi is selected as developing tool. The monitoring software is designed in modular. There are ten function modules: the main interface of monitoring system, database operation, communication test interface, data inquire and export, real-time display, running protection, real-time trend curve display, history trend curve display, alarm display and record module, Web browsers. 3.1. Communication program of upper computer. The system can realize the communication between upper computer and ADAM4050 intelligent module through thirdparty control of MSCOMM. It can build the connection between application program and serial port. And most of the underlying operations can be packaged in the controls. Therefore, there is no need for the programmers to spend time understanding the complicated API function. They just need to set and keep watch on the property of MSComm and event. And then asynchronous serial communication can be realized and the program operation is simplified greatly. MSComm owns many properties. Some need to be set and the other takes the default value. Since there have been many materials introduced, There is no need to introduce the detailed setting method [2]. As EDA9033D intelligent module takes MODBUS-RTU communication protocol [6], and the commands are agile. However, it needs to calculate the checking value of CRC16, and it is difficult to realize using MSCOMM controls. Therefore, it uses the third controls of Teda9033D to realize the communication with EDA9033D intelligent module. The control is developed for the user to use EDA9033D module conveniently. It packages all the electrical parameters collecting, control commands and response in the inner function. And then all the response result will reflect to the user in the form of control parameters. The third-party control of Teda9033D includes control functions and parameters. The command communication of module can be realized through calling control function. The result can be gotten through calling control parameter after calling control function. 3.2. Design of monitoring interface. The wiring diagram of main circuit should be written by AutoCAD. And then the picture is exported as the background of the main interface. The menu bar can be generated through adding Main Menu control. After adding Sharp control, the control will become red when the breaker closes and it will become green when the breaker breaks. The operation record can be written into XML document through loading XML Document control. Figure 2 shows the main monitoring interface. System displays the main wiring diagram and the switch state of each circuit breaker in real time. If necessary, the circuit breakers can be switched quickly and directly by a mouse click on the switching control of corresponding circuit breaker, and the operation record is generated automatically at the same time. The three phase current and voltage of busbar, three phase current, active power, reactive power of each circuit and other electrical parameters display at the corresponding position of the main wiring diagram. When the abnormal conditions occur or the electricity parameters beyond their limits, corresponding alarm signals will be sent by the system monitoring interface, and circuit breaker will disconnect automatically if necessary. Part code of main interface: begin form3.eda9033d.closeport (); MSComm1.CommPort:=3; //choose serial port 1 MSComm1.InputLen:=0; //read the whole content in the buffer MSComm1.InBufferCount:=0; //clear the input buffer MSComm1.OutBufferCount:=0; // clear the output buffer

822 R. J. Zheng, X. S. Huang, and H. Q. Deng Figure 2. Monitoring main interface MSComm1.Sthreshold:=0; //OnComm event will not happen when sending data MSComm1.Rthreshold:=1; //OnComm event will be generated when receiving a byte if mscomm1.portopen =true then MSComm1.PortOpen:=false; MSComm1.PortOpen:=true; // open serial port Sbuf:=vararraycreate([0,7],varbyte); Sbuf[0]:=1; Sbuf[1]:=5; Sbuf[2]:=0; Sbuf[3]:=ionum; if ison= false then Sbuf[4]:=strtoint( $ + ff ) else Sbuf[4]:=0; Sbuf[5]:=0; if ison= false then begin Sbuf[6]:=strtoint( $ + 8c ); Sbuf[7]:=strtoint( $ + 3a ); end else begin Sbuf[6]:=strtoint( $ + cd );

Design of Substation and Distribution Station Monitoring System 823 Sbuf[7]:=strtoint( $ + ca ); end; BF:=Sbuf; mscomm1.output:=bf; //send data MSComm1.PortOpen:=false; form3.eda9033d.openport(3, 9600,n,8,1 ); end; 3.3. Monitoring interface design of inlet and outlet circuit. Monitoring interface of inlet and outlet circuit mainly shows the three phase voltage, current balance and every electrical parameters: active power, reactive power, power factor, frequency and so on. It also can show the state of the breaker and they can control it by opening or closing it through the system. Three phase voltage and current balance can be shown in the form of histogram through Bar of TeeChart. The problem of showing several parameters can be solved through using PageControl control for supplying multiple pages showing in a window. Module communication signal can be realized through the Shape control. The message window should update data regularly which is completed by timer control. The monitoring interface of loop is shown in Figure 3. Figure 3. Monitoring interface of inlet and outlet circuit Otherwise, operation record interface, history curve interface, system setting interface, alarm record interface and so on are designed. As shown in Figure 4 to 6. The flow chart of the monitoring software is shown in Figure 7. The monitoring interface can realize the functions as follows: controlling the breaker closed when the close button is pushed and then collecting the closing signal. The detected current, power and so on

824 R. J. Zheng, X. S. Huang, and H. Q. Deng Figure 4. Operation record interface Figure 5. History curve interface Figure 6. System setting interface can be displayed on the analog instruments. The alarm lamp will flash and the alarm bell will make a sound if the current is over the limit. After 5 seconds, the breaker will break automatically. If there is a malfunction to the breaker when in the closed state, it will alarm.

Design of Substation and Distribution Station Monitoring System 825 Figure 7. Flow chart of the monitoring 4. Conclusion. The system proposed has been tested in practice project, and proved to have good extensibility, good flexibility, strong real-time performance and a high costeffectiveness. The user interface developed is friendly and flexible. It is easy to be used and managed. The monitoring system and its communication method are especially suitable for the automatic reform and update of traditional substations. For the substation with intelligent primary equipment, acquisition module is not needed by using the technology solution proposed. Acknowledgment. This work is supported by the Project Supported by Fujian Provincial Natural Science Foundation of China (2011J01281 and 2015J01630). REFERENCES [1] J. Huang, Y. Xiong, Y. Liun, et.., Delphi serial communication program [M]. Beijing Posts and Telecom Press, 2001. [2] Z. P. Wang, The application of Delphi in Substation and Distribution Station Monitoring System Guangdong Automation & Information Engineering, no.1, pp.47-49, 2004. [3] X. L. Wu, Design and realization of serial communication software based on multithread, J. Control Engineering, vol.11, no.2, pp.171-174,2004. [4] R. J. Zheng, S. B. Wang, M. F. Guo, Supervisory Control Software Design of Substation Based on Delphi, J. Electrotechnical Application, no.3, pp.71-74, 2006. [5] M. F. Guo, Supervisory Control Software Design of Substation Based on multithread, Electrotechnical Journal, no.4, pp.39-41,2004. [6] X. L. Wen, F. Yu, Design of the Serial Communication Software Based on MODBUS Protocol, Journal of Hunan University of Technology, vol. 22, no. 6, pp.79-81, 2008.