Remote units Hands free or telephone handset options available. Master to remote and remote to master calling

Similar documents
Folknoll. System Manual. Disabled Refuge EVC. Disabled Refuge EVC RA System Manual

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

Product Data Sheet. Hochiki 8 Way I/O Card. Features

3.3: Setting momentary / latching switches Page Warning Regarding Operation Page 8

Universal Expander Module INSTALLATION MANUAL. Overview. Electrical Specifications

Installation Manual for D244X Series 24-volt Power Supplies

Installation and Operation Manual for the D5000 Audio Verification Unit

TECHNICAL MANUAL. 25H/DDA One button DDA audio intercom kit TECHNICAL MANUAL EDITION 1.1

INSTALLATION INSTRUCTIONS 921P EntryCheck TM

CA-A480-A Elevator Controller. Reference & Installation Manual

Vital. Safety controller. Approvals: Control of: Features: Entire safety system based on the dynamic safety circuit.

SMARTSCAN INFORMATION

TECHNICAL MANUAL EDITION 1.4 SENTRY TECHNICAL MANUAL

Lexicomm ViLX-228 EVCS Master Station. Installation and Commissioning Manual

INSTALLATION INSTRUCTIONS 920 EntryCheck TM

Ellard Product Instructions

V-9939C MICROPHONE ADAPTER

Measurement Systems Datascan Installation and User Guide

Chassis Power Supplies

PM4 INSTRUCTIONS. PM4 WIRING (See Tables 1 & 2 and Wiring Examples)

Nova Light Source Range

THIS PAGE LEFT BLANK

9. Settings and Adjustments Switch Setting Chart Speech Levels Trades Clock Parts List 13

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide

Model HM-535 Power Supply Installation and Service Instructions

Instruction Manual. ICENI/MA-01 MODBUS Master Module. Pub_ Issue 1

Product Information. DCM Standard indoor stations TK IS A 514 A.. TK IS A 514 AD.. (Design)

ETM Supplement: NSX Cellular Phone Troubleshooting

INSTALLATION INSTRUCTIONS 920P EntryCheck TM

V-9908 MESSAGE/PAGE PANEL

Sigma-XT-ECU-LCS Extinguishant Control Unit Local Control Station Operation and Maintenance Manual

T0046 PROFESSIONAL LAN CABLE TESTER USER GUIDE

Artistic Licence. Rail-Switch II. User Guide. Rail-Switch II User Guide. Version 5-5

System Installation guide

CRC220 and CRC221 INSTALLATION GUIDE. REF No.: DOC0014 ISSUE: 09

KDS Channel DMX Controlled Servo Kit

Wi-Card Skeet-Trap Claymate Operator and User Manual

Sigma Si. Extinguishant Status Unit (K , K , K , K , K , K , K , K )

S 180 OPTICAL AND AUDIBLE MODULAR DEVICES. This is our idea that lead us to create and engineering this modular lamp. MODULAR CONFIGURATION

M260 Load Cell Amplifiers

Operating and Maintenance Instructions

POWERHOUSE. -- the finest in Digital Command Control -- PRODUCT MANUAL FOR PB-205a DUAL 5AMP POWER STATION

SOFTWARE VERSION 3.10

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

Vehicle Intercom System

Product Data Sheet. BMS/Graphics Interface. Features

The Exp-007 unit connects directly to Remote Status Indicator units to provide 2 programmable 1-Amp rated, volt free, clean contact outputs.

Sigma XT Ancillary Board (K588)

Sensacell Troubleshooting Guide

POWERHOUSE. -- the finest in Digital Command Control -- PRODUCT MANUAL FOR PB-110A TEN AMP POWER STATION

Sigma Si Weatherproof Extinguishant Status Unit (W911000W8, W911100W8, W911110W8, W911113W8)

660/960 Installation Guide

Calisto USB Speakerphone. User Guide

Multi-channel system install guide

LS351 Desktop, single circuit unit, with XLR connectors (XLR3F, XLR3M loop-through). Local plug-in PSU option.

Blue Point Engineering

DAS 250L CONTROL COMMUNICATOR INSTALLATION MANUAL

Integriti 8-32 Zone LAN Expander Module Kit INSTALLATION MANUAL

AVC 2 AUTOMATIC VOLUME CONTROL USERS MANUAL

C-Bus Network Bridge 5500NB. Series. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

SERVICE MANUAL MODEL WPP-531-X-ADA MODEL SSP-511- X-ADA

180 Series Keypad. Handbook. Revision 2.1

Installation Manual for D24XX Series of 24V Switched Mode Power Supplies

2 in 1 LAN Tester and Multimeter Model:

Installation Instructions. i-net Access Control Units. Part Code: IA-PCB IA-ACB IA-ACU IA-KIT

HOUSING DEVICES, INC. HDI ADA - ARCU. Installation & Operations Manual. Made in the USA

Installing Keypad and Backplate

Installation & User Manual

Allen-Bradley PLCs. 100 Programmable Controller Processor Unit -Catalog Nos LPI01, -LP102, -LP103, -LP104 SLC TM. The Unit

Robocolor II System. users guide

AirTest Model CN9000 Series Sensor Controller

8000 Series: Installation Supplement R2-1-12

MODEL KP-100 ACCESS CONTROL DIGITAL KEYPAD OPERATING INSTRUCTIONS

Electrical Demand Specification (Reference SOP: )

TCM-1 Beamtracking Ceiling Microphone TCM-1A Beamtracking Ceiling Microphone with Amplifier TCM-1EX Beamtracking Expansion Ceiling Microphone

V-9939B MICROPHONE ADAPTER

4XLFN6WDUW*XLGH. LYNXR is not intended for UL985 Household Fire applications.

INSTALLATION INSTRUCTIONS

FTK5 PROXIMITY KEYPAD

DEEP SEA ELECTRONICS PLC

POWERWISE INDAC SETUP MANUAL

Installation & User Manual V2.08

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

Instruction Manual. Contents

Quick Start Installation Guide

Operating instructions Evaluation system for flow sensors VS / / 2013

603 D E C T I n t e r c o m

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

DEEP SEA ELECTRONICS PLC

RECORD & PLAYBACK KIT

CHAPTER Wi r i n g NOTICE:


212iL Rev. 1.1

Series F75 Fail-Safe Module Installation, Operation and Maintenance Instructions

FEATURES DESCRIPTION MODEL 110B. Power Supply

PS-4100 POWER SUPPLY MANUAL

Useful Notes: Guide to Railway Telephones

is then retained absolutely without interruption.

Troubleshooting Guide for Firecom Intercoms

9212i INSTALLATION. Stand-Alone Keypad. Instructions

Transcription:

(ORB/L/RS16 LOOP WIRED) Remote units Hands free or telephone handset options available Master to remote and remote to master calling Fully monitored for open and short circuit cable failures. Remotes connected via : 4 core Loop to each remote. Compliant to BS5839 Pt.9 2010 & BS9999 Revision 7 : 12/05/2011

Installation manual Disabled Refuge Call CDC/L/RS16 Loop Wired Contents 1) Installation Procedure 2) Commissioning Procedure 3) System Test 4) Fault Indications Note: In all cases please use Drawing C51297/A (at the back of this manual) for reference to the above sections. Page 2

1) INSTALLATION PROCEDURE (refer to Dwg. C51297/A) Install central enclosure, with cable entry gland at top, at a height of approx 1.5 metres above floor height. Ensure fixings can support a load of 20 Kg. The field cabling described below must be installed via top entry to the enclosure. The system batteries will sit on the lower edge of the enclosure, and the entire space below the main PCB assembly must be kept clear to accommodate these items. 1.1 Connect Field Cabling A Connect 5A (lighting rated) A.C. Mains supply (220 240V) to appropriate (L)ive, (N)eutral and (E)arth terminals on the modular PSU unit DSP60, located on DIN Rail fixings at the right of the main enclosure (Max system load is 40 Watts). N.B. Earth terminal must be connected to building earth. B1 Connect 4 core (+screen) enhanced fire rated cable out to first remote loop location. Observe colour coding on PCB ident for cable cores: GY (Grey) BN (Brown) BK (Black) BU (Blue) SCN : COM (0V common reference) : PWR (+ 24VDC) : LIN (loop cable audio line) : DAT (loop cable data line) :Cable screen (connected to system earth and COM internally) This cable is then connected, in a daisy chain configuration, sequentially to all remote node locations, and terminated to the appropriately identified terminals on the PCB subassembly CS807/8 located in the back box at each remote location. Continue to observe colour coding as listed above. B2 Connect loop cable returns from the last remote node location to these terminals. Observe the same polarities as the B1 terminations listed above. The following connections are optional, and are fitted only when the system specification requires these functions C Volt free Fault Out changeover contacts, for remote fault reporting. (Fault relay is normally energised). D Volt free changeover contact changes state with any call on the system. Use if remote call indication is required. E Short these terminals with a volt free closing contact (rated 50mA or higher) to enable the system Anti Tamper feature. (The Anti Tamper feature enables the system to automatically disable incoming calls, whilst retaining system monitoring of the remote cabling and outstations. The system is returned to full operation with this contact opened). Page 3

1.2 Switch F The setup switch is used for commissioning the system. 1.3 Connector J The Cat5 (RJ45) socket is only used for the master control panel. These are intended to be connected via standard (non fire rated) UTP Cat 5 cable, to the main control panel. 1.4 Connector K The Cat5 (RJ45) socket is only used where a remote control panel (repeater) is fitted. These are intended to be connected via standard (non fire rated) UTP Cat 5 cable, to a cable junction box adjacent (within the same fire zone) to the main control panel. From that location, the control functions are serialised, and forwarded to the remote control panel location via a four pair (+screen) enhanced fire rated cable. 1.5 Flush Mounted 1.6 Surface Mounted Page 4

2) COMMISSIONING PROCEDURE (refer to Dwg C51297/A) 2.1 Batteries Fit battery loom as indicated on this drawing. CHECK RED LEAD IS CONNECTED TO THE RED (+) BATTERY TERMINAL. CONNECTING THE BATTERY LEAD WITH REVERSE POLARITY WILL DAMAGE THE EQUIPMENT. 2.2 Remote Outstation Addressing Remote outstation addressing: CS9658. Each outstation requires an address which relates to the switch position on the master control panel. SW1 & SW2 are located on CS9658 as below. The remote outstation address is SW1 Tens and SW2 Units Examples Switch No. Switch Set Address SW1 (Tens) 0 SW2 (Units) 1 (Unit 1) SW1 (Tens) 0 SW2 (Units) 7 (Unit 7) SW1 (Tens) 1 SW2 (Units) 5 (Unit 15) Page 5

2.3 Loop Cable Testing Remote outstation loop wiring tests: The following measurements are required before applying A.C power to the system: Ensure that B1 and B2 are disconnected from the CS9117 PCB. With a DC meter on 200 ohms range, the following measurements are required to be 6 ohms or less <. COM (0V common reference) : Loop out (B1) to Loop Return (B2). < 6 Ohms PWR (+ 24VDC) Loop out (B1) to Loop Return (B2). < 6 Ohms LIN (loop cable audio line) Loop out (B1) to Loop Return (B2). < 6 Ohms DAT (loop cable data line) Loop out (B1) to Loop Return (B2). < 6 Ohms Cable screen Loop out (B1) to Loop Return (B2). < 6 Ohms 2.4 Apply A.C. Power to the system Check before power up that the master control panel RJ45 connector is plugged into connector J. Disconnect the return of the loop. (B2) Plug the two way cable loom terminal to the Batt. +/ terminals, located at the lower right edge of the main control PCB type CS911. (N.B. note that the system will not power up, until A.C. power is applied). On power up the system will display all faults. Pressing the Lamp Test / Silence Fault button will mute the fault sounder. All control panel zone switches will illuminate in time with the fault indicators. Page 6

2.5 System Setup Press and hold the setup button (F) on CS9117 until the setup switch illuminates. This can take up to 10 seconds. The front control panel will sound three times to signify that the system is in a setup mode. In this mode the system will send out addresses for all sixteen outstations. With a response from an outstation a solid illumination will appear on the front control panel. Once all outstations are correctly displaying on the control panel front the system unit set is ready. Plug in the return of the loop. (B2) Press the setup button (F) on CS9117 until the setup switch illumination goes out. The front control panel will sound twice to signify that the system has come out of the setup mode. Page 7

3) SYSTEM TEST (refer to Dwg. C51297/A) Once the installation and commissioning procedures are complete, test for correct system operation, and fault reporting functions: Test all locations for correct call in / call out functions, by following the operational instructions listed on the Central control front panel. Remove primary power, to check correct operation of battery support supply. Central control will report a fault condition. The fault sounder will be activated on the main control panel, and the fault LED s will be illuminated with a slow flash pattern. The fault out relay will be deenergised. Press the silence fault / lamp test switch on the control panel momentarily, to silence the fault sounder to an intermittent state. Open the main enclosure to confirm display of the mains fail and charge fail fault LED s located near the bottom edge of the main PCB ref. CS911. Reconnect primary power. Where utilised, check the function of the antitamper feature by applying a volt free closed contact (or temporary wire link) across the Antitamper terminals. Under this condition, any call made from a remote hands free outstation will be automatically cancelled by the central controller. The system will remain inactive from remote calling for c.10 seconds, to minimise nuisance recalling. An open circuit at the antitamper terminals will allow normal system operation. Note that making a call out from the master is not effected by the antitamper status. Note that use of the antitamper facility is not recommended where telephone type remote outstations are used. If a remote telephone is maliciously left off hook, the anti tamper circuitry will continue to attempt to clear the call until the handset is replaced. This will disable the remote fault monitoring system, until such time as the system is activated. Page 8

4) FAULT INDICATIONS (refer to Dwg. C51297/A) The LED function references on Dwg. C51297/A, and on PCB CS9117, identify the function of all fault indications within the central enclosure. Note that any fault condition will cause the front panel fault Light Emitting Diodes (LED s) to indicate with a slow flashing pattern, and will activate the audible fault sounder as a continuous tone. Pressing the Lamp Test / Silence Fault switch will change the sounder function to intermittent. (A short reminder bleep approx every 90 seconds). Generation of a second fault condition will reactivate the fault sounder to a continuous tone. The following table lists the various fault LED s, and describes the action to be taken to help identify specific faults. Fault LED Description Nature of Fault Action required to assist fault location Action required to clear fault state, after correction 1 Common Fail 2 Power Fail Loop common cable open circuit Loop Power cable open circuit Test loop wiring as per 2.3 Press and hold Setup Switch switch F, to reset loop monitors. 3 Line Fail 4 Master H.SET Fault 5 Remote Fault 6 Data bus Fail 7 Load Loop Lin(e) cable open circuit Master Handset short circuit or disconnected Failure of one (or more) remote units to respond Data loop cable open circuit Indication of periodic battery load test 8 Mains Fail Failure of primary supply 9 Batt Fail 10 Charge fail Failure of support battery(s) under load condition Failure of battery connection, or failure of primary supply Test loop wiring as per 2.3 Check master handset connections. Check CAT 5 connection to front panel Check for missing responses on UNIT LEDS in setup mode Test loop wiring as per 2.3 Ensure all outstations are responding in set up mode. No Fault Check for primary power to enclosure check for + 28V DC out from DSP60 Din Rail PSU Move L6 to position B to reduce load interval to approx 1 minute. Momentarily press setup switch to start new test sequence, and allow 2 minutes for repeat test. If Batt Fail indicator illuminates again, replace batteries Check battery connection loom, including the inline protection fuse Replace if necessary (5A antisurge) Press and hold Setup Switch switch F, to reset loop monitors. Press and hold Setup Switch switch F, to reset loop monitors. Replace faulty DSP60 power supply if necessary. Momentarily press setup switch after replacement batteries are fitted. Return L6 to position A 4.1 Jumper Links There are a number of jumper links located on the main PCB. L2 Fit for ground refer handset (NOT NORMALLY FITTED) L4 Programming enable (FITTED TO POSITION A) L5 Fit to disable battery load timer (NOT NORMALLY FITTED) L6(A) Fit to enable battery load timer (Normal setting) L6(B) Fit to enable shortened (c.1 minute) battery load timer (Test setting Page 9

LIVE J2 B1 J1 B2 J6 C CDC/L/RS16 LOOP WIRED J K J8 J9 LINE COMMON POWER DATA BUS LINE PICK UP FAULT O/P SPARE O/P SLEEP MODE J11 J10 J7 D E EARTH NEUTRAL A POWER SUPPLY DSP6024 REMOTE FAULT MASTER H/SET FAULT RING MASTER DC IN + J1 + + F SET UP LOAD MAINS CHARGE BATT. BATT. J2 + CS911 FUSE5A(A/S) + + 7AH 12V BATTERY Type Y712 7AH 12V BATTERY Type Y712 YELLOW C51297/A 04.11.11 Revision 7 : 12/05/2011