Mitigating Arc Flash Hazards

Similar documents
SE Engineering, PC strives to be a leader in the power system engineering field by providing our customers with the highest level of quality,

RELT Reduced Energy Let Thru 2018

Switchgear Survival Guide: Ten Tips to Optimize Switchgear and Enhance Reliability

Enhancing Reliability of Legacy Systems with New Generation Low-Voltage Circuit Breaker Upgrades

30-Cycle Rated Switchboards - Selectivity Tradeoffs

Best practices for making switchgear safer.

Siemens Dynamic Arc Flash Reduction System and its application in motor control centers

Dynamic Arc Flash Reduction System

Best practices for making switchgear safer

INFRARED WINDOWS APPLIED IN SWITCHGEAR ASSEMBLIES: TAKING ANOTHER LOOK

ELG4125: System Protection

Thermal and Arc Flash Analysis of Electric Motor Drives in Distribution Networks

StruxureWare Power Monitoring Expert 8.0 Data Center Edition

Certification Exams. Detailed Content Outlines Level 2 Certified Assistant Technician Level 3 Certified Technician Level 4 Certified Senior Technician

UL 508A Industrial Control Panels Eaton. All Rights Reserved.

Industries. Switchgear Interlock Applications. Process safety Control. Power Distribution Power Generation Power Transmission.

POWER SYSTEMS STUDY: SIGNIFICANT (OR TOTAL) DELETION OF EXISTING TEXT

White Paper. UL Standards for Power Control System Equipment

ACCESS 9340/9360 Meter Input/Output Module

Understanding SCCR. THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Conext CL-60 Inverter Firmware Upgrade Process

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

2008 Code Changes for Power Distribution

Prime Point on Wave Energy Reducing Switchgear ( SWITCHGEAR ).

3- and 4-pole switching in UPS installation

Explosion-Protected Arc-Fault Protection ExAFCI Arc-Fault Circuit Interrupter

2 ms arc-flash protection and feeder relay in one platform

MEDIUM VOLTAGE PRODUCTS. UniSec Air-insulated medium voltage secondary distribution switchgear Informed choice for safety

Free Standing Emergency Department DGL Project No SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL

UL 508 A standard-compliant design of industrial control panel

Power Quality of Commercial Buildings - Advanced

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

high RESISTANCE STOPLIGHT Instruction Manual C-101EM

110.4 Use of Equipment.

Equipment Short-Circuit Current Rating and Available Fault Current

Document Owner: Name: Phil Langlois Department: Lead Electrical Engineer

IEC H.P. Rated Pin and Sleeve Sequential contacts engagement during mating and un-mating IEC configurations specific to each voltage and

Switchgear Design Impacts the Reliability of Backup Power Systems

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

1. Coordination of series-rated devices is permitted where indicated on Drawings.

Impact of Proposed IEEE 1584 Empirical Model in Comparison to Existing Arc-Flash Hazard Assessment Calculation Methods

Short Circuit Current Ratings and AC Drives

LV MCC with Arc Flash Mitigation (AFM) Units

Secondary Surge Arrester Instruction Manual Page 1 of 5

PRODUCT BROCHURE. Deploying effective power protection in data centers

Galaxy VM. System Bypass Cabinet 640 kva Installation GVMSBC640KHEL 06/2016.

WiAutoLink Frequently Asked Questions

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter

Innovation on Medium Voltage Switchgear

Symmetra PX 160. Maintenance Bypass Enclosure. Installation 05/

GE Energy Industrial Solutions. Entellisys 4.5. Low-Voltage Switchgear Application Guide

Risk Mitigation of Aging Electrical Infrastructure

Source-Transfer Application Guide

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016

Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins

SENTRON. Protective devices Selectivity for 3VA molded case circuit breakers. Introduction. Selectivity - terms and definitions

Design Considerations for Highly Reliable Electrical Systems

Presentation Title ( Arial, Font size 28 ) Electrical Safety at Office

2014 NEC Code Changes. Code changes based on the 2014 NEC

Great Western Painting Assured Equipment Grounding Conductor Program OR Ground Fault Circuit Interrupter (GFCI)

Digitrip 520MC with Maintenance Mode

Model 8020-KHV. Kelvin Keithley Triaxial Connector Card. Description / October 2014 *P * 1

IEC & 2 standard. The reference for safe and reliable LV switchboards

Type VR Electrically Operated Ground and Test Device

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY. Subject: Control Reliability for Machinery & Equipment

Innovation for MV distribution

Instructions for Operation of S&C Test Accessory Catalog Number TA-2669

Data Center Design: Power, Cooling & Management

MultiTech Router Commissioning for Com X 200/210/510

Product brochure. Cyberex. Remote Power Panel (RPP) Power distribution system

Power Quality of Commercial and Industrial Power Systems

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Installation, Operation and Maintenance Manual

DEFINITIONS TO BE USED WITH THE ANSI B11 SERIES OF SAFETY STANDARDS FOR MACHINES

Executive summary. by Michel Bonnet, Maximilien Laforge, and Jean-Baptiste Samuel

Document C0. Use for:

OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123. Bicotest High Voltage Products Ltd

THE MSD/ERGONOMICS PROGRAM STANDARD

Model 8020-STC. Kelvin Standard Triaxial Connector Card. Description / October 2014 *P * 1

Electrical Service Change-Tn Neenah

AUS X CONTROL UNIT... 4 OPERATING MODES DESCRIPTION AUTOMATIC... 4 MANUAL... 5 CONNECTION OF EXTERNAL CONTACTORS K1 and K2...

SURE TRIP RETRO KITS With RMS CURRENT MEASUREMENT

ZC Series Zone Monitoring Controllers

Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET

Model 2657A-LIM-3 LO Interconnect Module

MAXIMA+ Series Rotary Level Indicator

CELLULAR TELEPHONE USE POLICY

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

ARC-FLASH INCIDENT ENERGY REDUCTION USING ZONE SELECTIVE INTERLOCKING

Isolation of Electrical Energy Guidance

APPLICATION CONTROL GUIDELINES. IntelliROL Power Supply PN Revision Date: March 15, 2017

Model 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1

Model 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1

Electrical network protection Sepam series 20 Sepam series 40 Quick start

Galaxy Shore Connection 500 kva. Operation 04/

TRENDS IN SWITCHGEAR SPECIFICATIONS

Lockout/Tagout Training:

DIVISION 16 SECTION Surge Protective Device Submittal (SPD)

Transcription:

1910DB1402 / March, 2015 by Antony Parsons, Ph.D., P.E. and Reza Tajali, P.E. Schneider Electric Engineering Services Make the most of your energy SM

Contents 1.0 Introduction... 3 2.0 What is Arc Flash Mitigation?...4 3.0 Reduce Arc Flash Energy Levels... 5 3.1 The Role of the Circuit Breaker or Fuse...6 3.2 Over-Current Protective Device (OCPD) Coordination Study...6 3.3 Specialized Relaying / Optical Technology... 7 3.4 Virtual Main Arc Flash Mitigation System... 7 4.0 Remove Workers from Harm s Way...9 4.1 Infrared Viewing Windows...9 4.2 Online Temperature Monitoring...9 4.3 Remote Racking Systems for Circuit Breakers...9 5.0 Conclusion...10 2 White paper on arc flash mitigation strategies

1.0 Introduction While the threat of shock and electrocution from inadvertent contact with energized parts has long been recognized, the arc flash and arc blast hazards have only fairly recently been incorporated into the electrical safety standards. The Occupational Safety and Health Administration (OSHA) enforces electrical workplace safety standards outlined in the National Fire Protection Association s NFPA 70E: Standard for Electrical Safety in the Workplace. Basic compliance to the requirements of NFPA 70E is established with a five-step process: Step 1: Develop and audit an Electrical Safe Work Practices (ESWP) policy. Step 2: Conduct an electrical system study to determine the present degree of arc flash hazards and label the equipment. Step 3: Ensure adequate supplies of personal protective equipment (PPE). Step 4: Conduct regular safety training and employee assessments. Step 5: Maintain all electrical distribution system components. Companies can take additional steps to reduce the potential for an arc flash. The remainder of this paper will focus on mitigating arc flash hazards, specifically engineering controls. Electrical equipment should be installed, operated, serviced, and maintained only by properly trained and qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. White paper on arc flash mitigation strategies 3

2.0 What is Arc Flash Mitigation? According to Webster s dictionary, mitigation is defined as, to make milder, less severe or less violent. When applied to electrical workplace safety, arc flash mitigation involves taking steps to minimize the level of hazard and/or the risk associated with an arc-flash event. ANSI Z10-2012, Occupational Health and Safety Management Systems, released a hierarchy of arc flash mitigation controls, as shown below. Hierarchy of Arc Flash Mitigation Controls Most Effective Elimination Substitution Arc Flash Mitigation Hazard A source of possible injury or damage to health. Risk A combination of the likelihood of occurrence of injury or damage to health and the severity of injury or damage to health that results from a hazard. Engineering Controls Warnings Administrative Controls Personal Protective Equipment Typically Included in ESWP Least Effective Disaster Recovery Did You Know? PPE is often mistakenly viewed as the solution to arc flash hazards. The reality is that even when PPE is properly selected, it does not guarantee freedom from injury. NFPA 70E only makes the claim that injuries sustained during an arc flash event would be reduced and survivable due to mitigating effects of arc-rated PPE. 4 White paper on arc flash mitigation strategies

2.0 What is Arc Flash Mitigation? - con t. The most effective arc flash safety programs look to incorporate safety by design. Though not as effective as substitution or elimination, the goal of Engineering Controls is to reduce the degree of hazard. Administrative controls and warnings are less effective because they rely on workers following proper procedures and safe work practices. The engineering controls covered in the following pages will either: 1) Reduce arc flash energy to a level where permitted tasks can be performed, or 2) Locate the worker so that he/she is not subject to harm. 3.0 Reduce Arc Flash Energy Levels Arc flash reduction systems do not eliminate the electric shock hazard of working on or inside energized equipment. The amount of arc flash energy reduction will be determined by an engineering analysis. The goal of reducing arc flash energy levels is to reduce the severity of the potential arc flash hazards to which a worker may be exposed. Personal protective equipment (PPE) is required when an arc flash energy reduction system is employed, but the level of PPE may be reduced. Obviously, too little PPE can increase the worker s exposure to burns and injury. Too much PPE can also have a detrimental effect such as heat stress, loss of motion and visibility, and carelessness due to rushing the task at hand. Fabric Ratings 25 Cal/cm 2 40 Cal/cm 2 100 Cal/cm 2 White paper on arc flash mitigation strategies 5

3.0 Reduce Arc Flash Energy Levels - con t. 3.1 The Role of the Circuit Breaker or Fuse in Lowering Arc Flash Energy Levels Why is a circuit breaker or fuse always considered in the arc flash analysis? Because arcing time is the key determining factor for arc flash energy. Per the equations in IEEE Std. 1584-2002, arc flash incident energy varies linearly with time. If the duration of the arcing fault doubles, the available energy doubles; halve the duration and you cut the energy in half. Energy = Volts x Amps x Time Faster clearing time = Lower energy Circuit breakers and fuses determine how fast a circuit is cleared. Since incident energy is proportional to arcing time, the use of faster-acting devices is key. As a result, proper selection of overcurrent protective devices in particular, selecting devices that will quickly clear arcing faults from the power system is a powerful mitigation strategy. 3.2 Over-Current Protective Device (OCPD) Coordination Study An OCPD coordination study optimizes the protective device setting for reliability and arc flash protection. While an OCPD study is not a requirement of an arc flash analysis, it is recommended to have this study completed as a component of an arc flash analysis. The OCPD coordination study will determine if minor adjustments in circuit breaker (or other over-current protective device) settings can lower incident energy levels. However, settings must be chosen to properly protect equipment while still allowing for normal load currents and routine temporary overcurrents (e.g., motor starting current) to flow without causing a trip. 6 White paper on arc flash mitigation strategies

3.0 Reduce Arc Flash Energy Levels - con t. 3.3 Specialized Relaying, Such as Optical Technology Quickly clearing faults is a key to arc flash mitigation. Circuit breaker or relay settings near the source of power may have significant time delays to allow for coordination of downstream devices. A relatively new way to address this issue is to use relays that detect the presence of arcing faults by looking for the flash of light associated with the arcing fault in addition to the characteristic current flow. However, for an arcing fault to be detected, both the high current and a burst of light must exist. When both conditions are present, the optical relay can operate very quickly to clear the fault. This typically occurs through the operation of an overcurrent protective device. Alternatively, the optical relay can activate a shorting switch that creates a bolted fault that clears the arc even more quickly than a circuit breaker could operate. Optical relays can also be used as the protective relay in a virtual main configuration. 3.4 Virtual Main Arc Flash Mitigation System Switchgear and switchboards can be subjected to dangerous levels of arc flash incident energy when fed directly from a power transformer. The addition of a virtual main system reduces the arc flash energy on the entire switchgear, including the main incoming section. A digital relay and overcurrent sensing is added to the low-voltage side of the service transformer and is designed to trip an existing upstream fault breaking device, often a medium-voltage circuit breaker or other vacuum interrupter. This mitigation solution can take one of two forms: 1) A maintenance selector switch, which temporarily lowers the instantaneous short circuit current setting. The maintenance setting lowers the available arc flash incident energy and temporarily forfeits selective coordination. An arc may propagate to the supply side of all devices in the same enclosure. That is why virtual main systems trip the upstream device. White paper on arc flash mitigation strategies 7

3.0 Reduce Arc Flash Energy Levels - con t. 2) Zone-selective interlocking with downstream branch circuit breakers in the switchgear eliminates the need for the maintenance selector switch. Arc flash energies can be permanently reduced with zone-selective interlocking. Example of a Before and After Single Line Diagram Before: No Main on Low-Voltage Switchgear LV Switchgear MV Relay 50 51 5,000 Amperes Utility Available Fault Current 1,500 kva 13,800 V PRI 480Y/277 V SEC 5.5% Z Arc Flash Incident Energy 62 Cal/Cm 2 2 Second Duration After: Addition of Virtual Main MV Relay 50 51 1,500 kva 13,800 V PRI 480Y/277 V SEC 5.5% Z LV Switchgear 5,000 Amperes Utility Available Fault Current 50 51 Digital Relay (Virtual Main) Maintenance Switch Arc Flash Incident Energy 5.7 Cal/Cm 2 0.180 Second Duration Reduced arc flash energy is based on the virtual main relay being properly set to below 85% of the arcing current. A protective device coordination study is required. De-energizing equipment does not absolve the facility from the responsibility of performing the arc flash analysis or providing the necessary PPE. OSHA and NFPA have rules that prohibit energized work. In order to establish that a circuit is de-energized, the circuit must be approached to verify that it has been de-energized. Until then, the circuit must be considered energized per NFPA 70E and the worker who performs the verification test must wear full PPE. Hiring contractors to perform electrical work does not absolve the facility from performing the calculations and providing the arc flash exposure levels to the contractor s workers. 8 White paper on arc flash mitigation strategies

4.0 Remove Workers from Harm s Way The following arc flash mitigation solutions remove a worker from the location of, or place a barrier between, the worker and exposed energized parts. 4.1 Infrared Viewing Windows Having infrared (IR) windows permanently installed into electrical equipment enables IR scans to be performed without exposing the worker to hazardous energy. IR windows are made of a glass-like material that is transparent to infrared rays and allows hot spots to be registered by a thermographic camera. They also facilitate permanent access for inspection of electrical components without disturbing operations. 4.2 Online Temperature Monitoring Online temperature monitoring, via wireless sensors, provides 24/7 access to critical connection points where traditional thermography cannot be used. This technology evaluates the equipment s current condition without exposing workers to energized parts since equipment covers do not have to be removed. The sensors are installed during a planned outage and can be used in equipment with high arc flash ratings without a risk of danger to personnel or equipment. 4.3 Remote Racking System A remote racking system (RRS) allows circuit breaker racking operations to be performed via a control panel located away from the cell, removing the operator from manual contact with the circuit breaker. If the operator controlling the RRS is located outside the arc flash boundary, the need for PPE is eliminated. Remote racking systems are available for LV and MV circuit breakers. White paper on arc flash mitigation strategies 9

5.0 Conclusion Electrical hazards are a significant safety and financial risk for electrical workers and their employers. OSHA mandates that work on electrical equipment must be performed in a manner that does not expose the worker to undue risk of injury. Complying with the safe work practices dictated by NFPA 70E and implementing arc flash mitigation strategies through engineering controls will enhance workplace safety for employees and reduce the financial risk for your company. Photo Courtesy of Oberon Schneider Electric USA, 800 Federal Street Andover, MA 01810 Tel: 978-794-0800 www.schneider-electric.com/us 2015 Schneider Electric. All rights reserved. Document Number 1910DB1402R03/15 March 2015