Simulation of Series Compensated Transmission Lines Protected with Mov Abdolamir Nekoubin

Similar documents
IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online):

Transient stability of 11-bus system using SVC and improvement of voltage profile in transmission line using series compensator

POWER FACTOR CORRECTION USING SVC WITH FUZZY LOGIC CONTROLLER

Modeling and Simulation of Static VAR Compensator Controller for Improvement of Voltage Level in Transmission Lines

SAMPLE. MOVs are sometimes referred

MONITORING ABSTRACT KEYWORDS. TRANSFORMERS MAGAZINE Special Edition: Bushings, 2017

Mitigation of Voltage Swells I

The following standards are the basis of design, manufacture, and test of SPD equipment: Guide for Surge Voltages in Low-Voltage AC Power Circuits

WESTERN PROTECTIVE RELAY CONFERENCE TESTING AND OPERATIONAL EXPERIENCES WITH HIGH SPEED DISTANCE RELAY IN BPA 500 KV SERIES COMPENSATED NETWORK

White Paper. AC Surge Protection. Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems

Quantum Chargers Enhanced AC Line Transient Immunity

Installation Instructions

Purpose of High Voltage Circuit Switchers

Transient Stability Improvement of Long Transmission Line System by Using SVC

Application of Transmission Line Surge Arresters to Reduce Switching Overvoltages

Final Report. Mini Project TET Group nr 7 - Project nr 4. Students: Hans Lavoll Halvorson, NTNU

Lightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany

Introduction to new ABB STATCOM portfolio Power Grid Integration FACTS

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI EE-2401 POWER SYSTEM OPERATION AND CONTROL UNIT-III REACTIVE POWER VOLTAGE CONTROL

Integrating Monitoring and Diagnostic Equipment on Aging Transformers

1278 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 21, NO. 3, JULY 2006

ELG4125: System Protection

AN ADVANCED APPROACH TO IDENTIFY INRUSH CURRENT AND HARMONICS USING ARTIFICIAL INTELLIGENCE FOR POWER SYSTEM PROTECTION

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

Improvements in Transmission Switching Reliability using SF 6 Interrupter Technology

SARDAR RAJA COLLEGE OF ENGINEERING ALANGULAM : PROTECTION AND SWITCHGEAR

4. Fundamental Research, Educational, or Technological Advancement Barriers and Methodologies Used to Address Them

SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD

Main Components of a Static Var Compensator (SVC)

Residual overvoltage relay

Medium Voltage Metal-Enclosed Harmonic Filter Systems

Electromagnetic Compatibility ( EMC )

Suppressing Transients: A New Approach

Static Var Compensator: Effect of Fuzzy Controller and Changing Membership Functions in its operation

Geomagnetic Induced Current (GIC) Mitigation System Summary for the White Paper

Lessons Learned in Static VAR Compensator Protection

2 Principle of lightning protection

Series AMEL20-MAZ 20 Watt AC-DC / DC-DC Converter

Simulation and Analysis of Static Var Compensator with Matlab

Designing with Thermally Protected TCMOV Varistors for Type 1 and Type 2 UL1449 3rd Edition Applications

Safety wherever needed

Overvoltage Protection

Each VariSTAR Type AZU arrester must pass the following production tests: 100% Physical Inspection 100% Leakage Current Test 100% RIV Test

Transient Stability Improvement in Transmission System Using SVC with fuzzy logic Control

ENGR. MARITES R. PANGILINAN, P.E.E.

LIGHTNING PROTECTION of SCADA AND TELEMETRY SYSTEMS

Externally Gapped Line Arresters Smart Solution for Stable Power Supply

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Power Transmission Division Link between power generation and distribution

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

Research Article Development of Inexpensive Static Var Compensator Using PIC

Externally Gapped Line Arresters Smart Solution for Stable Power Supply

POWER QUALITY (UNIT-3) ELECTRICAL TRANSIENT:

CIRCUIT BREAKER TYPE DISCONNECTOR for OVERVOLTAGE PROTECTOR

METAL-OXIDE SURGE ARRESTER PROTECTION OF DISTRIBUTION SYSTEMS

ABB static var compensator stabilizes Namibian grid voltage

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

Study Committee SC A3

Application Techniques CENTERLINE 2100 Motor Control Centers

Figure 1. Storm Trapper H. E. arrester, external mount. Figure 2. Storm Trapper H.E. arrester, metal enclosed. use in Storm Trapper H.E. arresters.

CHAPTER 4 FACTS CONTROLLERS FOR OPTIMIZATION OF POWER SYSTEM

REOHM series 156 Max. continous power: W

Ethernet Protection A Whole Solution Han Zou, ProTek Devices

Manual for overvoltage protection for LED luminaires rev 1

(1986; Rev. 1989) Molded Case Circuit Breakers and Molded Case Switches. (1985; Rev. 1988) Enclosures for Electrical Equipment (1000 Volts Maximum)

Series AMEL20-AZ 20 Watt AC-DC / DC-DC Converter

Data Sheet. Surge protection devices - A technical overview

Christian PAYERL, Poznan, 20 th May, 2009 ABB FACTS Grid connection of Wind Farms. ABB Group May 22, 2009 Slide 1

www. ElectricalPartManuals. com

Series AMEL5-MAZ 5 Watt AC-DC / DC-DC Converter

Using the Bitronics 70 Series to Improve Local Monitoring and Control

LAB1 INTRODUCTION TO PSS/E EE461: POWER SYSTEMS COLORADO STATE UNIVERSITY

ECE 528 Understanding Power Quality. Paul Ortmann (voice) Lecture 23

International Journal of Scientific & Engineering Research Volume 4, Issue 2, February ISSN

PROTEC Z LV the universal solution for transient switching protection for LV motors, generators, transformer LV secundaries, VSD and UPS equipment

Collector System Design Considerations for Wind Farms. Sean Carr Ernst Camm S&C Electric Co.

Control System for Electrical Exploding Wire Opening Switch Experimental Equipment

Application of the Lightning Location System for the selection of Lightning Protection of Overhead Medium Voltage Lines using Long Flashover Arresters

Handling Transient Threats in RS-485 Systems

GLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc.

ABM Status Input Active Burden Module

YOU NEED A WHOLE- HOUSE PROTECTION SYSTEM

It is the job of the protection system equipment to recognize and remove the fault.

Energization Study of 10.4 MVAR Capacitor Bank in 38KV System

AC Surge Protection Devices

Voltage Profile Improvement of Transmission Lines Using Static VAR Compensator

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Lightning and Surge Arresters

Evaluation of different solutions of faulted phase earthing technique for an earth fault current limitation

Automated Analysis of Digital Relay Data Based on Expert System

Power System Network Simulator (PSNsim)

High-Voltage Link for Transmitting Discrete Commands in Relay Protection, Automation and Control Systems

Study of Transient Stability Improvement of IEEE 9-Bus System by using SVC

Survey on new electrical devices with different technology compared to existing electrical devices

CVU-3K-KIT. 3 kv Bias Tee Kit. Description. Parts list / October 2014 *P * 1

Optimal Placement and Sizing of SVC for Improving Voltage Profile of Power System

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment

Guideline on How to Size an NGR

HyperLink Brand Weatherproof PTZ Camera Lightning and Surge Protector Model: AL-VDP Series

BS th Edition wiring regulations Furse overview

Transcription:

Vol:5, No:, Simulation of Series Compensated Transmission Lines Protected with Mov Abdolamir Nekoubin Open Science Index, Electrical and Computer Engineering Vol:5, No:, waset.org/publication/54 Abstract In this paper the behavior of fixed series compensated extra high voltage transmission lines during faults is simulated. Many over-voltage protection schemes for series capacitors are limited in terms of size and performance, and are easily affected by environmental conditions. While the need for more compact and environmentally robust equipment is required. use of series capacitors for compensating part of the inductive reactance of long transmission lines increases the power transmission capacity. Emphasis is given on the impact of modern capacitor protection techniques (MOV protection). The simulation study is performed using MATLAB/SIMULINK and results are given for a three phase and a single phase to ground fault. Keywords Series compensation, MOV - protected series capacitors, balanced and unbalanced faults I I. INTRODUCTION N recent years, the highly increasing cost of building new transmission lines, compounded by the difficulty to obtain new transmission corridors, has led to a search for increasing the transmission capacity of existing lines[-]. use of series capacitors for compensating part of the inductive reactance of long transmission lines increases the power transmission capacity[3-4]. It also increases transient stability margins, optimizes load-sharing between parallel transmission lines and reduces system losses [5-6-7]. Transmission line compensation implies a modification in the electric characteristic of the transmission line with the objective of increase power transfer capability[8]. In the case of series compensation, the objective is to cancel part of the reactance of the line by means of series capacitors[9]. This result is an enhanced system stability, which is evidenced with an increased power transfer capability of the line, a reduction in the transmission angle at a given level of power transfer and an increased virtual natural load []. Series compensation has been in use since the early part of the th century. The first series capacitor for EHV power transmission application was installed in a 45 kv line back in 95 in Sweden [3]. It was followed by a similar project in the USA in 95[4]. The first 4 kv series compensation project was energized in 954 in Sweden[5]. In 96s the first 5 kv series compensation project was introduced in the USA[6]. As a result of the success of these projects, series compensation has become a common practice Abdolamir Nekoubin is with the Electrical Engineering Department, Islamic Azad University Najaf Abad Branch (e-mail: nekoubin@yahoo.com). to enhance the power transfer over long AC transmission lines[7]. One of the main considerations in the design and application of series capacitors is their protection against overvoltage. In modern installations, the traditional gap type scheme which bypasses the series capacitor to avoid overvoltage is replaced with Metal Oxide Varistor (MV). The main advantage of this Protection scheme is that the capacitor is not entirely bypassed during a fault, so reinsertion is instantaneous and without transients[89]. The presence of the capacitor in the circuit immediately after a fault is very important, because it helps the transient stability of the system. Also in case of unbalanced faults, only the protection devices of the faulted phases operate leaving the capacitor of the other phases on line. To determine the various design parameters for planning and implementing, MOV protected capacitors in a network; it is indispensable to be able to model such devices in a fault Analysis program and predict the level of short circuit currents as well as the energy absorbed by the conducting MOV. II. MOV PROTECTION The typical circuit for MOV-protected series capacitors is shown in Fig.. Fig. MOV protection scheme for series capacitors Under normal operation, as long as the voltage across the capacitor is below a protective level, the varistor presents high resistance. When the varistor conducts, its resistance becomes very low and it diverts part of the fault current away from the capacitor. Since there is an upper limit for energy dissipation in the MOV, for its protection there is special circuitry with an energy monitor, which calculates the energy dissipated by the varistor and triggers the air gap to divert the current from the MOV. The bypass switch closes when the gap energy limit is reached. International Scholarly and Scientific Research & Innovation 5() 385 ISNI:99563

Vol:5, No:, III. POWER SYSTEM SIMULATION The system of Fig. is studied using MATLAB/simulink. The transmission line is one 4 kv double circuit, heavy type, with conductors per phase. 3 x 5 Vcs(v) - Open Science Index, Electrical and Computer Engineering Vol:5, No:, waset.org/publication/54 Fig. Power system Total line reactance in positive-sequence is5.6 ohms and Capacitance required for 4% compensation is Xc=4.4 ohms or Cs= 6.8 µf. MOV protection level required to protect the capacitors at.5 times the nominal capacitor voltage. A. Single line to ground fault We study the transient performance of this system when phase-to-ground faults are applied on phase A. The fault and the two line circuit breakers CB and CB are simulated with blocks from the three-phase library. A line-to-ground fault is applied on phase A at t = s. The two circuit breakers which are initially closed are then open at t =.8 s(four cycle later). The fault is eliminated at t =.s, one cycle after line opening. When a line-to-ground fault is applied the fault current reaches.8 KA. During the fault, the MOV conducts at every half cycle and the energy dissipated in the MOV builds up to 5.8 MJ. At t =.8s the line protection relays open breakers CB and CB and the energy stays constant at 5.8 MJ. As the maximum energy does not exceed the MJ threshold level, the gap is not fired. After breaker opening the fault current drops to a small value and the line and series capacitance start to discharge through the fault and the shunt reactance. The fault current extinguishes at the first zero crossing after the opening order given to the fault breaker (t =. s). Then, the series capacitor stops discharging and its voltage oscillate around kv. MOV-Current(A) MOV-Energy(J) -3.5..5..5 Fig 3 Voltage of the series capacitor 6 4 - -4-6.5..5..5 Fig 4 MOV-current 6 x 6 5 4 3.5..5..5 Fig. 5 Energy dissipated in the MOV International Scholarly and Scientific Research & Innovation 5() 386 ISNI:99563

Vol:5, No:, VabcB(pu).8.6.4. -. -.4 -.6 when a three phase-to-ground fault is applied the fault current reaches. ka.during the fault, the MOV conducts at every half cycle and the energy reaches the MJ threshold level after cycles, two cycles before opening of the line breakers. As a result, the gap is fired and the capacitor voltage quickly discharges to zero through the damping circuit. 3 x 5 -.8.5..5..5.5 Fig. 6 Voltage at BUS(pu) Vcs(v) - Open Science Index, Electrical and Computer Engineering Vol:5, No:, waset.org/publication/54 Fault-current(A) VabcB(pu).5 -.5 -.5.5..5..5 Fig. 7 Voltage at BUS(pu).5 x 4.5..5..5 Fig. 8 Fualt current B. Three line to ground fault Now we study the transient performance of this system when three phase-to-ground faults are applied. The fault and the two line circuit breakers CB and CB are simulated with blocks from the three-phase library. A three phase-to-ground fault is applied at t = s. The two circuit breakers which are initially closed are then open at t =.8 s(four cycle later). The fault is eliminated at t =.s, one cycle after line opening. MOV-Current(A) MOV-Energy(J).8.6.4. -. -.4 -.6 -.8-3.5..5. Fig. 9 Voltage of the series capacitor x 4.5..5..5 4 x 6 8 6 4 Fig. MOV-current.5..5..5 Fig. Energy dissipated in the MOV International Scholarly and Scientific Research & Innovation 5() 387 ISNI:99563

Vol:5, No:, Open Science Index, Electrical and Computer Engineering Vol:5, No:, waset.org/publication/54 VabcB(pu) -. -.4 -.6 -.8 VabcB(pu).8.6.4..5..5..5 Fault-current(A).5.5 -.5.5 Fig. Voltage at BUS(pu) -.5..5..5 Fig. 3 Voltage at BUS(pu).5 x 4.5 -.5.5..5..5 Fig. 4 Fualt current IV. SIMULATION RESULTS As long as the voltage across the capacitor is above the protective level, the current is flowing into the MOV and the capacitor current is null when the voltage passes below the protective level, the MOV offers a high resistance and the current, starts flowing into the capacitor again. In any halfcycle of current first the capacitor conducts and then the current is switched to the MOV for the rest of half cycle. The current through the MOV in the unfaulted line is very small compared to that of the faulted phases. It should be noted that the energy of the faulted phases is in MJ, while that of unfaulted line is in mj. During single line to ground fault, the MOV conducts at every half cycle and the energy dissipated in the MOV builds up to 5.8 MJ. At t =.8s (4 cycle later) the line protection relays open breakers CB and CB and the energy stays constant at 5.8 MJ. As the maximum energy does not exceed the MJ threshold level, the gap is not fired. During three line to ground fault, the MOV conducts at every half cycle and The energy reaches the 3 MJ threshold level after cycles, two cycle before opening of the line breakers. As a result, the gap is fired and the capacitor voltage quickly discharges to zero through the damping circuit. V. CONCLUSION The main results regarding MOV protected series compensation, obtained by the fault simulation are summarized as follows: During a three phase fault, the MOV protection devices operate immediately, in order to remove the capacitor banks from the system. However, the capacitor is not isolated from the line, so its reinsertion is instantaneous. An important result is that as soon as the bypass switch closes the line current is reduced to a value, as if there were no capacitor banks in the system. During single phase fault, only protection equipment of faulted phase function, while the capacitor banks of the other phases remain in the system to maintain stability. Also, the MOVs absorbtion of energy is measured in all phases and the energy is exchanged between the capacitor and the MOV. REFERENCES [] J. D. Glover and M. S. Sarma, Power Systems: Analysis and Design. Pacific Grove, CA: Brooks/Cole - Thomson Learning,. [] P. Kundur, Power System Stability and Control. New York: Mc-Graw Hill, 994. [3] S. Henschel, L. Kischner, and M. C. Lima, "Transient Recovery Voltage at Series Compensated Transmission Lines in Piauí, Brazil," Proceedings of the International Conference on Power System Transients (IPST'5), pp. -6, June 5. [4] D. McNabb, M. Granger, Q. B. Van, M. Rousseau, and M. Pilot, "Transient Design Studies for the Transmantaro Series-Compensated Transmission System," Proceedings of the International Conference on Power System Transients (IPST'), pp. -6, June. [5] O. Trad, G. Ratta, and M. Torres, "Experiences in Setting Protection of Series Capacitor Compensated Lines," Proceedings of the International Conference on Power System Transients (IPST'), pp. -6, June. [6] Q. Bui-Van, E. Portales, D. McNabb, and V. Gajardo, "Transient Performance of 5-kV Equipment for the Chilean Series-Compensated Transmission System," Proceedings of the nternational Conference on Power System Transients (IPST'3), pp. -6, October 3. [7] IEEE 4-bus test system data available at: http://www.ee.washington.edu/research/pstca/ International Scholarly and Scientific Research & Innovation 5() 388 ISNI:99563

Vol:5, No:, Open Science Index, Electrical and Computer Engineering Vol:5, No:, waset.org/publication/54 [8] Puerto Rican Electric Power Authority Standard of Construction of Overhead Transmission Lines, May 99. [9] R. Zimmerman, D. Gan, Matpower 3., PSERC Cornell University, USA, December 997. Available at: http://www.pserc.cornell.edu/matpower/ [] ABB Metal Oxide Surge Arresters EXLIM P, ABB Electrical Apparatus, May 5. [] T. J. Miller, Reactive Power Control in Electric Systems. New York: Wiley-Interscience, 98. [] Q. Y. Xuan, A. T. Johns, Digital Simulation of Series compensated EHV (Extra High Voltage) Transmission Systems, IEE Colloquium on Simulation of Power System, 99. [3] M. Courwl & C.T. Nguyen, I Lord, X Do, Modeling MOV- Protected Series Capacitors for Short-circuit Studies,IEEE Transaction5 on Power Delivery, Vol 8, January 997. [4] D.L.Goldsworthy, A Linearized Model for MOVProtectedSeries Capacitors, I EEE Transactions on Power Systems, Vol. PWRS-, No 4, November 987, pp. 953-958. [5] R. Lord, "Validation d'un logiciel de court-circuits adapte pour la compensation serie", Hydro Quebec Internal Report, February989. [6] S. de Oliveira, eta,"representation of Series Capacitors in Electric Power System Stability Studies", paper presented at IEEE/PES winter meeting, New-York, Feb. 99. [7] Courts and E.C.star, "Experience with 5 KV Series Capacitor Installations and New Protection Schemes on the BPA systems", CIGRE 3-9,98. [8] R. Gruenbaum, "Series capacitors for improving power transfer", Power Technology International, 989. [9] P.M, "Analysis of Faulted Power Systems", Iowa StateUniversity Press/AMES, 983. Abdolamir Nekoubin was born in Iran, in985. He received the B.S. degree in 7 and the M.S. degree in 9, all in electrical engineering from Islamic Azad University, Najaf Abad Branch. His current research interests include induction motor, linear induction motor, and nonlinear control theory. Currently he is member of young researchers club. International Scholarly and Scientific Research & Innovation 5() 389 ISNI:99563