Liquipoint T FTW 31, FTW 32 Level limit switch for multiple point detection in conductive liquids

Similar documents
Liquipoint T FTW31, FTW32

4 â Active barrier RN221N with optional HART diagnosis. Technical Information

Minicap FTC260, FTC262

Assembly. Function 41

Signal conditioning instruments for level switches. Conductive VEGATOR 256C VEGATOR 532 VEGATOR 631. Product Information

Liquiphant T FTL20. Technical Information. Level limit switch for liquids

Assembly. 1 Compact version with valve plug 2 Short tube version with cable 3 Compact version with M12 plug 4 Short tube version with M12 plug

Functional safety manual Liquiphant M/S with FEL58 and Nivotester FTL325N

PHOENIX CONTACT - 12/2007

PI-EX-ME-2NAM/COC-24VDC

PI-EX-ME-2NAM/COC-120VAC

TECHNICAL INFORMATION Vibracon LVL-B1, LVL-B2

Level. Conductive. Level detection. Overview Page 142 VEGAKON series 60 Page 144 EL 1 EL 8 Page 148 Limit switches VEGATOR Page 157

Technical Information Minicap FTC260, FTC262

Technical Information Liquipoint FTW23

Soliphant M FTM50, FTM51, FTM52

Technical Information Promonitor NRF560

Contact protection relay

Assembly. max Example: 2-wire connection IH More connection types see section electrical connections. Auxiliary voltage.

Capacitive Limit Detection minicap FTC 260, FTC 262

Assembly. Front view. LED yellow: Relay output. LED red: LB/SC Power Rail

DMP 333 DMP 333. Industrial Pressure Transmitter For High Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial

FOR LIQUIDS AND SOLIDS

JUMO ecotrans ph 03 Microprocessor transmitter/ switching device for ph/redox voltage and temperature

Intrinsically Safe Barriers

SYSTEM COMPONENTS SYSTEM COMPONENTS MODULES

LS 6600 Technical Datasheet

Technical Information RIA15

LS 5000 series Vibration Level Switch for liquids

WG 20. The WG 20 achieves an extraordinarily. accuracy for hazardous-area. applications.

Inductive sensor BI5-EM18-Y1X-H1141

NIVOSWITCH VIBRATING FORK LEVEL SWITCHES

Technical Information RIA16

24 V DC typ. 0,65 W. Liquid level with conductive probes (type SK1, SK5) Resistance measurement E1-E0, E2-E0, E3-E0, E4-E0

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

Capacitance level switches LS 210 LS 220

Operating Instructions. Intrinsically Safe Isolation Relay for Switches Model: REL manual_rel-6_0505

Operating Instruction

Model Number Structure

Inductive sensor NI3-EG08K-Y1-H1341

Model Number Structure

Indicating Digital Transmitter for Differential Pressure and Flow. Media 6 with LCD Media 6 with LED

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

Assembly. Front view. LED yellow/red: Status output Ι/ Fault signal Function. Switch Power Rail

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

Flow Measurement SITRANS F M. Transmitter MAG 6000 I/6000 I Ex de. 3/46 Siemens FI

Inductive sensor BI1.5-EG08-Y1-H1341

Easy Analog RNB130. Technical Information. Primary switched-mode power supply

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

Temperature Switches

Inductive sensor BI1.5-EG08-Y1-H1341

Magnetic field sensor Magnetic-inductive Proximity Sensor BIM-M12E-Y1X

Zelio Control-modular measurement and control relays 1

Inductive dual sensor For rotary actuators NI4-DSU35TC-2Y1X2/S933

Operating Instructions VEGAMET 381

JUMO PINOS L01. Calorimetric flow sensor. Brief description. Special features. Customer benefits. Data Sheet

Technical Information Liquipoint FTW33

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

Magnetic Field Sensor Magnetic-inductive Proximity Sensor BIM-M12E-Y1X-H1141

Series 3730 Electropneumatic Positioner Type

Operating Instructions

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

Operating Instructions for Digital Thermometers. Model: DTM

Inductive sensor For rotary actuators NI4-DSU35TC-2Y1X2/S933

External level devices for conductive point level switch

Mobrey Squitch 2. Ultrasonic Liquid Level Switch. Product Data Sheet December 2014 IP207, Rev DA

Article no. BWU2045: AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input 1.23 NC

Operating instructions. Standstill monitor A / / 2011

TECHNICAL INFORMATION Vibracon LVL-A7

Inductive sensor Dual sensors with extended temperature range NI4-DSU35TC-2Y1X2/S97

Operating Instructions Soliswitch FTE20

02/11/2015

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Termination Board. HiCTB08-SCT-44C-SC-RA. Features. Assembly. Function. Connection. 24 V DC (I), 24 V DC (II), Fault. Zone 0, 1, 2 Div.

QUINT-PS/ 1AC/24DC/ 5

Limit switches for Dial Thermometers and Pressure gauges

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

Flow Measurement SITRANS F US Inline

Flow Measurement SITRANS F US Inline

Solid State Remote Power Controller E /627

INSTRUCTION MANUAL. SIL 3 Relay Output Module DIN-Rail Models D1092S-069, D1092D-069 D1092S D1092D-069

Assembly. Front view. LED yellow: Relay output I. LED yellow: Relay output II

MINI MCR-SL-PT100-UI(-SP)(-NC)

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

MACX MCR-EX-SL-NAM-R(-SP)

T M. IRDH375 Series. Digital Ground Fault Monitor / Ground Detector For Ungrounded (Floating) AC/DC Systems. Technical Bulletin NAE / 09.

Signal processor MS96 for flow sensors MS96-11EX0-R/230VAC

Pressure transmitter for highest pressure applications Up to 217,500 psi (15,000 bar) Model HP-2

Thread length (overall length) material

Linear Position Transducer HLT 1000-R2

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

Indication and Adjustment Product Information VEGADIS 61. Level Switching Pressure

Electronic timer CT-EAS ON-delayed and OFF-delayed with 1 c/o contact Data sheet

Series 3730 Type Electropneumatic Positioner

Process display RIA 251. Digital loop powered display for ma current loops. Application areas. Plant and machine construction.

EMD-SL-LL-230. Electronic monitoring relay for level monitoring of conductive liquids. INTERFACE Data sheet _en_04. 1 Description.

Inductive sensor For rotary actuators NI4-DSU35TC-2Y1X2

4 mm. 8 mm. Proximity Sensor. Sensing head Sensing distance Output configuration Part Number M18 Shielded 4 mm DC 3-wire PNP-NO E2EZ-X4B1 M30

Inductive Cylinder Position Sensors

Transcription:

Technical Information Level limit switch for multiple point detection in conductive liquids Applications The Liquipoint T sensors are used in conductive liquids (down to 0 µs/cm) for determining level limits. Depending on the number of measuring points (up to five rods or cables), the measuring sensors provide overspill protection, dry running protection, two-point control of pumps, or multiple point detection. All points can be implemented using a single process connection. Your benefits Detect up to five level points with one unit Two-point control and additional maximum and minimum detection Select either rod or cable version for optimal adaptation to the application Flexible instrumentation: - with built-in electronic insert, either transistor or relay output for or 3 rod/cable probes - for connection to a separate transmitter power supply No calibration required, standard setting for the most common conductive liquids No moving parts in the tank: - long service life - reliable operation with no wear or blockages WHG overspill approval Four measuring ranges can be set; 00 Ω, kω, 0 kω, or 00 kω Cost-effective probe for conductive liquids Electronic inserts for: - NAMUR output - Relay output - Transistor output (PNP) TI 375F/4/ae/08.04

Table of contents Function and system design..................... 3 Measuring principle................................... 3 Measuring system..................................... 3 Input...................................... 4 Measured variable.................................... 4 Measuring range (application)............................ 4 Input signal......................................... 5 Output..................................... 5 Electronic insert FEW 5 (DC-PNP)....................... 5 Electronic insert FEW 54 (relay).......................... 6 Electronic insert FEW 58 (NAMUR)....................... 7 Cable monitoring..................................... 8 Power supply................................ 8 Electrical connection (wiring diagrams)..................... 8 Cable entry........................................ Cable specifications.................................. Certificates and approvals..................... 0 CE mark.......................................... 0 Overspill protection.................................. 0 Other standards and guidelines.......................... 0 Ex-approvals....................................... 0 Type of protection................................... 0 Ordering information......................... Liquipoint FTW 3.................................. Liquipoint FTW 3.................................. Accessories................................ 3 Liquipoint T....................................... 3 Supplementary Documentation................. 3 Operating Instructions................................ 3 Certificates........................................ 3 Accuracy with built-in electronic insert........... Reference operating conditions.......................... Measuring error..................................... Repeatability........................................ Hysteresis.......................................... Switch-on delay.................................... Influence of ambient temperature........................ Installation conditions........................ Installation instructions................................ Environment............................... 4 Ambient temperature range............................ 4 Storage temperature.................................. 4 Climate class....................................... 4 Degree of protection.................................. 4 Shock resistance..................................... 4 Vibration resistance (at min. rod length)................... 4 Electromagnetic compatibility........................... 4 Process conditions........................... 4 Medium temperature limits............................ 4 Conductivity....................................... 4 Limiting medium pressure range........................ 4 Mechanical construction...................... 5 Design, dimensions.................................. 5 Weight............................................ 7 Material........................................... 7 Fitted electrodes..................................... 7 Human interface............................ 9 Operating elements.................................. 9 Display elements.................................... 9 Endress+Hauser

Function and system design Measuring principle An alternating voltage exists between the rod probes in an empty tank. As soon as the conductive liquid in the tank creates a connection between the ground probe rod and, for example, the maximum probe rod, a measurable current flows and the Liquipoint T switches. With level limit detection, the Liquipoint T switches back as soon as the liquid clears the maximum probe. With two-point control, the Liquipoint T does not switch back until the and MIN probe is cleared. Using alternating voltage prevents corrosion of the probe rods and electrolytic destruction of the product. The material used for the tank walls is not important for measurement because the system is designed as a closed potential-free circuit between the probe rods and the electronics. There is absolutely no danger if the probe rods are touched during operation. Measuring system Probes with integrated electronic insert (compact-instrument version) The measuring system consists of: FTW 3, FTW 3 with two/three rods or cables and an electronic insert Control units, switches or signal transmitters, e.g. process control systems PLC, relays, etc. E X FTW 3 - points - 3 rods Nonhazardous Area s FTW 3 - points - 3 cables s Independent of the tank material L00-FTW3xxxx-4-05-xx-en-00! Note! The compact-instrument version with three probes or rods is always used in s mode. Endress+Hauser 3

FTW 35 FTW 35 FTW 35 FTW 35 FTW 35 FTW 35 FTW 35 FTW 35 Probes without integrated electronic insert (separate-instrument version) for one or two point detection respectively The measuring system consists of: FTW 3, FTW 3 with two/three rods or cables Nivotester FTW 35 or FTW 470 Z Control units, switches or signal transmitters, e.g. process control systems PLC, relays, etc. FTW 3/3 - points - 3 rods/cables FTW 35 or FTW 470 Z FTW470Z FTW 3/3 3 points 3 rods/cables FTW 35 or FTW 470 Z FTW470Z FTW470Z Switch points dependent on the tank material L00-FTW3xxxx-4-05-xx-en-00 Probes without integrated electronic insert for multiple point detection The measuring system consists of: FTW 3, FTW 3 with five rods or cables Two Nivotester FTW 35 or FTW 470 Z Control units, switches or signal transmitters, e.g. process control systems PLC, relays, etc. FTW 3/3 4 points 5 rods/cables FTW 35 or FTW 470 Z FTW470Z FTW470Z FTW 3/3 5 points 5 rods/cables FTW 35 or FTW 470 Z FTW470Z FTW470Z FTW470Z Switch points dependent on the tank material L00-FTW3xxxx-4-05-xx-en-003 Input Measured variable Measuring range (application) Resistance change between two conductors caused by the presence or absence of a conductive product. The measuring range is dependent on the mounting location of the probes. Rod probes can have a max. length of 60" (4000 mm) and cable probes up to 50 feet (5 m). 4 Endress+Hauser

Input signal Probes covered => a measurable current is flowing between the probes. Probes uncovered => there is no measurable current flowing between the probes. Output Electronic insert FEW 5 (DC- PNP) Output signal Three-wire direct current version Preferred in conjunction with programmable logic controllers (PLC). Positive signal at the switch output of the electronics (PNP). The output is blocked after the level limit is reached. Fail-safe mode Switch point Output signal Red Max. * * 3 L+ I L 3 * * 4 < 00 µa 3 Min. L+ I L 3 MIN + < 00 µa 3 * = load current (connected); * residual current (disconnected); *3 LED not lit; *4 LED lit See also Electrical connection on page 8. L00-FTW3xxxx-5-05-xx-en-00 If the probe is covered and the red LED flashes continuously, the next more sensitive measuring range has to be set. This ensures a safe switch point even if the conductivity of the medium varies slightly. Fail-safe mode Selecting the correct fail-safe mode ensures that the output always runs in quiescent current fail-safe. Maximum fail-safe: the output voltage is 0 V if the switch point is exceeded (probe covered), a fault occurs or the power supply fails. Minimum fail-safe: the output voltage is 0 V if the switch point is undershot (probe uncovered), a fault occurs or the power supply fails. Switching delay A switching delay of.0 s can be activated or deactivated via a DIL switch. If the switching delay is set to 0 s, the device switches after approx. 0.3 s. Measuring ranges A total of four measuring ranges (00 Ω; kω; 0 kω; 00 kω) can be set via two DIL switches (SENS). The setting on delivery is 00 kω. s MIN 0s L00-FTW3xxxx-5-05-xx-xx-00 Endress+Hauser 5

Signal on alarm In the event of a power failure or a damaged probe: < 00 µa Load The load is switched via a transistor (PNP). Cycled overload and short-circuit protection, continuous 00 ma (short-circuit proof). Residual voltage at transistor at I max <.9 V Electronic insert FEW 54 (relay) Output signal AC/DC connection with relay output When connecting a device with high inductance, a spark barrier must be fitted to protect the relay contact. A fine-wire fuse (load-dependent) protects the relay contact in the event of a short-circuit. Both relay contacts switch simultaneously. Fail-safe mode Switch point Output signal Red * * 3 Max. 3 4 5 * 6 7 8 * 4 3 4 5 6 7 8 Min. 3 4 5 6 7 8 MIN 3 4 5 6 7 8 * = relay energized; * relay de-energized; *3 LED not lit; *4 LED lit See also Electrical connection on page 9. L00-FTW3xxxx-5-05-xx-en-00 If the probe is covered and the red LED flashes continuously, the next more sensitive measuring range has to be set. This ensures a safe switch point even if the conductivity of the medium varies slightly. Fail-safe mode Selecting the correct fail-safe mode ensures that the relay always runs in quiescent current fail-safe. Maximum fail-safe: the relay de-energizes when the switch point is exceeded (probe covered), a fault occurs or the power supply fails. Minimum fail-safe: the relay de-energizes when the switch point is undershot (probe uncovered), a fault occurs or the power supply fails. Measuring ranges A total of four measuring ranges (00 Ω; kω; 0 kω; 00 kω) can be set via two DIL switches (SENS). The setting on delivery is 00 kω. s MIN 0s L00-FTW3xxxx-5-05-xx-xx-00 6 Endress+Hauser

Switching delay A switching delay of.0 s can be activated or deactivated via a DIL switch. If the switching delay is set to 0 s, the device switches after approx. 0.3 s. Signal on alarm Output signal in the event of a power failure or a damaged probe: relay de-energized. Load Loads are switched via potential-free change-over contacts. I~ max. 4 A, U~ max. 53 V; P~ max. 000 VA, cos ϕ =, P~ max. 700 VA, cos ϕ > 0.7; I max. 4 A to 30 V, I max. 0. A to 50 V. When connecting a functional extra-low voltage circuit with double insulation in accordance with IEC 00: the sum of the relay output and power supply voltages is max. 300 V. Galvanic isolation All input channels, output channels and relay contacts are galvanically isolated from each other. Electronic insert FEW 58 (NAMUR) Output signal For connecting to isolating amplifiers acc. to NAMUR (IEC 60947-5-6) Output signal jump from high to low current on limit (H-L-edge). Fail-safe circuit Level Output signal LEDs gn ye = lit = flashes = unlit Fail-safe circuit Max. Min. Level Output signal LEDs gn. to + 6.5 ma 0.4 to +.0 ma. to + 6.5 ma 0.4 to +.0 ma ye L00-FTL5xxxx-07-05- xx-xx-00 L00-FTW3xxxx-04-05-xx-xx-006 Fail-safe mode Selecting the correct fail-safe mode ensures that the relay always runs in quiescent current fail-safe. Maximum fail-safe: the output signal is <.0 ma when the switch point is exceeded (probe covered), a fault occurs or the power supply fails. Minimum fail-safe: the output signal is <.0 ma when the switch point is undershot (probe uncovered), a fault occurs or the power supply fails. Measuring ranges A total of four measuring ranges (00 Ω; kω; 0 kω; 00 kω) can be set via two DIL switches (SENS). The setting on delivery is 00 kω. Endress+Hauser 7

s MIN 0s L00-FTW3xxxx-5-05-xx-xx-00 Cable monitoring! Note! Switching delay A switching delay of.0 s can be activated or deactivated via a DIL switch. If the switching delay is set to 0 s, the device switches after approx. 0.3 s. Load Refere to "Technical Data" date sheet of the connected isolating amplifier acc. to NAMUR (IEC 60947-5-6) For probes without an electronic insert, an additional printed circuit board must be installed in the housing, which enables cable monitoring. It is always switched or connected between rod/cable and. When using switching units (transmitters) that do not support cable monitoring, these must be removed. Power supply Electrical connection (wiring diagrams) Compact instrumentation with FEW 5 Transistor circuit for load The load connected to terminal 3 is switched by a transistor, contactless and therefore without bouncing. In normal switching status, terminal 3 has a positive signal. The transistor is blocked in the event of a level alarm or a power failure. Protection against voltage peaks When connecting a device with high inductance, always connect a voltage limiter. FEW 5 M 3 (+) F R L+ L Power supply Connecting the FEW 5 electronic insert. L00-FTW3xxxx-04-05-xx-en-00 F: Fine-wire fuse 500 ma, semi-time lag M: Ground connection to earth ground Power supply (FEW 5) Supply voltage: V = 0.8 V to 45 V Load connection: open collector; PNP Switching voltage: max. 45 V Connected load, continuous: max. 00 ma Protected against reverse polarity 8 Endress+Hauser

Power consumption P <. W Current consumption I < 5 ma (without load) Compact instrumentation with FEW 54 Relay contact circuit for load The connected load is switched via potential-free relay contacts (change-over contact). In the event of a level alarm or a power failure, the relay contacts break the connections between terminals 3 and 4 and terminals 6 and 7. The relays always switch simultaneously. Protection against voltage peaks and short-circuits When connecting a device with high inductance, fit a spark barrier to protect the relay contact. A fine-wire fuse (load-dependent) can protect the relay contact in the event of a short-circuit. FEW 54 M 3 4 5 6 7 8 F F F L + N GND NO C NC NO C NC Power supply Potential-free relay contacts Vessel Connecting the FEW 54 electronic insert. L00-FTW3xxxx-04-05-xx-en-00 F : Fine-wire fuse 500 ma, semi-time lag F : Fine-wire fuse to protect the relay contact, load-dependent M: Ground connection to earth ground (GND) Power supply (FEW 54) Supply voltage: V = 0 to 55 VDC or V = 0 V to 53 VAC, 50/60 Hz Peak inrush current: max. A, max. 400 µs Output: two potential-free change-over contacts Contact load capacity: V max. 53 VAC, I max. 4 A, V = 30 VAC/4 A; 50 VAC/ 0. A Power consumption P <.0 W Current consumption 60 ma Compact instrumentation with FEW 58 To be used with isolating amplifiers acc. to NAMUR (IEC 60947-5-6) Output signal jump from high to low current on limit (H-L-edge). Signal transmission on a two-wire line: H-L-edge. to 6.5 ma / 0.4 to.0 ma When using a multiplex the cycle time must be set to a minimum of s. FEL 58 E X Hazardous area I Nonhazardous area EX + IEC 60947-5-6 (NAMUR) Connecting the FEW 58 electronic insert. L00-FTW3xxxx-04-05-xx-en-005 Endress+Hauser 9

Power supply (FEW 58) Refere to "Technical Data" date sheet of the connected isolating amplifier acc. to NAMUR (IEC 60947-5-6) Signal on alarm Output signal with damaged sensor: <.0 ma Separate instrumentation for two-rod or two-cable probes with cable monitoring 7 9 FTW 35 7 9 CH or CH d4 z4 d z FTW 470 Z d4 z4 d z CH or CH * Max * Max * Printed circuit board for cable monitoring The power supply and evaluation are provided by switching units, e.g. Nivotester FTW 35 or FTW 470 Z L00-FTW3xxxx-04-05-xx-en-003 Separate instrumentation for three-rod or three-cable probes with cable monitoring 7 8 9 FTW 35 7 8 9 CH d4 b d FTW 470 Z d4 b d CH CH z4 b4 z z4 b4 z CH * Min Max * Min Max 3 3 * Printed circuit board for cable monitoring The power supply and evaluation are provided by switching units, e.g. Nivotester FTW 35 or FTW 470 Z L00-FTW3xxxx-04-05-xx-xx-00 0 Endress+Hauser

7 8 9 7 8 9 Separate instrumentation for five-rod or five-cable probes with cable monitoring 0 4 5 6 4 5 6 Master (M) / Slave (S) 7 9 9 8 8 0 7 9 9 8 8 FTW 35 * Max off on Min FTW 35 * Max off on Min 7 (M) 4 5 3 4 5 3 (S) 7 * Printed circuit board for cable monitoring The power supply and evaluation are provided by switching units, e.g. Nivotester FTW 35 or FTW 470 Z L00-FTW3xxxx-04-05-xx-en-004 Cable entry M 0x.5 Degree of protection: NEMA 4 (IP66) Quantity in F4 housing: (separate-instrument version) Quantity in F6 housing: (compact-instrument version) NPT /" Quantity in F4 housing: (separate-instrument version) Quantity in F6 housing: (compact-instrument version) Conductor cross-section (including wire end sleeve): 0." (.5 mm) Cable specifications Use a commercially available cable (5 Ω per wire). Accuracy with built-in electronic insert Reference operating conditions Measuring error Repeatability Hysteresis Ambient temperature: 73 F (3 C) Medium temperature: 73 F (3 C) Medium viscosity: medium must release the probe again (drain off). Medium pressure p e : 0 psi (0 bar) bar Probe installation: vertically from above ± 0 % at 00 Ω - 00 kω ± 5 % at kω - 0 kω ± 5 % at 00 Ω - 00 k ± % at k - 0 k 0% for the probe, in reference to the switch point. s function deactivated. Endress+Hauser

Switch-on delay Influence of ambient temperature Installation instructions < 3 s < 0.05 %/K Installation conditions Mounting location The rod and cable probes are mounted predominantly in tanks made of plastic or metal. Piping (partially filled) Two-rod probes can be used in piping as, for example, dry running protection for pumps. L00-FTW3xxxx--05-xx-xx-00 Orientation Rod probes, dimensions in inches (mm) Level limit detection for standard applications in tanks made of plastic or metal. a. b. c. 7.87 (00) d. L00-FTW3xxxx--05-xx-xx-00 a. Vertical mounting, minimum detection; Probe length set to the level limit required; Rods must not come into contact with the tank. b. Vertical mounting, maximum detection; Probe length set to the level limit required c. Lateral mounting, maximum detection; Maximum probe length 8" (00 mm), only applies to two-rod probes. d. Lateral mounting, minimum detection; Maximum probe length 8" (00 mm), only applies to two-rod probes. Endress+Hauser

Cable probes, dimensions in inches (mm) Level limit detection for standard applications in tanks made of plastic or metal. a. b. 0 to590 (50 to 5,000) a. Vertical mounting, minimum detection; Cable length set to the level limit required; Cable ends must not come into contact with the tank b. Vertical mounting, maximum detection; Cable length set to the level limit required L00-FTW3xxxx--05-xx-xx-003 Example applications Level limit detection (standard applications) MIN MIN ) ) Two-point control ( s) e.g. pump control L00-FTW3xxxx-5-05-xx-xx-00 Level limit detection (standard applications) MIN Level limit detection (), maximum and minimum detection for compact-instrument devices only possible with s. L00-FTW3xxxx-5-05-xx-xx-003 Endress+Hauser 3

Environment Ambient temperature range Storage temperature Non-hazardous area -40 to +58 F ( 40 to 70 C) -40 to +40 F ( 40 to 60 C), for FEW 58 NAMUR -40 to +76 F ( 40 to 80 C) Climate class Tropicalized as per DIN EEC 68, part -38 Degree of protection Shock resistance Vibration resistance (at min. rod length) Electromagnetic compatibility NEMA 4 (IP66) Practical test DIN 60068--64 / IEC 68--64: 0 to 000 Hz, (m/s ) /Hz Interference Emission to EN 636, Electrical Equipment Class B Interference Immunity to EN 636, Annex A (Industrial) Use for separte-instrumented probes a shielded cable between the probe and the switching unit. For installation instructions for shielded cables and general instructions for EMC inspection conditions of E+H devices, see also TI 4F. Process conditions Medium temperature limits Permissible ambient temperature T at the housing as a function of the measuring material temperature T in the vessel: T F ( C) 58 (70) T FEW 5, FEW 54 40 (60) FEW 58 (NAMUR) (50) 04 (40) 86 (30) T 68 (0) -40 (-40) 50 (0) 50 (0) 3 - -4 4 (0) (-30) (-0) (-0) 4 (-0) -4 (-0) 68 (0) 86 (30) 04 (40) (50) 40 (60) 58 76 (70) (80) 94 (90) (00) T F ( C) - (-30) -40 (-40)! Note! For separately instrumented devices (without FEW 5x) there are no restrictions in the indicated temperature range. Conductivity 0 µs Limiting medium pressure range -4.5 to 45 psi ( to 0 bar) 4 Endress+Hauser

Mechanical construction Design, dimensions Rod and cable version with G /" (compact-instrument version with electronic insert) FTW 3 ø3.35 (85) max..99 (76) FTW 3 ø3.35 (85) max..99 (76) 5.7 (45) 5.7 (45) 0.87 () 0.87 () AF 55 G½ ø0.0 (5) 0.94 (4).46 (37) Probe length L 4 to 60 (00 to 4000) AF 55 G½ ø0.0 (.5).46 (37) Probe length L 0 to590 (50 to 5,000) ø0.6 (4) 3.94 (00) ø0.40 (0) L00-FTW3xxxx-06-05-xx-en-00 Rod and cable version with G /" (separate-instrument version without electronic insert) FTW 3 ø.60 (66) max..48 (63) FTW 3 ø.60 (66) max..48 (63) 0.87 ().5 (64) 0.87 ().5 (64) AF 55 G½ ø0.0 (5) 0.94 (4).46 (37) AF 55 G½.46 (37) Probe length L ø0.0 4 to 60 (.5) (00 to 4000) Probe length L 0 to590 (50 to 5,000) ø0.6 (4) 3.94 (00) ø0.40 (0) L00-FTW3xxxx-06-05-xx-en-00 Endress+Hauser 5

Rod and cable version with NPT -/" (compact-instrument version with electronic insert) FTW 3 ø3.35 (85) max..99 (76) FTW 3 ø3.35 (85) max..99 (76) 6.6 (68) 6.6 (68) 0.93 (3.5) 0.93 (3.5) AF 55 -/ NPT ø0.0 (5) 0.94 (4).5 (38.5) Probe length L 4 to 60 (00 to 4000) AF 55 -/ NPT ø0.0 (.5).5 (38.5) Probe length L 0 to590 (50 to 5,000) ø0.6 (4) 3.94 (00) ø0.40 (0) L00-FTW3xxxx-06-05-xx-en-003 Rod and cable version with NPT -/" (separate-instrument version without electronic insert) FTW 3 ø.60 (66) max..5 (64) FTW 3 ø.60 (66) max..5 (64) 0.93 (3.5) 3.39 (86) 0.93 (3.5) 3.39 (86) AF 55 -/ NPT ø0.0 (5) 0.94 (4).5 (38.5) Probe length L 4 to 60 (00 to 4000) AF 55 -/ NPT.5 (38.5) ø0.0 (.5) Probe length L 0 to590 (50 to 5,000) ø0.6 (4) 3.94 (00) ø0.40 (0) L00-FTW3xxxx-06-05-xx-en-004 6 Endress+Hauser

Weight Separate-instrument version Rod, 3 ft ( m long) FTW 3 with, 3 or 5 rods; 0.9 lb,. lb,.7 lb (45 g, 530 g, 760 g) Cable, 3 ft ( m) long FTW 3 with, 3 or 5 cables; 0.8 lb, lb,.4 lb (390 g, 470 g, 640 g) Compact-instrument version Rod, 3 ft ( m) long FTW 3 with or 3 rods;.3 lb,.6 lb (600 g, 70 g) Cable, 3 ft ( m) long FTW 3 with or 3 cables;.5 lb,.8 lb (70 g, 800 g) Material Probes Rods Rod: 36L SS (.4404) Insulation: PP Cables Cable: 36Ti SS (.457) Insulation: FEP Weight: 37L SS (.4435) Housing F4 (separate-instrument version) Housing: PPS Cover: PBT F6 (compact-instrument version) Housing: PBT Cover: PBT Adapter: PBT Process connections G / -/" NPT Fitted electrodes Rod probes Compact-instrument version: or 3 rods; Separate-instrument version:, 3 or 5 rods Diameter without insulation: 0.6" (4 mm) Maximum rod length: 57" (4000 mm) Minimum rod length: 4" (00 mm) Thickness of insulation: 0.0" (0.5 mm) Length of non-insulated area (tip of rod): 0.78" (0 mm) Extraction forces (parallel probe rod): 5 lbf (000 N) Endress+Hauser 7

Cable probes Compact-instrument version: or 3 cables; Separate-instrument version:, 3 or 5 cables Diameter without insulation: 0.04" ( mm) Maximum cable length: 50 feet (5 m) Minimum cable length: 0" (50 mm) Thickness of insulation: 0.03" (0.75 mm) Weight length: 4" (00 mm), not insulated Weight diameter: 0.39" (0 mm) Extraction forces (parallel probe rod): lbf (500 N) 8 Endress+Hauser

Human interface Operating elements FEW 5, FEW 54, FEW 58 One DIL switch for min/max position One DIL switch for 0 s or s switching delay Two DIL switches for setting the measuring ranges 00 Ω, kω, 0 kω, 00 kω Display elements Separate-instrument version Dependent on the connected switching unit (e.g. FTW 35 or FTW 470 Z) Compact-instrument version FEW 5 One red light emitting diode: fault message, switching status One green light emitting diode: operation U 0.8 to 45V DC I max : 00mA 3 + - FEW5 3 3 MIN s 0s L00-FTW3xxxx-07-05-xx-xx-00 FEW 54 One red light emitting diode: fault message, switching status One green light emitting diode: operation 0 to 55V DC 0 to 53V AC L N FEW54 MIN/ SENS 0s/s 3 5 6 8 4 7 3 4 5 6 7 8 L00-FTW3xxxx-07-05-xx-xx-00 FEW 58 One yellow light emitting diode: fault message, switching status One green light emitting diode: operation Namur IEC 60947-5-6 - + FEW58 I <.0mA I >.ma MIN s 0s L00-FTW3xxxx-07-05-xx-xx-003 Endress+Hauser 9

! Note! For FEW 5, FEW 54 If the probe is covered and the red LED flashes continuously, the next more sensitive measuring range has to be set. This ensures a safe switch point even if the conductivity of the medium varies slightly. Relay rd 345 678 measuring range limit level switch point MIN Relay 345 678 rd measuring range limit MIN switch point 345 678 345 678 level L00-FTW3xxx-5-05-xx-en-00 Certificates and approvals CE mark Overspill protection Other standards and guidelines Ex-approvals The Liquipoint T meets the legal requirements of the EC directives. Endress+Hauser confirms that the device has been successfully tested by applying the CE mark. Approvals WHG Leak test (Leakage) Other standards and guidelines that were observed during the design and development of the Liquipoint T FTW 3 and FTW 3. Low voltage equipment directive (73/ 3/ EEC) DIN EN 600 part, 00 Safety regulations for electrical equipment for measurement, control and laboratory use Part : General requirements EN 636 Electrical equipment for measurement, control and laboratory use EMC requirements The Endress+Hauser sales office provides information on the currently suppliable Ex versions (ATEX EEx ia and ATEX EEx na/c(l)). All data relevant for explosion protection can be found in separate Ex documentation (see: Supplementary Documentation on page 6). This can be viewed as necessary. Type of protection [EEx ia] IIC (FEW 58) [EEx na/c(l)] IIC (FEW 5, FEW 54) 0 Endress+Hauser

Ordering information Liquipoint FTW 3 0 Certificates A B C D Y Version for non-hazardous areas Version for non-hazardous areas, WHG, Leakage detection ATEX II 3 G EEx na/c(l) IIC T6, WHG ATEX II G EEx ia IIC T6 Special version 0 Process connection and material Threaded connection G /", PPS Threaded connection NPT -/", PPS 9 Special version 30 Quantity and material of rods A rods, 36L A3 3 rods, 36L A5 5 rods, 36L Y9 Special version 40 Length of probe L, 4" to 57" (00 to 4000 mm) A mm L, probe length B inch L, probe length C 40" (000 mm) L, probe length D 80" (000 mm) L, probe length Y Special version 50 Housing and cable entry A Plastic housing IP66, M0x.5 B Plastic housing IP66, NPT /" C Plastic housing IP66, G /" Y Special version 60 Electronic insert 0 Without electronic insert FEW 5/54 retrofit FEW 5 output PNP 0.8 to 45 V DC 4 FEW 54 relay output 0 to 53 V AC, 0 to 55 V DC 8 FEW 58 output NAMUR 9 Special version 70 Additional equipment A Without additional equipment Y Special version FTW 3 complete product designation Endress+Hauser

Liquipoint FTW 3 0 Certificates A B C D Y Version for non-hazardous areas Version for non-hazardous areas, WHG, Leakage detection ATEX II 3 G EEx na/c(l) IIC T6, WHG ATEX II G EEx ia IIC T6 Special version 0 Process connection and material Threaded connection G /", PPS Threaded connection NPT /", PPS 9 Special version 30 Quantity and material of cables D cables, 36Ti SS D3 3 cables, 36Ti SS D5 5 cables, 36Ti SS Y9 Special version 40 Length of probe L, 0" to 590" (50 to 5000 mm) A mm L, probe length B inch L, probe length Y Special version 50 Housing and cable entry A Plastic housing IP66, M0x.5 B Plastic housing IP66, NPT /" C Plastic housing IP66, G /" Y Special version 60 Electronic insert 0 Without electronic insert FEW 5/54 retrofit FEW 5 output PNP 0.8 to 45 V DC 4 FEW 54 relay output 0 to 53 V AC, 0 to 55 V DC 8 FEW 58 output NAMUR 9 Special version 70 Additional equipment A Without additional equipment Y Special version FTW 3 complete product designation Endress+Hauser

Accessories Liquipoint T Lock nut G /" Hexagon, AF 60 TN 50446 Electronic insert FEW 5 Output PNP 0.8 to 45 V DC PN 5077 Electronic insert FEW 54 Output Relay, 0 to 53 V AC, 0 to 55 V DC PN 5077 Electronic insert FEW 58 Output NAMUR (IEC 60947-5-6) PN 50773 Supplementary Documentation Operating Instructions Liquipoint T: FTW 3, FTW 3 (separate-instrument version), KA 03F/00 Liquipoint T: FTW 3, FTW 3 (compact-instrument version), KA 04F/00 Certificates WHG Liquipoint T: ZE 043F/00 ATEX II 3G EEx na/c(l) IIC T6 Liquipoint T: XA 6F/00 ATEX II G EEx ia IIC T6 Liquipoint T: XA 30F/00 Endress+Hauser 3

United States Endress+Hauser, Inc. 350 Endress Place Greenwood, IN 4643 Tel. 37-535-738 Sales 888-ENDRESS Service 800-64-8737 Fax 37-535-8498 inquiry@us.endress.com www.us.endress.com Canada Endress+Hauser Canada 075 Sutton Drive Burlington, ON L7L 5Z8 Tel. 905-68-99 800-668-399 Fax 905-68-9444 www.ca.endress.com Mexico Endress+Hauser, México, S.A. de C.V. Av. Gustavo Baz No. 43 Fracc. Bosques de Echegaray Naucalpan de Juárez, C.P. 5330, Estado de México México Tel: (5) 55-537-0 Fax (5) 55-537-8 eh.mexico@mx.endress.com TI375F/4/ae/04.05 005 Endress+Hauser, Inc. 4 Endress+Hauser