Operating instructions Electronic temperature sensor TN /00 04/2011

Similar documents
Operating instructions Control monitor for temperature sensors TR /00 04/2011

Operating instructions Pressure sensor. PN70xx / / 2012

Operating instructions Pressure sensor. PN70xx / / 2010

Operating instructions Pressure sensor. PE30xx / / 2010

Operating instructions Combined pressure sensor. PN22xx / / 2010

Operating instructions Electronic temperature sensor TN7511

Operating instructions Electronic pressure sensor. PF295x /00 07/2016

Operating instructions Pressure sensor. PN50xx / / 2010

Operating instructions Control monitor for temperature sensors TR7439

Operating instructions Electronic pressure sensor PI28xx

Operating instructions Electronic pressure sensor PI22xx PI23xx

Operating instructions Electronic pressure sensor. PN72xx PN73xx PN76xx / / 2016

Operating instructions Pressure sensor. PN78xx / / 2010

Operating instructions Electronic pressure sensor PN7xxx

Operating instructions Electronic pressure sensor. PI22xx PI23xx / / 2013

Operating instructions Electronic pressure sensor. PI109x / / 2010

Operating instructions Mechatronic flow sensor SBY2xx SBG2xx SBN2xx SB0524

Operating instructions Electronic pressure sensor. PN2xxx / / 2015

Operating instructions Electronic pressure sensor. PN22xx PN26xx / / 2015

Operating instructions Optical distance sensor O1D / / 2008

Operating instructions Electronic digital pressure sensor EPS25-XXXX-1001

Operating instructions Optical distance sensor O1D / / 2012

Installation Instructions Temperature transmitter TAA /00 06/2011

Operating instructions Programming and display unit PP / / 2010

Pressure switch RE B/ Type HEDE10.../1/ Operating instructions

Operating instructions Electronic pressure sensor. PM205x /01 09/2011

Operating instructions Electronic level sensor LK81xx

Operating instructions Memory plug E /02 11/2011

Operating instructions Electronic level sensor LK10xx LK70xx

Operating instructions Flow sensors SAxx04 SAxx14

Operating instructions Binary level sensor LMC / / 2014

Operating instructions Vortex flow meter. SVxxx / / 2015

Operating instructions Photoelectric distance sensor OGD592 OGD593

Operating instructions Encoder PerformanceLine. RxP5xx /00 04/2018

Operating instructions Optical distance sensor. O5D15x / / 2014

Operating instructions IO-Link INLINE DISPLAY 1.44" E30430

Operating instructions Optical distance sensor. OID25x / / 2014

Instruction manual. Electronic pressure gauge (EPG) IM-TE91K033-EN5. Original manual

Operating instructions Optical distance sensor. OID20x / / 2014

Operating instructions Optical distance sensor. OID20x / / 2015

Original operating instructions Fail-safe inductive sensor GI711S / / 2010

Operating instructions Optical distance sensor. OID25x / / 2015

SM9000. Magnetic-inductive flow meter. Made in Germany

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

Manual pressure sensors DW35311x DW36311x

Operating instructions. Speed monitor D / / 2014

Pressure switch type DG 51 E

SM9000. Made in Germany

Operating instructions Binary level sensor LMTx0x LMTx1x LMTx2x

Operating instructions Diagnostic electronics for vibration sensors VSE002 / VXE002 / VXE003 VYE001 / VYE002 / VYE003 / VYE /01 05/2015

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions ClassicLine module AC5203 / AC5205 AC5208 / AC5211 AC5213 / AC5214 AC5215 / AC5233 AC /00 02/2015

Operating instructions. Monitor FD / / 2013

Original operating instructions Safety relay with relay outputs with and without delay G1502S / / 2016

Original operating instructions Safety relay with relay outputs G1501S / / 2016

Operating instructions. Standstill monitor A / / 2011

Original operating instructions Fail-safe inductive sensor GG711S

Original operating instructions Fail-safe inductive sensor GI712S

Operating instructions Evaluation system for flow sensors VS / / 2013

Installation instructions Diagnostic electronics for vibration sensors VSE / / 2007

Installation instructions Inclination sensor EC2019 EC / / 2013

Communication. Features. Device variant. Copyright 2015, Builder: , Time: 09:23:27

TV7. Communication. Features. Device variant. Copyright 2017, Builder: , Time: 05:34:05

Operating instructions RFID evaluation unit DTE / / 2016

Communication. Features. Device variant. Copyright 2017, Builder: , Time: 02:39:41

Communication. Features. Device variant. Copyright 2017, Builder: , Time: 01:29:48

Operating instructions. ProcessLine analogue module AC / / 2012

PN7. Communication. Features. Device variant. Copyright 2015, Builder: , Time: 04:31:57

Communication. Features. Device variant. Copyright 2016, Builder: , Time: 04:59:44

Operating instructions. Monitor FS-2 / FS-2N / / 2013

Operating instructions Monitor FD-2 DR2005 DR / / 2007

Operating instructions. Monitor FR-1 / FR-1N / / 2013

JUMO MIDAS C08. OEM Pressure Transmitter Basic. Applications. Brief description. Special features. Customer benefits

Thread length (overall length) material

JUMO MIDAS C08. OEM Pressure Transmitter Basic. Applications. Brief description. Special features. Customer benefits

Dimensions. Model Number. Electrical connection emitter. Features. Electrical connection receiver. Product information. Pinout OBE12M-R100-S2EP-IO-V31

Operating instructions. Monitor FS-1 / FS-1N / / 2013

standard, short, preferential, top

Safety System CES-FD. Non-contact safety system CES-FD- Direct connection to decentralized peripheral systems (e.g. ET200pro) PLC

Electronic Level Switch ENS 3000

Encoders Absolute Singleturn Encoder Types A58CS8

M18 Ultrasonic Sensor UK1

VM series. features. web contents. code description. available models. inductive sensors. Cylindrical M12 in AC B H

JUMO PINOS L01. Calorimetric flow sensor. Brief description. Special features. Customer benefits. Data Sheet

Technical Data. General specifications. Output type Rated operating distance s n 8 mm

RoHS. Shock / vibration resistant. Short circuit proof. Flexible. . XXXX e. . XXXX e

PFK series M18 cylindrical inductive sensors

Quick reference guide 3D sensor O3D3xx

TSE. Functional Description. Order Code TSE HA /2010. Electrical Pressure Switch N D. p max up to 400 bar (5801 PSI)

Technical Data. General specifications Switching element function PNP NO/NC Rated operating distance s n 5 mm

Technical data. General specifications. factory setting: 125 ms Memory Non-volatile memory Write cycles Indicators/operating means

Installation Sensing distance Connection Output configuration Operation mode NO Operation mode NC

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm. Short-circuit protection

Display Solid-state Temperature Switch

XUK8TAKSMM12 photo-electric sensor - XUK - diffuse - Sn 5m 1Q auto PNP/NPN

DI572 Digital Input Module

4. Sensing Distance. 2: 2 mm. 4: 4 mm 8: 8 mm 15: 15 mm 16: 16 mm 20: 20 mm

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

Rotary Measuring Technology Absolute encoders, Multiturn, optional with incremental track

DI561 Digital Input Module

Transcription:

Operating instructions Electronic temperature sensor TN7531 UK 704772/00 04/2011

Contents 1 Preliminary note3 1.1 ymbols used 3 2 afety instructions 3 3 Functions and features 4 4 Function 4 4.1 Communication, parameter setting and evaluation 4 4.2 witching function 5 5 Installation 6 6 Electrical connection7 7 Operating and display elements 8 8 enu9 8.1 enu structure 9 8.2 Explanation of the menu 10 9 Parameter setting 11 9.1 General parameter setting 11 9.2 Configuration of the display (optional) 13 9.3. etting of the output signals 13 9.3.1 etting of the output function 13 9.3.2 etting of the switching limits 13 9.4 User settings (optional) 14 9.4.1 Zero point calibration 14 9.4.2 etting the switching delays 14 9.4.3 etting of the error behaviour of the outputs 14 9.4.4 etting of the switching logic for OUT1 14 9.5 ervice functions 14 9.5.1 Reading of the min/max values for the system temperature 14 9.5.2 Reset of all parameters to factory setting 14 10 Operation 15 10.1 Reading of the set parameters 15 10.2 Fault indication 15 11 cale drawing 16 2

12 Technical data 17 12.1 etting ranges 18 13 Factory setting 18 UK 1 Preliminary note 1.1 ymbols used Instruction > Reaction, result [ ] Designation of pushbuttons, buttons or indications Cross-reference Important note Non-compliance can result in malfunctions or interference. 2 afety instructions Please read this document prior to set-up of the unit. Ensure that the product is suitable for your application without any restrictions. Improper or non-intended use may lead to malfunctions of the unit or to unwanted effects in your application. That is why installation, electrical connection, set-up, operation and maintenance of the unit must only be carried out by qualified personnel authorised by the machine operator. Check the compatibility of the product materials ( 12 Technical data) with the media to be measured in all applications. 3

3 Functions and features The unit monitors the system temperature in machinery and plant. 4 Function 4.1 Communication, parameter setting and evaluation The unit displays the current system temperature. It generates 2 output signals according to the parameter setting. OUT1 OUT2 witching signal for system temperature limit value. witching signal for system temperature limit value. It moreover provides the process data via IO-Link. The unit is laid out for fully bidirectional communication. o, the following options are possible: -- Remote display: Reading and displaying the current system temperature. -- Remote parameter setting: Reading and changing current parameter settings with the FDT service program ifm Container or via IO-Link. -- Using the FDT service program ifm Container, the current parameter settings can be stored and transferred to other units of the same type. The program library of the available DT objects can be found at www.ifm.com ervice Download. Device-specific parameter lists for IO-Link parameter setting are available at: www.ifm.com elect your country Data sheet direct: 4

4.2 witching function OUTx changes its switching state if it is above or below the set switching limits (Px, rpx). The following switching functions can be selected: Hysteresis function / normally open: [OUx] = [Hno] ( fig. 1). Hysteresis function / normally closed: [OUx] = [Hnc] ( fig. 1). First the set point (Px) is set, then the reset point (rpx) with the requested difference. Window function / normally open: [OUx] = [Fno] ( fig. 2). Window function / normally closed: [OUx] = [Fnc] ( fig. 2). The width of the window can be set by means of the difference between Px and rpx. Px = upper value, rpx = lower value. UK T 1 T FE 2 P rp HY P rp 1 0 1 0 t Hno Hnc 1 0 1 0 t Fno Fnc T = system temperature; HY = hysteresis; FE = window When set to the window function the set and reset points have a fixed hysteresis of 0.25 % of the measuring range. This keeps the switching state of the output stable if the temperature varies slightly. 5

5 Installation Using process adapters the unit can be adapted to different process connections. Adapters have to be ordered separately as accessories. Immersion depth of the sensor: min. 12 mm in the pipe. If you use the adapter supplied as accessory the correct immersion depth is ensured. ounting dimensions with 12 adapter ounting dimensions with G¼ adapter ounting dimensions with G½ adapter 13,5 27 13,5 27 21 35 For optimum response times: Orientation of the unit: Connector against the flow direction of the medium. Before installing and removing the unit: Ensure that no medium can leak at the process connection. 1 2 3 A Grease the threads of the process connection (1), adapter (2) and nut (3). Note: The sensor tip (A) must not be in contact with grease. crew the suitable adapter into the process connection. Place the temperature sensor onto the adapter and tighten the nut. Tightening torque max. 50 Nm. Ensure that the unit is correctly oriented. 6

6 Electrical connection The unit must be connected by a qualified electrician. The national and international regulations for the installation of electrical equipment must be adhered to. Voltage supply to EN 50178, ELV, PELV. Disconnect power. Connect the unit as follows: 2 3 1 4 2 x positive switching 2 x negative switching 1 BN 1 BN L+ 2 WH 2 WH L+ 4 BK 4 BK 2: OUT2 3 BU 2: OUT2 4: OUT1 L 4: OUT1 3 BU L UK Pin 1 Pin 3 Pin 4 (OUT1) Pin 2 (OUT2) Ub+ Ub- Binary switching output temperature monitoring. Data channel for bidirectional communication. Binary switching output temperature monitoring. Core colours of ifm sockets: 1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black) 7

7 Operating and display elements 1 2 3 4 5 6 7 8 9 ode/enter et 10 11 1 to 8: Indicator LEDs --LED 1: Current temperature in C. --LED 2: Current temperature in F. --LED 7, LED 8 = switching state of the corresponding output. 9: Alphanumeric display, 4 digits --Display of the current system temperature. --Indication of the parameters and parameter values. 10: et button --etting of the parameter values (scrolling by holding pressed; incrementally by pressing once). 11: ode/enter button --election of the parameters and acknowledgement of the parameter values. 8

9 UK 8 enu 8.1 enu structure RUN

8.2 Explanation of the menu P1/rP1 P2/rP2 OU1 OU2 Upper / lower limit value for system temperature at which OUT1 switches. Upper / lower limit value for system temperature at which OUT2 switches. Output function for OUT1: witching signal for the temperature limit values: Hysteresis function [H..] or window function [F..], either normally open [. no] or normally closed [. nc]. Output function for OUT2: witching signal for the temperature limit values: Hysteresis function [H..] or window function [F..], either normally open [. no] or normally closed [. nc]. EF Extended functions / opening of menu level 2. HI LO COF d1 / d2 dr1 / dr2 FOU1 FOU2 P-n di Uni re aximum value memory for system temperature. inimum value memory for system temperature. Zero-point calibration. witch-on delay for OUT1 / OUT2 witch-off delay for OUT1 / OUT2. Behaviour of output 1 in case of an internal fault. Behaviour of output 2 in case of an internal fault. Output logic: pnp / npn. Update rate and orientation of the display. Unit of measurement for system temperature. Restore factory settings. 10

9 Parameter setting During parameter setting the unit remains in the operating mode. It continues its monitoring function with the existing parameters until the parameter setting has been completed. 9.1 General parameter setting 3 steps must be taken for each parameter setting: 1 election of the parameter Press [ode/enter] until the requested parameter is displayed. ode/enter et UK 2 etting of the parameter value Press [et] and keep it pressed. > > Current setting value of the parameter flashes for 5 s. ode/enter et > > After 5 s: etting value is changed: incrementally by pressing the button once or continuously by keeping the button pressed. Numerical values are incremented continuously. For reducing the value: Let the display move to the maximum setting value. Then the cycle starts again at the minimum setting value. 3 Acknowledgement of the parameter value Press [ode/enter] briefly. > > The parameter is displayed again. ode/enter et The new setting value is stored. etting of other parameters tart again with step 1. Finishing the parameter setting Press [ode/enter] several times until the current measured value is displayed or wait for 15 s. > > The unit returns to the operating mode. If [Loc] is displayed when attempting a modification of a parameter value, the sensor is locked via software. This locking can only be removed via a parameter setting software. In case of parameter setting with the user interface of the ifm Container program, the values can be directly entered in the specified fields. For IO-Link parameter setting device-specific parameter lists at: www.ifm.com elect your country Data sheet direct: 11

Change from menu level 1 to menu level 2: Press [ode/enter] until [EF] is displayed. If the submenu is protected with an access code, [Cod1] flashes in the display. Press [et] and keep it pressed until the valid code no. is displayed. Press [ode/enter] briefly. On delivery by ifm electronic: no access restriction. Press [et] briefly. > > The first parameter of the sub-menu is displayed (here: [HI]). ode/enter et ode/enter et With the user interface of the ifm Container program: Activate the [EF] button. If menu level 2 is protected by an access code, the input field for the code no. is activated. Enter valid code no. Locking / unlocking The unit can be locked electronically to prevent unintentional settings. ake sure that the unit is in the normal operating mode. Press [ode/enter] + [et] for 10 s. ode/enter et > > [Loc] is displayed. During operation: [Loc] is briefly displayed if you try to change parameter values. For unlocking: Press [ode/enter] + [et] for 10 s. > > [uloc] is displayed. ode/enter et On delivery: unlocked. Timeout: If no button is pressed for 15 s during parameter setting, the unit returns to the operating mode with unchanged values. 10 s 10 s 12

9.2 Configuration of the display (optional) elect [Uni] and set the unit of measurement: [ C] or [ F]. elect [di] and set the update rate and orientation of the display: --[d1]: Update of the measured values every 50 ms. --[d2]: Update of the measured values every 200 ms. --[d3]: Update of the measured values every 600 ms. --[rd1], [rd2], [rd3]: Display as for d1, d2, d3; rotated by 180. --[OFF]: The display is switched off in the operating mode. 9.3. etting of the output signals 9.3.1 etting of the output function elect [OU1] and set the function: --[Hno] = Hysteresis function / normally open. --[Hnc] = Hysteresis function / normally closed. --[Fno] = Window function / normally open. --[Fnc] = Window function / normally closed. elect [OU2] and set the function: --[Hno] = Hysteresis function / normally open. --[Hnc] = Hysteresis function / normally closed. --[Fno] = Window function / normally open. --[Fnc] = Window function / normally closed. UK 9.3.2 etting of the switching limits elect [P1] / [P2] and set the value at which the output switches. elect [rp1] / [rp2] and set the value at which the output switches off. rpx is always smaller than Px. The unit only accepts values which are lower than the value for Px. 13

9.4 User settings (optional) 9.4.1 Zero point calibration elect [COF] and enter value. etting range: -10.0...10.0 C in steps of 0.1 C. -18.0...18.0 F in steps of 0.1 F. The internal measured value "0" is shifted by this value. 9.4.2 etting the switching delays [d1] / [d2] = switch-on delay for OUT1 / OUT2. [dr1] / [dr2] = switch-off delay for OUT1 / OUT2. elect [d1], [d2], [dr1] or [dr2] and set a value between 0.1 and 50 s (at 0.0 the delay time is not active). 9.4.3 etting of the error behaviour of the outputs elect [FOU1] or [FOU2] and set the value: --[On] = Output 1 / 2 switches ON in case of a fault. --[OFF] = Output 1 / 2 switches OFF in case of a fault. 9.4.4 etting of the switching logic for OUT1 elect [P-n] and set [PnP] or [npn]. 9.5 ervice functions 9.5.1 Reading of the min/max values for the system temperature elect [HI] or [LO], briefly press [et]. [HI] = maximum value, [LO] = minimum value. Delete memory: elect [HI] or [LO]. Press [et] and keep it pressed until [----] is displayed. Press [ode/enter] briefly. 9.5.2 Reset of all parameters to factory setting elect [re]. Press [et] and keep it pressed until [----] is displayed. Press [ode/enter] briefly. We recommend taking down your own settings in the table before carrying out a reset ( 13 Factory setting). 14

10 Operation After power on, the unit is in the Run mode (= normal operating mode). It carries out its measurement and evaluation functions and provides output signals according to the set parameters. Operating indications Chapter 7 Operating and display elements. 10.1 Reading of the set parameters Press [ode/enter] until the requested parameter is displayed. Press [et] briefly. > > The unit displays the corresponding parameter value for about 15 s. After another 15 s the unit returns to the Run mode. 10.2 Fault indication [OL] Temperature too high (measuring range exceeded by more than 3% of the final value of the measuring range). [UL] Temperature too low (measuring range below the final value of the measuring range by more than 10%). [Err] Detection zone is exceeded (T < -60 C or T > +160 C). [C1] hort circuit in OUT1* [C2] hort circuit in OUT2* [C] hort circuit in both switching outputs* [Loc] etting pushbuttons of the unit locked, parameter change rejected. [Loc] Unit locked via software, parameter change rejected. [PARA] etting value of a parameter outside the valid range the unit is not ready for operation. The error may occur with IO-Link parameter setting. If an invalidly set parameter is activated, [PARA] is displayed instead of the parameter value. *The output concerned is switched off as long as the short circuit exists. The messages Err, PARA and C1 are shown even if the display is switched off. Response of the outputs in case of a parameter setting fault [PARA]: OUT1 OUT2 Invalid setting [OU1] / [OU2] OFF OFF Invalid setting [FOU1] / [FOU2] OFF OFF Invalid setting [P-n] OFF OFF Invalid setting of other parameters acc. to setting [FOU1] acc. to setting [FOU2] 15 UK

11 cale drawing 2 3 34 48 1 45 12x1 14 94,5 128 8,2 22 4 Dimensions in mm 1: Display 2: LEDs 3: Programming button 4: Internal thread 18x1.5 16

12 Technical data easuring range [ C / F]... -40...150 / -40...302 Communication interface... IO-Link 1.0 Baud rate [kbaud]... 38.4 Operating voltage [V]... 18...32 DC Current rating [ma]... 250 hort-circuit protection (pulsed); protected against reverse polarity and overload Integrated watchdog Voltage drop [V]...< 2 Current consumption [ma]...< 50 easuring element...1 x PT 1000 according to DIN EN 60751, class B Dynamic response T05/T09 [s]...1 / 3 (to DIN EN 60751) Accuracy (the values apply to flowing water) - switching output [K]...± 0.3 - display [K]...± 0.3 Resolution - switching output [K]...0.1 - display [K]...0.1 Housing materials... stainless steel (30415); EPD/X (antoprene); PC Copolymer; PBT (Pocan) FP (Viton) PA aterials (wetted parts)... stainless steel 316L / 1.4404; O-ring: FP 8 x 1.5 gr 80 hore A Operating temperature [ C]... -25...70 torage temperature [ C]... -40...85 Pressure resistance [bar]...300 Protection rating... IP 67 Protection class...iii hock resistance [g]... 50 (DIN / IEC 68-2-27, 11 ms) Vibration resistance [g]... 20 ( DIN / IEC 68-2-6, 10-2000 Hz) EC EN 61000-4-2 ED:... 4 kv CD / 8 kv AD EN 61000-4-3 HF radiated:... 10 V/m EN 61000-4-4 Burst:... 2 kv EN 61000-4-5 urge:... 1 kv EN 61000-4-6 HF conducted:... 10 V UK 17

12.1 etting ranges P1 / P2 rp1 / rp2 min max min max T C -39.8 150.0-40.0 149.8 0.1 F -39.6 302.0-40.0 301.6 0.1 T = step increment 13 Factory setting Factory setting User setting P1 60.0 rp1 50.0 OU1 OU2 Hno Hno P2 120.0 rp2 100.0 COF 0.0 d1 0.0 dr1 0.0 d2 0.0 dr2 0.0 FOU1 FOU2 P-n di OFF OFF PnP d2 Uni C Further information at www.ifm.com 18