36 to 120 k for small installation protection Data Sheet 2789_en_F 1 Description PHOEIX OTT 2011-04-29 2 Features The (SPD) provides surge protection in a compact, affordable package. high-energy suppression circuit provides 36 to 120 k (depending upon the model) of surge current rating per phase. Each surge suppression mode in the is individually fused for safety. The SPD uses a sealed, EM 4X housing, allowing installation in harsh environments with limited space. Operating status lights are easily observed and provide verification of protection. The VL-SQ SI 36-2-120 provides compact protection of 120 V applications with bonded neutral and ground. The VL-SQ SI 40-3-600 is for three-phase Wye applications up to 600 V with bonded neutral and ground. The VL-SQ SI 40-3-600D is for three-phase Delta applications up to 600 V. The 120/240S SPDs are for single- and split-phase 120/240 applications with common or separate neutral and ground. ompact design for flexible mounting locations 36 to 120 k surge current capacity per phase (L- and -G) protects against high-energy lightning strikes and transient voltages UL nominal surge discharge current (I n ) rating of 10 k EM 4X enclosure LEDs provide continuous feedback on the status of each phase UL/cUL listed; meets UL 1449 3 rd edition DGER: HZRD OF ELETRI SHOK OR R FLSH onfirm the SPD voltage rating on the module or nameplate label is the same as the operating voltage. Risk of electric shock. Disconnect power before installing or servicing. Service to be performed by qualified personnel only. The products described in this data sheet are exclusively for export outside of the European Economic area (E). Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/catalog. This data sheet is valid for all products listed on the following page: 8251-0208F
3 Ordering Data Products Description Type Part o. Pcs./Pkt. Surge protective device, 36 k, 2-phase, 2-wire + ground for 120 V (L-) applications with common GD- Surge protective device, 50 k, 2-phase, 2-wire + ground + neutral for Surge protective device, 80 k, 2-phase, 2-wire + ground + neutral for Surge protective device, 100 k, 2-phase, 2-wire + ground + neutral for Surge protective device, 120 k, 2-phase, 2-wire + ground + neutral for Surge protective device, 40 k, 3-phase, 3-wire + ground for up to 600 V (L-) applications with common GD- Surge protective device, 40 k, 3-phase, 3-wire for up to 600 V (L-) applications without ground VL-SQ SI 36-2-120 2800003 1 VL-SQ SI 50-120/240S 2800323 1 VL-SQ SI 80-120/240S 2800324 1 VL-SQ SI 100-120/240S 2800325 1 VL-SQ SI 120-120/240S 2800326 1 VL-SQ SI 40-3-600 2800007 1 VL-SQ SI 40-3-600D 1 4 Technical Data Surge Protection Data 2800003 2800323 2800324 2800325 2800326 2800007/ Maximum surge current per phase 36 k 50 k 80 k 100 k 120 k 40 k Short circuit current rating (SR) 25 k 200 k ominal voltage 120 V 600 V 1 urrent rating (I n ) ircuit type 1 Up to 600 V 10 k MOV technology UL lass Type 1 Part o. Type MOV Voltage Protection Rating (VPR) L- -G L-L L-G 2800003 VL-SQ SI 36-2-120 150 700 1200 2800323 VL-SQ SI 50-120/240S 150 700 1200 800 2800324 VL-SQ SI 80-120/240S 150 700 1200 800 2800325 VL-SQ SI 100-120/240S 150 700 1200 800 2800326 VL-SQ SI 120-120/240S 150 700 1200 800 2800007 VL-SQ SI 40-3-600 750 2500 4000 VL-SQ SI 40-3-600D 750 2500 4000 General Data Dimensions (WxHxD) Weight Phase connection onduit connector Enclosure material 2800003 2800323 2800324 2800325 2800326 2800007/ 2.25 x 2.25 x 1.94 in. (57 x 57 x 49 mm) 0.53 lb. (0.24 kg) #14 WG 3.00 x 3.60 x 2.67 in. (76 x 91 x 68 mm) 3.60 x 3.00 x 2.64 in. (92 x 76 x 64 mm) 1.6 lb. (0.73 kg) 1.0 lb. (0.45 kg) 1/2-in. PT on-metallic 2789_en_F PHOEIX OTT 2
General Data Housing rating Operating frequency EM 4X 50/60 Hz Operating temperature -40 to 70 (-40 to 160 F) Operating altitude 0 to 12,000 ft. (3,658 m) pprovals U 2800003 2800323 2800324 2800325 2800326 2800007/ 1449 3 rd edition 1283 S 22.2 o. 8-M1986 IEEE 62.41.1-2002 62.41.2-2002 62.45-2002 5 Dimensions 2.25 in. 57 mm 3.60 in. 91 mm 0.75 in. 19 mm 2.64 in. 67 mm 1.94 in. 49 mm 2.25 in. 57 mm 3.00 in. 76 mm Figure 1 2800003 Dimensions 0.75 in. 19 mm Figure 2 2800007, Dimensions 2789_en_F PHOEIX OTT 3
0.75 in. 19 mm 3.00 in. 76.2 mm 3.60 in. 91.4 mm 0.87 in. 22 mm 2.67 in. 68 mm Figure 3 2800323, 2800324, 2800325, 2800326 Dimensions 6 Installation 6.1 Mounting and connection DGER: Turn off all power supplying this equipment before working on or inside equipment. lways follow federal and local regulations during installation. pply appropriate personal protective equipment (PPE) and follow electrical work practices. Only qualified electrical personnel may install and service this equipment. ever open SPD. o serviceable parts are inside. WRIG: This equipment depends upon an effective ground. Failure to obtain a quality ground connection may result in explosion or arc flash. OTE: Megger or hi-potential tests will damage this surge protective device. Turn off all power supplying the equipment and isolate the surge protective device before testing. OTE: Variant 2800007: Suitable for use on a circuit capable of delivering not more than 200,000 rms symmetrical mperes. ll variants except the 2800007: Suitable for use on a circuit capable of delivering not more than 25,000 rms symmetrical mperes. 1. Position the so the LEDs are visible and the wires are as short and straight as possible. The SPD can be mounted in any orientation. It attaches through any side of the enclosure being protected using 1/2-PT threaded nipple. OTE: over or remove components inside any enclosure before drilling to prevent shavings from causing short-circuits across terminals and races. 2789_en_F PHOEIX OTT 4
2. reate a hole in the enclosure, 2, for 1/2-in. conduit attachment, approximately 7/8 in. (22 mm) diameter. 2 12 1 1 3 Figure 5 Single-phase, 3-wire, 120/240 V connection 1 SPD 2 Protected device 3 Strain relief nut Figure 4 Mounting the SPD 3. Route the wires and nipple through the hole and secure the to the enclosure with the strain relief nut, 3. 4. onnect the to the appropriate phases and ground lines. Table provides a cross reference between the figure number and order number. Wires are color coded as shown. If equipped with a green wire, it must be connected to ground. 121 121 Figure o. onfiguration Order o. 5 3-wire, 120/240 V single 2800003 phase 6 3-phase Wye, 208 V 2800003 1 7 3-wire + ground, 120V single phase 8 3-phase Wye, 208, 480 or 600 V 9 3-phase High-Leg Delta, 120/240 V 10 3-phase, Delta, 240, 480, 600 V 2800323 2800324 2800325 2800326 2800007 2800007 Figure 6 3-phase Wye, 208 V connection 1 requires two SPDs 2789_en_F PHOEIX OTT 5
1 2 33 1 Green 3 lack 21 11 Figure 7 1- or 2-phase, 120 V connection Figure 9 3-phase High-Leg Delta, 120/240 V connection 21 11 111 Figure 8 3-phase Wye, 208, 480 or 600 V connection Figure 10 3-phase, Delta, 240, 480, 600 V, connection, corner ground or floating ground 2789_en_F PHOEIX OTT 6
Type 1 SPDs can be connected on either side of the service entrance. Disconnects to the SPD are recommended. ll wires must be connected to properly installed circuit breakers sized according to the wire gauge. Use an appropriate breaker, i.e., 2- or 3-pole, for the electrical configuration. 7 Operation LEDs indicate the operating status of the individual phases of the The LEDs illuminate when the relevant phase is operating correctly. Device LED Phase LEDs Phase LEDs ll wires must be connected for the SPD to function correctly. The wires between the SPD and protected device should be twisted 1/2 turn every 12 in. (300 mm). Do not loop or coil wire. Excess wire must be removed without applying stress to wires. Figure 11 LED location If a phase is not operating correctly or a fault occurs, the corresponding LED is not lit. When a phase LED is not lit, verify the correct voltage is present on each phase. If power is present, the VL-SQ SI must be replaced. There are no serviceable parts. 2789_en_F PHOEIX OTT GmbH & o. KG 32823 lomberg Germany Phone: +49-(0) 5235-3-00 7 PHOEIX OTT P.O.ox 4100 Harrisburg P 17111-0100 US Phone: +717-944-1300