Replacement and Calibration of Electronic Spare (PCB) Cassettes - Rosemount 2120 Vibrating Fork Liquid Level Switch

Similar documents
Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Speed monitor D / / 2014

Operating instructions. Standstill monitor A / / 2011

High Precision Quad Output DC Power Supply

Control unit SG-EFS 104/2W. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/2W 24 V=/~

Your Global Flow Control Partner. Series 50 Valve Status Monitor Operation and Maintenance Manual

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Model 7705 Control Module

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

Models 2601B, 2602B, and 2604B System SourceMeter Instruments Quick Start Guide

USER MANUAL VIBRATION CONTROL RMA-POWER-BOX 107/230

Polymer Electric. Operating Instructions. Control Unit SG-EFS 1X4 ZK2/1 8k2. Version 3

Operating Instructions

IV-30 Operating Manual for Pulse Distributor Cassette with potential separation

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL:

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

CVU-200-KIT. 200 V Bias Tee Kit. Description. Parts list / October 2014 *P A* 1

Control unit SG-EFS 104/4L. EN Operating instructions. Innovative by tradition. Version SG-EFS 104/4L AC/DC 24 V

Manual Control Unit GFC 32

D1093S INSTRUCTION MANUAL. D SIL 3 Relay Output Module with Line and Load diagnostics. DIN-Rail Model D1093S

CVU-3K-KIT. 3 kv Bias Tee Kit. Description. Parts list / October 2014 *P * 1

OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123. Bicotest High Voltage Products Ltd

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

BMX DDM Mixed Relay Input/Output module

Operation Manual Series W-500

Polymer Electric. Operating Instructions. Control Unit SG-RST 153. Version 0.3

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Model 2657A-LIM-3 LO Interconnect Module

OPERATING INSTRUCTIONS PA AMPLIFIER P-1812

INSTRUCTION MANUAL. SIL 3 Switch/Proximity Detector Repeater Relay Output, Termination Board Models D6032S, D6032D

Part No. Z , IA Jul OPERATION MANUAL. High Voltage Digitalmeter A

PI-EX-ME-2NAM/COC-120VAC

PI-EX-ME-2NAM/COC-24VDC

INSTRUCTION MANUAL. SIL 3 Relay Output Module DIN-Rail Models D1092S-069, D1092D-069 D1092S D1092D-069

ELECTRICAL SUPPLY TROUBLESHOOTING QUICK GUIDE SAFETY PRECAUTIONS

Part No. Z , IA Mar OPERATION MANUAL. High Voltage Digitalmeter A

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL

Assembly and Operating Instructions. M2 module for BDC-i440 control units

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

MARTINDALE INSTRUCTIONS MM35 DIGITAL MULTIMETER ELECTRIC. Trusted by professionals

Manual Simatek Control Unit GFC 32

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

INSTALLATION INSTRUCTIONS

LED PANEL. User Manual Please read the instructions carefully before use LED-7TC. Innovation, Quality, Performance 15-

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

PHOENIX CONTACT - 12/2007

EC Series. Safety Guide

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

FX1N-4EX-BD Input Expansion Board

I/O module (Expansion module)

The following symbols are used to show dangerous operation or handling. Make sure you understand them before reading the guide.

D5090S INSTRUCTION MANUAL. D A SIL 3 Relay Output Module for NE Load. DIN-Rail and Termination Board, Model D5090S

External level devices for conductive point level switch

Operating instructions. Monitor FD / / 2013

User's Guide. Digital Multimeter. Model MN42

Smart Wireless THUM Adapter

User's Guide. Model High Precision Quad Output DC Power Supply

200B-G Tone Probe. 200EP-G Tone Probe INSTRUCTION MANUAL. with Adjustable Volume

Owner's Manual. True RMS Multimeter. Model No Safety Operation Maintenance Español

XTM1250SA DIN rail three phase four wire LCD display energy meter

Model 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL

RCD Fused Connection Unit Model: RCD10WPV. RCD Double Sockets Models: RCD05WAV, RCD06WPV, RCD07MAV, RCD08MPV. Installation & Operating Instructions

PSR DC/ESP4/2X1/1X2

Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

Operating Manual FPGA-based High-Speed Micro-PLC

LC2300 Level Controller Installation and Maintenance Instructions

DEEP SEA ELECTRONICS PLC DSE103 MK II Speed Switch Operators Manual

Manual Control Unit GFC 16

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

User Guide. Cloning interface small option module for Unidrive and Commander GP. Part Number: Issue Number: 3

E2Q4 Square Proximity Sensor

igus motion Plastics dryve D3, DC-Motor Control System

FOR SERVICE TECHNICIAN S USE ONLY

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

Original operating instructions Safety relay with relay outputs G1501S / / 2016

User Guide True RMS Multimeter Extech EX205T

PanelView Plus/VersaView CE Terminals and Display Modules

Part No. Z , IA Nov OPERATION MANUAL. High Voltage Digitalmeter A

Operating instructions Diagnostic electronics for vibration sensors VSE002 / VXE002 / VXE003 VYE001 / VYE002 / VYE003 / VYE /01 05/2015

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

SMVector Additional I/O Module Installation and Operation Manual

TG basic 1. Appliance tester for testing protective measures in accordance with DIN VDE (DIN EN 62638)

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

LED PANEL. User Manual Please read the instructions carefully before use LED-212RGB TABLE OF CONTENTS. 1. Safety Instructions

Operating instructions Monitor FD-2 DR2005 DR / / 2007

GE Power Conversion T1930EN INSTRUCTION SHEET REV. 09 MV3000E DELTA MAINS VOLTAGE MONITOR UNIT MVC X 1. DESCRIPTION

PACSystems* RX3i and Series IC693MDL940 / IC694MDL940

SE-135 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

TABLE OF CONTENTS 1. SAFETY PRECAUTIONS GENERAL DESCRIPTION FEATURES AND FUNCTIONS 4. CONNECTIONS 6. APPLICATIONS...

Operating Manual -ENGLISH- Page 1 KWG-ISO

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

DM3058/DM3058E Digital Multimeter

Mini Digital Multimeter

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

Transcription:

Manual Supplement 00809-0200-400, Rev AA July 2005 Rosemount 220 Replacement and Calibration of Electronic Spare (PCB) Cassettes - Rosemount 220 Vibrating Fork Liquid Level Switch Refer to the Rosemount 220 Vibrating Fork Level Switch manual (00809-00-400) for additional instructions. Protection afforded by compliance to EN6- (200) may be impaired if the equipment is not used as specified. The Rosemount 220 is a liquid level switch. It must be installed, connected, commissioned, operated and maintained by suitably qualified personnel only, observing any national and local requirements that may apply. Electrical shock could cause death or serious injury. If the level switch is installed in a high voltage environment and a fault condition or installation error occurs, high voltage may be present on switch leads and terminals. Use extreme caution when making contact with the leads and terminals. Replacement and Calibration of Electronic (PCB) Cassettes When replacing a damage or faulty cassette, it is necessary to calibrate the cassette with the operating frequency of the fork assembly. This is a list of actions required to enable calibration to occur. Please make sure you understand them prior to starting. Calibration sequence steps to are time dependent and must be carried out within the noted times. The time dependency and switching sequence is to prevent an accidental calibration occurring. If this replacement is taking place in a (Potentially Explosive Atmosphere) Hazardous Area, a suitably qualified person must carry it out. All work in hazardous areas must be carried out in accordance to local code of practice. For general hazardous area requirements for this equipment, refer to the Rosemount 220 manual (00809-00-400). This calibration routine takes a bit of practice; do not be surprised if the unit does not calibrate after the first attempt. www.rosemount.com

Rosemount 220 Manual Supplement 00809-0200-400, Rev AA July 2005 Replacement Sequence On I.S. units, it is recommended that replacement and calibration be performed in a safe (non-hazardous) area. NOTE: I.S. cassettes can only be replaced with I.S. cassettes. Non-I.S. cassette types can be interchanged with other non-i.s. cassettes, but the new label must be fitted and the original part number transferred to the new label. Before starting the replacement and calibration procedure, ensure that any controlled process will not be adversely affected. To replace the cassette, do the following:. Isolate and disconnect the power to the 220. Insulate ends of the wires. NOTE: On relay units, there may be more than one power source. 2. Remove the screwed-on lid and disconnect the wires, noting connections (Figure ). Also, note the exact Mode switch position (Figure 2) on the cassette that is to be replaced.. Remove and retain the two fixing screws from the base of the cassette and unplug the cassette. 4. Plug in the replacement cassette, refit the screws, reconnect the wires and set the Mode switch to Wet = ON with a one second delay (Figure ). 5. Reconnect the power to the unit. (Reverse step ). Figure. Cassette to be replaced. 2

Manual Supplement 00809-0200-400, Rev AA July 2005 Rosemount 220 Figure 2. Mode switch set to Dry = ON, second delay. This is an example of how the existing cassette may look. Take note of the actual setting. 0. 0. 0 0 Figure. Mode switch of replacement cassette set to Wet = ON, second delay. 0. 0. 0 0 NOTE: Switching time delay: 0.,,, or 0 seconds (mode switch selection) Status Indication LED: On continuous: Output ON One flash per second: Output OFF One flash every 4 seconds: Load Fault (Current too high, short circuit or load omitted) Calibration Sequence To calibrate the cassette, do the following:. Ensure that the sensor forks are completely dry and the mode switch is set to Wet = On, time delay second. 2. Check that the LED is flashing at one flash per second. If it is on continuously, proceed to step 8.. Apply magnet to test point. With the housing conduit nearest to you, the test point can be found halfway down the housing on the right hand side in line with the PCB cassette. On the external housings, a target indicates this. See Figure 4. 4. After a one second delay, the LED will light continuously. 5. Within three seconds rotate the Mode switch two steps clockwise. 6. After a two second delay, the LED will go out. 7. Within three seconds, rotate the Mode switch two steps anti-clockwise. Proceed to step. 8. Apply magnet to test point, indicated by a target on external label (Figure 4). By touching a magnet on the target the 220 output will change state for as long as the magnet is present. 9. After a one second delay, the LED will flash at one flash per second..within three seconds, rotate the Mode switch two steps clockwise.. After a two second delay, the LED will go out (stop flashing). 2.Within three seconds, rotate the Mode switch two steps anti-clockwise..after a two second delay, the LED should flash twice per second.

Rosemount 220 Manual Supplement 00809-0200-400, Rev AA July 2005 4.If the LED is flashing twice per second, the calibration has occurred correctly. Remove the magnet. After a one second delay, the unit will return to normal operation. Proceed to step 7. 5.If the LED is flashing once per second or it is on continuously, the calibration has failed. If this occurs, remove the magnet, wait ten seconds and then repeat from step 2 onwards. 6.If the LED stays off after the two second delay of step, the sensor is not working correctly. Check that the sensor forks are clean and dry. Also, check that there is nothing jammed in or touching the sensor. If no fault is found with the sensor, the entire unit should be returned for repair. 7.Set the Mode switch to the setting noted in step 2 of the Replacement Sequence. Wait five seconds for the new setting to be acted upon. 8.Replace the lid and check the system works. Figure 4. Magnetic test point 4

Manual Supplement 00809-0200-400, Rev AA July 2005 Rosemount 220 220 Direct Load Switching (2-Wire, Red label) Direct load switching (2-wire Red) LOAD LINE 2 OPERATION MODE Mode Dry Wet Wet Dry Mode 0. 0. 0 0 Direct Load Switching WARNING Isolate Supply Before Removing PE (Ground) R I L Neutral Fuse 2A(T) Live DPST (see note) R = External load (must be fitted) U = 20-264V ~ (ac) (50/60Hz) I OFF < ma I L = 20-500mA î = 5A, 40ms 0V V U = 20-60V (dc) I OFF < ma I L = 20-500mA î = 5A, 40ms NOTE: DPST = Double Pole, Single Throw (on/off) switch - must be fitted for safe disconnection of the power supply. Fit the switch as near to the 220 as possible. Keep the switch free of obstructions. Label the switch to indicate that it is the supply disconnection device for the 220. RELAY CONNECTION WARNING: The Rosemount 220 requires a minimum current of ma, which continues to flow when the 220 is off. If selecting a relay to wire in series with the 220, the user must ensure that the drop-out voltage of the relay is greater than the voltage which will be generated across the relay coil when ma flows through it. 5

Rosemount 220 Manual Supplement 00809-0200-400, Rev AA July 2005 High level Dry = ON Low level Wet = ON 0. 0. 0 0 0. 0. 0 0 I L ΔU 2V Fuse 2A(T) <ma I L Fuse 2A(T) I L ΔU 2V Fuse 2A(T) <ma I L Fuse 2A(T) DPST DPST DPST DPST N L 0V V N L 0V V N L 0V V N L 0V V LED on continuously LED flashes every second LED on continuously LED flashes every second 6

Manual Supplement 00809-0200-400, Rev AA July 2005 Rosemount 220 PNP/PLC Version PNP output for load switching and direct PLC switching (-wire Yellow) OPERATION MODE PLC/PNP OUT - 2 4 Mode Dry Wet Wet Dry Mode 0. 0. 0 0 Earth (Ground) Fuse 2A(T) U = 20-60V I < 4mA I L (dc) V O/P 0V I L (MAX) = 0-500mA î = 5A, 40ms U OUT(ON) = U - 2.5V I L (OFF) < 0μA 7

Rosemount 220 Manual Supplement 00809-0200-400, Rev AA July 2005 High level Dry = ON Low level Wet = ON 0. 0. 0 0 0. 0. 0 0 OUT - OUT - OUT - OUT - PLC (positive input) ΔU <V IL I/P <0μA I/P IL ΔU <V IL I/P <0μA I/P IL PLC PLC PLC PLC OUT - OUT - OUT - OUT - PNP dc Fuse A(T) ΔU <V R IL Fuse A(T) R IL <0μA Fuse A(T) ΔU <V R IL Fuse A(T) R IL <0μA LED on continuously LED flashes every second LED on continuously LED flashes every second 8

Manual Supplement 00809-0200-400, Rev AA July 2005 Rosemount 220 Replay Output Relay output, SPCO (Green label) N L 2 OPERATION MODE Mode Dry Wet Wet Dry Mode 0. 0. 0 0 RELAY NC C NO 4 5 6 PE (Ground) Fuse 0.5A (T) NC C NO N 0V Live V DPST (see note) U = 20-264V ~ (ac) (50/60Hz) I < 6mA U = 20-60V (dc) I < 6mA U MAX = 250V ~ (ac) I MAX = 5A P MAX' = 250VA, resistive P MAX' = 00VA, inductive U MAX = 60V (dc) I MAX = 5A, U < 0V I MAX =.5A, U < 60V = Load Off =Load On NOTE: DPST = Double Pole, Single Throw (on/off) switch - it must be fitted for safe disconnection of the power supply. Fit the switch as near to the 220 as possible. Keep the switch free of obstructions. Label the switch to indicate that it is the supply disconnection device for the 220. 9

Rosemount 220 Manual Supplement 00809-0200-400, Rev AA July 2005 High level Dry = ON Low level Wet = ON 0. 0. 0 0 0. 0. 0 0 NC C NO NC C NO NC C NO NC C NO LED on continuously LED flashes every second LED on continuously LED flashes every second

Manual Supplement 00809-0200-400, Rev AA July 2005 Rosemount 220 Intrinsically Safe NAMUR Intrinsically safe NAMUR (Blue label and cassette) - 2 OPERATION MODE Mode Dry Wet Wet Dry Mode 0. 0. 0 0 Intrinsically Safe EN 50227/ NAMUR I ON = 2.2... 2.5 ma I OFF = 0.8....0 ma _ Isolating amplifier to NAMUR (IEC60947-5-6, EN50227) must be used to meet I.S. requirements NOTE: This I.S. cassette can not be interchanged with any other cassette.

Rosemount 220 Manual Supplement 00809-0200-400, Rev AA July 2005 High level Dry = ON Low level Wet = ON 0. 0. 0 0 0. 0. 0 0 - - - - >2.2 ma <.0 ma >2.2 ma <.0 ma LED on continuously LED flashes every second LED on continuously LED flashes every second 2

Manual Supplement 00809-0200-400, Rev AA July 2005 Rosemount 220 Troubleshooting If there is a malfunction, see Table for information on possible causes. Table. Troubleshooting chart. Fault Symptom/Indication Action/Solution Does not switch No LED; no power Check the power supply; (check load on direct load switching electronics model) Incorrect switching Faulty switching LED flashes per second LED flash every 2 seconds LED flash every 4 seconds Fork damaged Thick encrustation on forks 5 second delay on changing mode/delay Dry = On, Wet = On set correctly Turbulence Excessive electrical noise Internal failure; contact supplier Uncalibrated; return to supplier Load fault; load current too high, load short circuit; check installation Replace Clean the fork with care Wait 5 seconds Set the correct mode on electronics insert Set a longer switching time delay Suppress the cause of the interference

Rosemount 220 Manual Supplement 00809-0200-400, Rev AA July 2005 4

Manual Supplement 00809-0200-400, Rev AA July 2005 Rosemount 220 5

Rosemount 220 Manual Supplement 00809-0200-400, Rev AA July 2005 6