Accessories IC690ACC900

Similar documents
Four opto-isolated signal channels: SD, RD, RTS, and CTS. Electrical compatibility with RS-485. A 5V DC/DC converter for power isolation

This Datasheet is for the IC693CBL300. I/O Bus Expansion Cables.

Integrity Instruments

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount.

1. FEATURES AND BENEFITS

PLC Racks IC697CHS782/783

Series Specialty PLCs

Installing the Panel. Installing the Panel

IC693PWR331 High Capacity Power Supply, 24 VDC Input

This Datasheet is for the IC693PWR332. High Capacity Power Supply, 12 VDC Input.

Weight ounces Panel Fasteners... Four holes to accept four 16x32 machine screws NEMA Rating... NEMA 1

This Datasheet for the IC697BEM733. Series Genius Remote I/O Scanner.

Appendix G. CJ1W-CIF11 RS-422A Converter

Installation and Programming Manual. This Manual describes the IBSS InterBus-S Slave, its uses and set up.

ABB Drives. User s Manual RS-485 Adapter Board FRSA-00


CS485. User s Manual. Version ZYPEX, Inc.

Device/PLC Connection Manuals

Bus Transmitter Expansion Module (Fiber Media) with built-in switch. PROFINET Slave, Version 2.2 Class A IO-Device

Installation & Operation Guide

Overview. The DIN-RS232 has three primary functions: Isolated parallel RS-232 interface Fused power distribution Animatics peripheral expansion bus

CPU Module IC200CPU005

MODEL DRIVER Ic Ip VDC

This Datasheet for the IC670MDL VDC Pos/Neg Logic Input 16 Pt. Grouped.

VersaMax* Serial Communications Module

1 1 Getting Started $ "% # + %#! & %! + % $!% +!% $% # * %&# $ +!% ' *!# * %&# $ + $$ %!% "&% &%"&% # $$ $ +!( % " % $!%! %$ + $) % "$!# %% "!

EasyCoder 501/601 Installation Instructions

ME778C-RJ45 MAIN MODULE (FRONT CARD) MAIN MODULE. Line: RJ-45. Line: RJ-45 INTERFACE MODULE (REAR CARD) Serial: 10-Pin RJ.

This Datasheet is for the IC693MDL /24 Volt DC, 0.5A Positive Logic Output, 32 Point.

CPU Modules CPU001 and CPU002

Analog Current Input - 16 Channel IC693ALG223. Current Ranges. Power Requirements and LEDs. Location in System. Analog Input Modules

Introduction. General Ratings

Building the Communication Cable

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication

Serial Communication Converters & Adapters Instruction Manual

CPU Module IC200CPU005

TABLE OF CONTENTS. Communication Functions

Installation Manual CCL 20 D PTZ camera controller unit DIN-rail mounting

VersaMax IP Input Module

Data Sheet Rev DALLIS Serial Data

Device/PLC Connection Manuals

VersaMax* IC200BEM003. PROFIBUS Master Module. Ordering Information. Specifications. GFK-2739 April of their respective owners.

GE Fanuc IC694ALG221. Rx3i PacSystem

This Datasheet for the IC697CMM711. Communications Coprocessor, CMM, RTU, SNP, and SNPx Protocols

Moxa TCC-100 Series User s Guide

Moxa TCC-100 Series Hardware Installation Guide

This Datasheet for the IC670ALG310. Analog Output Voltage, 8 Channel, +/-10V, 0 to 10V.

USER MANUAL MODEL 2017P MODEL 2017P60. RS-232 to 20mA and. RS-232 to 60mA Current Loop Converters

T1K MODBUS Base Controller Specifications

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison

Model User Manual Revision E 04/29/99. OEM Gaging System. Part Number R01

DIN-191 and DIN-192 SERIES CONVERTER BOXES USERS MANUAL

205 CPU NETWORK ADAPTER F2-UNICON

Discrete Input Modules IC697MDL653

Two Door Controller GEN-045

Summary. Introduction

Installation Guide Serial Interface T942SI

Classic Brain Boards. Classic Brain Boards. Features. Description. Networking. Part Numbers

Frame Relay Cabling This section describes the cabling and connector pinouts for the Frame Relay cards.

GE Fanuc IC694ALG391. Rx3i PacSystem

ADAM-4510 RS-422/RS-485 Repeater ADAM-4510S Isolated RS-422/485 Repeater ADAM-4520 Isolated RS-422/485 Converter Startup Manual

GE Fanuc Automation Programmable Control Products. PACSystems RX3i. Serial Communications Modules. User s Manual, GFK-2460A.

Discrete Output Modules IC697MDL750

Installing the DX LCD Display

MEV Limited USB232/485 INSTRUCTION MANUAL

This Datasheet for the IC697BEM721. I/O Link Interface Module for the Series

Discrete Output Modules IC697MDL740

AD-8923-BCD. Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD

Defining the Future in Motion Control

Automationdirect.com. D i r e c t L o g i c M O D B U S S L A V E F 4 S L V - M B

Product Information. Firmware Version 3.10 Programmer Compatibility Expansion I/O Compatibility

UC-2000 Installation Manual Unicorn Computers Technology Limited

Pmod modules are powered by the host via the interface s power and ground pins.

es Six programmable controller and Input/Output Communications Control Module (I/O CCM) IC600BF948 General Description GEK-90824D July 1989

FEATURES DESCRIPTION MODEL 110B. Power Supply

intan intan RHD2000 Dual Headstage Adapter RHD2000 Dual Headstage Adapter Features Applications Description TECHNOLOGIES, LLC

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions

USB/RS232 TO cctalk COMMUNICATION BOARD Technical Information

This Datasheet for the IC697CMM741. Series MMS or TCP/IP Ethernet LAN Interface.

Connecting a Cisco Input Module

TCNM-ACBB1 Installation Manual

MS-5000: MiniStar Reader

Miniature Asynchronous 4-Wire High Speed Modems

Vorne Industries. 87/708 Master Clock Display User's Manual

Discrete Output Modules IC697MDL750 24/48 Volt DC, 0.5 Amp, 32 Point Output Module

VersaMax IP. Proficy Machine Edition. Publication Reference Chart

Package Contents. GP Options (Made by Digital)

PXL-250 Tiger Controller

Mini Driver V (Mini Driver MP with 5-Screw Terminal Block) MINI DRIVER MP

INTERFACES TRADITIONAL PC ADAPTER CARD. DATA SHEET page 1/6. Description

GE Fanuc IC695CMM004. Rx3i PacSystem

CPU Modules CPU001 and CPU002

How to wire DMX/RDM lighting systems

BioPointe Reader Installation Guide

TB21. NO - Relay. Relay. Common - Relay. NC - Relay. Input J23. Ground TB22 TB23. NO - Relay Common - Relay NC - Relay Input Ground.

Product Information. Firmware Version 3.00 Programmer Compatibility Expansion I/O Compatibility

6222 Two Door Module Technical Operations Manual

Quick Start Installation Guide

icex-cmtm General specs and Installation guide

F1000 User's Manual. (Version: V1.01)

Transcription:

(IC690ACC900) datasheet Features Provides the IC69* programmable controllers with an interface to devices that use the RS- interface. Allows connection to programming computer without a Work Station Interface board. Easy cable connection to either an IC69, IC69, or IC69 programmable controller. No external power needed - operates from + volt DC power on the programmable controller backplane. Convenient, light weight self-contained unit. Functions The provides an RS- serial interface for the IC69* programmable controllers, which have a built-in RS-/RS- interface. Specifically, it provides a serial connection between an IC69, IC69, or IC69 programmable controller serial port and the serial port on the 6 IC690ACC900 programming computer without the need for a Work Station Interface to be installed in the computer. The programming computer can be an IBM XT, AT, or PS/ or compatible Personal Computer. Location in System The RS-/RS- to RS- converter is a free-standing device which requires two cables as the connections between the programmable controller and the programmer. Its location is limited only by the length of the connecting cables as listed in the interface specifications (see Table ). The cable at the programmable controller end that connects to the RS-/RS- connector on the converter can be up to 0 feet in length (without an external source of + VDC) and up to 000 feet (00m) in length with an external source of + VDC. The cable from the RS- connector on the converter to the programming computer s serial port can be up to 0 feet (m) in length. FRONT VIEW REAR VIEW a69 IC690ACC900A CABLE ADAPTER MADE IN USA IBM and PS/ are registered trademarks of International Business Machines Corporation.

Installation Installation of the consists of connecting two cables. Select the proper cables for your installation. Prewired cables (see below) are available, or if cables of different lengths are required by your application, you can build your own cables. Specifications for building these cables are provided later. You do not need to connect an external source of power to the converter for a cable length of 0 feet, or less, since the necessary power connections of + VDC and signal ground are derived from the programmable controller s backplane bus through the cable which connects to the IC69, IC69, or IC69 programmable controller. Select one of the three RS- compatible cables (0 feet in length) that will connect the programmer s (or other serial device) RS- serial port to the RS- port on the converter. The catalog numbers of these cables are: IC690CBL0 (use with the IC60 industrial computer, or IBM PC-XT or compatible personal computer), IC690CBL0 (use with IBM PC-AT or compatible personal computer), and IC690CBL0 (use with the IC6 industrial computer, or IBM PS/ or compatible personal computer). A standard 6-foot cable (HHP compatible) is available to connect the RS-/RS- port on the converter to the RS- port on the programmable controller. The catalog number of this cable is IC69CBL0. Installation of these cables should be done with the programmable controller powered-down. Connect the -pin male connector on the 0 foot cable to the -pin female connector on the converter. Connect the female connector (9-pin or -pin) on the opposite end of this cable to the male RS- connector (serial port) on the selected programming (or other serial) device. If you build you own cable, use a connector that is compatible with your serial device. Notice that both ends of the 6-foot RS-/RS- compatible cable are the same; a -pin male connector is attached at both ends. Connect one end of this cable to the -pin female connector on the RS-/RS- connector on the converter. Connect the other end of this cable to the -pin female connector, which interfaces to the RS- compatible serial port on the IC69* programmable controller. For the IC69 programmable controller, this connector is accessed by opening the hinged door on the power supply. The serial port connector for the IC69 programmable controller is on the CPU module, and is accessed by opening the hinged door on the module. The serial port for the IC69 programmable controller is located on the CPU module. Cable Description The serial connection to the IC69 programmable controller (see Figure ) is to the RS-/RS- compatible serial port connector, located at the bottom of the CPU module behind the hinged door, through an available 6 foot ( meter) serial interface cable - IC69CBL0. Wiring information and recommended cable and connectors are provided for those who may want to build their own cable having a different length. The serial connection to the IC69 programmable controller is to the RS-/ compatible serial port connector located behind the hinged door on the right front of the power supply, also through the same 6 foot serial interface cable, IC69CBL0 - or equivalent, as shown in Figure. The serial connection to the IC69 programmable controller (see Figure ) is to the RS-/RS- compatible serial port connector, located on the lower right of the CPU module, also through the available 6 foot ( meter) serial interface cable - IC69CBL0.

C P U PROGRAMMABLE CONTROLLER RS- RS- PROGRAMMER a69 Figure. Typical Configuration with an IC69 Programmable Controller PROGRAMMABLE CONTROLLER RS- RS- PROGRAMMER a6 Figure. Typical Configuration with an IC69 Programmable Controller PROGRAMMER RS- a0 PROGRAMMABLE CONTROLLER RS- Figure. Typical Configuration with an IC69 Programmable Controller RS- Interface Pin Assignments Pin assignments and signal definitions for the RS- interface are given in the table below. Pin Table. RS- Interface for Converter Signal Name Function I/O Shield Cable shield - SD Transmitted Data Out Received Data In RTS Request to Send Out Clear to Send In 6 - No connection - SG Signal Ground - Data Carrier Detect In 9-9 - No connection - 0 Data Terminal Ready Out - - No connection - RS-/RS- Interface Pin Assignments Pin assignments and signal definitions for the RS- interface are given in the table below. Pin Table. RS-/RS- Interface for Converter Signal Name Function I/O Shield Cable shield (A) Differential Data Carrier Detect Out (B) Differential Data Carrier Detect Out ATCH/ Attach (used with HHP) n/a + VDC Logic Power In 6 RTS(A) Differential Request To Send Out SG Signal Ground, 0V In (B ) Differential Clear To Send In 9 RT Resistor Terminator n/a 0 (A ) Differential Receive Data In (B ) Differential Receive Data In SD(A) Differential Send Data Out SD(B) Differential Send Data Out RTS(B) Differential Request To Send Out (A ) Differential Clear To Send In

Logic Diagram The following figure is a logic diagram of the. RS- - SHIELD RS-/RS- (IC690ACC900) a9 RS-/RS- - SHIELD 9 TERMINATOR RESISTOR 0 Ω ( B ) SD 0 ( A ) SD (B ) SD (A ) RTS MODEM ( B ) ( A ) RTS ( B ) 6 RTS ( A ) ( B ) ( A ) LOGIC POWER + SG NC SG 0 ATTACH ATCH/ Figure. Logic Diagram

Jumper Configuration There are three jumper locations on the converter board for selection of user options. Each jumper position has three pins, as shown in the following illustration. These jumper positions, labeled JP, JP, and JP, are accessed by removing the square plastic cover on the top of the converter. Configuration can be changed as required by carefully removing one or more of the jumpers with a pair of needle nose pliers RS-/RS and placing it on the desired pair of pins. Refer to the description of these selectable jumper positions in the following table and place the jumper on the selected pair of pins. The pins are numbered,, and. As shown in Figure and Table, the default jumper locations are indicated by a rectangle over the pins to be jumpered for each position. The default pin numbers are and. a60 RS- Figure. Location of Jumpers for User Options Table. Jumper Configuration for Jumper Position Label Jumper Configuration Description JP Default position and is used when the device communicating with the PLC does not supply the Carrier Detect signal. JP forces the signal active on the RS- port. Use jumper positions and if the device does supply the Carrier Detect signal. This allows the programming device to control. JP MODEM Default position and is used when an attached Modem does not require the Clear To Send () signal. This allows the programming device to control the RTS signal. Jumper positions and are used when the attached Modem does require the signal (most modems require this signal). Forces RTS to be continually active. JP ATTACH Default position and is used for most applications communicating with the PLC via a serial programming port. Jumper positions and are used if the device communicating with the PLC is intended to emulate the Hand-Held Programmer protocol. Refer to the documentation for your serial device for signal requirements.

6 Example of Cable Connections The following figure is an example of the wiring connections for the cables required in a typical PLC system using the RS-/RS- to RS- converter. HOST COMPUTER TD RTS GND RS- SHIELDED PAIRS 0 SD RTS GND SHLD - RS-/RS- (IC690ACC900) - FE RS- - FE RS- (A) (B) (A ) (B ) SD (A) SD (B) RT (A ) (B ) RTS (A) RTS (B) +V 0V SHLD * POWER SOURCE FOR POINT-TO-POINT CONNECTION 0 FEET ( METERS) ONLY. POWER SOURCE BEYOND 0 FEET ( METERS) AND FOR MULTIDROP CONNECTION MUST BE EXTERNAL SOURCE. ** TERMINATION RESISTANCE FOR THE RECEIVE DATA () SIGNAL NEEDS TO BE CONNECTED ONLY ON UNITS AT THE END OF THE LINES. THIS TERMINATION IS MADE ON THE IC69 PLC PRODU BY CONNECTING A JUMPER BETWEEN 9 AND 0 INSIDE THE - D-SHELL WITH THE FOLLOWING EXCEPTION. FOR IC69 PLCS, CATALOG NUMBERS IC69CPU AND IC69CPU, THE TERMINATION FOR AT THE PLC IS IMPLEMENTED BY A JUMPER BETWEEN 9 AND. - 0 9 6 RS- TWISTED SHIELDED PAIRS Figure 6. Example of Cable Wiring Connections to Converter Multidrop Configuration The following figure is an example of using the converter in a multidrop configuration. SD (A) SD (B) 0 (A ) (B ) ** 9 RT 6 RTS (A) RTS (B) (A ) (B ) * +V * 0V SHLD - a0 IC69 PLC RS- - FE * PROGRAMMER RS- - IC690CBL0 OR EQUIVALENT RS- SHIELDED PAIRS TD RTS GND - FE RS-/RS- (IC690ACC900) NOTE WHEN WIRING RS- / MULTIDROP CABLES REFLECTIONS ON THE TRANSMISSION LINE CAN BE REDUCED BY CONFIGURING THE CABLE IN A DAISY CHAIN FASHION AS SHOWN BELOW. MASTER SLAVE STATION LAST STATION 0 - FE RS- - FE RS- ALSO IT IS RECOMMENDED TO MAKE ANY NECESSARY CONNECTIONS INSIDE THE CABLE CONNECTOR TO BE MOUNTED ON THE PLC. IT IS NOT RECOMMENDED TO USE TERMINAL STRIPS OR OTHER TYPES OF CONNECTORS ALONG THE LENGTH OF THE TRANSMISSION LINE. 0 TD GND SHLD - (A) (B) (A ) (B ) SD (A) SD (B) RT (A ) (B ) RTS (A) RTS (B) +V POWER SOURCE FOR PLC - CONNECTOR FOR IC69 PLC; LOCATED ON POWER SUPPLY FOR IC69 PLC: LOCATED ON CPU BOA TERMINATION RESISTANCE FOR THE RECEIVE DATA () SIGNAL NEEDS TO BE CONNECTED ONLY ON UNITS AT THE END OF THE LINES. THIS TERMINATION IS MADE ON THE IC69 PLC PRODU BY CONNECTING A JUMPER BETWEEN 9 AND 0 INSIDE THE - D-SHELL WITH THE FOLLOWING EXCEPTION. FOR IC69 PLCs, CATALOG NUMBERS IC69CPU AND IC69CPU, THE TERMINATION FOR AT THE PLC IS IMPLEMENTED BY A JUMPER BETWEEN 9 AND. GROUND POTENTIAL: MULTIPLE UNITS, NOT CONNECTED TO THE SAME POWER SOURCE, MUST HAVE COMMON GROUND POTENTIALS OR GROUND ISOLATION FOR PROPER OPERATION OF THIS SYSTEM. 0V SHLD - 0 9 6 V 0V RS- MAKE CONNECTIONS INSIDE D-CONNECTORS TO OTHER PLC s Figure. Example of Multidrop Configuration with Converter * * SD (A) SD (B) 0 (A ) (B ) 9 RT 6 RTS (A) RTS (B) (A ) (B ) +V 0V SHLD - SD (A) SD (B) 0 (A ) (B ) 9 RT 6 RTS (A) RTS (B) (A ) (B ) +V 0V SHLD - a SLAVE STATION IC69 PLC CPU RS- - FE LAST STATION IC69 PLC PS RS- - FE

Power Requirements Table. Specifications for IC690ACC900 * Voltage + volts DC, +% Current 0 ma, ±% RS-/RS- Interface Cable Maximum Cable Length Cable Lengths: 000 feet (00 meters) Cable Type: 6 feet ( meters) Belden 90, AWG # (0.mm ) wire 0 feet (0 meters) Belden 909, AWG # (0.6 mm ) wire } 0 feet (0 meters), up to 000 feet (00 meters) Same cable as for 0 feet (0 meters) Connector Type RS- Interface Cable Maximum cable length Up to 0 feet ( meters) Connector Type -pin D-type Male Subminiature (programming device end) 0 feet ( meters) Converter end: -pin D-type Female Subminiature Programming device end: 9-pin, -pin, or -pin (depending on type of connector on your serial device) D-type Female Subminiature Catalog numbers are provided as suggestions only. Any cable having the same electrical characteristics is acceptable. It is strongly recommended that you use stranded wire. Since it is sometimes hard to find a cable with the desired number of twisted pairs (the Belden 909 has an extra pair), you may end up with a cable with extra pairs. For distances over 0 feet ( meters), the + volt DC logic power source must be provided externally by connecting an external power supply to the +V and SG (0V) connections at the converter end of the cable. The +V pin at the PLC connector end of the cable must not be connected to the cable. The +V and SG connections from the external power supply must be isolated from its own power line ground connection. Ensure that there is no connection between the external supply and the PLC except the SG cable connection. * Refer to GFK-06B, or later for product standards and general specifications. Table. Ordering Information Description Converter, RS-/RS- to RS- Catalog Number IC690ACC900