IB IL 120 DI 1. Function. INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area. Data Sheet 5764B

Similar documents
IB IL 24 DI 16 IB IL 24 DI 16-PAC

IBS IL 24 BK RB-T-2MBD

IB IL 24/48 DOR 2/W-XC-PAC

PHOENIX CONTACT - 11/2007. This data sheet is only valid in association with the IB IL SYS PRO UM E user manual.

FLM DI 8 M12. Function. Fieldline Modular Device With Eight Digital Inputs. Data Sheet

IBS IL 24 RB-LK-2MBD:

ILBIB24DO16-DSUB. Inline Block IO Module for INTERBUS With 16 Digital Outputs; Bus Connection via D-SUB Connectors

This data sheet is only valid in association with the IL SYS INST UM E user manual.

VersaPoint I/O Module

IB IL IB IL PAC

IBS ST (ZF) 24 BK LB-T

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

IB ST 24 AO 4/EF. INTERBUS-ST analog output module, 4 outputs, 0-10 V, ±10 V, 0-20 ma, 4-20 ma. Data sheet. 1 Description

IB IL AO 2/SF... Inline terminal with two analog outputs. AUTOMATION Data sheet 6655_en_06. 1 Description

IB IL RS 232 IB IL RS 232-PAC

PB IL 24 BK DIO 16/16

PHOENIX CONTACT - 10/2006

ILC 200 IB ILC 200 IB-PAC

IL CAN BK-TC-PAC. Extract from the online catalog. Order No.:

ILB DN 24 DI16 DO16. Inline Block IO Module for DeviceNet With 16 Digital Inputs and 16 Digital Outputs. AUTOMATIONWORX Data Sheet 6885_en_05

IBS ST 24 BK-T INTERBUS-S. Data Sheet. Bus Terminal Module. Product Description

PSR UC/ESAM4/3X1/1X2/B

MINI-PS AC/10-15DC/8

PI-EX-ME-2NAM/COC-24VDC

PHOENIX CONTACT - 07/2006

PHOENIX CONTACT - 12/2007

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

PI-EX-ME-2NAM/COC-120VAC

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

IBS PCI SC/I-T. Controller Board for PC Systems With PCI Bus. Data Sheet 6039B

AXL E IOL AO1 U M12 R

PHOENIX CONTACT - 05/2007

Rexroth Inline terminal with one analog output

VersaMax IP I/O Module

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

8 24 V DC, 8 24 V DC,

PSR DC/ESP4/2X1/1X2

PHOENIX CONTACT - 01/2007

PSR-SCP- 24DC/SSM/2X1 PSR-SPP- 24DC/SSM/2X1

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

PSI-MODEM-SHDSL/SERIAL

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Automation terminals of the Inline product range. User manual

ASI QUINT /2.4 EFD

MACX MCR-EX-SD LP(-SP)

QUINT-PS/ 1AC/24DC/ 5

TRIO-DIODE/12-24DC/2X10/1X20

MINI MCR-SL-UI-2I. Configurable signal duplicator. Data sheet. 1 Description

STEP-PS/1AC/24DC/1.75

RAD-DOR4-IFS. I/O extension module, 4 digital relay outputs. INTERFACE Data sheet. 1 Description

IL CAN BK-TC-PAC. Extract from the online catalog. Order No.:

PHOENIX CONTACT - 10/2009

QUINT-BUFFER/24DC/24DC/40

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/24DC/1

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

TRIO-PS/1AC/24DC/20. Extract from the online catalog. Order No.:

QUINT-PS-3x AC/24DC/10

VersaMax IP Input Module

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

Redundancy Module QUINT-DIODE/40

PHOENIX CONTACT - 06/2007. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

Rexroth RECO Fieldline INTERBUS Devices

Extract from the online catalog

PHOENIX CONTACT - 11/2008

PHOENIX CONTACT - 01/2008

PHOENIX CONTACT - 02/2008

Operating instructions. Standstill monitor A / / 2011

PHOENIX CONTACT - 01/2010. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

QUINT-PS/1AC/24DC/10. Extract from the online catalog. Order No.:

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

RSTI-EP Slice I/O. Digital Output Module

MINI MCR-SL-RPS-I-I. Repeater power supply, active. Data sheet. 1 Description

PSR-PS21. SIL coupling relay. Data sheet. 1 Description

PHOENIX CONTACT Features

FL MC 2000E (SM40) LC

UNO-PS/1AC/12DC/30W. Primary-switched power supply unit. Data sheet. 1 Description

MINI MCR-SL-PT100-UI-200

GFK-2415A March Type of sensor connection

MINI-DC-UPS/12DC/4. Extract from the online catalog. Order No.:

EMD-FL-C-10. Electronic monitoring relay for overcurrent and undercurrent monitoring of direct and alternating current in single-phase networks

QUINT-PS/24DC/48DC/ 5

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

DPO A4. Description. Module with 4 digital outputs. Datasheet

PSR-PC20. SIL coupling relay. Data sheet. 1 Description

MINI MCR-SL-PT100-UI(-SP)(-NC)

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

MINI MCR-SL-UI-2I(-SP)(-NC)

ILB BT ADIO 2/2/16/16

RSTI-EP Slice I/O Digital Input Modules EP-1214, EP-1218, EP-1318, EP-125F, EP-1804 Digital Input Module with Time Stamp EP-12F4

PHOENIX CONTACT - 05/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

QUINT-PS AC/24DC/10

ELR W1/ 6-24DC. Extract from the online catalog. Order No.:

Power Supply, Primary Switch Mode for Universal Use QUINT-PS AC/48DC/5

Operating instructions. Speed monitor D / / 2014

MINI MCR-SL-PT100-UI. Active resistance thermometer measuring transducer. Data sheet. 1 Description

SUBCON-PLUS-PROFIB...

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

Original operating instructions Fail-safe inductive sensor GF711S / / 2013

Transcription:

INTERBUS Inline Terminal With One Digital Input in the 120 V AC Voltage Area Data Sheet 5764B 09/2000 # % $ This data sheet is only valid in association with the INTERBUS Inline System Manual IB IL SYS PRO UM E. Function The terminal is designed for use within an INTERBUS Inline station. This terminal is used to detect digital input signals in the 120 V AC voltage area. Dangerous Voltage Connecting and disconnecting the terminal is only allowed if the power supply is disconnected. When working on the terminal and wiring, always switch off the supply voltage and ensure it cannot be switched on again. If these instructions are not followed, there is a danger of damage to health, or even of a life-threatening injury. Features Connections for one digital sensor Maximum permissible load current 500 ma Diagnostic and status indicators Figure 1 # % $ % terminal with connector Please note that the connector is not supplied with the terminal. Please refer to Ordering Data on page 12 to order the appropriate connectors for your application. 5764B 1

Safety Instructions for Inline Terminals for Installation in Areas Outside the SELV (Low Voltage Area) Only qualified personnel may work on low voltage area Inline terminals. Qualified personnel are people who, because of their education, experience and instruction, and their knowledge of relevant standards, regulations, accident prevention and service conditions, have been authorized by those responsible for the safety of the plant to carry out any required operations, and who are able to recognize and avoid any possible dangers. (Definitions for skilled workers according to EN 50110-1:1996.) The instructions given in this data sheet must be followed during installation and startup. Technical modifications reserved. Correct Usage The terminal is only to be used within an Inline station as specified in this data sheet and the INTERBUS Inline System Manual. Phoenix Contact accepts no liability if the device is used for anything other than its designated use. This data sheet describes the module-specific features of the terminal. For general information on the INTERBUS Inline product family, please refer to the IB IL SYS PRO UM E INTERBUS Inline System Manual. 2 5764B

General Description Local Diagnostic and Status Indicators,, 1 Des. Color Meaning D Green Bus diagnostics 1 Yellow Input status indication Terminal Assignment Terminal Point Assignment 1.1 Not used 1.2 Digital input 1.3 Connection of phase L 1.4 Neutral conductor connection (N) 2.1, 2.2, Not used 2.3, 2.4 # % $ Figure 2 with the appropriate connector Function Identification Cobalt blue with lightning bolt Housing/Connector Color Gray housing Gray connector, color-coded according to function 5764B 3

Internal Circuit Diagram Key: 1 6-4 * 7 5 7 2 + OPC INTERBUS protocol chip (bus logic including voltage conditioning) LED Optocoupler Digital input Isolated area Terminal point, without metal contact Terminal point, without metal contact, with filler plugs 8 ) + Other symbols are explained in the IB IL SYS PRO UM E User Manual. # % $ * Figure 3 Internal wiring of the terminal points 4 5764B

General Installation Instructions Installing the System Install the system according to the requirements of EN 50178. Starting Up an Inline Station An Inline station can only be started up if it has been properly installed. This means: all terminals must be installed with their connectors the station must be terminated with the end plate and the two end clamps Avoiding malfunctions The AC terminal must only be connected to the Inline station through an appropriate power terminal. The voltage should only be switched on when the AC area has been terminated with the end terminal and all the connectors are connected. The special features of the AC and SELV terminals and connectors are listed in the user manual and in the data sheets for the power terminals for AC areas. 5764B 5

Installation Instructions and Notes for an AC Area Dangerous Voltage Please note that these are dangerous voltages when working on circuits that do not meet SELV requirements. Connecting and disconnecting terminals for the AC voltage area is only allowed if the power supply is disconnected. When working on terminals and wiring, always switch off the supply voltage and ensure it cannot be switched on again. Structure of an AC Area An AC area must have an AC power terminal at one end and an AC end terminal at the other. I/O terminals that are suitable for this area can be used between these terminals. The number is limited by the system restrictions of the INTERBUS Inline station and the entire INTERBUS system (see IB IL SYS PRO UM E User Manual). Please Use Grounded AC Networks * ) 4 + * 6 4,, 7 7 5 7 Inline terminals for the AC voltage area should only be operated in grounded AC networks. Figure 4 Example of an Inline AC area # $ $ * 1 Bus terminal 2 AC power terminal 3 Various AC input/output terminals 4 AC end terminal 6 5764B

Fusing an AC Area Protect each AC area using an intrinsically safe fuse. Please note that the fuse required depends on the specific application. Connecting the Supply and the I/O in the AC Area Multiple supplies are not permitted The supply voltage must only be supplied to the power terminal for which it is meant. The connecting cables of all actuators and sensors should only be connected to the Inline AC terminals. The use of external bus bars for group voltages is not permitted. Interrupting PE Jumpering in the AC Area The PE jumper begins at the power terminal of the AC area and, in a complete AC area, ends at the end terminal. If a terminal is removed from this area, the PE jumper is interrupted. As long as the installation instructions are followed, all subsequent terminals will be disconnected. 5764B 7

Connection Example Programming Data,, 1 ID code BE hex (190 dec ) Length code C2 hex Process data channel 2 bits Input address area 2 bits Output address area 0 bits Parameter channel 0 bits (PCP) Register length (bus) 2 bits INTERBUS Process Data Assignment of the Terminal Points for the IN Process Data 1 Figure 5 8 # % $ Typical sensor connections Observe the current carrying capacity The maximum total current flowing through the potential jumpers is 8 A. Bit View Bit 1 0 Terminal Terminal point 1.2 (signal) Terminal point 1.3 (L) Terminal point 1.4 (N) Status indication LED 1 For the assignment of the bit view shown to your control or computer system, please refer to data sheet DB GB IBS SYS ADDRESS, Part No.9000990. 8 5764B

Technical Data General Data Housing dimensions (width x height x depth) Weight Operating mode Sensor connection type Permissible temperature (operation) Permissible temperature (storage/transport) Permissible humidity (operation) 12.2 mm x 120 mm x 66.6 mm (0.480 in. x 4.724 in. x 2.622 in.) 39 g (without connector) Process data operation with 2 bits 3-wire -25 C to +55 C (-13 F to +131 F) -25 C to +85 C (-13 F to +185 F) 75% on average, 85% occasionally In the range from -25 C to +55 C (-13 F to +131 F) appropriate measures against increased humidity (> 85%) must be taken. Permissible humidity (storage/transport) 75% on average, 85% occasionally For a short period, slight condensation may appear on the housing if, for example, the terminal is brought into a closed room from a vehicle. Permissible air pressure (operation) 80 kpa to 106 kpa (up to 2000 m [6562 ft.] above sea level) Permissible air pressure (storage/transport) 70 kpa to 106 kpa (up to 3000 m [9843 ft.] above sea level) Degree of protection IP 20 according to IEC 60529 Interface INTERBUS local bus Through data routing Power Consumption Communications power Current consumption from the local bus Power consumption from the local bus I/O supply voltage Nominal current consumption on the I/O supply voltage 7.5 V 30 ma, maximum 0.23 W, maximum 120 V AC (nominal value) Depends on the sensor Supply of the Module Electronics Through the Bus Terminal and of the I/O Through the Power Terminal Connection method Through potential routing 5764B 9

Digital Input Number 1 Input features According to EN 61131-2 Type 1 Definition of switching thresholds Signal 0 0 V AC ˆ U IN ˆ 40 V AC Signal 1 77 V AC ˆ U IN ˆ 135 V AC Nominal input voltage U IN 120 V AC Permissible range 108 V AC ˆ U IN ˆ 135 V AC Nominal input current for U IN 8.1 ma at 120 V AC, 60 Hz Total current Depends on the sensor Characteristic curve of the current Linear in the area 1 V < U IN < 135 V Delay time T ON 40 ms, typical T OFF 10 ms, typical Permissible cable length to the sensor 30 m (98.425 ft.) Protection No integrated protection against short circuit and overload Behavior in the event of an error (short circuit) Protective element in the power terminal is damaged Short circuit protection can be achieved by means of a pre-connected fuse with an appropriate fusible element. Switching frequency Maximum network frequency, depending on bus length, data rate, and ambient conditions Input Characteristic Curve Frequency (Hz) Input Voltage (V) Typical Input Current (ma) Active Power Loss (mw) 60 30 2.55 213 60 60 4.54 254 60 90 6.46 321 60 120 8.10 416 60 150 9.46 537 10 5764B

Power Dissipation Formula to calculate the power dissipation of the electronics 7 1 7 2-9 1 N Ω $ & Ω Where P EL Total power dissipation of the terminal Z Reactance (Z = 18813 W [60 Hz]) U IN Input voltage of the input Power Dissipation of the Housing P HOU 0.7 W (within the permissible operating temperature) Concurrent Channel Derating None Safety Devices Overload/short circuit in phase L Surge voltage Using external fuse Protective circuits of the power terminal Electrical Isolation/Isolation of the Voltage Areas Common Isolated Groups Phase and neutral conductor have the same potential. PE is a separate potential area. Separate system potentials consisting of bus terminal/power terminal in the 24 V DC area and supply terminals/i/o terminals in the AC area - Test Distance - Test Voltage 5 V supply incoming remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min 5 V supply outgoing remote bus/7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min 7.5 V supply (bus logic)/i/o area 2500 V AC, 50 Hz, 1 min Routine test 1200 V AC, 50 Hz, 1 min I/O area/pe 500 V AC, 50 Hz, 1 min Input/phase 500 V AC, 50 Hz, 1 min Error Messages to the Higher-Level Control or Computer System None 5764B 11

Ordering Data Description Order Designation Order No. Terminal with one digital input in the 120 V AC voltage area 28 36 70 6 A connector is needed to complete the terminal. I/O connector with 8 connections using the spring-clamp method (gray, with color print) pack of 10 IB IL SCN-8-AC-ICP 27 40 26 1 INTERBUS Inline System Manual IB IL SYS PRO UM E 27 43 04 8 Phoenix Contact GmbH & Co Flachsmarktstr. 8 32825 Blomberg Germany + 49-52 35-30 0 + 49-52 35-34 12 00 www.phoenixcontact.com Phoenix Contact 09/2000 Subject to technical modification TNR 94 24 96 2 12 5764B