GE FANUC Parts 1. DeviceNet Network Master/Slave August 2002 GFK-1539A. Quick Start Guide. Product Description. Specifications. Preinstallation Check

Similar documents
VersaMax* DeviceNet Network Master/Slave

GE Fanuc Automation. Series Programmable Controller. Programmable Control Products. DeviceNet Modules

VersaMax* Serial Communications Module

GE Intelligent Platforms Programmable Control Products. DeviceNet Modules for PACSystems* RX3i and Series 90*-30 User's Manual

IMPORTANT PRODUCT INFORMATION

GE Fanuc Automation. Generation D Real-Time Operating System. Programmable Control Products. DeviceNet Reference Guide

MPCR Series DeviceNet Technical Manual TDMPCRDNTM2-0EN 01/08 Subject to change without notice

L5351 DeviceNet Communications Interface

VersaMax* IC200BEM003. PROFIBUS Master Module. Ordering Information. Specifications. GFK-2739 April of their respective owners.

Analog Input, 16-Bit Thermocouple Module

VersaMax* PROFIBUS Network Interface Unit

MPCR Series DeviceNet Technical Manual

VLT 5000 DeviceNet and Allen Bradley Control logix 5550

VersaMax* Analog Input, 16-Bit Thermocouple Module

USER S MANUAL. FX2N-64DNET DeviceNet Interface Block

MRUC-20 Modul-R CAN Bus Network

01348(N or G) MH** -- Material Handling (N or G) MH** -- Material Handling

(Controller Area Network)

2002 Series DeviceNet Technical Manual

G3 Series DeviceNet TM Technical Manual

VersaMax Genius Network Interface Unit

This Datasheet for the IC660BBA026. Block 24/48Vdc Analog Current Source 6 Inputs.

GE Fanuc IC695ALG708. Rx3i PacSystem

WRC-CANX CAN Bus Extender, Version 2 User s Manual

High Performance FieldBus cards

ELC-CODNETM. Effective December Users Manual

Installation and maintenance instructions

High Performance FieldBus cards

INSTRUCTION SHEET. Eaton Logic Controller DeviceNet Distributed I/O Adapter Module. [Applicable Distributed I/O Adapter Module] ELC-CADNET

1782-JDA8 SmartMux-Lite / DeviceNet User s Manual

This Datasheet for the IC660BBA104. Block 115Vac/125Vdc Analog Current Source 4 Inputs / 2 Outputs

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

GE Fanuc IC695CMM004. Rx3i PacSystem

Preface Digital Electronics Corporation. All rights reserved. Digital Electronics Corporation December LT Type-D User Manual Supplement 1

PAC BI-DP BIM and 8701-CA-BI Carrier

Bus Transmitter Expansion Module (Fiber Media) with built-in switch. PROFINET Slave, Version 2.2 Class A IO-Device

1782-JDC DeviceNet/Serial Gateway User s Manual

HE-65 CAN-BUS. (DeviceNet-Slave) Technical Information TR - ECE - TI - GB /30/2016

This Datasheet for the IC697BEM721. I/O Link Interface Module for the Series

User Manual for the HE693DNT750. DeviceNet Slave. Third Edition 22 June 2000 MAN

PACSystems* RSTi-EP EPSCPE100 Enhanced performance standalone controller for RSTi-EP Platform CPU Quick Start Guide

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO

FieldServer FS DeviceNet Master Adapter Driver

BridgeWay. PROFIBUS to DeviceNet Gateway User Manual. Part No. AB7605. Publication PUB-AB

PACSystems* RX3i and Series 90*-30 IC694ALG223 and IC693ALG223

CPU Module IC200CPU005

This Datasheet for the IC660BBA020. Block 24/48Vdc Analog 4 Inputs / 2 Outputs.

This Datasheet for the IC660BBD025. Block 5/12/24Vdc Sink I/O 32 Circuits.

Flex Series User Guide

Diagnostics (Logical) Diagnostics (Physical)

Series SD6 with DeviceNet (Addendum)

This Datasheet for the IC660BBR100. Block Relay Output Normally Closed 16 Circuits.

This Datasheet for the IC660BBD110. Block 115Vac Input 16 Circuits.

Allen-Bradley Automation

1. FEATURES AND BENEFITS

01325T -- Robot Welder

PACSystems* RX3i IC694ALG232

FC 300 DeviceNet and Allen Bradley Control logix 5550

EM23-DIN COMMUNICATION PROTOCOL. Version 0 Revision 0

Powered Roller Controller for DeviceNet

PACSystems* RX3i IC694ALG233

DeviceNet Master (Scanner)

DeviceNet. Controller Area Network control of Rotork actuators. Redefining Flow Control

SMARTLINX INTERFACE MODULE

PACSystems* RX3i and Series 90*-30 IC694ALG442-CC and IC693ALG442-EC

GE Fanuc Automation Programmable Control Products. PACSystems RX3i. Serial Communications Modules. User s Manual, GFK-2460A.

Installation and Setup

CDN127 DeviceNet SPECIFICATIONS

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

This Datasheet is for the IC693CBL300. I/O Bus Expansion Cables.

Remote I/O Scanner. Catalog Number 1747-SN. Installation Instructions. Publication

DeviceNet. Controller Area Network control of Rotork actuators. Established Leaders in Valve Actuation. Electric Actuators and Control Systems

DNP31.0 DeviceNet Interface

D485 Modbus to DeviceNet Converter Instruction Manual

CDN067 DEVICENET SPECIFICATIONS

CDN572-5 DEVICENET SPECIFICATIONS

1782-JDC DeviceNet Serial Gateway User s Manual

Shown with terminal block Supports diagnostic point fault contacts in the logic program

PACSystems* RSTi-EP EPSCPE100 Enhanced performance standalone controller for RSTi-EP Platform CPU Quick Start Guide

I/O EXPANSION MODULES

G3 Series PROFIBUS DP Technical Manual

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

Operation Manual. Fieldbus system EX510-GDN1. DeviceNet Compatible GW unit

BL compact fieldbus station for DeviceNet 2 Analog Inputs for Current or Voltage and 2 Analog Outputs for Voltage BLCDN-4M12S-2AI2AO-VI

PACSystems* RSTi DeviceNet Network Adapter

CPU Module IC200CPU005

This Datasheet for the IC670GBI002 24VDC BUS INTERFACE UNIT.

EMERALD SERIES AUTOMATION CONTROLLER JANUARY 2017 EMERALD EMC INDUSTRIAL INDEXING SYSTEMS, Inc. INSTRUCTION BOOK

Varispeed SERIES OPTION CARD DeviceNet COMMUNICATION INTERFACE CARD USER'S MANUAL Model: SI-N1

Instructions to printer DO NOT PRINT THIS PAGE

RS 485 Mini Modbus 1AO

SMARTLINX INTERFACE MODULE

DeviceNet - CIP on CAN Technology

CONTENTS 1. BEFORE USE GENERAL DESCRIPTION POINTS OF CAUTION HARDWARE SPECIFICATIONS... 4

Motors I Automation I Energy I Transmission & Distribution I Coatings. SymbiNet CFW-11. User s Manual

PACSystems* RX3i Genius* Communications Gateway, IC695GCG001. Quick Start Guide, GFK-2891C August 2016

DNETEXT-C CAN Bus Extender, Version 3 User s Manual. Brad Harrison

GE Intelligent Platforms Programmable Control Products PACSystems* RX3i DNP3 Slave Module IC695EDS001. Quick Start Guide GFK-2912 October 2014

This Datasheet for the IC660BBD101. Block 115Vac I/O Low Leakage 8 Circuits.

Analog Current Input - 16 Channel IC693ALG223. Current Ranges. Power Requirements and LEDs. Location in System. Analog Input Modules

Transcription:

Product Description Revision Letter: BA Firmware version: 1.10 Firmware upgrades: DeviceNet Certification: Product Name: None Certificate available upon request. DeviceNet Network Control Module (NCM) Specifications Operating Modes: Master only, Slave only, Combined Master/Slave Slaves Supported: Up to 40 slave devices may be configured for the Master mode Configuration: Configured as a Generic Communication Module with contiguous %I, %Q, %AI, and %AQ references. Status Data: Slave presence bit per each slave device, 64 bits total. DeviceNet Features: Slave only - Group 2 Only Server or UCMM Capable (COMMREQ selectable) Master or Master/Slave - UCMM Capable DeviceNet network 0 to 63. COMMREQ selectable. address: DeviceNet network data rate: Indicators (3): 125K, 250K, 500K baud. COMMREQ selectable. OK LED to indicate the status of the NCM after powerup. Mod LED to indicate the status of the NCM module. Net LED to indicate communication status on the DeviceNet network. Power Consumption: 140mA at 5V, 10mA at 3.3V The DeviceNet Network Control Module is a DeviceNet master/slave module that provides an interface to the a DeviceNet network. One or more NCMs may be installed at any location in the PLC. Quick Start Guide 1. Install the Communications Carrier on the DIN Rail by simply clicking it into place. Note: Connecting carriers must be installed on the same section of 35mm x 7.5mm DIN rail. The DIN rail must have a conductive (unpainted) finish for proper grounding. 2. Install the Module on the Communications Carrier. The latch on the module must be in the unlocked position. Align the connectors and the latch post and press the NCM down until the two tabs on the bottom of the NCM click into place. Turn the latch to the locked position to secure the NCM to the top of the carrier. 3. Connect the communications bus to the connector on the front of the Network Control Module. (Refer to the heading Bus Installation Guidelines for detailed bus installation instructions.) 4. Remove the connector cover on the right-hand side of the Communications Carrier. Do not discard this cover; you will need to install it on the last carrier. It protects the connector pins from damage and ESD during handling and use. Connector PLC CPU power supply Optional booster power supply DeviceNet Network Control Module 5. Install additional modules by mounting modules on their carriers and sliding them along the DIN rail to fully engage the connectors in the sides of the carriers. Preinstallation Check Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to transport or ship any part of the system. GE FANUC Parts 1

6. Power up the System, and Observe the Module LEDs. The LEDs indicate the presence of power and show the operating mode and status of the NCM. OK MOD NET OK MOD NET OFF when the NCM has not yet started its powerup sequence. Blinking green indicates the NCM is performing its powerup sequence and has not yet finished successfully. Green indicates the NCM has successfully completed powerup diagnostics. Amber when the NCM has either failed powerup diagnostics or has not yet received a valid configuration from the CPU. Blinking amber means the NCM has failed powerup diagnostics. The number of blinks indicates the fault type. OFF when the NCM is not powered. blinks green if the NCM configuration is missing, incomplete, or incorrect. The NCM may be in Standby state. green when the NCM is operating normally. blinks red if there is a recoverable fault. red if there is an unrecoverable fault. The NCM may need replacing. OFF when the NCM is not online or not powered. blinks red and green if the NCM detects a Network Access error and is in the Communications Faulted state. blinks green if the NCM is online but has no connections in the established state. It has no established connections to other nodes. green when the NCM is online and has connections in the established state. blinks red if one or more I/O Connections are in the Timed-Out state. red if an error renders the NCM incapable of communicating on the network. Bus Installation Guidelines The network cable required for DeviceNet operation is specified in the following table. A 5-conductor cable is necessary. One wire is a drain, two wires are for carrying power on the network, and the remaining two wires are to carry the data transmission. On a DeviceNet fieldbus, every device must, at least, power its network transceivers from the network power source. Some devices draw all of their power from the network supply. DeviceNet specifies two types of network cable, Thick and Thin cable. Thick cable provides for longer distances and more power. Generally, Thick cable is used for the Trunk cable. Thin cable is used for shorter distances and is generally used for drop cables or where cable flexibility is necessary. Thick Cable General Specifications Thin Cable General Specifications Network Topology Redundancy Network Power for Node devices Allowed Nodes (Bridging excluded) Data Packet Size Duplicate Address Detection Error Detection / Correction Bus Length DeviceNet Cable Specifications Two shielded pairs - Common axis with drain wire in center Overall braid shield - 65% coverage; 36 AWG or 0.12mm tinned Cu braid minimum (individually tinned) Drain wire- #18 Copper minimum; 19 strands minimum (individually tinned) Outside diameter - 0.410 inches (min) to 0.490 inches (max.) roundness - radius delta to be within 15% of 0.5 O.D. Two shielded pairs - Common axis with drain wire in center Overall braid shield - 65% coverage; 36 AWG or 0.12mm tinned Cu braid minimum (individually tinned) Drain wire - #22 Copper; 19 strands minimum (individually tinned) Outside diameter - 0.240 inches (min.) to 0.280 inches (max.) roundness - radius delta to be within 20% of 0.5 O.D. Bus with limited branching (trunkline/dropline) Not Supported Nominal 24 volt DC ±4% 64 nodes 0-8 bytes with allowance for message fragmentation Addresses verified at power-up CRC - retransmission of message if validity not acknowledged by recipient The maximum length of the bus is limited by the cable type, transfer rate, and the number and accumulated length of drop lines. Individual branch lengths may not exceed 6 meters and are limited to one network node per drop. However, the node may be a node offering multiple ports. With Thin cable, the maximum bus length, regardless of data rate, is 100m. With Thick cable used as the trunk line, the maximum bus length is as shown in the following table. Data Rate 500Kbps 250Kbps 125Kbps Bus length and drop length restrictions 100m bus length and branches totaling < 39m 250m bus length and branches totaling < 78m 500m bus length and branches totaling < 156m 2

Bus Connectors and Termination DeviceNet uses several forms of connectors. The NCM provides the 5-pin standard Phoenix open-style pluggable connector. The pin-tosignal-to-wire color assignments are shown in the following table: Pin Signal Wire Color 1 V- Black 2 CAN_L Blue 3 Shield Bare 4 CAN_H White 5 V+ Red Connector orientation on the NCM is shown in figure below: 1 - V- 2 - CAN_L 3 Shield 4 - CAN_H 5 - V+ Termination of a DeviceNet network is passive and includes one resistor at each end of the network. A terminating resistor is placed across the data communication signals at pin 2 (CAN_L) and pin 4 (CAN_H). Correct terminating resistor is a 121 ohm 1% ¼ watt resistor. Bus Power Supply and Grounding DeviceNet requires a power supply of 24VDC (±4%) at a 16A maximum. However, with the use of Thick cable, a maximum of 8A is permitted on a single network segment. This is possible if the power supply is placed at the center point of two network segments, thus supplying 8A to each segment. With the use of Thin cable, a maximum of 3A is permitted. As with most Fieldbus networks, grounding of the network and its devices is very important. In DeviceNet, it is required that all cable shields be tied to ground at each device connection. This is done by tying the bare wire of the cable to pin 3 (Shield) of the connector. In addition, the DeviceNet network power supply must be grounded, but only at one point. The V- signal must be connected to Protective Earth Ground at the power supply only. If multiple power supplies are used, only one power supply must have V- connected to Earth Ground. Configuration Guidelines The DeviceNet Network Control Module must be configured in two steps. The first step uses the configuration software to include the module in the PLC configuration. The second step uses the programming software to send a COMMREQ containing the network addressing and data lengths to the NCM. PLC Configuration for the DeviceNet NCM The NCM is configured as part of the overall PLC system configuration. The configuration software is used to specify the following module characteristics: A location. The NCM can be placed in any module location in the system. In the selected location, insert a Communication Carrier. On that Carrier, insert a Generic Communications Module. Settings: Select the Reference Address and Length for an I/O area in each of the 4 reference types: I, AI, Q, and AQ. The length for each must exactly match the total amount of data of that type for all the slave devices controlled by the NCM, including the 64 bits of Communications Status Data provided by the NCM itself. For example, the %I length must equal the total amount of all discrete input data contained in the NCM s input data area, described later in this chapter. And the %AI length must equal the total amount of all analog input data contained in the NCM's input data area. Conversely, the %Q and %AQ lengths must equal the total amount of all discrete and analog output data, respectively. Enter the Module ID: FFFF9808. Wiring: can be used to enter tags for the different data points. Power Consumption: can be used to enter the power consumption figures for the DeviceNet NCM. Programming Guidelines The second part of configuring an NCM is to send a single COMMREQ from the application program to the NCM. No communications can occur until a valid COMMREQ is received by the NCM. The format of this COMMREQ is shown below. The configuration COMMREQ defines whether the NCM is used as a DeviceNet Master, a DevceNet Slave, or as both simultaneously. It specifies the network address and data rate of the NCM. It also specifies the network address of each device, the I/O mode, and the lengths of each slave s data. The sum of the I/O data for each slave device (including the NCM itself, if the NCM is a Slave) and the 64 bits of Communications Status Data must exactly equal the length for each reference type entered using the configuration software. Configuring the NCM as a DeviceNet Master Only When configuring the NCM as a Master, the COMMREQ must specify: the network address of the Master. the network data rate of the Master. For each subordinate slave: its network address its I/O mode the amount of I/O data of each type: I, AI, Q, AQ Configuring the NCM as a DeviceNet Slave Only When configuring the NCM as a Slave, the COMMREQ must specify: the network address the network data rate the network mode the amount of I/O data of each type: I, AI, Q, AQ Configuring the NCM as a DeviceNet Master and Slave Combined When configuring the NCM as both a DeviceNet Master and Slave, the COMMREQ must provide all of the configuration information for both a Master and Slave. Note that in this combined scenario, the network mode of the slave is ignored as the Master configuration requires the slave to be UCMM-capable. the network address of the Master/Slave. the network data rate of the Master/Slave. For the NCM as a Slave the amount of I/O data of each reference type: I, AI, Q, AQ For each subordinate slave: the network address the I/O mode the amount of I/O data of each type: I, AI, Q, AQ GE FANUC Parts 3

COMMREQ Command Block Word # Contents 1 Length of the data block in words. (Shown below, number of slaves = length): 0 slave = 8, 1 slave =11, 2 slaves = 14, 3 slaves =17,, n slaves = 8 + n * 3. 2 Always 0 3 Status Pointer Memory (8 = R, 10 = AI, 12 = AQ) 4 Status Pointer Offset (0 based) 5-6 Always 0 The slave devices can be entered in the COMMREQ in any order. The NCM checks that the lengths for the four data areas sent in the PLC configuration file match the sum of the lengths sent in the COMMREQ. For convenience, the units of length in the configuration of a Generic Communication Module match the units of length defined in the COMMREQ. Any bit length field must be entered as a multiple of 8 bits, such as 8, 16, 24, etc. COMMREQ Data Block Word # Byte # Contents 1 1-2 COMMREQ Command Number = 1000H 2 3 Master Address (0 63) 4 Master Baud Rate (0 = 125k, 1 = 250k, 2 = 500k) 3 5 If NCM is Slave, Length of its I data (in bits, 0 if none) 6 If NCM is Slave, Length of its AI data (in words, 0 if none) 4 7 If NCM is Slave, Length of its Q data (in bits, 0 if none) 8 If NCM is Slave, Length of its AQ data (in words, 0 if none) 5 9-10 Reserved for Master Scan Rate, 0 = Scan as fast as possible 6 11-12 NCM Slave communication mode (0 = UCMMcapable, 1 = Group 2 Only) This field is only applicable when the NCM is configured as a Slave only. This field is also ignored when the NCM is configured as a Master device. In the Master case, the NCM Slave communication mode is fixed as UCMM-capable. 7-8 13-16 Reserved 9 17 First Slave s Address (0 63) 18 First Slave s I/O mode (1 = Poll, 2 = Strobe, 4 = COS w/ack, 0xC = COS w/o Ack) 10 19 First Slave s I data length (in bits, 0 if none) 20 First Slave s AI data length (in words, 0 if none) 11 21 First Slave s Q data length (in bits, 0 if none) 22 First Slave s AQ data length (in words, 0 if none) 12-14 23-28 Second Slave s configuration : : : : : 126-128 251 256 Fortieth Slave s configuration COMMREQ Return Codes The following table lists the possible return codes returned by the COMMREQ upon completion. The return code is written to the Status Pointer location specified by Words 3 and 4 of the COMMREQ Command Block. Return Code (Hex) Description 1 Successful Status - Network operation can proceed 2 NCM has already received a COMMREQ 3 NCM has not been configured via PLC configuration 4 NCM is using the default configuration, i.e. configuration includes 64 bits %I only 5 COMMREQ does not include sufficient data (length must be 8 when configured as a Slave Only) 6 Slave information is incomplete (length must be 11,14,17, etc when configured as a Master) 7 COMMREQ Command number is invalid (must be 0x1000) 8 Reserved fields (Words 7-8) are not 0 as required 9 Total Discrete Input length does not match the module configuration A Total Discrete Output length does not match the module configuration B Total Analog Input length does not match the module configuration C Total Analog Output length does not match the module configuration D NCM network address is invalid (must be 0-63) E NCM network data rate is invalid (must be 0,1,2) F Slave network address is invalid (must be 0-63) 10 Reserved 11 Slave I/O type is invalid (must be 1,2,4, or 0xC) 12 Multiple I/O types are specified for a slave (must be 1,2,4,or 0xC) 13 When configured as a Strobe device, the output data length must be 0 14 When configured as a Strobe device, input data length must 1-8 bytes 15 Duplicate configuration for a slave device. There are two or more entries with the same Slave network address. 16 Master or Slave Discrete Input Length must be divisible by 8 (8,16,24, etc) 17 Master or Slave Discrete Output Length must be divisible by 8 (8,16,24, etc) 18 Unknown Configuration error 19 Headend stopped - aborted configuration 4

COMMREQ Example The following example illustrates the COMMREQ function block of the PLC logic and the COMMREQ Command Block, Data Block, and Return Code. The COMMREQ Command Block is placed at %R00001 through %R00006 and the Data Block follows immediately from %R00007 through %R00029. When specifying the input and output lengths for the slave devices, specify the number of bits for discrete data and the number of words for analog data. Hence, 1 byte of input data is specified as 8 bits. And 1 word of output data is specified as 1 word. IN SYSID TASK COMMREQ Parameters The IN parameter specifies the location of the Command and Data Block. The SYSID parameter specifies the physical slot location of the NCM. In the following example, the NCM is in slot 1 next to the PLC CPU. The TASK parameter specifies the NCM application task to which the COMMREQ is directed. The TASK must always be 0. %R00001 1 0 COMM REQ IN SYSID TASK The following example configures the NCM to communicate with 5 slave devices with Slave Addresses 1 through 5. The Master will use address 0 and operate the network at 500Kbits/sec. The Master will not act as a slave device in this configuration. Address Device Description Network I/O Requirements 1 2 input points 2 output points 2 4 input points 4 output points 3 4 input points 4 output points, 2 analog inputs 2 analog outputs 4 2 input points 2 output points 5 1 input point 1 output point FT 2 bytes Input (1 byte of data +1 byte of status) 2 bytes Input (1 byte of data + 1 byte of status) 2 bytes Input (1 byte of data + 1 byte of status) 2 words Input 2 words Output 1 byte Input 1 byte Input COMMREQ Area Command Block Data Block Ref Value Description Table %R1 23 Length of Data Block (23 words, %R7-%R29) %R2 0 Not used (must be 0) %R3 8 Reference Table (8=%R) %R4 99 Reference Table Offset %R100 %R5 0 Not used (must be 0) %R6 0 Not used (must be 0) %R7 0x1000 COMMREQ Command %R8 0x200 Master Address = 0 Baud Rate = 500K %R9 0 NCM is not a slave %R10 0 NCM is not a slave %R11 0 Reserved (must be 0) %R12 0 NCM is not a slave %R13 0 Reserved (must be 0) %R14 0 Reserved (must be 0) %R15 0x101 Slave Address 1 %R16 0x10 (16) 16 bits (2 bytes) input %R17 0x08 8 bits (1 byte) output %R18 0x102 Slave Address 2 %R19 0x10 (16) 16 bits (2 bytes) input %R20 0x08 8 bits (1 byte) output %R21 0x103 Slave Address 3 %R22 0x210 2 words input 16 bits (2 bytes) input %R23 0x208 2 words output 8 bits (1 byte) output %R24 0x104 Slave Address 4 %R25 0x08 8 bits (1 byte) input %R26 0x08 8 bits (1 byte) output %R27 0x105 Slave Address 5 %R28 0x08 8 bits (1 byte) output %R29 0x08 8 bits (1 byte) input GE FANUC Parts 5

Finally, when specifying the Generic Communication Module configuration for the NCM, it is necessary to add up the I/O requirements of each of the slave devices. Also add the 64 bytes of status for the NCM. Generic Communication Module Reference and Lengths %I 128 (64 for the NCM status + 16 + 16 + 16 + 8 + 8) %Q 40 (8 + 8 + 8 + 8 + 8) %AI 2 %AQ 2 Operating Notes/Restrictions 1. The DNCM is limited to communicating with up to 40 slave devices. 2. Because a quick RUN-STOP-RUN transition of the CPU headend may cause the NCM to become confused during configuration, it is suggested that the Configuration COMMREQ to the NCM be delayed at least 4 seconds after first scan. 3. Contact Technical Support for network performance data. Communications Status Data Format The first 8 bytes (64 bits) of the NCM input data contain the communications status of each of the 64 node addresses. By looking at this data first, the application program in the PLC can determine the validity of each device s input data. MSB 7 6 5 4 3 2 1 LSB 0 Byte 0 - Node addresses 0-7 Byte 1 - Node addresses 8-15 Byte 2 - Node addresses 16-23 Byte 3 - Node addresses 24-31 Byte 4 - Node addresses 32-39 Byte 5 - Node addresses 40-47 Byte 6 - Node addresses 48-55 Byte 7 - Node addresses 56-63 MSB 55 54 53 52 51 50 49 LSB 48 Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Each bit represents the status of the device corresponding to that node address. For example, bit 0 in byte 0 represents the status of the device with node address 0. Bit 1 in byte 0 represents the status of the device with node address 1, and so on. When the NCM is configured as a Slave device, the corresponding bit for the NCM address represents the status of the Slave device. When the NCM is configured as a Master only, the corresponding bit is 0. Bit Value Description 0 The device is NOT successfully exchanging I/O data on the DeviceNet network 1 The device is successfully exchanging I/O data on the DeviceNet network 6