Communications Quick-Start Guide

Similar documents
Step 1: Choose the Appropriate CPU Step 2: Make the Connections

Chapter. Modbus. In This Chapter...

Serial CFW-11. Communication Manual. Phone: Fax: Web:

Weight ounces Panel Fasteners... Four holes to accept four 16x32 machine screws NEMA Rating... NEMA 1

Motors I Automation I Energy I Transmission & Distribution I Coatings N2 CFW501. User s Manual

Do-more H2 Series PLC System Specifications

General Specifications. P2-SCM Serial Communications

T1K MODBUS Base Controller Specifications

Motors I Automation I Energy I Transmission & Distribution I Coatings. SymbiNet CFW-11. User s Manual

C-more Micro-Graphic Power Connection Wiring

DeviceNet Drive Profile CFW-09

Installing the Panel. Installing the Panel

CANopen CFW100. User s Manual. Phone: Fax: Web: -

Motors I Automation I Energy I Transmission & Distribution I Coatings. CANopen CFW500. User s Manual

Anybus-CC CFW-11. User s Manual. Phone: Fax: Web: -

P3-RS Remote Slave Module

Motors I Automation I Energy I Transmission & Distribution I Coatings. Modbus RTU CFW300. User s Manual

Motors I Automation I Energy I Transmission & Distribution I Coatings. Modbus RTU CFW500. User s Manual

GE Fanuc IC695CMM004. Rx3i PacSystem

P USB 2.0 (Type B) Port - Programming - Online monitoring

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

Product Family: GS Drives Number: AN-GS-006

RS485 MODBUS Module 8AO

User Manual. RS485 Option Board for SV-iS5/iH Series. LG Industrial Systems

Modbus RTU CFW100. User s Manual. Phone: Fax: Web: -

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

RS485 MODBUS Module 6RO

PACSystems* RX3i IC695CMM002 and IC695CMM004

RS 485 Mini Modbus 1AO

Motors I Automation I Energy I Transmission & Distribution I Coatings. SoftPLC CFW100. User Manual

Profibus DP CFW-11. Communication Manual. Phone: Fax: Web:

P1-540 CPU. CPU Specifications

GS1 Series Introduction

Chapter. In This Chapter...

SMART RELAY SRW 01 V4.0X

CANopen CFW-11. Communication Manual. Phone: Fax: Web:

Appendix A Example Programs

RS485 MODBUS Module 8I8O

C-more Micro-Graphic Panel Accessories

GPD 506 / Modbus RTU Technical Manual

E510. Compact Drive IP 20/ NEMA HP (230V) 1-75 HP (460V)

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Automationdirect.com. D i r e c t L o g i c M O D B U S S L A V E F 4 S L V - M B

DeviceNet Communication Manual

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

DeviceNet CFW500. User s Manual. Phone: Fax: Web: -

P3-SCM. General Specifications

Motors Automation Energy Transmission & Distribution Coatings. Profibus DP SRW 01. User s Manual

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION

SCB-C08 USB to RS232/422/485 Converter

PACSystems* RX3i IC695CMM002 and IC695CMM004

SmartMod DC Digital Input Module HE359DIM610 12/24VDC Negative Logic

This is the procedure to use the Clone module as a serial converter: To enable communication you must set the following parameters in the drive.

Voltsys Inverter Control Unit

Motors I Automation I Energy I Transmission & Distribution I Coatings. Modbus RTU CFW701. User s Manual

Installation and Setup. In This Chapter... Installing the H0 PSCM The Profibus Network Configuring the Module

ICP DAS. ICP DAS 2015 M2M WLAN Wireless Solutions

RS485 MODBUS Module 8I8RO

USB-16COMi-M 16-Port RS-422/485 USB Serial Adapter User Manual. Features and Specifications. Power Supply

Motors I Automation I Energy I Transmission & Distribution I Coatings. DeviceNet CFW700. User s Manual

SENSORLESS VECTOR CONTROL

APPENDIX B SERIAL I/O MODULE INSTALLATION / OPERATION WHEN USING T&D VER. 5.2 OR 5.3

MGate 4101-MB-PBS Series

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

Document Name: User Manual for SC10MK, Modbus RTU to Modbus TCP Converter

Description. 100MBit Ethernet Communication Module. 10Base-T Ethernet Module. Description

Chapter 5: Communications 5 1 SR55 Communications Overview 5 2

D4--DCM. Data Communications Module. Manual Number D4-DCM-M

User Guide SE73-PROFIBUS-DP. Commander SE. Part Number: Issue Number: 4.

over time. Improper wiring practices could result in drive malfunction due to loose terminal connections. Control Circuit Terminal Block Functions Dri

MRUC-20 Modul-R CAN Bus Network

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

GW-7238D J1939 to Modbus TCP Server / RTU Slave Gateway

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION

Installation and Programming Manual. Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO USA

PACSystems* RX3i IC695CMM002-EG and IC695CMM002CA-EG IC695CMM004-EG, IC695CMM004CA-EG, and IC695CMM004LT-EG

Accessories Part Numbering...A 2 Line Reactors...A 2

Index EA-USER-M Hardware User Manual, 2nd Ed. Rev. H, 05/18 i-2

PORT MULTIPLEXER USER S MANUAL

Wiring Section 3-3. NQ-Series communication ports support various types of (serial) communication.

Voltsys Inverter Control Unit

Characteristics and functioning

Motors I Automation I Energy I Transmission & Distribution I Coatings. SoftPLC CFW500. User s Manual

Product Manual. USB to Optical Adapter Industrial Isolated RS- 232/422/485. Coolgear, Inc. Version 2.1 December 2018 Model Number: USB-COMi-Si-M

Serial Communications Accessories SITRANS RD200/300. Operating Instructions 05/2013 SITRANS

ADVANCED OPERATOR PANEL (AOP)

MGate MB3000 Modbus Gateway User Manual

Instruction Manual. Save These Instructions. Centrifugal Compressor Control System. Model Xe-145F Modbus. Instruction Manual

i 2 Index Communications Ports, 2 6 Conventions Used, 1 3 exclamation mark, 1 3 notepad, 1 3

Copyright: December 2017 Nidec Issue: E

SAFETY PRECAUTIONS. Throughout this manual we use the following two illustrations to make you aware of safety considerations:

Using Yaskawa CM049 BACnet Option with Delta Controls DSM-RTR

RS485 IO Slim Module MOD-ETH

The benefits are ease of set-up, more data available for the user from the drive, fast control, and state of the art technology.

Status line The top line of the LCD display shows the basic status information of the drive.

SDM-8I8O. Expansion Module 8 digital inputs, 8 digital outputs. Manufactured for

Getting Started with your D3000M Series Module

MXPLC. Compact PLC process station. Summary. Application HVAC control systems, data acquisition, interfacing 3 rd party systems.

KTA-250 Anemometer Alarm Card

Modbus Communications Board

Transcription:

WEG CFW300 AC Drives Serial Communications Quick-Start Guide NOTE: This Quick-Start guide is intended for the sole purpose of establishing communications connections between WEG CFW300 AC Drives and AutomationDirect programmable controllers, or between the CFW300 and the USB port of a personal computer. Please refer to WEG CFW300 documents for specifications and instructions for using the WEG CFW300 AC Drives. Table of Contents Communications Parameters Summary................................5 2 Summary Serial Communication Parameters............................... 5 2 Explanation of Scaling/Count Frequency Command/Feedback...................5 5 Connecting PC to CFW300 Using AutomationDirect Cable USB-485M...............5 5 Connecting Communication Cables to CFW300 AC Drives.....................5 6 AutomationDirect PLCs as Modbus Master..............................5 7 Communication Cable Connections..................................... 5 7 RS-232C to RS-485 Conversion........................................ 5 8 AutomationDirect PLC Cable Connections................................. 5 9 AutomationDirect PLC Example Programs for WEG CFW300 AC Drive..................5 12 CLICK PLC Example Program for WEG CFW300 AC Drive.........................5 12 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018 Page 5 1

Communications Parameters Summary A summary of the WEG CFW300 AC drives Communications Parameters is listed below. NOTE: Refer to the WEG CFW300 Frequency Inverter Programming Manual and the Modbus RTU User s Manual for a complete listing of all CFW300 AC drives parameters, including details and Modbus addresses. Summary Serial Communication Parameters WEG CFW300 Serial Communication Parameters Summary1) Parameter2) Range Setting Modbus Address Comm Default3) Hex Modicon4) 1) To read parameters, use Function Code 3; To write parameters, use Function Code 6 or 16 2) indicates a parameter that can be changed only with a stopped motor 3) RO = Read Only 4) Modicon Modbus addressing for the CFW300 is 40001 + the Parameter Address; Example: P222 Modicon Modbus address would be 40001 + 222 = 40223 5) Speed references and commands via Modbus RTU will always be Remote references; not Local 6) Baud rate in the PLC must match the baud rate in the AC drive (19200 bits/s) General Parameters P000 Access to Parameters 0 to 9999 1 0 40001 P001 Speed Reference 0 to 9999 RO RO 1 40002 P002 Output Speed (Motor) 0 to 9999 RO RO 2 40003 P003 Motor Current 0.0 to 40.0 A RO RO 3 40004 P004 DC Link Voltage (Ud) 0 to 524 V RO RO 4 40005 P005 Output Frequency (Motor) 0.0 to 400.0 Hz RO RO 5 40006 P200 Password 0 = Inactive 1 = Active 2 to 9999 = New Password 0 C8 40201 Parameters neccessary to communicate with the drive using module CFW-CRS232 or CFW-CRS485 0 = Always Local 1 = Always Remote 2, 3 = not used 4 = DIx P220 LOC/REM Selection Source 5) 5 = Serial/USB (LOC) 6 = Serial/USB (REM) 1 0 DC 40221 7, 8 = not used 9 = CO/DN/DP (LOC) 10 = CO/DN/DP (REM) 11 = SoftPLC P222 REM Reference Selection 0 = HMI Keys 1 = AI1 2 = AI2 3 = not used 4 = FI 5 = AI1 + AI2 > 0 6 = AI1 + AI2 7 = E.P. 8 = Multispeed 9 = Serial/USB 9 1 DE 40223 10 = not used 11 = CO/DN/DP 12 = SoftPLC 13 = not used 14 = AI1 > 0 15 = AI2 > 0 16 = not used 17 = FI > 0 (table continued next page) Page 5 2 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018

WEG CFW300 Serial Communication Parameters Summary1) (continued) Parameter2) Range Setting Modbus Address Comm Default3) Hex Modicon 1) To read parameters, use Function Code 3; To write parameters, use Function Code 6 or 16 2) indicates a parameter that can be changed only with a stopped motor 3) RO = Read Only 4) Modicon Modbus addressing for the CFW300 is 40001 + the Parameter Address; Example: P222 Modicon Modbus address would be 40001 + 222 = 40223 5) Speed references and commands via Modbus RTU will always be Remote references; not Local 6) Baud rate in the PLC must match the baud rate in the AC drive (19200 bits/s) 0 = Forward 1 = Reverse 2, 3 = not used 4 = DIx 5 = Serial/USB (FWD) P226 REM FWD/REV Selection 6 = Serial/USB (REV) 4 E2 40227 7, 8 = not used 9 = CO/DN/DP (FWD) 10 = CO/DN/DP (REV) 11 = not used 12 = SoftPLC P227 REM Run/Stop Selection 0 = HMI Keys 1 = DIx 2 = Serial/USB 3 = not used 2 1 E3 40228 4 = CO/DN/DP 5 = SoftPLC P308 Serial Address 1 to 247 1 1 134 40309 P310 Serial Baud Rate 6) 0 = 9600 bits/s 1 = 19200 bits/s 1 1 136 40311 2 = 38400 bits/s P311 Serial Interface Byte Configuration 0 = 8 bits, np, 1 stop bit 1 = 8 bits, even, 1 stop bit 2 = 8 bits, odd, 1 stop bit 3 = 8 bits, np, 2 stop bits 1 1 137 40312 4 = 8 bits, even, 2 stop bits 5 = 8 bits, odd, 2 stop bits P312 Serial Protocol 0, 1 = reserved 2 = Slave Modbus RTU 3, 4 = reserved 2 2 138 40313 5 = Master Modbus RTU P313 Action for Comm Error 0 = Inactive 1 = Ramp Stop 2 = General Disable 3 = Go to LOC 1 1 139 40314 4 = LOC Keep Enable 5 = Cause Fault P314 Serial Watchdog 0.0 to 999.0 0.0 0.0 13A 40315 P316 Serial Interface Status 0 = Inactive 1 = Active RO RO 13C 40317 2 = Watchdog Error (table continued next page) CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018 Page 5 3

WEG CFW300 Serial Communication Parameters Summary1) (continued) Parameter2) Range Setting Modbus Address Comm Default3) Hex Modicon 1) To read parameters, use Function Code 3; To write parameters, use Function Code 6 or 16 2) indicates a parameter that can be changed only with a stopped motor 3) RO = Read Only 4) Modicon Modbus addressing for the CFW300 is 40001 + the Parameter Address; Example: P222 Modicon Modbus address would be 40001 + 222 = 40223 5) Speed references and commands via Modbus RTU will always be Remote references; not Local 6) Baud rate in the PLC must match the baud rate in the AC drive (19200 bits/s) 0 to FFFF (hex) Bit 0 = reserved Bit 1 = Run Command Bit 2 = Fire Mode Bits 3 and 4 = reserved Bit 5 = 2nd Ramp Bit 6 = Config. Status P680 Logical Status Bit 7 = Alarm Bit 8 = Running RO RO 2A8 40681 Bit 9 = Enabled Bit 10 = Forward Bit 11 = JOG Bit 12 = Remote Bit 13 = Undervoltage Bit 14 = reserved Bit 15 = Fault P681 Motor Speed in 13 bits 0 to FFFF (hex) RO RO 2A9 40682 P682 Serial//USB Control 0 to FFFF (hex) Bit 0 = Ramp Enable Bit 1 = General Enable Bit 2 = Run Forward Bit 3 = JOG Enable Bit 4 = Remote RO RO 2AA 40683 Bit 5 = 2nd Ramp Bit 6 = reserved Bit 7 = Fault Reset Bit 8 to 15 = reserved P683 Serial/USB Speed Reference 0 to FFFF (hex) RO RO 2AB 40684 Page 5 4 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018

Explanation of Scaling/Count Frequency Command/Feedback When using WEG CFW300 drives, speed/frequency is shown in counts. In order to convert to Hz/ rpm, it is needed to know that the Base Frequency (P403) is equivalent to 8192 (2^13). Also, the Motor Rated speed (P402) can be scaled using the same method. Actual Frequency (P681) and Command Frequency (P683) can be calculated using that ratio. For instance: P681 = 2048(dec). Freq = 2048*60.00/8192 = 15.00 Hz RPM = 2048*1740/8192 = 435.00 rpm Connecting PC to CFW300 Using AutomationDirect Cable USB-485M An AutomationDirect cable, part number USB-485M, provides a quick and easy method of communicating to a WEG CFW300 AC Drive from a PC which has WEG CFW-WPS software installed. NOTE: Refer to the WEG WPS Software User Manual for information and instructions regarding using the WPS software to configure CFW300 AC Drives. CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018 Page 5 5

Connecting Communication Cables to CFW300 AC Drives The CFW300-CRS485 drive communication module includes a DIP switch that will switch in a 120Ω terminating resistor for the RS-485 network. An external terminating resistor is not required for the drive end. An external termination resistor may be required on the other end of RS-485 network; especially on long runs. Select resistors that match the impedance of the cable (between 100Ω and 500Ω). The CFW300 serial communication port is an RS-485 input. Please note that terminals A(-) and B(+) are shared with the USB connector. CFW300 to CFW300 serial connections can be accomplished with standard RS-485 cable (L19827-1 or similar). RS-232 signals can be converted to RS-485 by using a separate converter (see the FA-ISOCON drawings on page 5 8). CFW300-CRS485 Serial Communications Module 1 SAFETY INFORMATION 1.1 SAFETY WARNINGS NOTE! Only use the RS485 module (CFW300-CRS485) on WEG CFW300 series inverters. It is recommended reading the CFW300 user s manual before installing or operating this accessory. The content of this guide provides important information for the full understanding and proper operation of this module. CFW300-CRS485 1.2 PRELIMINARY RECOMMENDATIONS ATTENTION! Always disconnect the general power supply before connecting or disconnecting the accessories of the CFW300 frequency inverter. Wait for at least 10 minutes for the full discharge of the inverter. 5 CONFIGURATIONS The RS485 interface connections must be done on the connector as per Table 1. Table 1: Connector signals of the RS485 interface DIP 29.5 [1.162] RS485 interface connector Connector Description 25 RS485: A(-) RS485 (Terminal A) 26 RS485: B(+) RS485 (Terminal B) 27 GND Reference 0 V 28 Shield Cable shield 29 GND Reference 0 V B+ A- 62.5 [2.461] Mini USB Figure A2: CFW300-CRS485 dimensions in mm [in] and connectors location 25 26 27 28 29 Shield Shield B (+) B (+) A (-) A (-) Ref (0 V) Ref (0 V) Figure A3: Example of connection of the accessory to the RS485 network 21.2 [0.835] The location of the DIP switch to select the RS485 network termination can be better viewed in Figure A2 and it must be configure as per Table 2. Figure A3 shows a connection example of the CFW300-CRS485 accessory to a RS485 network. The connection complies with the directions of the user's manual of the Modbus RTU for the CFW300. Table 2: Configuration of the switches to configure the RS485 Comunication Switch Switch Setting Option RS485 S1 (*) S1.1 = OFF and S1.2 = OFF RS485 termination off S1.1 = ON and S1.2 = ON RS485 termination on (**) (*) Any other combination of the switches is not allowed. (**) It is recommended to use this termination with cables longer than 3 m. The CFW300-CRS485 module has the necessary resources to perform setting, command and monitoring of the inverter by means of the WPS software - WEG Programming Suite (www.automationdirect.com). For further details, refer to chapter 7 of the user's manual of the CFW300. NOTE! The mini USB connector (see Figure A2) is used for communication with the CFW300-KHMIR kit only. The use of the mini USB connector for other connections is not permitted. WARNING: Do NOT use this USB port for any PC Connections for any reason, as it may very well damage the Drive and your PC. It is for connection of the Remote Keypad Kit CFW300-KHMIR ONLY. Recommended RS-485 cable: Belden 9842, AutomationDirect L19954 series, or equivalent. Page 5 6 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018

AutomationDirect PLCs as Modbus Master Communication Cable Connections Serial Modbus-capable AutomationDirect PLCs can communicate with CFW300 drives which have an optional communication card installed. Serial Modbus control is easier to accomplish from a PLC that supports dedicated Modbus messaging. [Older PLCs may require programming to construct the Modbus strings.] We recommend PLCs with dedicated Modbus serial commands: CLICK (with RS-485 ports), P1000, P2000, P3000, BRX/Do-more, DirectLogic (DL06 or D2-260). Other PLC-Drive connectivity is possible: Please refer to the Typical ADC PLC to CFW300 Serial Connectivity Matrix below. Typical ADC PLC to WEG CFW300 RS-232 Serial Communications Connectivity Typical ADC PLC to WEG CFW300 RS-232 Serial Communications Connectivity Matrix Recommended PLC Connectivity CFW300 Communication Direct Cable PLC Port # Port Type Port Type CLICK 2 RJ12 ZL-RJ12-CBL-2P D2-260 2 HD15 D2-DSCBL-2 DL06 2 HD15 D2-DSCBL-2 BRX/Do-more RS-232 3 screw terminals L19772-1 cable Do-more H2-DM1 RS-232 RJ12 RS-232 ZL-RJ12-CBL-2P P1-540 RS-232 RJ12 ZL-RJ12-CBL-2P P2-550 RS-232 RJ12 ZL-RJ12-CBL-2P P3-530 RS-232 RJ12 ZL-RJ12-CBL-2P P3-550 RS-232 RJ12 ZL-RJ12-CBL-2P P3-550E RS-232 RJ12 ZL-RJ12-CBL-2P Other PLC Connectivity D2-250-1 2 HD15 D2-DSCBL-2 D4-450/D4-454 2 RJ12 ZL-RJ12-CBL-2P DL05 2 RJ12 ZL-RJ12-CBL-2P DL06 + DCM 2 RJ12 RS-232 ZL-RJ12-CBL-2P Do-more H2-DM1 + H2-SERIO-4 1,2 RJ12 ZL-RJ12-CBL-2P Do-more T1H-DM1 RS-232 RJ12 ZL-RJ12-CBL-2P P2-SCM 1,2,3 RJ12 ZL-RJ12-CBL-2P P3-SCM 1,2,3 RJ12 ZL-RJ12-CBL-2P Typical ADC PLC to WEG CFW300 RS-485 Serial Communications Connectivity CFW300- CRS232 screw terminals RX TX Ref(0V) Typical ADC PLC to WEG CFW300 RS-485 Serial Communications Connectivity Matrix Recommended PLC Connectivity CFW300 Communication Direct Cable PLC Port # Port Type Port Type CLICK 3 3 screw terminals RS-485 L19954 cable D2-260 2 HD15 RS-485 D2-DSCBL-2 DL06 2 HD15 RS-485 D2-DSCBL-2 BRX/Do-more RS-485 3 screw terminals RS-485 L19954 cable Do-more H2-DM1 RS-232 RJ12 RS-232 to RS-485 FA-ISOCON with L19954 cable P2-550 RS-485 3 screw terminals RS-485 L19954 cable P3-530 RS-485 3 screw terminals RS-485 L19954 cable P3-550 RS-485 3 screw terminals RS-485 L19954 cable P3-550E RS-485 3 screw terminals RS-485 L19954 cable Other PLC Connectivity D2-250-1 2 HD15 RS-485 D2-DSCBL-2 D4-450/D4-454 1 DB25 RS-232 to RS-485 FA-ISOCON with L19954 cable DL05 2 RJ12 RS-232 to RS-485 FA-ISOCON with L19954 cable DL06 + DCM 2 HD15 RS-485 D2-DSCBL-2 Do-more H2-DM1 + H2-SERIO-4 3 5 screw terminals RS-485 L19954 cable Do-more T1H-DM1 RS-232 RJ12 RS-232 to RS-485 FA-ISOCON with L19954 cable P2-SCM 4 4 screw terminals RS-485 L19954 cable P3-SCM 4 4 screw terminals RS-485 L19954 cable CFW300- CRS485 screw terminals A(-) B(+) Ref(0V) CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018 Page 5 7

RS-232C to RS-485 Conversion An RS-485 network cable can span up to 1000 meters (4000 feet). However, many AutomationDirect PLCs have only RS-232C communication ports, and require an FA-ISOCON (RS-232C to RS-422/485 network adapter) in order to make an RS-485 connection. If an FA-ISOCON module is used, set the module dipswitches as required. Refer to the FA-ISOCON manual for more detailed information. FA-ISOCON Switch Settings: S21 S23: OFF, ON, ON (19200 baud) S24 S27: OFF (Automatic Network Transmit Enable) Terminate: ON (end of run term resistors) Bias (2): ON (end of run bias resistors) 1/2 DPX (2): ON (RS-485 TXD/RXD jumpers) Helpful Hint: Some applications require that the FA-ISOCON baud rate is set faster than the drive/network baud rate. FA-ISOCON Wiring RS-232 to RS-485 Conversion Wiring Schematic TXD RXD CTS RTS GND 3 RXD 4 TXD 2 CTS 6 GND A TXD + TXD - RXD - RXD + COM B FA-ISOCON RS-232 to RS-485 converter with ANTE C D +V COM A Connect shield to signal ground at one end only FA-ISOCON RJ-12 Serial Comm Port A RS-232 Input Port 1: Signal Ground 2: CTS (input) 3: RXD (input) 6 1 4: TXD (output) 5: +5VDC in 6: Signal Ground 120Ω Termination Resistor at both ends of network [FA-ISOCON has a built-in terminating resistor controllable by switch settings] 24VDC + 24VDC - CFW300-CRS485 Comm Terminals B (+) 26 A (-) 25 Ref (0V) 27 Node 1 CFW300-CRS485 Comm Terminals B (+) 26 A (-) 25 Ref (0V) 27 Node 2 120Ω Termination Resistor at both ends of network [CFW300 has a built-in 120Ω terminating resistor controllable by switch SW5 above the I/O terminal strip] For information regarding configuration of AutomationDirect PLCs or other PLCs, please refer to the applicable PLC user manual for your application. Page 5 8 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018

AutomationDirect PLC Cable Connections CLICK Series Port 2, Do-more Series H2-DM1 Productivity Series P1-540, P2-550, P3-530/550/550E via RS-232 CLICK Series Port 3 via RS-485 DirectLogic Series D2-250-1, D2-260, DL06 Port 2 via RS-232 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018 Page 5 9

DirectLogic Series D2-250-1, D2-260, DL06 Port 2 via RS-485 Do-more BRX Series via RS-232 Do-more BRX Series via RS-485 Page 5 10 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018

Productivity Series P1 via RS-485 Productivity Series P2/P3 via RS-485 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018 Page 5 11

AutomationDirect PLC Example Programs for WEG CFW300 AC Drive Example programs for various AutomationDirect PLCs are available for free download from AutomationDirect: https://support.automationdirect.com/examples.html. Also, an example CLICK PLC ladder diagram is show in the following section. CLICK PLC Example Program for WEG CFW300 AC Drive THIS INFORMATION PROVIDED BY AUTOMATIONDIRECT.COM TECHNICAL SUPPORT IS PROVIDED AS IS WITHOUT ANY GUARANTEE OF ANY KIND. These documents are provided by our technical support department to assist others. We do not guarantee that the data is suitable for your particular application, nor do we assume any responsibility for them in your application. CLICK PLC Example Program for WEG CFW300 AC Drive (program continued next page) Page 5 12 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018

CLICK PLC Example Program for WEG CFW300 AC Drive (continued) (program continued next page) CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018 Page 5 13

CLICK PLC Example Program for WEG CFW300 AC Drive (continued) (program continued next page) Page 5 14 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018

CLICK PLC Example Program for WEG CFW300 AC Drive (continued) (program continued next page) CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018 Page 5 15

CLICK PLC Example Program for WEG CFW300 AC Drive (continued) Page 5 16 CFW300 AC Drives Serial Communications Quick-Start Guide 1st Edition 12/07/2018