Initial Review of ASHRAE/ANSI/ACCA Standard 180 (2010)

Similar documents
Western HVAC Performance Alliance

What Could Possibly Go Wrong? A Laboratory Investigation of In-Field and Onboard FDD on a 5 Ton RTU

Advanced RTU Campaign Taking Action Toward Efficient RTUs Michael Deru February 25, 2014

Utility Incentives for RTU FDD in California. Mel Johnson Southern California Edison

Western HVAC Performance Alliance CQI Definition of an Efficient Commercial HVAC Installation

A NEW RECIPE FOR HVAC SYSTEM

Poor Installations Undermine the Benefits of High Efficiency HVAC Equipment

A NEW RECIPE FOR HVAC SYSTEM PERFORMANCE & EFFICIENCY COOKING UP SAVINGS BY IMPROVING HVAC SYSTEM EFFICIENCY

Experiences Commercializing FDD in the Northwest. Danny Miller, President Transformative Wave

SPRING 2017 TRAINING PLYMOUTH, MN

Economizer Fault Detection and Diagnostics (FDD) for Built-Up Air Handlers Draft Report

NOTE ON PERFORMANCE TESTING

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

Nonresidential HVAC Stakeholder Meeting #3

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

BEFORE THE PUBLIC UTILITIES COMMISSION OF THE STATE OF CALIFORNIA

A New Paradigm for Retrocommissioning: Moving Building Science to Green Collar Trades

Fast Route to Reliable Energy Savings ZIP Economizer

Installation Service. 1.0 Executive Summary. Factory Trained Technician Train Customer Support Staff On Basic Operation Of The Equipment

How Green can you go?

2013 Building Energy Efficiency Standards Non-Residential HVAC Alterations

Second Stakeholder Meeting for Nonresidential HVAC Proposals Based on ASHRAE Revisions to Waterside Economizer

EER Optimizer for DX Air Conditioners

Data Center Energy Savings By the numbers

Western HVAC Performance Alliance CQI Standardized Field Data Specification for Commercial HVAC Installation

How to Get the Most out of Your Rooftop AC

EVALUATING THE EFFECTS OF COMMON FAULTS ON A RESIDENTIAL SPLIT SYSTEM

Rooftop Unit Optimization Offering Frequently Asked Questions and Updates Released April 1, 2013

INSTALLATION INSTRUCTIONS ECONOMIZERS WITH EXHAUST. For Use with Bard 3-1/2 through 6 Ton Wall Mount Air Conditioners and Heat Pumps

CT AEE 2018 Energy Trends Fair

Economizer Control 2-1

ASHRAE. Shaping Tomorrows Built Environment Today. Erich Binder - Director At Large

SECTION (16410) - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Certification Working Group Gaps Report

Setting Your Business Apart Through Industry Certification

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

WHAT IS THE DIGI-RTU South 59 th Street Omaha, NE bes-tech.net

Peter C. Jacobs, Architectural Energy Corporation Cathy Higgins, New Buildings Institute Rachael Shwom, Consortium for Energy Efficiency

INSTALLATION INSTRUCTIONS ECOHPRS Series Horizontal Economizer for York PRESTIGE for ZX 04-07; ZY 04-06

New Wisconsin Energy Code: What it Means for Me?

FDD Evaluator 0.1. Draft Software documentation and technical background. January 11, 2013

Field Installation Manual External Bolt-On Economizer for ComPac I Air Conditioners

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat

Advanced RTU Campaign Webinar June 17, 2013

Goal 4: Onboard/In-Field Fault Detection and Diagnostics Committee December 15, 2014

Onboard and In-Field Fault Detection and Diagnostics Industry Roadmap. April 30, 2012

ELITE CONTRACTOR FUJITSU ELITE CONTRACTOR PROGRAM FOR INSTALLERS OF FUJITSU HALCYON AND AIRSTAGE SYSTEMS

FALL TRAINING SCHEDULE 2017

Smart Equipment Controls (SEC)

Development and Evaluation of an Automated Virtual Refrigerant Charge Sensor Training Kit

TECHNICAL TRAINING CATALOG

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

Upstream Rebate Programs UC Davis Meeting

ecoenergy Innovation Initiative Research and Development Component Public Report

Development of an Embedded RTU FDD using Open-Source Monitoring and Control Platform

Advanced Rooftop Controller

Last updated January 29, Approved by ECC March 3, 2015

Unique Tracking Number Assigned by MORTS Work Statement TC/TG: 7.5 Smart Building Systems

Evaluating Fault Detection and Diagnostics Tools with Simulations of Multiple Vapor Compression Systems

REPORT CBEI REPORT. Funded by U.S. DOE. Title: Virtual RTU Sensing Automation, Demonstration, and Assessment. Report Date: April 30, 2016

Energy Engineering: Tools and Trends

System User Manual. AKC 55 Rack Controller

Modeling of Compressors and Expansion Devices With Two-Phase Refrigerant Inlet Conditions

Retro-Commissioning Report

CalCERTS Title 24 & Whole House Rater HERS Certification Training Overview. CalCERTS HERS Rater Certification Courses

Trailblazer AGZ-E air-cooled scroll chillers

HIGH EFFICIENCY 15 and 17 SEER TWO STAGE HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT. Min. Circuit Ampacity

Professional Experience

Up on the Roof Up on the roof I've found a paradise that's trouble proof, up on the roof. C. King/G. Goffin 1962

Min. Circuit Ampacity. Max. Fuse or Breaker. Ship / Operating Weight lbs. (kg) C4H524GKD 2 24,

Impact Evaluation of the 2012 Rooftop Unit Tune-up Initiative

Data Centers. Powerful Solutions That Put You in Control. Energy Management Solutions. Where your energy dollars are used. 1

SPRING 2017 TRAINING MILWAUKEE, WI

Climate Technologies Investor Update

Data Analytics and Modeling for Building Energy Efficiency

The Platform for Productivity

Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

INSTALLATION INSTRUCTIONS ECONOMIZER WITH EXHAUST

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

SMART VENTILATION MANAGEMENT: CHANGING THE WAY WE THINK ABOUT VENTILATION

Experimental Study on Fault Detection Algorithm Using Regression Method for Plural Indoor Units Faults of Multi-Heat Pump System under Heating Mode

REGARD mA output module. Installation, operation and maintenance

Air-Cooled Chillers. R134a. Performance Matters

Transformative Wave Technologies Kent, Washington

1510 MOTOR CONTROLLERS

Introducing the Heat Wheel to the Data Center

How Big Data Analytics Helps Hotels Improve Maintenance and Comfort, and Save Energy

Standard Practice for Inspection and Maintenance of Commercial Building HVAC Systems

Aquaflair. BREC/F and BCEC/F kw

Features and Benefits of XeteX Controls. Other Unit Control Functions. Energy Recovery Functions

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

BAS Chillers 8/15/2016. Achieving Energy Savings with BAS and Data Analytics Guanjing Lin Lawrence Berkeley National Laboratory August 10, 2016

Warning. Important. Always follow all local building electrical codes. PECCSUN3672DB46M PECCSUN3672EN46M

NEWTON COUNTY OPEN RECORDS ACT POLICY

ASHRAE Standard 90.1

Your Solution For Energy and Cost Savings. McQuay Packaged Chiller Plant

Automated Fault Detection and Diagnostics for Vapor Compression Cooling Equipment

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

HVAC INDUSTRY SECTOR WORKSHOP

ACCREDITATION COMMISSION FOR CONFORMITY ASSESSMENT BODIES

Transcription:

Summary This 2010 document is the first in a series of documents by Western HVAC Performance Alliance (WHPA) industry volunteers of ASHRAE/ANSI/ACCA Standard 180. More recent WHPA documents provide detailed review and contributions to the Standard. Finalized: February 27, 2010 Use of this Document This document provides a first review by the Western HVAC Performance Alliance of the 2008 version of ASHRAE/ANSI/ACCA Standard 180 for quality maintenance of commercial HVAC systems. It is based on an official WHPA Work Product of February 27, 2010, titled CQM Committee ANSI/ASHRAE/ACCA. This Work Product was developed by the WHPA Non-Residential Quality Maintenance Committee. This document, and also the WHPA Work Product, may be used in part or whole at no charge. Attribution to the Western HVAC Performance Alliance is requested. We would also ask that you inform the WHPA through info@performancealliance.org if you have made use of either document, so that we can inform and encourage the hundreds of volunteers who donate their time to providing expert HVAC advice in order to support energy efficiency objectives. (2010) 1. Background...2 2. Objectives...2 3. Approach...2 4. Findings...3 5. Recommendations...4 6. Next Steps...5 7. EXHIBIT A...6 8. EXHIBIT B...7 Table of Contents WHPA 1 of 7 02/27/2010

1. Background The Non-Residential Quality Maintenance Committee of the Western HVAC Performance Alliance appointed a Tasking Subcommittee to complete a detailed review of ASHRAE/ACCA Standard 180-2008 and to make recommendations as to how it might be used in California s Statewide HVAC Program, specifically the Non-Residential Quality Maintenance Sub Program. In addition to determining whether this national standard was suitable for use in California s climatic zones, the Subcommittee was to propose any additions or more specific tasking, details or instructions that might be necessary to operationalize the Standard. Additionally, the Tasking Subcommittee was asked to consider options for and recommend an array of maintenance measures not mentioned in Standard 180 that, if added, could foster a further reduction in HVAC energy consumption and that could be incorporated into a Premium (or Enhanced) Maintenance program. The Subcommittee was also authorized to address any other details that it determined important to increasing market acceptance of QM as called for in the California Long Term Energy Efficiency Strategic Plan and the IOUs 2010-2012 HVAC Program Implementation Plans. 2. Objectives 2.1. To achieve consensus around the adoption of ASHRAE/ACCA Standard 180-2008 as the foundation of California s Non-Residential Quality Maintenance program. 2.2. To define specific tasking that would, if completed, constitute a Standard-compliant maintenance program. 2.3. To recommend specific tasking that would, if added to the tasking above, define a Premium (or Enhanced) maintenance program. 2.4. To make known any exceptions or deficiencies that the Subcommittee finds to accepting the ASHRAE/ACCA Standard 180-2008 as a recommended California Quality Maintenance Standard. 3. Approach 3.1. The Non-Residential Quality Maintenance Committee established a Tasking Subcommittee. 3.2. The Non-Residential Committee Chairman, Don Langston, served as Chairman of the tasking Subcommittee. 3.3. Members of the Subcommittee were recruited by the Chairman from members of the full Committee based on the following criteria (See Exhibit B): 3.3.1. Interest in serving on the Subcommittee 3.3.2. Possessing strong HVAC service, maintenance, and technical knowledge 3.4. The Subcommittee met by conference call one hour per week from December 18, 2009, to February 24, 2010, to work on the goals assigned to it. WHPA 2 of 7 02/27/2010

4. Findings 4.1. The Subcommittee accepted the ASHRAE/ACCA Standard 180-2008 as the correct basis for a recommended use in California s Non-Residential QM Program with the following exception: Standard 180 should be augmented to include economizer maintenance tasking and motor maintenance tasking. 4.2. One goal of the Subcommittee was to add tasking detail to Section 5 of Standard 180. This was not achieved. The Subcommittee concluded that, because of the wide range of equipment covered under the Non-Residential HVAC category--and the relatively long life of that equipment--developing specific tasking that would be appropriate for any and all make or models is simply not achievable in a single document. This is not only due to the amount of information that would be required, but also due to the lack of manufacturer- supplied data necessary (see finding 4.4 below). 4.3. The Subcommittee determined that Section 5 of Standard 180 is silent on some points that the committee believes need to be addressed, specifically economizers and motors. 4.4. The Subcommittee recognized that there is an unacceptable lack of manufacturer-supplied data and information [see Exhibit B] easily and readily available to technicians for use in the field including, but not limited to: 4.4.1. Specific information about the design of the unit: 4.4.1.1. EER or SEER rating 4.4.1.2. Heat pump COP 4.4.1.3. Subcooling goal for TxV units 4.4.1.4. Superheat 4.4.2. Specific information about maintaining the air conditioner: 4.4.2.1. Belt tightness specification 4.4.2.2. Lubrication instructions 4.4.3. Specific information about the refrigeration cycle: 4.4.3.1. Expected performance parameters under the full range of testing conditions 4.4.4. Specific testing instructions for other unit sub-systems: 4.4.4.1. Economizer testing procedures and set-point recommendations 4.4.4.2. Specific procedures for testing and optimizing the gas combustion process 4.5. The Subcommittee recognized that making unit-specific information available to the technician on the job may require the deployment of technologies that are not generally available to the average technician such as: 4.5.1. A database of model-specific information as described in 4.4 above. WHPA 3 of 7 02/27/2010

4.5.2. Computerized tools that enable calculations and algorithms that are more complex than the technician can perform manually: 4.5.2.1. Estimating the desired operating parameters of various equipment designs under a wide set of operating conditions 4.5.2.2. Parsing out appropriate repair strategies when multiple coincidental faults and installation defects exist 4.6. The Subcommittee concluded that Standard 180 envisions a never-ending process of continual improvement. 4.7. The Subcommittee concluded that Standard 180 designates the building owner as ultimately responsible for meeting the requirements of the Standard. 4.8. The Subcommittee concluded that Standard 180 requires that the frequency of the maintenance tasks for each piece of equipment, be evaluated in an ongoing manner, until the correct frequency of maintenance is determined for that unit. 4.9. The Subcommittee concluded that Standard 180 requires documentation be created by the maintenance contractor to: 4.9.1. Provide evidence of the required testing to determine correct frequency has taken place 4.9.2. Provide evidence of specific requests by the contractor to the owner for authorization to make required repairs and the owner s response. 5. Recommendations 5.1. The Subcommittee recommends that ASHRAE/ACCA Standard 180-2008 be adopted as the minimum specification for use in California Non-Residential QM Program with the following additions: [See Exhibit A] 5.1.1. Economizer maintenance requirements 5.1.2. Indoor blower motor and sheave maintenance requirements 5.1.3. Ductwork integrity, leakage and airflow performance requirements 5.1.4. Basic training in identifying Mold and biological growth and remediation requirements 5.1.5. Effective communication and documentation with Building Owner when health and safety concerns are found during maintenance inspections. 5.2. The Subcommittee recommends that the additions to the Standard called out above (Section 5.1) also be recommended to the ASHRAE/ACCA Standard committee for inclusion in subsequent versions of Standard 180. (NOTE: In response to this recommendation, ACCA s Donald Prather reports that the economizer inspection tasks shown in Exhibit A of this report will be submitted for consideration to the ASHRAE Standard 180 Committee by Standard 180 Committee Member, Glenn Hourahan, ACCA Division VP. According to Prather, some of these recommendations came directly as the result of the work/discussions of the Non-Residential Quality Maintenance Tasking Subcommittee.) WHPA 4 of 7 02/27/2010

5.3. The Subcommittee recommends that a system be put in place by an appropriate organization to track required documentation as described in Section 4.9 and to determine and certify compliance with the Standard. 5.4. The Subcommittee recommends that the Non-Residential Quality Maintenance Committee call for appropriate technology development and deployment to meet the needs defined in this report. 6. Next Steps 6.1. The Subcommittee intends to next consider maintenance tasking that exceeds the Standard. This tasking will be considered enhanced tasking and will meet the requirements called out in the Program Implementation Plans as Premium Maintenance. WHPA 5 of 7 02/27/2010

EXHIBIT A Recommended additions to be proposed to the ASHRAE Standard 180 Committee by Standard 180 Committee Member, Glenn Hourahan, ACCA Division Vice President PROPOSED TABLE 5-25 Economizers Inspection/Maintenance Task Check conditions of outside air filters; clean and replace as necessary. Check condition setting and operation of outdoor sensor or change over controller. Repair, adjust or replace components to ensure proper operation. Check condition setting and operation of the economizer controller. Repair, adjust, or replace components to ensure proper operation. Check condition setting and operation of the mixed air/discharge sensor or change over controller. Repair, adjust or replace components to ensure proper operation. Check dampers for proper operation, condition, setting and operation. Repair, adjust, lubricate, or replace components to ensure proper operation. Check condition setting and operation of the economizer damper motors. Repair, adjust, lubricate, or replace components to ensure proper operation. Check integrity of all panels on equipment. Replace fasteners as needed to ensure proper integrity and fit/finish of equipment. Check condition and operation of the return air sensor or changeover controller. Repair, adjust, or replace components to ensure proper operation. Visually inspect areas of moisture accumulation for biological growth. If present, clean or disinfect as needed. Lubricate field serviceable Bearings. Check condition setting and operation of the freeze Stat. Repair, adjust, or replace components to ensure proper operation. Frequency a Annually Annually Note a: Refer to Section 4.2.2.d for procedure to modify frequency. WHPA 6 of 7 02/27/2010

EXHIBIT B Excerpt from the Technology and Diagnostics Advocacy Sub-Program of the IOU Statewide HVAC Program Implementation Plan approved by the CPUC for 2010-2012. These items were recommended from a national HVAC Roundtable held in California in 2006. 2. Technical Review of Refrigerant Charge Diagnostic Tables/Charts. There is an immediate need for manufacturers to review and revise as needed, the current refrigerant cycle tables along with evaporator and condenser performance charts partly in relation to the low ambient item noted above, and also for other reasons including differences in operating pressures in newer higher efficiency vs. older lower efficiency units. The Carrier representative noted that not taking into account the different operating pressures of new higher efficiency units could result in overcharging. Sub-Program Benefits: More accurate diagnostic tools, in this case the foundational metrics for charge diagnostics, leads to more effective performance maintenance of the equipment. 3. Industry Standard Unit Data for Field Service. There is a critical need for manufacturers to provide data labeling via stickers, plates, or potentially an RFID tag, with enhanced data sets such as superheat/subcooling charts for a wide range of conditions (indoor & outdoor dry bulb/ wet bulb temperatures), permanently affixed to each unit. Depending on the approach chosen, a standard graphic layout and mounting location should be established industry wide. Sub-Program Benefits: An industry standard approach will help service technicians perform field diagnosis and correction as needed. 4. Minimum FDD Standards. The industry should develop a minimum standard for onboard diagnostics functionality for all units. It could take the form of a universal plug point for all manufacturers with a universal protocol for data requirements, data analysis and data display. A new PIER FDD project will expand these standards to include embedded remote communications capability so as to enable remote diagnostics by service technicians, owner/managers, and utility program operators for QI/QM, M&V, and persistence of savings evaluation requirements. Sub-Program Benefits: An industry standard will help service technicians with diagnosis and repair of operating faults. 5. Industry Standards Sensor Mount Locations. Manufacturers should create a standard or specification for designated sensor mount locations for conducting field diagnostics. Manufacturers should mark appropriate locations for technicians to attach sensors. At least one manufacturer has a product with sensor mounting locations marked. One manufacturer provides a sensor port accessible without requiring the service technician to open the unit for certain service work. Sub-Program Benefits: An industry standard will help service technicians with diagnosis and repair of operating faults. WHPA 7 of 7 02/27/2010