Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling

Similar documents
Trane mytest Water-cooled Chiller Performance Validation What you spec is what you get *

Adaptive Frequency Drive Superior Chiller Performance

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

CGAM air-cooled scroll chiller. Highly efficient, yet extremely quiet

Designing Ultra-Efficient Building Cooling Systems

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Trane Series S CenTraVac Chillers with AdaptiSpeed Technology tons

Trane Cold Generator TM. Scroll Chillers. Comfort and Process Cooling Solutions

Trane Controls. Smart Solutions for Smart Buildings

where we are, where we could be, how we can get there. 12/14/2011

Series S CenTraVac Chillers Leading efficiency and proven reliability BEYOND EFFICIENCY. BEYOND RELIABILITY. BEYOND SUSTAINABILITY. LET S GO BEYOND.

User Guide. FreeCool : Free Cooling unit V1.1 ENGY-SVU001A-GB

Committed to Energy Efficiency

Identify the Right Applications

Achieving Operational Excellence

Energy Engineering: Tools and Trends

Retro-Commissioning Report

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

The Future. Today. YZ MAGNETIC BEARING CENTRIFUGAL CHILLER

Efficiency of Data Center cooling

APPLIED SYSTEM AWS FAMILY FOR LARGE APPLICATIONS PRODUCT LEAFLET. Capacity from 600 to 2,010kWr. Engineered for flexibility and performance

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

CGWN/CCUN indoor liquid chillers The compact AquaStream² solution

Building Re-Tuning (BRT) Lesson 4: SOI Air-Handling Unit Part II

Chiller Replacement and System Strategy. Colin Berry Account Manager

Energy Logic: Emerson Network Power. A Roadmap for Reducing Energy Consumption in the Data Center. Ross Hammond Managing Director

Next Generation DCP Optimization using MV VSDs

Silicon Valley Power Data Center Program Rebate Application

MSYS 4480 AC Systems Winter 2015

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

CLICK TO EDIT MASTER TITLE STYLE. AdvanTEC Solutions CHILLER PLANT HEALTH MANAGER

UC DAVIS THERMAL ENERGY STORAGE (TES) TANK OPTIMIZATION INVESTIGATION MATTHEW KALLERUD, DANNY NIP, MIANFENG ZHANG TTP289A JUNE 2012

HIGH DENSITY DATACOM INTEGRATED COOLING SYSTEM.

Data Centers. Powerful Solutions That Put You in Control. Energy Management Solutions. Where your energy dollars are used. 1

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

New Design Strategies for Energy Saving. Intelligent free-cooling

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

Trailblazer AGZ-E air-cooled scroll chillers

High Efficient Data Center Cooling

Air-Cooled Series R Chiller

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

CenterPoint Energy Retro-Commissioning Program Application

HVAC Energy Management System

Air-Fi wireless system Get comfortable, with industry-leading reliability and performance.

Pathfinder AWV air-cooled screw chillers

Precision Cooling for Business-Critical Continuity. Liebert HPC-S. Designed for the Efficient Cooling of Small Data Centers

DATA CENTER AIR HANDLING COOLING SOLUTIONS

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers

Waterside Economizing in Data Centers: Design and Control Considerations

Water cooled chiller plant (all-variable)

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Table of Contents. Executive Summary Site and Unit Background Chiller Chiller Appendix... 11

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

New Wisconsin Energy Code: What it Means for Me?

Energy-efficient heating, ventilation and air-conditioning Technologies for certified buildings

Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer

TWO FINANCIAL IMPACT STUDIES. Seal IT Equipment Cabinets for Significant Annual Cost Savings and Simple Payback in a Few Short Months

AIR-COOLED A (Surprisingly) Cost-Effective Alternative to Water-Cooled Chiller Plants

Date: 26th August 2017 Presented By: Pinaki Mukherjee, Sudeep Saha

2017 NEHES Fall Conference Technical Breakout Session: Deep Chiller Plant Optimization

Energy Management of the Refrigeration Systems at Zurich Airport. Burkhard Bein. Schaffhausen,

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

SUPERSAVER. Energy Efficiency Optimization Software for Freecooling Systems

What is the Carrier ChillerVu series counterflow application?

TRACE 700. Slide 1. Today, we will be talking about Airside Economizers in TRACE 700. Slide 2

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

Driving Proactive Facility Operations with Automated HVAC Diagnostics

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB

DUKE UNIVERSITY DESIGN & CONSTRUCTION STANDARDS

District Cooling Marches on in Dubai The Emirates Towers Case Study

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

that may have a direct effect on your bottom line. The question

energy solutions MEASUREMENT &VERIFICATION& ELLEN FRANCONI, ROCKY MOUNTAIN INSTITUTE,

Precision Cooling Mission Critical Air Handling Units

3300 kw, Tier 3, Chilled Water, 70,000 ft 2

Energy Action Plan 2015

Hot vs Cold Energy Efficient Data Centers. - SVLG Data Center Center Efficiency Summit

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

T66 Central Utility Building (CUB) Control System Reliability, Optimization & Demand Management

ecoenergy Innovation Initiative Research and Development Component Public Report

IBM - Energy Efficiency Recommissioning: Improving Buildings Systems Efficiency Jean-Pierre Boulianne, Pierre Lefèbvre, Yves Veilleux ICEBO 2013

Airside Economizer Comparing Different Control Strategies and Common Misconceptions

Air-Cooled Chillers. R134a. Performance Matters

Climate Technologies Investor Update

Aquaflair. Uniflair TRAC, TRAF and TRAH. Air-cooled chillers, free-cooling chillers and heat pumps with scroll compressors.

Onity Energy Management Solutions

Optimiz Chilled January 25, 2013

CHILLERS & HEAT PUMPS DYNACIAT HIGH ENERGY PERFORMANCE WITHIN OPTIMISED FOOTPRINT

Better Building Controls Through Simulation

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

Motivair MLC-SC Air-Cooled Scroll Chillers Tons

Fault Detection and Diagnostic Software

How Big Data Analytics Helps Hotels Improve Maintenance and Comfort, and Save Energy

Data Center Optimized Controls

How Green can you go?

30XAV & 30XWV. Air and water-sourced, variable-speed screw units. AquaForce with Greenspeed intelligence, Because you should not have to choose.

Transcription:

Trane Engineering News Chiller Plant Case Study: Variable-Primary Flow Series Chillers with Free Cooling CHILLER PLANT CONTROLS The challenges of producing chilled water are not the same as those a decade ago. Today, protecting the environment and preserving resources play an important role in the design, construction and operation of a chiller plant. The advancement in technology for HVAC controls applied to chilled-water production now make it possible to reduce the environmental impact and operating costs. This white paper compares the advantages of designing a series configuration using variableprimary flow (VPF), free cooling and efficient sequence of operation through a comparison with a high-efficiency decoupled system. Four basic design principles When designing an efficient chiller plant there are four basic design principles to consider to achieve and sustain the highest efficiency possible. Choose efficient equipment and components. The chillers are the biggest consumers in the chiller plant but other equipment such as pumps, cooling towers, dry coolers, fans and motors should also be considered. All components should be selected for stand-alone as well as system efficiency. Select chillers that are efficient at both full and partial loads and pumps and motors that have high efficiency at all operating conditions. Employ efficient system design practices. Using an appropriate plant design is essential for achieving energy savings. Combining plant configurations such as variable primary flow (VPF) and/or series water flow with specific technologies such as free-cooling or heat recovery can result in significant energy savings when applied and controlled properly. State-of-the-art design of the chiller plant control system. Chiller plant designs that employ sophisticated energy-saving strategies can be inefficient if not controlled and operated properly. To ensure sustainable system efficiency in these cases, it s crucial to have a well-designed chiller plant control system that includes proper system instrumentation and reporting capability to realize the potential savings. Proper system commissioning and operation. A formal commissioning process which tests the equipment and the plant under the different modes of operation is required to verify and maintain the performance of the chiller plant. In addition, periodic maintenance of system components helps maintain high system efficiency. With these basic design considerations in mind let s move into our comparison systems to demonstrate a high-efficiency design that leverages control technology advancements to achieve a high-performing chiller plant.

Base hydraulic system: Decoupled system with highseasonal efficiency (HSE) chillers Our base decoupled system (Figure 1) uses common traditional design concepts constant water flow through each chiller evaporator and variable water flow to the distribution side. Figure 1. Base chilled-water system HSE air-cooled chillers with AFDs As implemented this design includes: A constant-speed (essentially constant-volume) pump and check valve for each chiller A variable-flow distribution pump system to serve the terminal units (speed and pressure modulation is usually accomplished by providing the pump with a variablefrequency drive) pumps terminal units 7 C 12 C Two-way control valves to regulate the amount of chilled water that flows through the cooling coils of the terminal units and therefore the whole distribution system (e.g. fan coil unit, air-handling unit, etc.) A bypass to hydraulically decouple the primary (production) and secondary (distribution) sides of the system water can flow in either direction, as needed to balance the system Commonly used chiller-water temperatures of 12 to 7 C are assumed for this system As the two-way valves adjust the chilled-water flow through the coils to satisfy the existing load, the distribution pump speed responds to maintain required dynamic water pressure. State-of-the art system: VPF series HSE chillers with free cooling on the upstream chiller We ll compare this base decoupled system with a highefficiency system that incorporates the following design strategies. These strategies are complementary when presented in the same plant. Integrated free-cooling, air-cooled chiller. A method of free cooling is to transfer heat between the chilled water and the outside air through the use of additional water coils within the air-cooled chiller. When the outside air temperature is colder than the desired chilled-water temperature, the compressors are turned off and an automatic isolation valve inside the unit is opened. This allows the chilled water to flow through the water coils and be cooled by the outdoor air. If the outdoor air temperature drops below freezing conditions anti-freeze may be required. Low Flow Systems. The ASHRAE GreenGuide recommends reducing system design flow rates and increasing system delta T compared to past design practices. Efficiency is improved by reducing the pump energy used to transport cooling (and heating) throughout a building. It has become more common to find cooling systems with optimized design flow rates and delta Ts for chilled water. (e.g. 15-5 C versus the traditional 12-7 C).

Series Chillers. The concept of series chillers is not new. Early Trane Engineer s Newsletters and application manuals discuss parallel versus series chillers. [1] [2] A significant advantage of this configuration is that when chillers are piped in series, the upstream chiller s leavingwater temperature is higher, reducing the lift and work the upstream chiller requires resulting in less kw input per kw cooling output. A higher return temperature is also beneficial to the freecooling operation because the system will operate for a longer period in this mode and thus improve the total system efficiency. The series configuration also greatly simplifies sequencing in a VPF system, since there is no flow rate change when transitioning from one chiller to two chillers. Variable Primary Flow (VPF). VPF designs use fewer pumps and piping connections than the traditional primarysecondary systems. Again, this is not a new concept, but is enhanced by new advanced chiller controls and driven by the promise of pump energy savings at a lower installation cost. With a reduced footprint for the chiller plant and fewer components and electrical connections, VPF chilled-water systems are currently experiencing growing interest for new installations and renovation projects. Combining concepts Our state-of-the-art VPF system (Figure 2) incorporates these four concepts. The water flow varies throughout the entire system that is, through the evaporator of each operating chiller as well as through the cooling coils. Figure 2. State-of-the-art, VPF system with high seasonal efficiency (HSE) chillers and free-cooling upstream of chiller HSE air-cooled chiller with AFD and free cooling pumps with VFDs motorized bypass valves 15 C 10 C 5 C HSE air-cooled chiller with AFD terminal units Two-way control valves, isolation valves (for optional bypass), and a minimum chiller flow bypass are required to implement a VPF system. However: Variable-flow capable chillers eliminate the need for separate chiller pumps. This reduces the system installed cost and space required. The bypass can be positioned either upstream or downstream of the cooling coils. The control valve in the bypass is modulated to ensure that the amount of flow that returns to the operating chiller(s) never falls below the manufacturer-recommended minimum limit. An optional set of chiller bypass pipes and shutoff valves have been added to the plant to reduce the pump power when only one chiller is enabled. They are not required as the chiller s pressure drop falls to the square power of the VPF flow reduction. They also allow one chiller to operate while the other chiller is serviced and provides the same level of redundancy compared to the parallel configuration. 5 C 15 C

State-of-the art design considerations. [3] The following discussion summarizes a few key considerations when desiging a VPF system. Chiller selection. Chillers must be able to provide acceptable temperature control with a change of flow of at least 30 percent per minute, and remain operating, uninterrupted, with a change of 50 percent per minute is even better. Chillers need to be selected with adequate flow turndown that is the ratio of design to minimum flow rates. Ideally, the turndown ratio should be at least 2:1. It s important that the minimum and maximum flows must never be violated. Plant configuration and accessories. Correctly size the bypass line and the modulating bypass valve. Oversizing will result in unstable operation. Select flow-sensing devices that provide precise, repeatable measurements at the minimum flow control point. Impacts on terminal units and AHUs. Cooling coil selections require careful attention to ensure they are selected with the same delta Ts and flow as the chillers. Select slow-acting valves to control the chilled-water coils and ensure the valves are selected to give proper flow at all conditions. To minimize flow variations use more than one air handler and stagger their start/stop times. Control of series/vpf with free-cooling chiller plants. In a parallel VPF system, varying the water-flow rate through the chiller evaporator poses two control challenges: Since there is no flow rate transition when the second chiller is enabled, in a VPF series configuration, system control is much easier. Integrated free-cooling requires the implementation of additional intelligent controls to reduce the plant energy consumption. Implementing specific control sequences are essential to improve the efficiency of the plant. Examples sequences include: optimizing the chilled-water setpoint of the upstream chiller when both units are operating, applying chilled-water reset, particularly during free cooling, operating the most efficient chiller according to the building demand and outside conditions, and bypassing the evaporator of a chiller not called for in the sequence. These specific sequences improve chiller performance, extend the free-cooling operation mode, decrease pumping energy and improve the overall efficiency of the plant. It s also important that the control system measure and trend log the energy use of the chiller plant components and calculate the overall system efficiency. 1. Maintain the chiller flow rate between the minimum and maximum limits of the evaporator. Ultimately, this data can be analyzed and used to draw conclusions on how to improve chiller plant operation. 2. Manage transient flows without compromising stable operation.

Quantifying the Benefits One benefit of configuring chiller evaporators in series with a large delta T, is lower overall plant energy use. Series chillers. The upstream chiller operates more efficiently since it need only cool the water from 15 C to 10 C, resulting in less total chiller power. This is partially offset by the downstream chiller operating at a colder leaving-water temperature. Variable primary flow (VPF). When both chillers are enabled, the system water flow is pumped through both chiller evaporators; the incremental pump power is higher compared to systems with the chillers in parallel at full load and full flow. But the total power for both chillers plus pumping power is still lower with the chillers configured in series versus the chillers in parallel. Also at lower load conditions the flow rate is lower, evaporator pressure drop is reduced by the square of the flow rate reduction. The resulting system pump energy nears that of a traditional decoupled system. In addition, the higher return temperature (compared to a parallel arrangement) along with supply chilled-water temperature reset results in more hours of free-cooling economizing. A plant load simulation, using Trane Chiller Plant Analyzer (TCPA), was created for a typical office building equipped with the following (Figure 3): two chillers, 500 kw each, 500 terminal units and two AHUs for managing fresh air base load: 200 kw (24-hour operation) peak load: 1.000 kw at 35 C outside air temperature during the weekly hours of operation (from 06:00 to 21:00). Figure 3. Load profile versus outside air temperature In addition, because bypass pipes and shutoff valves can be added to the plant to reduce pump power when only one chiller is enabled, the series pump pressure may only exceed that of the parallel configuration when both chillers are operating. This strategy adds complexity because there is now a flow transition when the second chiller is enabled. An additional benefit of the bypass is that it allows one chiller to operate while the other chiller is isolated for service. Free cooling and higher return temperature. Piping the free-cooling chiller in the upstream position allows the integrated free-cooling chiller to be preferentially loaded during the free-cooling period, since it receives the warmest return water temperature. cooling demand (kw) 1000 800 600 400 200 0-10 5 0 5 10 15 20 25 30 35 temperature ( C)

Figure 4. Electrical consumption profile comparison of base decoupled system versus VPF series with free cooling (Paris, France) electricity consumption (kwhe/month) 70,000 60,000 50,000 40,000 30,000 20,000 10,000 base system secondary pumps primary pumps chillers 0 Jan Feb Mar Apr May Jun month Jul Aug Sep Oct Nov Dec Figures 4 illustrates annual electrical consumption profiles for our comparison systems using the weather profile for Paris, France. Various locations throughout Europe were analyzed (Table 1). Cost savings for the VPF series with free cooling were estimated to result in savings between approximately 5.200-9.500 /year based on an electricity price of 0.10 /kwh. Installed Cost. The cost of the equipment (chillers, freecooling option, terminal units and AHUs) was based on a quote from a manufacturer s representative. The installation, piping, insulation and valves costs would be specific to each individual installation. The cost is based on the assumptions that piping for the plant and throughout the building would be designed for a low flow system for a building located in France. The first cost of the VPF series with free-cooling system was estimated to 4.000 (over the cost of a parallel, decoupled system) based on material and installation cost estimates shown in the Table 2. Costs will vary depending on local labor and component costs. Table 1. Expected annual electrical consumption comparison for both systems in various European locations FR-Paris GB-Manchester CZ-Prague DE-Frankfurt ES-Madrid IT-Milano PL-Warsaw Decoupled Chillers (kwh/year) 385.210 351.629 380.626 390.288 493.465 438.816 373.327 Primary pumps (kwh/year) 39.579 41.437 40.957 39.703 40.177 41.728 40.758 Secondary pumps (kwh/year) 53.896 50.970 53.719 54.278 61.949 58.928 52.846 Total (kwh/year) 478.685 444.036 475.302 484.270 595.591 539.472 466.931 Series VPF with free-cooling Chillers (kwh/year) 321.320 279.207 288.758 309.395 459.741 373.536 267.546 Primary pumps (kwh/year) 90.444 99.821 100.184 96.097 83.555 92.806 103.406 Total (kwh/year) 411.764 379.028 388.942 405.492 543.295 466.342 370.953 Savings (KWh/year) 66.921 65.008 86.360 78.778 52.296 73.130 95.978

Table 2. First cost investment for VPF series with free cooling Cost increases unit cost ( ) quantity total cost ( ) Impact on the design of the terminal units (cooling coils) 40 500 20.000 Impact on the design of the AHUs (cooling coils) 500 2 1.000 Chiller free-cooling option 17.000 1 17.000 Total investment 38.000 Cost reductions Impact on chiller plant room piping and accessories (pumps, valves, wiring, concrete, etc.) 19.000 1 19.000 Impact of building piping (pipes, valves, insulation, support, etc.) 15.000 1 15.000 Total savings 34.000 Final investment (Total investement-total saving) 4.000 Estimated Payback. Based on the annual energy savings (between 5.500 and 9.500 /year) and the 4.000 incremental installed cost of the VPF series with FC system, the simple payback for the system is less than 1 year in all locations. Use of the concept in other systems. It is expected that it would also be energy efficient in other types of applications such as buildings with AHUs and chilled beams due to the presence of high-return chilled-water temperatures from the beams. It s also expected to be cost-effective in industrial applications with high temperature processes, where relatively warm central chilled-water cooling is used. Other free-cooling strategies may be more efficient and may result in greater savings in similar applications. This case study should not be interpreted as recommending one free-cooling configuration over another but rather a strategy that may be considered in specific cases. Conclusion The analysis presented showed that the VPF series with free-cooling chilled-water system configuration provides a cost-effective way to save energy in office applications with low base load (10-20 percent of the maximum demand). In addition, this system configuration is simpler to operate since there are no flow rate transitions during chiller sequencing, and it has the versatility to respond to many different load profiles. One important question remains. Would this solution be as interesting for an application without a base load? There is no single answer and only a more detailed study can validate the relevance of this solution. But in the vast majority of cases, a VPF series configuration brings significant savings and advantages over a conventional parallel piped system.

References [1] S. Hanson and M. Schwedler, 2011. Multiple-Chiller-System Design and Control, Trane application manual SYS-APM001-EN [2] L. Cline, 2009. Series Chillers and VPF Chiller Plants. Engineers Newsletter, volume 38-3. [3] M. Schwedler and B. Bradley, 2002. The Saga Continues: Variable- Primary-Flow Systems Revisited, Engineers Newsletter, volume 31-4. Trane believes the facts and suggestions presented here to be accurate. However, final design and application decisions are your responsibility. Trane disclaims any responsibility for actions taken on the material presented. Ingersoll Rand (NYSE:IR) is a world leader in creating and sustaining safe, comfortable and efficient environments in commercial, residential and industrial markets. Our people and our family of brands including Club Car, Ingersoll Rand, Thermo King and Trane work together to enhance the quality and comfort of air in homes and buildings, transport and protect food and perishables, and increase industrial productivity and efficiency. We are committed to sustainable business practices within our company and for our customers. 2016 Trane All rights reserved BAS-APN003A-GB September 01, 2016 ingersollrand.com