Safegard V4 Panel. Installation Datasheet. Safegard V4 Panel Installation Instructions and Datasheet release 1.7 August 2016

Similar documents
Panel Installation Datasheet

Line Impedance Stabilization Network (LISN)

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

Original operating instructions Fail-safe inductive sensor GI711S / / 2010

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

LED PANEL. User Manual Please read the instructions carefully before use LED-7TC. Innovation, Quality, Performance 15-

MC 11 EB-2 Power supply cabinet with external bus, AC version

Operating instructions. Speed monitor D / / 2014

60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application

hp uninterruptible power system r12000 xr models installation instructions

QUALITY POWER SOLUTIONS BACKED UP BY REAL-WORLD ENGINEERING EXPERIENCE

RE-82 RACK MOUNT DIMMER OWNERS MANUAL. 8 X 2400Watts. Revision /29/2007

RCD Fused Connection Unit Model: RCD10WPV. RCD Double Sockets Models: RCD05WAV, RCD06WPV, RCD07MAV, RCD08MPV. Installation & Operating Instructions

PowerLogic High Density Metering System 1-Meter Enclosure

Operating instructions. Switching amplifier DN0210 DN / / 2015

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

Operating and Installation Manual. EASYLAB Expansion modules Type EM-TRF for 230 V AC mains voltage

AC-DC Converter REC K10

BCM2 Series Branch Circuit Monitors Quick Setup Guide

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

SmartBlock I/O Module HE579MIX577/977 Isolated 4/8 Analog Inputs 2/4 Analog Outputs

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

E2A. Ordering Information. Cylindrical Proximity Sensor. Safe Mounting with Greater Sensing Distance. E2A Cylindrical Proximity Sensor 1

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

B60 Domestic Voltage Optimisation Unit

Conveyor Belt Alignment Switches from IDEM

INSTRUCTION MANUAL. SIL 3 Switch/Proximity Detector Repeater Relay Output, Termination Board Models D6032S, D6032D

ZBRN1 access point- 2 RJ V AC/DC-4 displays-5 LEDs-Eth-Modbus-wireless radio

Extension module for lighting control

ABL1REM Main. Rated power in W. Power supply output current V. <= 100 Aat 230 V AC. 2.5 Aat 240 V

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

HP UPS R/T3000 G2. Overview. Precautions. Kit contents. Installation Instructions

LED PANEL. User Manual Please read the instructions carefully before use LED-212RGB TABLE OF CONTENTS. 1. Safety Instructions

OTB1C0DM9LP. Main , length of segment <= 185 m , length of segment <= 160 m. 3.4 kohm for I8...I kohm I0...I1 5.7 kohm I6...

MAXIMA+ Series Rotary Level Indicator

GS400. Electronic Auto-Ranging DIN Panel Mounted Positioner

Test Asset Optimization Services Power Line Utilization Module (PLUM) DATA SHEET

RT4B-110V/12A RECTIFIER

Thread length (overall length) material

Model 7705 Control Module

SmartBlock I/O Module HE579MIX102 Isolated 6 Relay, 12 DC Inputs, 4 Analog Inputs

Junos WebApp Secure 5.0 Hardware Guide

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS

BS 287 DUAL CHANNEL POWER SUPPLY. User Manual. January 2017 V1.0

ILD15 HANDBOOK. Box Contents 1 x ILD15 1 x Earth Crimp Terminal 1 x A6 Deaf Logo 1 x Installation Handbook 1 x Designing an Induction Loop hb.

Specifications, Installation, and Operating Instructions

A0-10 ANALOG OUTPUT. Instruction Manual April 2001 NALOG OUTPUT

B60 Domestic Voltage Optimisation Unit. Installation Manual

Installation Job Aid for VSP 4850GTS

Electromotoric actuators Torques up to 60 Nm Running times ¹) s. ¹) Predefined by the basic unit (LMV5...)

USER MANUAL INSTALLATION MANUAL. Isolation transformers. ITR Isolation Transformer 7000 W 230V/32A

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Installation Sensing distance Connection Output configuration Operation mode NO Operation mode NC

IB IL 120 DI 1. Function. INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area. Data Sheet 5764B

Room Temperature Controller

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

LASERMET SLIMJIM LED SIGN INSTRUCTION MANUAL LEDS-SJ XXX

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

Manual Control Unit GFC 16

Product and functional description

PM Series Power Meter

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

CONTROL PANEL WIRING SPECIFICATIONS

G5 PDU Installation Guide

IF-80x Outdoor Terminal

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

MAXIMA + Series ROTARY LEVEL CONTROL

E2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

PanelView 600 Terminals

Manual Control Unit GFC 32

Quick Start Guide and Health and Safety Information

ABB Drives. User s Manual I/O Module Adapter AIMA-01

Installation manual for for Schleifenbauer DPM3

Operating instructions. Standstill monitor A / / 2011

OTB1E0DM9LP I/O distributed module OTB - Ethernet TCP/IP m

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

ABL8BBU24200 battery control module V DC - 24 V - 20 A - for regulated SMPS

RZ5/RZ5D/RZ6 Processor. Operator s Manual

Installation and commissioning guide SmartLink PSD Power Supply Module (DC)

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

ETC Installation Guide

Demonstration Case BENNING DB 1

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

WBS HARDWIRED SERIES 4-60KVA MAINTENANCE BYPASS SWITCH

RТTH DUAL ROOM SWITCH

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

RTU500 series Data Sheet Power Supply CP-E 24/2.5

BS 181 SINGLE CHANNEL POWER SUPPLY USER MANUAL

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!

EC Series. Safety Guide

ILUMEN PID SOLUTION INDOOR OUTDOOR ILUMEN PIDBOX MINI INSTALLATION MANUAL. Ilumen PIDbox mini Version 1.5

Product and functional description

INSTRUCTION MANUAL. SIL 3 Relay Output Module DIN-Rail Models D1092S-069, D1092D-069 D1092S D1092D-069

Switched Mode Power Supply Operating manual PAP800

PowerCore Model TEC-10 Installation Manual

Transcription:

Safegard V4 Panel Installation Datasheet ELECTROSTATIC SENSITIVE DEVICE This product forms part of a life safety system. Failure to correctly store, handle, install and maintain the product will directly put at risk the lives of the occupants and the fabric of the building. Always READ this document BEFORE INSTALLATION. Please Retain for future reference. - PAGE 1 -

Mounting Only use the mounting brackets provided. Mounting Diagram The height of the unit above the floor level should be chosen so that the centre of the PC is just above normal eye level (approximately 1.5 m). The unit should be placed in a naturally vented area and this area should be considered fire safe and free from high levels of shock and vibration. Conditions should not arise which may allow the temperature in this area to reach or exceed the operating temperature of the unit. Do not locate the unit where access to its internal components and connections are restricted. Flush mounted panel option available. WARNING: Observe all health and safety procedures when lifting or moving this equipment. Preparation Only trained and qualified personnel should be allowed to install, replace or service this equipment. Installation should be in accordance with the relevant local safety standards. The mains wiring should comply with IEC 60227 or IEC 60245. A switch or circuit breaker should be included as part of the installation. The switch or circuit breaker should meet the relevant requirements of IEC 60947-1 and IEC 60947-3. The switch or circuit breaker should be in close proximity to the equipment and be within easy reach of the operator. The switch or circuit breaker should be marked as the disconnecting device for the equipment and should disconnect both poles of the supply. The switch or circuit breaker should not interrupt the protected earth conductor. Panel sizes & weights There are 5 panel sizes as standard H x W x D(mm) Approx weight Handling Size 1: 500 x 500 x 210 15 kg One person Size 2: 600 x 600 x 210 25 kg Two people Size 3: 800 x 800 x 210 40 kg Three people Size 4: 1000 x 800 x 300 55 kg Forktruck Size 5: 1200 x 800 x 300 65 kg Forktruck Wire mains supply feed in right hand side of top gland plate UPS Batteries Control panels fitted with a Phoenix Contact battery are supplied with battery fuses removed and cable tied to the battery for installation prior to power being turned on. These batteries leave Safegard fully charged. Should the panel be placed in storage for more than 4 months, it is recommended that the power be applied to the panel to allow the battery charge to be maintained. This equipment MUST be earthed. - PAGE 2 -

Installation Wiring Diagram 1 (Mains supply feed) 1. Disconnect the local supply before commencing any work on this equipment. 2. Wire the mains supply feed in accordance with wiring diagram 1. When complete, secure the mains cable using the cable gland. 3. Wire the incoming mains cable in accordance with wiring diagram 2. 4. Wire the incoming live (brown) and neutral (blue) wires to the mains terminal. 5. Connect the incoming earth (green and yellow) wire to the protected earth stud using a ring connector. This connector must be fitted and secured independently using the shake proof washer and nut provided. The floating panel earth wire should be connected on top of this using the additional shake proof washer and nut provided. GLAND CIRCUIT BREAKER OR SWITCH 6. The mains cable should be fitted in such a manner that, should the cable be subject to strain, the earth wire would be the last wire to break loose. 7. Finally, the mains wires should be tie wrapped to prevent slippage. Once wiring is complete, apply power to the equipment. Wiring Diagram 2 (Incoming mains cable) PROTECTIVE EARTH STUD GLAND E L N - PAGE 3 -

Inputs Input Wiring The volt free input terminals are numbered 201, 202, 203, etc. Wire the first input as shown across and repeat for subsequent inputs. Please note that inputs are not optically isolated. The input cable diameter should be 1mm 2 or 1.5mm 2 201 202 Limit cable runs to 100m and avoid running input cables near sources of mains or noisy environments. Outputs The relay output terminals are numbered 401, 402, 403, etc. Wire the first output as shown across and repeat for subsequent outputs. It is the user s responsibility to ensure the switched equipment is adequately protected. As a precautionary measure, a standard 1AT fuse is used to protect each output irrespective of it switching 24 V or mains. The value of this fuse may have to be modified in accordance with the user s requirements. The user is responsible for the replacement policies of any fuses whose value deviates from the standard 1 AT fuse supplied. The non-fused terminals 401, 403, 405, etc. should be regarded as the output terminals to the switched equipment. The fused terminals 402, 404, 406, etc. should be regarded as the input terminals from the switched equipment. The two terminal wires from each output should be tie wrapped together to prevent slippage. Maintenance Mains terminal fuse replacements: Panel sizes 1-3: 1AT 250 VAC Panel sizes 4-5: 2AT 250 VAC Output terminal fuse replacement: 1AT 250 VAC Suggested replacement: Bussman S504 series. INPut terminal Number INPUT 1 201, 202 INPUT 2 203, 204 ETC. Output Wiring External switched equipment 401 402 1 AT OUTPUT Feed (Fused) Terminal Return Terminal Output 1 402 401 Output 2 404 403 ETC. - PAGE 4 -

Panel Network Wiring 101 102 To Smoke Fire Damper Interfaces (SFDI s) or any other field devices Network Cable Rules: NO EQUIVALENTS NO ALTERNATIVES 1. All devices to be wired in a daisy chain i.e. in and out. 2. Standard network rules apply i.e. network cables must NOT be run alongside any high voltage and/or high frequency sources. If SFDI s are wired in areas of high voltage such as plant rooms/lift lobbies, network cable must be installed in dedicated conduit. 3. Network cable types must NOT be mixed on a cable segment. If extended a network cable it must be of the same type as the original cable. NETWORK terminal Number NETWORK 1 101, 102 NETWORK 2 103, 104 ETC. The network terminals are numbered 101, 102... these free topology networks are internally terminated. Wire the first network as shown and repeat for subsequent networks. Non Fire Rated Cable: Belden 8471NH, 2 Core, 1.3mm 2 conductor size Fire Rated Cable Options: Prysmian (Pirelli) FP200 Gold, 2 Core, 1.5mm 2 Prysmian (Pirelli) FP200 Plus, 2 Core, 1.5mm 2 Firetuf FT30, 2 Core, 1.5mm 2 conductor size Firetuf FT120, 2 Core, 1.5mm 2 conductor size 4. Maximum TOTAL wire length for cable segment = 500M 5. Maximum distance SFDI to SFDI or any other field device = 400M 6. If > 60 SFDI s or any other field devices and/or a cable segment length of > 500M a network extender must be used. 7. SFDI s must be wired on a dedicated power supply. Warning: The Safegard V4 System is a life safety smoke/fire damper control & monitoring system and the network cables we supply are fundamental to the stable and reliable operation of the system. There are no alternatives or equivalents acceptable. Use of any other cables will void all warranties and such cables will have to be replaced to allow stable and reliable operation. Refer to SFDI installation instructions and datasheet. Field Network Wiring - PAGE 5 -

Specification Supply Input voltage (230 ± 23) V AC, 50 Hz Environmental Operating temperature 0 C to 40 C Maximum power consumption 750 VA Storage temperature -15 C to 45 C Inputs Contact type Sense current Outputs Contact type Maximum switched load non-isolated dry contacts 15 ma at 12 V DC SPCO mechanical relay contacts 1 A at 230 V AC 1 A at 30 V DC Humidity Maximum altitude Conformance 80 % RH to 31 C decreasing linearly to 50 % RH at 40 C 2000 m emc en 61326-1: 2006 +Corr 1 +Corr 2 en 50121-4: 2006 (EN harmonized standard for railway environments and London underground) LVd en 61010-1: 2010 +Corr 1: 2011 Complies with European standards WARNING: The responsible body shall be made aware that, if the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Safegard Systems Limited 2007. The information herein is subject to change without notice. We do not assume any liability arising out of the use of this product. Purchase of goods and services is subject to Safegard Systems standard terms and conditions. Product warranty 12 months from date of delivery. Systems House, Unit 33, Southern Cross Business Park, Bray, Co. Wicklow T: +353 1 2761600 F: +353 1 2761611 E: info@safegard.ie www.safegard.ie - PAGE 6 -