Bridge Quick Installation Guide
Warning Read and understand the following Safety Guidelines and Warnings to ensure a safe installation Failure to follow WARNING may result in injury or death. This equipment is to be installed by accredited electrician or similar technical personnel, as per these installation instructions. Read the installation instructions before connecting the system to the power source. All electrical work must be performed by a licensed technician, according to local regulations. Ultimate disposal of this product should be handled according to all national laws and regulations. Installation of the equipment must comply with local and national electrical legislation for installation of electric equipment. Do not install the devices outdoors or exposed to direct solar radiation, water, high relative humidity or dust. Install the equipment only in a restricted access location. When wall mounting, be sure to fix firmly on a stable surface and in accordance to the instructions below. When DIN rail mount fix the devices properly to the DIN rail following the instructions below. When mounting on DIN rail inside a metallic cabinet be sure to properly connected to earth. Unplug power when connecting the wires. Pay attention to the polarity of power and communication cables when connecting them Disconnect power of any bus or communication cable before connecting the system
Caution Contents Failure to follow CAUTION may result in serious injury, property damage or in some circumstances, even death. Do not allow children to play with the or. Do not disassemble, modify or repair the or, contact CoolAutomation support. Any damage caused by your modification or repair may result in an electric shock or fire. Do not expose or to moisture. Water can damage the or, resulting in an electrical components failure, electric shock or fire. Do not use flammable materials (e.g. hairspray or insecticide) near the or. Do not clean the or with organic solvents such as paint thinner. Use only a dry cloth to wipe if necessary. The maximum voltage that can be applied to directly is 4V DC. Do not apply AC0V or AC0V to the or. DO NOT INSTALL COOLINKHUB or COOLPLUG IN THE FOLLOWING LOCATIONS: a) Where mineral oil mist or oil spray or vapor is produced, for example, in a kitchen. Plastic parts may deteriorate and fall off. b) Where corrosive gas, such as sulfurous acid gas, is produced. c) Near machinery emitting electromagnetic waves. Electromagnetic waves may disturb or damage the operation of the. d) Where flammable gas may leak, where there is carbon fiber or ignitable dust suspensions in the air, or where volatile flammable such as thinner or gasoline are handled. Operating the or in such conditions can cause a fire. e) In high temperature areas or in near any flame. f) In moist areas, where there is exposure to water. 6 + System overview Network Topology Models 8 Connecting DK (Daikin) DK (Daikin) S DK (Daikin) P P DKS (Daikin) Siesta Connecting PN/SA/TO PN/SA/TO (Panasonic Sanyo Toshiba) Connecting FJ (Fujitsu) FJ (Fujistu/General) - Option FJ (Fujitsu/General) - Option FJ (Fujitsu/General) - Option 5 Connecting ME (Mitsubishi Electric) ME (Mitsubishi Electric)- CN-05 ME (Mitsubishi Electric) - 7 Connecting MH (Mitsubishi Heavy) MH (Mitsubishi Heavy) - 8 Connecting HT (Hitachi) HT (Hitachi) - 9 Connecting LG (LG) LG (LG) - 0 Connecting Home Automation, BMS & CoolRemote CoolRemote App registration Installation Complete Indicators Normal Operation Determining the UID Toggling the ON/OFF Resetting the 4 Mounting options 4 5
+ System overview Network Topology + s is a solution for complete integration of Multi-Split and Split units. is an designated adapter, that connects directly to the indoor unit on one side, and to on the other, by network. - protocol converter, that allows integration to any Home Automation and BMS system. Ducted Casette is a CoolAutomation s proprietary bus, running on shielded twisted pair cable (4AWG). utilizes free network topology ( star, daisy-chain, etc.) No loops allowed. Up to 0 s can be connected in a single network. Models DK Daikin Ductless models are manu facturer specific. The letters on the sticker (DK, DKS, etc.) indicate the manufacturer the relates to. DKS PA SA TO FJ ME MH Daikin Siesta Series Panasonic Sanyo Toshiba Fujitsu/General Mitsubishi Electric Mitsubishi Heavy HT Hitachi Home Automation / BMS LG LG 6 7
Connecting DK (Daikin) S Connecting DK (Daikin) P P Connecting to Connect the S cable supplied with the, between the RJ- connector and the S port on the indoor unit s PCB. Consult manufacturer s installation manual for location of S on Control Board. Connecting to Connect the signal wires of cable between terminals [-], [] and [], and terminals [VDC-], [] and [], respectively. DK - P P S P P S DK S Connecting to Connect the s [P], [P] terminals to [P], [P] terminals on indoor unit. Connecting to cable coming from the [VDC-], [] and [] terminals on the to the corresponding [-], [] and [] terminals on the, respectively. Controller () in parallel mode. DK - P P S P P S DK P P cable S cable 8 9
Connecting DKS (Daikin) Siesta Series Connecting to Connect the cable, supplied with the, to the port labeled Indoor on and the corresponding connector on the indoor unit. DKS - Indoor Indoor DKS Connecting PN/SA/TO (Panasonic Sanyo Toshiba) Connecting to Connect the s [A], [B] terminals to [A], [B] terminals on indoor unit. * To connect to Panasonic indoor unit use R R terminals. PN SA TO - A B A B PN SA TO Connecting to cable, using [VDC-], [] and [] terminals on the, to the corresponding [-], [] and [] terminals on the. Controller to the W.R.C socket on the. Use the cable supplied with the W.R.C Connecting to cable coming from the [VDC-], [] and [] terminals on the to the corresponding [-], [] and [] terminals on the. Controller (). A B 0
Connecting FJ (Fujitsu/General) Option * Connecting FJ (Fujitsu/General) Option * Connecting to Connect the s [W], [B Y], [R Y] terminals to corresponding terminals on the indoor unit, keeping the wire colors consistency. FJ - W B Y R Y W B R W B R W B R FJ Connecting to Connect the s [W], [B], [R] terminals to indoor unit. Consult manufacturer s installation manual for instructions. FJ - W B R W B R W B R W B R FJ Connecting to cable, using [VDC-], [] and [] terminals on the, to the corresponding [-], [] and [] terminals on the. Controller () * For indoors that work with models as indicated in the drawing. * Reset indoor unit power, once is installed Connecting to cable coming from the [VDC-], [] and [] terminals on the to the corresponding [-], [] and [] terminals on the. Optional: Connect the s [W], [B], [R] terminals to Fujitsu Wired Remote Controller () * For indoors that work with wired remote controllers as indicated in the drawing * Reset indoor unit power, once is installed A
Connecting FJ (Fujitsu/General) Option * Connecting ME (Mitsubishi Electric) CN-05 Connecting to Connect the s [B Y], [R Y] terminals to corresponding terminals on the indoor unit. Connecting to cable, using [VDC-], [] and [] terminals on the, to the corresponding [-], [] and [] terminals on the. Controller () * For indoors that work with -wire compatible models. FJ - W B Y R Y W B R W B R W B Y R Y FJ Connecting to Connect the ME CN-05 cable, supplied with the, between the RJ- connector and the CN-05 port on the indoor unit s Control Board. Consult manufacturer s installation manual for location of CN-05 on Control Board. Connecting to cable, using [VDC-], [] and [] terminals on the, to the corresponding [-], [] and [] terminals on the. ME - CN-05 CN-05 ME CN-05 CN-05 cable 4 5
Connecting ME (Mitsubishi Electric) [] [] Connecting MH (Mitsubishi Heavy) [] [] Connecting to Connect the s [], [] terminals to [], [] terminals on indoor unit. Consult manufacturer s installation manual for location of [] and []. Connecting to cable, using [VDC-], [] and [] terminals on the to the corresponding [-], [] and [] terminals on the. ME - CN-05 CN-05 ME Connecting Line to Mitsubishi Connect the s [], [] terminals to [A], [B] terminals on indoor unit. Consult manufacturer s installation manual for location of [A] and [B]. Connecting to cable, using [VDC-], [] and [] terminals on the to the corresponding [-], [] and [] terminals on the. - MH MH Controller (). Controller (). A B 6 7
Connecting HT (Hitachi) Connecting LG (LG) Connecting to Hitachi unit Connect the s [], [] terminals to [], [] terminals on indoor unit. Connecting to cable coming from the [VDC-], [] and [] terminals on the to the corresponding [-], [] and [] terminals on the, respectively. Controller (). - HT HT Connecting to Indoor unit Connect the cable supplied with the, between the [Y], [B], [R] terminals and the port on the indoor unit s PCB. Consult manufacturer s installation manual. Connecting to Connect the signal wires of cable between terminals [-], [] and [], and terminals [VDC-], [] and [], respectively. - Y B R R Y B LG LG A Controller () in parallel mode. 8 9
Connecting Home Automation, BMS & CoolRemote CoolRemote App Connect the device to the Internet for registration and setup. Option A - Automatic Option B - Manual RS Modbus IP RTU BMS -4 VDC Ethernet Router Scan the QR code from the type label to auto fill-in all the details for CoolRemote App. Go to: https://coolremote.net/register Enter SN number and PIN code, printed on the sticker. Internet 00V-40V AC 50/60hz Register your user-name (e-mail) and password to remotely control and monitor all your units. Register your user-name (e-mail) and password to remotely control and monitor your units. Home Automation / BMS CoolRemote App 0
Installation Complete Indicators The three LEDs that surround the Determining the UID The UID is flashed after one Short Press push-button provide information about the configuration and status. After applying power to the Firmware version is displayed by flashing LEDs followed by the operation state of the system. Short press on the push-button. Toggling the ON/OFF Toggle the state ON/OFF with one Long press on the push-button. long Press Normal Operation In normal operation the blue LED blinks infrequently. The green and orange LEDs are not lit. infrequent blinking Normal operation Problems LED OFF LED ON LED Blinking Green Line OK Line not connected Amber OK not connected Line errors errors Resetting the Reset the with one Short press followed by one Continuous press on the push-button. Short Press + long Press not lit not lit Blue Blinks infrequently twice is ON Blinks infrequently is OFF
Mounting the On Metal Surface The back plate has two magnets that allow you to mount it on any metal surface. On DIN rail Use back plate for DIN rail to attach it to the DIN rail utilizing magnets. On Wall Attach the back plate to the wall using screws as shown. The wires can be fed through the hole in the center of the cover or from the side as shown. 4 5
Need more help? Visit us: http://coolautomation.com/support Email us: support@coolautomation.com v_8.8.08